Viconics VTR8300 Series, VT8300 Series, VTR8350A5000B, VTR8350A5500B, VTR8350A5500BP Application Manual

Page 1
Fan Coil Unit Application Guide
VTR8300/VT8300 Series Room Controllers
For firmware Release 2.1
Page 2
TABLE OF CONTENTS
VTR83 - 3-SPEED FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
VTR83 - ECM FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
VT83 - 3-SPEED FAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
VT83 ECM FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
APPENDIX A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
APPENDIX B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
APPENDIX X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
DEPLOYMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Page 3
VTR8300 AND VC3000 | LINE-VOLTAGE FAN COIL ROOM CONTROLLERS AND RELAY PACKS
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Room Controller and the VC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, thereby reducing overall costs and installation time.
The VC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is not required for the VT8300 Series models.
Commercial interface (local override)
Power
Part Number Description Humidity PIR ZigBee Communication
3
VTR8350A5000B
VTR8350A5500B
VTR8350A5500BP
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
Transformer Relay Packs for VTR8300 Series
Power
Part Number Description
VC3500E5000 Transformer relay pack five relay fan outputs
VC3504E5000 Transformer relay pack five relay fan outputs, and four inputs
VC3514E5000 Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
VC3400E5000 Transformer relay pack four relay outputs and smart VDC output
VC3404E5000 Transformer relay pack four relay outputs, smart VDC output, and four inputs
VC3300E5000 Transformer relay pack three relay fan outputs
ZigBee Pro Module for VT(R)8300 Series
Part Number Description
Yes No No BACnet
Yes Yes No BACnet
Yes Yes Yes BACnet
®
®
®
Power
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
VCM8000V5000P Release 20
Optional ZigBee Pro module for VT(R)8300 Series room controllers.
Page 4
4
Terminal Controller
Terminal Controller
To others
To others
13 - COM +
14 - COM -
VTR83xxA
VTR83xxA
13 - COM +
14 - COM -
VTR8300 | TERMINAL IDENTIFICATION AND FUNCTION
Terminal Identification
Terminal 4 Tx – Rx Communication
Terminal 5 Power Hot 7.0 VDC
Terminal 6 Power Common
Ter min al 12 ECM 0-10 VDC output
Terminal 13 BACnet +
Terminal 14 BACnet -
Terminal 16 BI 1 ( Configurable )
Terminal 17 BI 2 ( Configurable )
Terminal 18 Scom
All VTR83xx Terminal Equipment Controller
COMMUNICATION WIRING TO VC3XXXE RELAY PACK
VTR83xxA
Terminal Controller
4 - Tx / Rx
5 - 7 Vdc Power Hot
6 - Power Common
VC3504E
Relay Pack
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
VC3300E
Relay Pack
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
To other VC3xxxE
Relay Pack
Only ONE VC3xxxE Relay Pack with remote monitoring inputs can be used under a single VTR83xxA Controller. All other slave units must be VC3xxxE Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxE Relay Packs can be used for a single VTR83xxA Room Controller.
From VTR83xxA to first VC3xxxE Relay Pack
• Uses existing or new field wires
• A minimum of 3 wires are required 14-18 Ga,
• Solid or Stranded, shield not necessary
From first VC3xxxE to all other slave VC3xxxE Relay Pack(s)
• Uses existing or new field wires
• A minimum of 2 wires are required 14-18 Ga, Solid or Stranded, shield not necessary
• Connect only two wires: Tx/Rx (1) and Power Common (3).
• Installation Note:
The maximum distance between the SER8300 Room Controller and the SC3000 relay pack is recommended at 50ft (15m) or less.
BACnet® Communication Shielded Wiring (if required)
• NOTE: See VTR8300 BACnet® integration manual for more details
Network Wiring Topology
Star Topology
Daisy Chained Topology
Mixed Daisy Chained & Star Topology
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 5
VT8300 LOW-VOLTAGE 24 VAC FAN COIL ROOM CONTROLLERS
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Room Controller.
The VT8300 Room Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control of both line-voltage and low-voltage end devices is required.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
Part Number Description Humidity PIR ZigBee Communication
5
VT8350U5000B
VT8350U5500B
VT8350U5500BP
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
Mixed-voltage Relay Packs for VT8300 Series
Part Number Description
VC1300E5000
VC2300E5000
3 on/off outputs, 110/130V 3 speed
3 on/off outputs, 220/240V 3 speed
Wireless Accessories for VT(R)8300 Series
Part Number Description
SED-DOR-P-5045 Wireless door switch
Yes No No BACnet
Yes Yes No BACnet
Yes Yes Ye s BACnet
®
®
®
SED-WIN-P-5045 Wireless window switch
SED-WDS-P-5045 Wireless window and door switch
SED-WDC-G-5045 Wireless window/door sensor
SED-CMS-P-5045 Wireless ceiling mounted motion sensor
SED-WMS-P-5045 Wireless wall mounted motion sensor
SED-MTH-G-5045 Wireless motion/temperature/humidity sensor
SED-WLS-G-5045 Wireless water leakage sensor
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 6
6
VT8300 | TERMINAL IDENTIFICATION AND FUNCTION FOR 3-SPEED FAN
Fan Type - ECM
Control Type On/Off Floating Analog
1- BO1 Normally Close Heat Valve Close Heat valve Not used
2- BO2 Not used Not used Not used
3- BO3 Not used Not used Not used
4- BO4 ECM Fan Star t ECM Fan Star t ECM Fan Star t
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 ECM Fan Analog Output ECM Fan Analog Output ECM Fan Analog Output
11- UO 11 Normally Open Cool Valve Open Cool Valve Analog Heat valve
12- U O12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- U I17 UI17 Function
18- Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21-Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 7
VT8300 | TERMINAL IDENTIFICATION FOR ECM FAN SYSTEM
Fan Type - ECM
Control Type On/Off Floating Analog
1- BO1 Normally Close Heat Valve Close Heat valve Not used
2- BO2 Not used Not used Not used
3- BO3 Not used Not used Not used
4- BO4 ECM Fan Star t ECM Fan Star t ECM Fan Star t
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 Analog ECM Fan Analog ECM Fan Analog ECM Fan
11- UO 11 Normally Open Cool Valve Open Cool Valve Analog Heat valve
12- U O12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- U I17 UI17 Function
18- Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21-Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used
7
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 8
VTR83 3-Speed
Page 9
VTR83
1, 2 OR 3-SPEED FAN APPLICATIONS
System Fan Cooling Heating Other
4 pipes 3 Speed 2 positions valve 2 positions valve Door and motion detect
4 pipes 3 Speed 2 positions valve 2 positions valve Motion detect
4 pipes Twice 3 speed 2 positions valve 2 positions valve Two VC3500 relays
2 pipes 3 Speed 2 positions valve Changeover sensor Window sensor
2 pipes 3 Speed 2 positions valve Heating SSR Dehumidification
2 pipes 3 Speed 2 positions valve Changeover sensor Motion detect
2 pipes 3 Speed 2 positions valve Changeover sensor Fresh air damper
See Appendix B for relay pack wiring.
9
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 10
10
VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
VTR83X0
Onboard PIR Sensor
3 Speed Fan
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
AND / OR
OR*
Wired Remote PIR Sensor
Configuration Parameter Name
Fan control 3 speed Fan Menu L-M-H-A Fan cont. heat. On BI1 Motion NO or Motion NC (remote PIR sensor only)
BI2 Door Dry Pulsed heating Off Pipe no. 4 Seq. operation Ht - Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 11
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
11
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU GRN YEL ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch and Motion
Wireless door switch automatically toggles occupancy to standby. Motion will switch to occupied as long as the door stays closed
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Can be configured for 2-pipe systems (without changeover).
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 12
12
VTR8350A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8350
3 Speed Fan
Airow Direction
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
VC3404E5000
SOLID STATE RELAY
SSR
(GENERIC)
Configuration parameter name
Fan control 3 speed Fan menu L-M-H-A Fan cont. heat On Pulsed heating On Pipe no. 2 Seq. operation Cool - Rht
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration settings
Page 13
VTR8350
Tx / Rx
7 VDC
13
VC3404E5000
1
Tx/Rx
2
7 Vdc
Com
Com
3
4
5
6
7
8
9
10
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
WHT BLK RED BLU GRN YEL ORG
BACnet+
SOLIDSTATE RELAY (4-32Vdc)
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
NOTE: See Appendix B for VC3400 wiring to fan coil
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 14
14
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 15
VTR83X0A5X00B WITH VC3504E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN
15
VTR83X0
Onboard PIR Sensor
3 Speed Fan
Airow Direction
VC3504E5000
Cooling / Heating Coil Supply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Configuration Parameter Name
Configuration Settings
Fan control 3 speed Fan Menu L-M-H-A Fan cont On BI1 Window RUI1 COS Pipe No 2 Seq. operation Cool
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 16
16
VTR83X0
BACnet+
VC3504E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU GRN YEL ORG
10K type 2
10K type 2
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/cooling when window is opened.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 17
17
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 18
18
VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
Fresh Air
DAMPER
VTR83X0
Return Air
3 Speed Fan
Airow Direction
VC3514E5000
COOLING VALVE / HEATING VALVE
C/O
SENSOR
10K OHM TYPE 2
Cooling / Heating Coil Supply Sensor
2 POSITION
SUPPLY SENSOR
10K OHM TYPE 2
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Fan cont. heat On RUI1 COS Pulsed Heating Occ Out Pipe no. 2 Seq. operation Cool
Configuration Settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 19
VTR83X0
BACnet+
19
VC3514E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
OCC -
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU GRN YEL ORG
For 7 Vdc SSR
Fresh Air Damper
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 20
20
VTR83X0A5X00B WITH VC3500E5000 AND VC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
VTR83X0
3 Speed Fan
Airow Direction
VC3300E5000
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Fan cont. heat On Pipe No 4 Seq. operation Ht-Cl
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 21
VC3500E5000T
21
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
1
2
Com
3
WHT BLK RED BLU GRN YEL ORG
VC3300E5000
1
2
3
NOTE: See Appendix B for VC3500 wiring to fan coil
SCom
WHT BLK RED BLU GRN YEL ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Can be configured for 2-pipe systems without changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 22
22
VTR83X0A5X00B WITH VC3504E5000 RELAY: HEATING/COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
Window Switch
SED-WIN-P-5045
3 Speed Fan
Airow Direction
Cooling / Heating Coil Supply Sensor
VTR83X0
Onboard PIR Sensor
VC3504E5000
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Configuration Parameter Name
Fan control 3 speed
Fan menu L-M-H-A
Fan cont. heat On
BI1 Window
RUI1 COS
Pipe no. 2
Seq. operation Cool
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 23
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
23
VC3504E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU GRN YEL ORG
BI1 (Window)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 24
24
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 25
VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED
AND / OR
OR*
FAN AND 2-POSITION VALVES
25
VTR83X0
Onboard PIR Sensor
3 Speed Fan
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Door Switch
SED-DOR-P-5045
Wired Remote PIR Sensor
Configuration Parameter Name
Wireless Remote PIR Sensor
Configuration Settings
Fan control 3 speed Fan menu L-M-H-A Fan cont. heat On BI1 Motion NO or Motion NC (remote PIR sensor only) BI2 Door Dry Pipe No 4 Seq. Operat Ht-Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 26
26
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU GRN YEL ORG
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch and Motion
Door switccs occupancy to standby. Motion will switch to occupied as long as door stays closed.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Can be configured for 2-pipe systems without changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
Low: red wire is energized
Med: blue wire is energized
High: brown wire is energized.
Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 27
VTR83 ECM
Page 28
28
VTR83
ECM FAN APPLICATIONS
System Fan Cooling Heating Other
4 pipes ECM 2 positions valve 2 positions valve Door and motion detect
4 pipes ECM 2 positions valve 2 positions valve Motion detect
2 pipes ECM 2 positions valve Changeover sensor Fresh air damper
2 pipes ECM 2 positions valve Changeover sensor Motion and Window detect
2 pipes ECM 2 positions valve Heating SSR Dehumifidication
See Appendix B for relay pack wiring.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 29
VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/ COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN AND 2-POSITION VALVES
29
VTR83X0
Onboard PIR Sensor
ECM Fan
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
AND / OR
OR*
Wired Remote PIR Sensor
Configuration Parameter Name
Fan control ECM Fan Menu L-M-H-A Fan cont. heat. On BI1 Motion NO or Motion NC (remote PIR sensor only) BI2 Door Dry Pulsed heating Off Pipe no. 4 Seq. operation Ht - Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Wireless Remote PIR Sensor
Configuration Settings
Page 30
30
VTR83X0
BACnet+
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
UI 17 - BI2
SCom
0-10Vdc
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
3
NOTE: See Appendix B for VC3500 wiring to fan coil
WHT BLK RED BLU BRN YEL ORG
(-)
(+)
ECM FAN
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 31
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Can be configured for 2-pipe systems (without changeover).
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
31
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 32
32
VTR8350A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH ECM FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8350
ECM Fan
Airow Direction
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
VC3404E5000
SOLID STATE RELAY
SSR
(GENERIC)
Configuration parameter name
Fan control ECM Fan menu L-M-H-A Fan cont. heat On Pulsed heating On Pipe no. 2 Seq. operation Cool-Rht
Configuration settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 33
VTR8350
WHT
Tx / Rx
7 VDC
33
VC3404E5000
1
Tx/Rx
2
7 Vdc
Com
Com
0-10Vdc
3
4
5
6
7
8
9
10
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
BLK RED BLU BRN YEL ORG
BACnet+
SOLIDSTATE RELAY (4-32Vdc)
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
(-)
(+)
(-)
(+)
ECM FAN
NOTE: See Appendix B for VC3400 wiring to fan coil
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 34
34
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 35
VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
35
Fresh Air
DAMPER
VTR83X0
Return Air
ECM Fan
Airow Direction
VC3514E5000
Changeover Sensor 10k Ohm type 2
SENSOR
Cooling / Heating Coil
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Supply Sensor 10k Ohm type 2
Configuration Parameter Name
Fan control ECM Fan menu L-M-H-A Fan cont. heat On RUI1 COS Pulsed Heating Occ Out Pipe no. 2 Seq. operation Cool
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 36
36
VTR83X0
BACnet +
BACnet -
BACnet REF
Tx / Rx
BI 1
7 VDC
BI 2
Com
Common
0-10VDC
ECM Fan
(+)
(−)
1
Tx/Rx
2
7 Vdc
Com
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
OCC -
NOTE: See Appendix B for VC3500 wiring to fan coil
VC3514E5045
WHT BLK RED BLU GRN YEL ORG
7 Vdc for SSR
Fresh Air Damper
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 37
37
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or return duct sensor ready.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 38
38
VTR83X0A5X00B WITH VC3504E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
Window Switch
SED-WIN-P-5045
ECM Fan
Airow Direction
Cooling / Heating Coil Supply Sensor
VTR83X0
Onboard PIR Sensor
VC3504E5000
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Configuration Parameter Name
Fan control ECM
Fan menu L-M-H-A
Fan cont. heat On
BI1 Window
RUI1 COS
Pipe no. 2
Seq. operation Cool
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 39
39
ECM Fan
VTR83X0
BACnet+
BI1 (Window)
(+)
(-)
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
0-10 VDC
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500 wiring to fan coil
VC3504E5000
WHT BLK RED BLU BRN YEL ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 40
40
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for service or filter monitoring.
Universal input can be configured for changeover sensor.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 41
VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN AND 2-POSITION VALVES
41
VTR83X0
Onboard PIR Sensor
AND / OR
ECM Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Door Switch
SED-DOR-P-5045
OR*
Wired Remote PIR Sensor
Configuration Parameter Name
Fan control ECM Fan menu L-M-H-A Fan cont. heat On BI1 Motion NO or Motion NC (remote PIR sensor only) BI2 Door Dry Pipe No 4 Seq. Operat Ht-Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 42
42
VTR83X0
Tx / Rx
7 VDC
ECM Fan
(+)
(-)
1
Tx/Rx
2
7 Vdc
Com
Com
0-10 VDC
3
NOTE: See Appendix B for VC3500 wiring to fan coil
VC3500E5000
WHT BLK RED BLU BRN YEL ORG
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch And Motion
Door switch automatically toggles occupancy to Standby. Motion will switch to Occupied, as long as the door stays closed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 43
43
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Can be configured for 2-pipe systems without changeover.
Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 44
VT83 3-Speed
Page 45
VT83
1, 2 OR 3-SPEED FAN APPLICATIONS
System Fan Cooling Heating Other
4 pipes 3 Speed Tri-state valve actuator Tri-state valve actuator
4 pipes 3 Speed 0-10Vdc valve actuator 0-10Vdc valve actuator Motion detect + dehumidification
4 pipes 3 Speed 2 positions valve actuator 2 positions valve actuator Motion detect + dehumidification
4 pipes 3 Speed 0-10Vdc valve actuator 2 positions valve actuator ---
2 pipes 3 Speed 0-10Vdc valve actuator Electric heater ---
2 pipes 3 Speed 0-10Vdc valve actuator None ---
2 pipes 1 Speed 2 positions valve actuator None Fresh air damper
See Appendix B for relay pack wiring.
Door and motion detect + dehumidification
45
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 46
46
AND / OR
OR*
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
3 Speed Fan
VT8350
Onboard PIR Sensor
Airow Direction
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
Wired Remote PIR Sensor
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Control Type Floating UI16 Motion NO or Motion NC (remote PIR sensor only) UI17 Door Dry Pipe no. 4 Seq. operation Cool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Configuration Settings
Wireless Remote PIR Sensor
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 47
47
VT8350
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
Floating Control + 3 Speed Fan
RH
- Close Cool V
BO8 - Aux Heat
UO9
UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
HEATING VALVE
Close Open Com.
COOLING VALVE
Close Open Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 48
48
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 49
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
49
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
Onboard PIR Sensor
Configuration Parameter Name
Fan control 3 speed Control type Analog Fan menu L-M-H-A Pipe no. 4 Seq. operation Cool / Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 50
50
VT8350
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
Modulating Control +
RH
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
V
BO8 - Aux Heat
- Analog Heat
UO11
UO12 - Analog Cool
3 Speed Fan
HEATING VALVE
0-10 v 24 v Com.
COOLING VALVE
0-10 v 24 v Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 51
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
51
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 52
52
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Control Type On/Off Pipe no. 4 Seq. operation Cool/Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 53
53
VT8350
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
On / Off Control + 3 Speed Fan
RH
- NC Cool V
UO9
BO8 - Aux Heat
UO10 - NC Heat V
UO11 - NO Cool V
UO12 - NO Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
HEATING VALVE
IF NC IF NO Com.
COOLING VALVE
IF NC IF NO Com.
or or
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 54
54
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 55
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE
55
Fresh Air
DAMPER
Return Air
VT8350
3-Speed Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Configuration Parameter Name
Fan control 3 speed Fan menu On-Auto Control Type On/Off BO8 AuxOut Aux NO Pipe no. 2 Seq. operation Cool only
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 56
56
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
C (Common)
1 2 3 4 5 6
1 2 3 4 5 6
On / Off Control +
RH
- Aux Heat
BO8
OU9 - NC Cool V
UO10 - NC Heat V
UO12 - NO Heat V
UO11 - NO Cool V
7 8 9 10 11 12
7 8 9 10 11 12
3 Speed Fan
FRESH AIR DAMPER
ON / OFF ACTUATOR
COOLING VALVE
L
S
IF NC IF NO Com.
or
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
13 14 15 16 17 18
13 14 15 16 17 18
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
19 20 21 22 23 24
19 20 21 22 23 24
UI 19
UI 20 - RS
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The auxiliary contact closes forcing fresh air damper to open.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The auxiliary contact opens causing fresh air damper to close completely.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter. The auxiliary contact closes forcing fresh air damper to open.
On Call for Cool
Cooling valve opens.
On Call for Heat
Cooling valve closes.
FAN
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 4-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured for two speed or three speed fan control.
1 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
On: BO4 is energized.
Auto: When there is no demand, BO4 is not energized. On demand, BO4 will be energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 57
VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE
57
VT83X0
3 Speed Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration Parameter Name
Fan control 3 speed Control type Analog Fan menu L-M-H-A BO8 Out Time 0 = 15 Minute BO8 AuxOut Reheat Pipe no. 4 Seq. operation Cool-rht
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 58
58
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Mod. & On / Off Control + 3 Speed Fan
- Aux Heat
BO8
V
HEATING VALVE
NC Com.
UO12 - Analog Cool
UO11 - Analog Heat
RH
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve starts modulating based on cooling demand.
On Call for Heat
Heating valve opens.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
Can be configured to single or two speed fan.
3 universal inputs can be used and configured for advanced functionality as required by the application.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 59
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE
59
VT83X0
3 Speed Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Configuration Parameter Name
fan control 3 speed Control type Analog Fan menu L-M-H-A Pipe no. 2 Seq. operation Cool only
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 60
60
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Modulating Control + 3-Speed Fan
RH
- Analog Heat
BO8 - Aux Heat
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
UO11
UO12 - Analog Cool
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 193
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 4-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured to two or three speed fan.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 61
VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE
61
3 Speed Fan
VT83X0
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating
ON / OFF DUCT
HEATER
Configuration Parameter Name
Configuration Settings
Fan control 3 speed Fan menu L-M-H-A Control Type On/Off BO8 Out Time 0 = 15 Minute BO8 AuxOut Reheat Pipe no. 2 Seq. operation Cool-rht
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 62
62
VT83X0
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
On / O Controlor+ 3 Speed Fan
RH
Close Cool V
BO8 - Aux Heat
UO9 -
UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
S
L
IF NC IF NO Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 4-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured to single or two speed fan.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
BO2 is energized.
BO3 is energized
BO4 is energized.
Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 63
VT83 ECM
Page 64
64
VT83
ECM FAN APPLICATIONS
System Fan Cooling Heating Other
4 pipes ECM Tri-state valve actuator Tri-state valve actuator
4 pipes ECM 0-10 Vdc valve actuator 0 -10 Vdc valve actuator Motion detect + dehumidification
4 pipes ECM
4 pipes ECM 0-10 Vdc valve actuator 2 positions valve actuator ---
2 pipes ECM 0-10 Vdc valve actuator Electric heater ---
2 pipes ECM 0-10 Vdc valve actuator None ---
2 positions valve actuator
2 positions valve actuator Motion detect + dehumidification
See Appendix B for relay pack wiring.
Door and motion detect + dehumidification
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 65
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
65
ECM Fan
VT8350
Onboard PIR Sensor
Airow Direction
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
AND / OR
OR*
Wired Remote PIR Sensor
Configuration Parameter Name
Fan control ECM Fan menu L-M-H-A Control Type Floating UI16 Motion NO or Motion NC (remote PIR sensor only) UI17 Door Dry Pipe no. 4 Seq. operation Cool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 66
66
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
C (Common)
BO1-Close Ht Vlve
1 2 3 4 5 6
1 5
13 14 15 16 17 18
13 14 15 16 17 18
Floating Control + ECM Fan
RH
- Close Cool V
BO8 - Aux Heat
UO9
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 10 1
19 20 21 22 23 24
19 20 21 22 23 24
UO10 - ECM 0-10 Vdc
HEATING VALVE
Close Open Com.
COOLING VALVE
Close Open Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 67
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4
“fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
67
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 68
68
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
ECM Fan
Airow Direction
VT8350
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
Configuration Parameter Name
Fan cotrol ECM Control type Analog Fan menu L-M-H-A Pipe no. 4 Seq. operation Cool / Heat
Onboard PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 69
69
VT8350
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Modulating Control + ECM Fan
RH
7 8 9 10 11 12
7 9 1
CM
UO10 - E
BO8 - Aux Heat
UO11 - Analog Heat
UO12 - Analog Cool
19 20 21 22 23 24
HEATING VALVE
0-10 v 24 v Com.
COOLING VALVE
0-10 v 24 v Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 70
70
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 71
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, 2-POSITION VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
71
ECM Fan
VT8350
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration Parameter Name
Fan control ECM Fan menu L-M-H-A Control Type On/Off Pipe no. 4 Seq. operation Cool/Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 72
72
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
BO1-Close Ht V
1 2 3 4 5 6
13 14 15 16 17 18
C (Common)
On / Off Control + ECM Fan
RH
- NC Cool V
UO9
BO8 - Aux Heat
7 8 9 10 11 12
UO11 - NO Cool V
UO12 - NO Heat V
UO10 - ECM 0-10 Vdc
19 20 21 22 23 24
HEATING VALVE
IF NC IF NO Com.
OR OR
COOLING VALVE
IF NC IF NO Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 73
73
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Models available with factory installed PIR sensor.
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 74
74
VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH ECM FAN, ANALOG COOLING VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE
VT83X0
ECM Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration Parameter Name
Fan control ECM Control type Analog Fan menu L-M-H-A BO8 Out Time 0 = 15 Minute BO8 AuxOut Reheat Pipe no. 4 Seq. operation Cool-rht
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 75
75
ECM Fan
SE83X0
BO2 - Fan L
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18 19 20 21 22 23 24
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
Mod. & On / Off Control + ECM Fan
RH
C (Common)
V
BO8 - Aux Heat
- Analog Heat
UO11
UO12 - Analog Cool
7 8 9 10 11 12
19 20 21 22 23 24
HEATING VALVE
NC Com.
COOLING VALVE
.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve starts modulating based on cooling demand.
On Call for Heat
Heating valve opens.
(−)
(+)
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 76
76
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
Can be configured to single or two speed fan.
3 universal inputs can be used and configured for advanced functionality as required by the application.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 77
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH ECM FAN AND 0-10VDC ANALOG COOLING VALVE FOR LOW VOLTAGE
77
VT83X0
ECM Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Configuration Parameter Name
Fan control ECM Control type Analog Fan menu L-M-H-A Pipe no. 2 Seq. operation Cool only
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 78
78
VT83X0
RC (24 Vac)
BO4 - Fan H
C (Common)
1 2 3 4 5 6
13 14 15 16 17 18
Modulating Control + ECM Fan
RH
- Analog Heat
BO8 - Aux Heat
7 8 9 10 11 12
UO11
UO12 - Analog Cool
UO10 - ECM 0-10 Vdc
19 20 21 22 23 24
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 193
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.
(-)
(+)
ECM Fan
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 79
79
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 4-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured to two or three speed fan.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 80
80
VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH ECM FAN, 2-POSITION VALVE AND ELECTRIC REHEAT FOR LOW VOLTAGE
ECM Fan
VT83X0
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating
ON / OFF DUCT
HEATER
Configuration Parameter Name
Fan control ECM Fan menu L-M-H-A Control Type On/Off BO8 Out Time 0 = 15 Minute BO8 AuxOut Reheat Pipe no. 2 Seq. operation Cool-rht
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 81
81
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
On / Off Control + ECM Fan
RH
Close Cool V
BO8 - Aux Heat
UO9 -
UO11 - Open Cool V
UO12 - Open Heat V
UO10 - Close Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
S
L
IF NC IF NO Com.
OR
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(Optional)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.
(-)
(+)
ECM Fan
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 82
82
Options
Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 4-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured to single or two speed fan.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 83
VT83 MIX VOLTAGE
Page 84
84
VT83
3-SPEED MIX VOLTAGE APPLICATIONS
System Fan Cooling Heating Other
4 pipes 3-speed 120 Vac 0-10 Vdc valve actuator 0-10 Vdc valve actuator need the optional SC1300 relay box
4 pipes 3-speed 240 Vac 0-10 Vdc valve actuator 0-10 Vdc valve actuator need the optional SC2300 relay box
4 pipes 3-speed 120 Vac Tri-state valve actuator Tri-state valve actuator need the optional SC1300 relay box
4 pipes 3-speed 240 Vac Tri-state valve actuator Tri-state valve actuator need the optional SC230 0 relay box
See Appendix B for relay pack wiring.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 85
MIX VOLTAGE VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
85
3-Speed Fan
VT8300
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
SC1300
Power supply 120 vac
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Pipe no. 4 Seq. operation Cool / Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 86
86
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO11
- Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Mix Voltage 120 volts
SC1300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply 120 Vac
COOLING VALVE
0-10v 24v Com.
HEATING VALVE
0-10v 24v Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Page 87
MIX VOLTAGE VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
87
3-Speed Fan
VT8300
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
SC2300
Power supply 240 vac
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Pipe no. 4 Seq. operation Cool / Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 88
88
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO11
- Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Mix Voltage 240 volts
SC2300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply 240 Vac
COOLING VALVE
0-10v 24v Com.
HEATING VALVE
0-10v 24v Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary. Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Page 89
MIX VOLTAGE VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
89
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
TRI-STATE
FLOATING VALVE
Heating Coil
TRI-STATE
FLOATING VALVE
SC1300
Power supply 120 vac
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Control Type Floating Pipe no. 4 Seq. operation Cool / Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 90
90
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8350
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO9 -
Close Cool V
UO10 - Close Heat V
UO11 - Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Floating Control Mix Voltage
SC1300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply 120 Vac
COOLING VALVE
Open Close Com.
HEATING VALVE
Open Close Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%. Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Page 91
MIX VOLTAGE VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
91
3 Speed High Voltage Fan
VT8350
Airow Direction
Cooling Coil
TRI-STATE
FLOATING VALVE
Heating Coil
TRI-STATE
FLOATING VALVE
SC2300
Power supply 240 vac
Configuration Parameter Name
Fan control 3 speed Fan menu L-M-H-A Control Type Floating Pipe no. 4 Seq. operation Cool / Heat
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Configuration Settings
Page 92
92
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8350
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO9 -
Close Cool V
UO10 - Close Heat V
UO11 - Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Floating Control Mix Voltage
SC2300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply 240 Vac
COOLING VALVE
Open Close Com.
HEATING VALVE
Open Close Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%. Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Options
Wireless adapter modules are available. (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2-pipe systems with changeover.
3 universal inputs can be used and configured for advanced functionality as required by the application.
Universal input can be configured for changeover sensor.
Page 93
APPENDIX A - SE8000 PIR SENSOR DETAILS
Typical Savings of 10-30%
Ener gy Usage (K Wh)
93
Energy Savings
PIR can maximize your energy saving from 10­30% by adjusting temperature set points in unoccupied zones during scheduled periods.
85 80
75 70
65 60 55
50 45
40 35
30 25 20
15 10
5 0
0 2 4 6 8 10 12 14 16 18 20 22 24
Time of Day (EST)
Typical Consumption PIR Thermostat Consumption Sa vings
50%
40%
Saving Percentage
30%
20%
10%
0%
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 94
94
APPENDIX B - OPTIONAL NETWORK SET-UP
TYPICAL WIRING EXAMPLES FOR 3 SPEED FAN
TYPICAL WIRING EXAMPLES FOR ECM FAN
Brown - Fan Start (Optional)
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 95
95
Setpoints
e
Stand-by timer reset
Unoccupied timer reset
APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION WITHOUT DOOR SENSOR
26.5°C
Unoccupied cool
Stand-by cool
24.5°C 76°F
80°F
Occupied cool
Occupied heat
Stand-by heat
noccupied heat
Deadband
Movement detected
-
22°C 72°F
70°F
Deadband
Deadband
22°C
72°F
70°F
21°C 21°C
Stand-by
time
66°F
19°C
Unoccupied
time
62°F
16.5°C
Into Stand-by mode
-
Into Unoccupied
mode
Next movement
detected
Tim
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 96
96
APPENDIX X - WIRELESS SENSORS
®
Wireless ZigBee
Fan Coil Room Controllers with SED Series ZigBee® Pro wireless switches can be used in stand-alone mode, or with integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions. Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VTR8300 or VT8300 Room Controller
Note that if a ZigBee wireless window switch is used, the VT8300 Room Controller cannot also use a remote PIR motion sensor, whether wired or wireless. Using one or more wireless remote PIR motion sensors means that a wired PIR motion sensor cannot be used, and vice versa.
The SED Series sensors are factory delivered with batteries and are ready to be installed, configured, and used right out of the box. Due to the extremely small current consumption of the sensors, the expected battery life is approximately 10 years, which is equivalent to the battery shelf life.
Model Selection
Window Switch Door Switch
Pro Motion Sensors
Wireless door switch SED-DOR-P-5045
Wireless window switch SED-WIN-P-5045
Wireless window and door switch
Wireless window/door sensor
Wireless ceiling mounted motion sensor
Wireless wall mounted motion sensor
Wireless motion/ temperature/humidity sensor
Wireless water leakage sensor
SED-WDS-P-5045
SED-WDC-G-5045
SED-CMS-P-5045
SED-WMS-P-5045
SED-MTH-G-5045
SED-WLS-G-5045
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 97
97
Deployment
Placement of the Room Controller must be given consideration. It is recommended to install the Room Controller as close to a door as possible (but not so as to be blocked by the door), or in an area with high occupant movement.
Ideally the Room Controller should be installed 5 feet (1.5 meters) above the floor surface to ensure maximum detection range is achieved. As well, Room Controller placement should ensure the occupant crosses the lens beam in a perpendicular path within the prescribed detection zone.
Example of Recommended Deployment
The below shows Room Controllers installed in ideal locations for two rooms.
The examination room shows one Room Controller installed adjacent to the door. In this area of the room, occupant traffic is high and ensures the occupant will almost always cross the PIR detection path laterally and within the detection range.
The waiting room shows one Room Controller installed beside a door in the middle of the room. As shown in the diagram below, occupant traffic is high in several areas of the room including the entrance, waiting room, access to the door and activity around the reception desk. Moreover, for each case aforementioned, occupant movement almost always moves lateral to the PIR, which ensures detection by the PIR, as well as respecting the PIR detection range of 20 feet (6 meters) at 140°, and 16 feet (5 meters) between 15° to 30° laterally.
Recommended Installation
Viconics Technologies Inc. www.viconics.com sales@viconics.com
028-0444-06 November 2018
Page 98
98
Example of Non-Recommended Deployment
The below shows four Room Controllers (two for each room) installed in non-ideal locations for the two rooms.
The examination room shows one Room Controller installed in a low traffic area near the door, and a second Room Controller installed on the wall directly opposite the door. For the Room Controller installed in the corner wall, the PIR could be blocked by the opened door, while occupant traffic cold also be minimal in this area of the room. For the second Room Controller installed opposite the door, the PIR detection could fall outside the specified detection zone, while at the same time most occupant movement would be not be lateral to the PIR, thereby not respecting optimal crossing patterns for PIR detection.
The waiting room shows one Room Controller installed in the corner of the room, and a second Room Controller installed beside the reception area. For the Room Controller installed in the corner, the opening/closing of the door creates high probability that the PIR would get blocked, and therefore, occupancy going undetected. For the Room Controller installed beside the reception area, occupant traffic could fall outside the detection zone, and the receptionist would often be below the 5 foot recommended installation height for the Room Controller.
Non-Recommended Installation