VTR8300 AND VC3000 | LINE-VOLTAGE FAN COIL ROOM CONTROLLERS AND RELAY PACKS
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components; the VTR8300 Room
Controller and the VC3000 Relay Pack. This solution allows existing line voltage wiring between the fan coil unit and temperature
controller to be re-used, thereby reducing overall costs and installation time.
The VC3000 Relay Pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional
horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers. The Relay Pack is
not required for the VT8300 Series models.
Commercial interface (local override)
Power
Part NumberDescriptionHumidityPIRZigBeeCommunication
3
VTR8350A5000B
VTR8350A5500B
VTR8350A5500BP
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
BACnet® fan coil Room Controller
Transformer Relay Packs for VTR8300 Series
Power
Part NumberDescription
VC3500E5000Transformer relay pack five relay fan outputs
VC3504E5000Transformer relay pack five relay fan outputs, and four inputs
VC3514E5000Transformer relay pack five relay outputs, smart VDC OCC output, and four inputs
VC3400E5000Transformer relay pack four relay outputs and smart VDC output
VC3404E5000Transformer relay pack four relay outputs, smart VDC output, and four inputs
VC3300E5000Transformer relay pack three relay fan outputs
ZigBee Pro Module for VT(R)8300 Series
Part NumberDescription
YesNoNoBACnet
YesYesNoBACnet
YesYesYesBACnet
®
®
®
Power
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
VCM8000V5000P
Release 20
Optional ZigBee Pro module for VT(R)8300 Series room controllers.
Page 4
4
Terminal Controller
Terminal Controller
To others
To others
13 - COM +
14 - COM -
VTR83xxA
VTR83xxA
13 - COM +
14 - COM -
VTR8300 | TERMINAL IDENTIFICATION AND FUNCTION
Terminal Identification
Terminal 4Tx – Rx Communication
Terminal 5Power Hot 7.0 VDC
Terminal 6Power Common
Ter min al 12ECM 0-10 VDC output
Terminal 13BACnet +
Terminal 14BACnet -
Terminal 16BI 1 ( Configurable )
Terminal 17BI 2 ( Configurable )
Terminal 18Scom
All VTR83xx
Terminal Equipment Controller
COMMUNICATION WIRING TO VC3XXXE RELAY PACK
VTR83xxA
Terminal Controller
4 - Tx / Rx
5 - 7 Vdc Power Hot
6 - Power Common
VC3504E
Relay Pack
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
VC3300E
Relay Pack
1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common
To other
VC3xxxE
Relay
Pack
Only ONE VC3xxxE Relay Pack with remote
monitoring inputs can be used under a single
VTR83xxA Controller. All other slave units must be
VC3xxxE Relay Pack(s) WITHOUT remote inputs. A
maximum of 10 VC3xxxE Relay Packs can be used
for a single VTR83xxA Room Controller.
From VTR83xxA to first VC3xxxE Relay Pack
• Uses existing or new field wires
• A minimum of 3 wires are required 14-18 Ga,
• Solid or Stranded, shield not necessary
From first VC3xxxE to all other slave
VC3xxxE Relay Pack(s)
• Uses existing or new field wires
• A minimum of 2 wires are required 14-18 Ga,
Solid or Stranded, shield not necessary
• Connect only two wires: Tx/Rx (1) and Power
Common (3).
• Installation Note:
The maximum distance between the SER8300
Room Controller and the SC3000 relay pack is
recommended at 50ft (15m) or less.
BACnet® Communication Shielded Wiring (if required)
• NOTE: See VTR8300 BACnet® integration manual for more details
Network Wiring Topology
Star Topology
Daisy Chained Topology
Mixed Daisy Chained & Star Topology
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 5
VT8300 LOW-VOLTAGE 24 VAC FAN COIL ROOM CONTROLLERS
This new cost-effective solution for upgrading low-voltage fan coil unit thermostats requires only the VT8300 Room Controller.
The VT8300 Room Controller can also be used along with a SC1300 or SC2300 Relay Pack for mixed-voltage solutions, when control
of both line-voltage and low-voltage end devices is required.
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
Part NumberDescriptionHumidityPIRZigBeeCommunication
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote
PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 11
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
11
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
GRN
YEL
ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closed.
Wireless Door Switch and Motion
Wireless door switch automatically toggles occupancy to standby.
Motion will switch to occupied as long as the door stays closed
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Can be configured for 2-pipe systems (without changeover).
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, or remote
night setback.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 12
12
VTR8350A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH
3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8350
3 Speed Fan
Airow Direction
Cooling CoilElectric Heating
2 POSITION
COOLING VALVE
VC3404E5000
SOLID STATE RELAY
SSR
(GENERIC)
Configuration
parameter name
Fan control3 speed
Fan menuL-M-H-A
Fan cont. heatOn
Pulsed heatingOn
Pipe no. 2
Seq. operationCool - Rht
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration settings
Page 13
VTR8350
Tx / Rx
7 VDC
13
VC3404E5000
1
Tx/Rx
2
7 Vdc
Com
Com
3
4
5
6
7
8
9
10
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
WHT
BLK
RED
BLU
GRN
YEL
ORG
BACnet+
SOLIDSTATE
RELAY
(4-32Vdc)
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
NOTE: See Appendix B for VC3400
wiring to fan coil
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 14
14
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on”
low (red), medium (blue) or high (brown) speed.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 15
VTR83X0A5X00B WITH VC3504E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/
COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN
15
VTR83X0
Onboard
PIR Sensor
3 Speed Fan
Airow Direction
VC3504E5000
Cooling / Heating CoilSupply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Configuration
Parameter Name
Configuration Settings
Fan control3 speed
Fan MenuL-M-H-A
Fan contOn
BI1Window
RUI1COS
Pipe No 2
Seq. operationCool
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 16
16
VTR83X0
BACnet+
VC3504E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
GRN
YEL
ORG
10K type 2
10K type 2
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens
to maintain room temperature, else valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve
opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/cooling
when window is opened.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 17
17
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on”
low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 18
18
VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED
FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
Fresh Air
DAMPER
VTR83X0
Return Air
3 Speed Fan
Airow Direction
VC3514E5000
COOLING VALVE / HEATING VALVE
C/O
SENSOR
10K OHM TYPE 2
Cooling / Heating CoilSupply Sensor
2 POSITION
SUPPLY SENSOR
10K OHM TYPE 2
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Fan cont. heatOn
RUI1COS
Pulsed HeatingOcc Out
Pipe no. 2
Seq. operationCool
Configuration Settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 19
VTR83X0
BACnet+
19
VC3514E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
OCC -
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
GRN
YEL
ORG
For 7 Vdc SSR
Fresh Air Damper
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The occupancy output opens fresh air damper to
minimum position.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve
opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating
valve opens to maintain room temperature, else the valve closes.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is
connected.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 20
20
VTR83X0A5X00B WITH VC3500E5000 AND VC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL
UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
VTR83X0
3 Speed Fan
Airow Direction
VC3300E5000
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Fan cont. heatOn
Pipe No 4
Seq. operationHt-Cl
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 21
VC3500E5000T
21
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
1
2
Com
3
WHT
BLK
RED
BLU
GRN
YEL
ORG
VC3300E5000
1
2
3
NOTE: See Appendix B for VC3500
wiring to fan coil
SCom
WHT
BLK
RED
BLU
GRN
YEL
ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Can be configured for 2-pipe systems without changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 22
22
VTR83X0A5X00B WITH VC3504E5000 RELAY: HEATING/COOLING WITH CHANGEOVER SENSOR
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
Window Switch
SED-WIN-P-5045
3 Speed Fan
Airow Direction
Cooling / Heating CoilSupply Sensor
VTR83X0
Onboard
PIR Sensor
VC3504E5000
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Configuration Parameter
Name
Fan control3 speed
Fan menuL-M-H-A
Fan cont. heatOn
BI1Window
RUI1COS
Pipe no. 2
Seq. operationCool
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 23
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
23
VC3504E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
GRN
YEL
ORG
BI1 (Window)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 24
24
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for
service or filter monitoring.
• Universal input can be configured for changeover sensor.
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires are not energized. On demand, system will automatically switch “on”
low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 25
VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED
AND / OR
OR*
FAN AND 2-POSITION VALVES
25
VTR83X0
Onboard
PIR Sensor
3 Speed Fan
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Door Switch
SED-DOR-P-5045
Wired Remote
PIR Sensor
Configuration
Parameter Name
Wireless Remote
PIR Sensor
Configuration Settings
Fan control3 speed
Fan menuL-M-H-A
Fan cont. heatOn
BI1Motion NO or Motion NC (remote PIR sensor only)
BI2Door Dry
Pipe No 4
Seq. OperatHt-Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 26
26
VTR83X0
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
SCom
3
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
GRN
YEL
ORG
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Door Switch and Motion
Door switccs occupancy to standby. Motion will switch to
occupied as long as door stays closed.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Models available with factory installed PIR sensor.
• Can be configured for 2-pipe systems without changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring
3 Speed Fan Operation
System Off
Brown, blue and red wires are not energized
System On: (Fan modes)
• Low: red wire is energized
• Med: blue wire is energized
• High: brown wire is energized.
• Auto: When there is no demand, brown, blue and red wires
are not energized. On demand, system will automatically
switch “on” low (red), medium (blue) or high (brown) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 27
VTR83 ECM
Page 28
28
VTR83
ECM FAN APPLICATIONS
SystemFanCoolingHeatingOther
4 pipesECM2 positions valve2 positions valveDoor and motion detect
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 29
VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/
COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN AND 2-POSITION VALVES
29
VTR83X0
Onboard
PIR Sensor
ECM Fan
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
AND / OR
OR*
Wired Remote
PIR Sensor
Configuration
Parameter Name
Fan controlECM
Fan MenuL-M-H-A
Fan cont. heat.On
BI1Motion NO or Motion NC (remote PIR sensor only)
BI2Door Dry
Pulsed heatingOff
Pipe no. 4
Seq. operationHt - Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Wireless Remote
PIR Sensor
Configuration Settings
Page 30
30
VTR83X0
BACnet+
VC3500E5000
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
UI 17 - BI2
SCom
0-10Vdc
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
3
NOTE: See Appendix B for VC3500
wiring to fan coil
WHT
BLK
RED
BLU
BRN
YEL
ORG
(-)
(+)
ECM FAN
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 31
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Can be configured for 2-pipe systems (without changeover).
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, or remote night setback
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
31
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 32
32
VTR8350A5X00B WITH VC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH
ECM FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8350
ECM Fan
Airow Direction
Cooling CoilElectric Heating
2 POSITION
COOLING VALVE
VC3404E5000
SOLID STATE RELAY
SSR
(GENERIC)
Configuration
parameter name
Fan controlECM
Fan menuL-M-H-A
Fan cont. heatOn
Pulsed heatingOn
Pipe no. 2
Seq. operationCool-Rht
Configuration settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 33
VTR8350
WHT
Tx / Rx
7 VDC
33
VC3404E5000
1
Tx/Rx
2
7 Vdc
Com
Com
0-10Vdc
3
4
5
6
7
8
9
10
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
BLK
RED
BLU
BRN
YEL
ORG
BACnet+
SOLIDSTATE
RELAY
(4-32Vdc)
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
(-)
(+)
(-)
(+)
ECM FAN
NOTE: See Appendix B for VC3400
wiring to fan coil
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 34
34
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 35
VTR83X0A5X00B WITH VC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED
FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
35
Fresh Air
DAMPER
VTR83X0
Return Air
ECM Fan
Airow Direction
VC3514E5000
Changeover Sensor
10k Ohm type 2
SENSOR
Cooling / Heating Coil
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Supply Sensor
10k Ohm type 2
Configuration
Parameter Name
Fan controlECM
Fan menuL-M-H-A
Fan cont. heatOn
RUI1COS
Pulsed HeatingOcc Out
Pipe no. 2
Seq. operationCool
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 36
36
VTR83X0
BACnet +
BACnet -
BACnet REF
Tx / Rx
BI 1
7 VDC
BI 2
Com
Common
0-10VDC
ECM Fan
(+)
(−)
1
Tx/Rx
2
7 Vdc
Com
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
OCC -
NOTE: See Appendix B for VC3500
wiring to fan coil
VC3514E5045
WHT
BLK
RED
BLU
GRN
YEL
ORG
7 Vdc for SSR
Fresh Air Damper
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum
position.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 37
37
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 38
38
VTR83X0A5X00B WITH VC3504E5000 RELAY: COOLING AND ELECTRIC HEAT
2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
Window Switch
SED-WIN-P-5045
ECM Fan
Airow Direction
Cooling / Heating CoilSupply Sensor
VTR83X0
Onboard
PIR Sensor
VC3504E5000
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Configuration Parameter
Name
Fan controlECM
Fan menuL-M-H-A
Fan cont. heatOn
BI1Window
RUI1COS
Pipe no. 2
Seq. operationCool
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 39
39
ECM Fan
VTR83X0
BACnet+
BI1 (Window)
(+)
(-)
1
Tx/Rx
2
7 Vdc
Com
Com
7 VDC
Tx / Rx
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
0-10 VDC
SCom
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
NOTE: See Appendix B for VC3500
wiring to fan coil
VC3504E5000
WHT
BLK
RED
BLU
BRN
YEL
ORG
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), cooling valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 40
40
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for
service or filter monitoring.
• Universal input can be configured for changeover sensor.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 41
VTR83X0A5X00B WITH VC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN
AND 2-POSITION VALVES
41
VTR83X0
Onboard
PIR Sensor
AND / OR
ECM Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
VC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Door Switch
SED-DOR-P-5045
OR*
Wired Remote
PIR Sensor
Configuration
Parameter Name
Fan controlECM
Fan menuL-M-H-A
Fan cont. heatOn
BI1Motion NO or Motion NC (remote PIR sensor only)
BI2Door Dry
Pipe No 4
Seq. OperatHt-Cl
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote
PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 42
42
VTR83X0
Tx / Rx
7 VDC
ECM Fan
(+)
(-)
1
Tx/Rx
2
7 Vdc
Com
Com
0-10 VDC
3
NOTE: See Appendix B for VC3500
wiring to fan coil
VC3500E5000
WHT
BLK
RED
BLU
BRN
YEL
ORG
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
BI2 (Door)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch And Motion
Door switch automatically toggles occupancy to Standby.
Motion will switch to Occupied, as long as the door stays closed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 43
43
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Can be configured for 2-pipe systems without changeover.
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or
provide alarms for service or filter monitoring.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized
• Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
2 pipes1 Speed2 positions valve actuatorNoneFresh air damper
See Appendix B for relay pack wiring.
Door and motion detect +
dehumidification
45
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 46
46
AND / OR
OR*
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, TRI-STATE FLOATING
VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
3 Speed Fan
VT8350
Onboard
PIR Sensor
Airow Direction
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
Wired Remote
PIR Sensor
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Control TypeFloating
UI16Motion NO or Motion NC (remote PIR sensor only)
UI17Door Dry
Pipe no.4
Seq. operationCool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Configuration Settings
Wireless Remote
PIR Sensor
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 47
47
VT8350
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
Floating Control + 3 Speed Fan
RH
- Close Cool V
BO8 - Aux Heat
UO9
UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
HEATING VALVE
Close Open Com.
COOLING VALVE
Close Open Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 48
48
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low
(BO2), medium (BO3) or high (B04) speed.
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 49
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 0-10 VDC ANALOG
VALVES AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
49
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
Onboard
PIR Sensor
Configuration
Parameter Name
Fan control3 speed
Control typeAnalog
Fan menuL-M-H-A
Pipe no.4
Seq. operationCool / Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 50
50
VT8350
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
Modulating Control +
RH
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
V
BO8 - Aux Heat
- Analog Heat
UO11
UO12 - Analog Cool
3 Speed Fan
HEATING VALVE
0-10 v 24 v Com.
COOLING VALVE
0-10 v 24 v Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 51
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low
(BO2), medium (BO3) or high (B04) speed.
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
51
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 52
52
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVES AND
DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Control TypeOn/Off
Pipe no.4
Seq. operationCool/Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 53
53
VT8350
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
On / Off Control + 3 Speed Fan
RH
- NC Cool V
UO9
BO8 - Aux Heat
UO10 - NC Heat V
UO11 - NO Cool V
UO12 - NO Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
HEATING VALVE
IF NC IF NO Com.
COOLING VALVE
IF NC IF NO Com.
oror
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 54
54
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are not energized. On demand, system will automatically switch “On” low
(BO2), medium (BO3) or high (B04) speed.
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 55
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH SINGLE SPEED FAN, 2-POSITION COOLING
VALVE AND FRESH AIR DAMPER FOR LOW VOLTAGE
55
Fresh Air
DAMPER
Return Air
VT8350
3-Speed Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Configuration
Parameter Name
Fan control3 speed
Fan menuOn-Auto
Control TypeOn/Off
BO8 AuxOutAux NO
Pipe no.2
Seq. operationCool only
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 56
56
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
C (Common)
1 2 3 4 5 6
1 2 3 4 5 6
On / Off Control +
RH
- Aux Heat
BO8
OU9 - NC Cool V
UO10 - NC Heat V
UO12 - NO Heat V
UO11 - NO Cool V
7 8 9 10 11 12
7 8 9 10 11 12
3 Speed Fan
FRESH AIR DAMPER
ON / OFF ACTUATOR
COOLING VALVE
L
S
IF NC IF NO Com.
or
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
13 14 15 16 17 18
13 14 15 16 17 18
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
19 20 21 22 23 24
19 20 21 22 23 24
UI 19
UI 20 - RS
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The auxiliary contact closes forcing fresh air damper to
open.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling. The auxiliary contact opens causing fresh air damper to
close completely.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter. The auxiliary contact closes forcing fresh
air damper to open.
On Call for Cool
Cooling valve opens.
On Call for Heat
Cooling valve closes.
FAN
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 4-pipe systems.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Can be configured for two speed or three speed fan control.
1 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• On: BO4 is energized.
• Auto: When there is no demand, BO4 is not energized. On
demand, BO4 will be energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 57
VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN, ANALOG COOLING
VALVE AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE
57
VT83X0
3 Speed Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration
Parameter Name
Fan control3 speed
Control typeAnalog
Fan menuL-M-H-A
BO8 Out Time0 = 15 Minute
BO8 AuxOutReheat
Pipe no.4
Seq. operationCool-rht
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 58
58
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Mod. & On / Off Control + 3 Speed Fan
- Aux Heat
BO8
V
HEATING VALVE
NC Com.
UO12 - Analog Cool
UO11 - Analog Heat
RH
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Analog valve starts modulating based on cooling demand.
On Call for Heat
Heating valve opens.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• Can be configured to single or two speed fan.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are
not energized. On demand, system will automatically switch
“On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 59
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 0-10VDC ANALOG
COOLING VALVE FOR LOW VOLTAGE
59
VT83X0
3 Speed Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Configuration
Parameter Name
fan control3 speed
Control typeAnalog
Fan menuL-M-H-A
Pipe no.2
Seq. operationCool only
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 60
60
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Modulating Control + 3-Speed Fan
RH
- Analog Heat
BO8 - Aux Heat
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
UO11
UO12 - Analog Cool
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 193
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach
setpoint.
On Call for Heat
Valve closes.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 4-pipe systems.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Can be configured to two or three speed fan.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are
not energized. On demand, system will automatically switch
“On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 61
VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, 2-POSITION VALVE
AND ELECTRIC REHEAT FOR LOW VOLTAGE
61
3 Speed Fan
VT83X0
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating
ON / OFF DUCT
HEATER
Configuration
Parameter Name
Configuration Settings
Fan control3 speed
Fan menuL-M-H-A
Control TypeOn/Off
BO8 Out Time0 = 15 Minute
BO8 AuxOutReheat
Pipe no.2
Seq. operationCool-rht
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 62
62
VT83X0
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
C (Common)
On / O Controlor+ 3 Speed Fan
RH
Close Cool V
BO8 - Aux Heat
UO9 -
UO10 - Close Heat V
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
S
L
IF NC IF NO Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The changeover sensor sends supply air temperature to
controller.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.
Options
• Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 4-pipe systems.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Can be configured to single or two speed fan.
3 speed Fan Operation
System Off
BO2, BO3 and BO4 are not energized
System On: (Fan modes)
• BO2 is energized.
• BO3 is energized
• BO4 is energized.
• Auto: When there is no demand, BO2, BO3 and BO4 are
not energized. On demand, system will automatically switch
“On” low (BO2), medium (BO3) or high (B04) speed.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 65
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, TRI-STATE FLOATING VALVES
AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
65
ECM Fan
VT8350
Onboard
PIR Sensor
Airow Direction
Cooling Coil
TRI-STATE
COOLING VALVE
Heating Coil
TRI-STATE
HEATING VALVE
AND / OR
OR*
Wired Remote
PIR Sensor
Configuration
Parameter Name
Fan controlECM
Fan menuL-M-H-A
Control TypeFloating
UI16Motion NO or Motion NC (remote PIR sensor only)
UI17Door Dry
Pipe no.4
Seq. operationCool / Heat
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
Wireless Remote
PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 66
66
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
C (Common)
BO1-Close Ht Vlve
1 2 3 4 5 6
1 5
13 14 15 16 17 18
13 14 15 16 17 18
Floating Control + ECM Fan
RH
- Close Cool V
BO8 - Aux Heat
UO9
UO11 - Open Cool V
UO12 - Open Heat V
7 8 9 10 11 12
7 10 1
19 20 21 22 23 24
19 20 21 22 23 24
UO10 - ECM 0-10 Vdc
HEATING VALVE
Close Open Com.
COOLING VALVE
Close Open Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low ambient lockout temperature, which is the cooling setpoint minus the
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 67
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4
• “fan start”is not energized. On demand, system will modulate from “low” to “high” voltages (adjustable from configuration menu)
and BO4 “fan start” is energized.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
67
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 68
68
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, 0-10 VDC ANALOG VALVES
AND DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
ECM Fan
Airow Direction
VT8350
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
Configuration
Parameter Name
Fan cotrolECM
Control typeAnalog
Fan menuL-M-H-A
Pipe no.4
Seq. operationCool / Heat
Onboard
PIR Sensor
Configuration Settings
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 69
69
VT8350
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
Modulating Control + ECM Fan
RH
7 8 9 10 11 12
7 9 1
CM
UO10 - E
BO8 - Aux Heat
UO11 - Analog Heat
UO12 - Analog Cool
19 20 21 22 23 24
HEATING VALVE
0-10 v 24 v Com.
COOLING VALVE
0-10 v 24 v Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 70
70
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low”
to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 71
VT8350U5X00B HEATING/COOLING 4-PIPE FAN COIL UNIT WITH ECM FAN, 2-POSITION VALVES AND
DEHUMIDIFICATION SEQUENCE FOR LOW VOLTAGE
71
ECM Fan
VT8350
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration
Parameter Name
Fan controlECM
Fan menuL-M-H-A
Control TypeOn/Off
Pipe no.4
Seq. operationCool/Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 72
72
VT8350
BO2 - Fan L
BO3 - Fan M
RC (24 Vac)
BO4 - Fan H
BO1-Close Ht V
1 2 3 4 5 6
13 14 15 16 17 18
C (Common)
On / Off Control + ECM Fan
RH
- NC Cool V
UO9
BO8 - Aux Heat
7 8 9 10 11 12
UO11 - NO Cool V
UO12 - NO Heat V
UO10 - ECM 0-10 Vdc
19 20 21 22 23 24
HEATING VALVE
IF NC IF NO Com.
OROR
COOLING VALVE
IF NC IF NO Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
(-)
(+)
ECM Fan
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 73
73
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low”
to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 74
74
VT83X0U5X00B COOLING WITH REHEAT 4-PIPE FAN COIL UNIT WITH ECM FAN, ANALOG COOLING VALVE
AND N.C ON/OFF HEATING VALVE FOR LOW VOLTAGE
VT83X0
ECM Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
Configuration
Parameter Name
Fan controlECM
Control typeAnalog
Fan menuL-M-H-A
BO8 Out Time0 = 15 Minute
BO8 AuxOutReheat
Pipe no.4
Seq. operationCool-rht
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 75
75
ECM Fan
SE83X0
BO2 - Fan L
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 1819 20 21 22 23 24
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
Mod. & On / Off Control + ECM Fan
RH
C (Common)
V
BO8 - Aux Heat
- Analog Heat
UO11
UO12 - Analog Cool
7 8 9 10 11 12
19 20 21 22 23 24
HEATING VALVE
NC Com.
COOLING VALVE
.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve starts modulating based on cooling demand.
On Call for Heat
Heating valve opens.
(−)
(+)
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 76
76
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• Can be configured to single or two speed fan.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low”
to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 77
VT83X0U5X00B COOLING ONLY 2-PIPE FAN COIL UNIT WITH ECM FAN AND 0-10VDC ANALOG COOLING
VALVE FOR LOW VOLTAGE
77
VT83X0
ECM Fan
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Configuration
Parameter Name
Fan controlECM
Control typeAnalog
Fan menuL-M-H-A
Pipe no.2
Seq. operationCool only
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 78
78
VT83X0
RC (24 Vac)
BO4 - Fan H
C (Common)
1 2 3 4 5 6
13 14 15 16 17 18
Modulating Control + ECM Fan
RH
- Analog Heat
BO8 - Aux Heat
7 8 9 10 11 12
UO11
UO12 - Analog Cool
UO10 - ECM 0-10 Vdc
19 20 21 22 23 24
COOLING VALVE
0-10 V 24V Com.
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(OPTIONAL)
UI 193
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.
(-)
(+)
ECM Fan
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 79
79
Options
• Wireless adapter modules are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 4-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
• Can be configured to two or three speed fan.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low”
to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 80
80
VT83X0U5X00B COOLING WITH REHEAT 2-PIPE FAN COIL UNIT WITH ECM FAN, 2-POSITION VALVE AND
ELECTRIC REHEAT FOR LOW VOLTAGE
ECM Fan
VT83X0
Airow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating
ON / OFF DUCT
HEATER
Configuration
Parameter Name
Fan controlECM
Fan menuL-M-H-A
Control TypeOn/Off
BO8 Out Time0 = 15 Minute
BO8 AuxOutReheat
Pipe no.2
Seq. operationCool-rht
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 81
81
VT83X0
BO2 - Fan L
1 2 3 4 5 6
1 2 3 4 5 6
13 14 15 16 17 18
13 14 15 16 17 18
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
On / Off Control + ECM Fan
RH
Close Cool V
BO8 - Aux Heat
UO9 -
UO11 - Open Cool V
UO12 - Open Heat V
UO10 - Close Heat V
7 8 9 10 11 12
7 8 9 10 11 12
19 20 21 22 23 24
19 20 21 22 23 24
COOLING VALVE
S
L
IF NC IF NO Com.
OR
FCU Low-voltage
TERMINAL BLOCK
COMM ON
24 VAC
FAN START
(Optional)
UI 19
UI 20 - RS
Common
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI22 - SS
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.
(-)
(+)
ECM Fan
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 82
82
Options
• Wireless adapter modules for BACnet models are available. (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 4-pipe systems.
• 3 universal inputs can be used and configured for advanced functionality as required by the application.
Can be configured to single or two speed fan.
ECM Fan Operation
System Off
UO12 = 0Vdc and BO4 (fan start) is not energized
System On: (Fan modes)
• Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• High: UO12 = 8.6 Vdc (adjustable from configuration menu) and BO4 “fan start” is energized.
• Auto: When there is no demand, UO12 = 0 Vdc and BO4 “fan start”is not energized. On demand, system will modulate from “low”
to “high” voltages (adjustable from configuration menu) and BO4 “fan start” is energized.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 85
MIX VOLTAGE VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL
UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION
SEQUENCE FOR LOW VOLTAGE
85
3-Speed Fan
VT8300
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
SC1300
Power supply
120 vac
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Pipe no.4
Seq. operationCool / Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 86
86
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO11
- Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Mix Voltage 120 volts
SC1300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply
120 Vac
COOLING VALVE
0-10v 24v Com.
HEATING VALVE
0-10v 24v Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The changeover sensor sends supply air temperature to
controller.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil
for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Universal input can be configured for changeover sensor.
Page 87
MIX VOLTAGE VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL
UNIT WITH HIGH VOLTAGE 3-SPEED FAN, AND 0-10 VDC ANALOG VALVES AND DEHUMIDIFICATION
SEQUENCE FOR LOW VOLTAGE
87
3-Speed Fan
VT8300
Airow Direction
Cooling Coil
ANALOG
COOLING VALVE
Heating Coil
ANALOG
HEATING VALVE
SC2300
Power supply
240 vac
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Pipe no.4
Seq. operationCool / Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 88
88
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO11
- Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Mix Voltage 240 volts
SC2300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply
240 Vac
COOLING VALVE
0-10v 24v Com.
HEATING VALVE
0-10v 24v Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating. The changeover sensor sends supply air temperature to
controller.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil
for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Universal input can be configured for changeover sensor.
Page 89
MIX VOLTAGE VT8350U5X00B AND SC1300 120 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT
WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE
89
3 Speed Fan
VT8350
Airow Direction
Cooling Coil
TRI-STATE
FLOATING VALVE
Heating Coil
TRI-STATE
FLOATING VALVE
SC1300
Power supply
120 vac
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Control TypeFloating
Pipe no.4
Seq. operationCool / Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 90
90
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8350
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO9 -
Close Cool V
UO10 - Close Heat V
UO11 - Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Floating Control Mix Voltage
SC1300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply
120 Vac
COOLING VALVE
Open Close Com.
HEATING VALVE
Open Close Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil
for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low
ambient lockout temperature, which is the cooling setpoint minus
the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Universal input can be configured for changeover sensor.
Page 91
MIX VOLTAGE VT8350U5X00B AND SC2300 240 VDC RELAY HEATING/COOLING 4-PIPE FAN COIL UNIT
WITH HIGH VOLTAGE 3-SPEED FAN, TRI-STATE FLOATING VALVES AND DEHUMIDIFICATION SEQUENCE
FOR LOW VOLTAGE
91
3 Speed High Voltage Fan
VT8350
Airow Direction
Cooling Coil
TRI-STATE
FLOATING VALVE
Heating Coil
TRI-STATE
FLOATING VALVE
SC2300
Power supply
240 vac
Configuration
Parameter Name
Fan control3 speed
Fan menuL-M-H-A
Control TypeFloating
Pipe no.4
Seq. operationCool / Heat
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Configuration Settings
Page 92
92
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8350
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
UO9 -
Close Cool V
UO10 - Close Heat V
UO11 - Analog Heat
UO12 - Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Floating Control Mix Voltage
SC2300
FAN HI
FAN MED
FAN LO
COMM ON
High Voltage Fan
Power supply
240 Vac
COOLING VALVE
Open Close Com.
HEATING VALVE
Open Close Com.
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and
heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and
heating.
Unoccupied Mode
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil
for reheat if necessary.
Dehumidification is only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Dehumidification is disabled if room temperature falls below low
ambient lockout temperature, which is the cooling setpoint minus
the configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes.
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Options
• Wireless adapter modules are available. (see Appendix B for
network wiring).
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• 3 universal inputs can be used and configured for advanced
functionality as required by the application.
• Universal input can be configured for changeover sensor.
Page 93
APPENDIX A - SE8000 PIR SENSOR DETAILS
Typical Savings of 10-30%
Ener gy Usage (K Wh)
93
Energy Savings
PIR can maximize
your energy
saving from 1030% by adjusting
temperature set
points in unoccupied
zones during
scheduled periods.
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
024681012141618202224
Time of Day (EST)
Typical ConsumptionPIR Thermostat Consumption Sa vings
50%
40%
Saving Percentage
30%
20%
10%
0%
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 94
94
APPENDIX B - OPTIONAL NETWORK SET-UP
TYPICAL WIRING EXAMPLES FOR 3 SPEED FAN
TYPICAL WIRING EXAMPLES FOR ECM FAN
Brown - Fan Start
(Optional)
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 95
95
Setpoints
e
Stand-by timer reset
Unoccupied timer reset
APPENDIX C - SCHEMATIC OF CONTROLLERS OCCUPANCY SEQUENCE OF OPERATION WITHOUT DOOR
SENSOR
26.5°C
Unoccupied cool
Stand-by cool
24.5°C
76°F
80°F
Occupied cool
Occupied heat
Stand-by heat
noccupied heat
Deadband
Movement detected
-
22°C
72°F
70°F
Deadband
Deadband
22°C
72°F
70°F
21°C21°C
Stand-by
time
66°F
19°C
Unoccupied
time
62°F
16.5°C
Into Stand-by mode
-
Into Unoccupied
mode
Next movement
detected
Tim
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 96
96
APPENDIX X - WIRELESS SENSORS
®
Wireless ZigBee
Fan Coil Room Controllers with SED Series ZigBee® Pro wireless switches can be used in stand-alone mode, or with integration
to a central management system, to allow for advanced functions such as central reservation and occupancy functions. Up to
ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a VTR8300 or VT8300
Room Controller
Note that if a ZigBee wireless window switch is used, the VT8300 Room Controller cannot also use a remote PIR motion sensor,
whether wired or wireless. Using one or more wireless remote PIR motion sensors means that a wired PIR motion sensor cannot be
used, and vice versa.
The SED Series sensors are factory delivered with batteries and are ready to be installed, configured, and used right out of the
box. Due to the extremely small current consumption of the sensors, the expected battery life is approximately 10 years, which is
equivalent to the battery shelf life.
Model Selection
Window SwitchDoor Switch
Pro Motion Sensors
Wireless door switchSED-DOR-P-5045
Wireless window switchSED-WIN-P-5045
Wireless window and door
switch
Wireless window/door
sensor
Wireless ceiling mounted
motion sensor
Wireless wall mounted
motion sensor
Wireless motion/
temperature/humidity
sensor
Wireless water leakage
sensor
SED-WDS-P-5045
SED-WDC-G-5045
SED-CMS-P-5045
SED-WMS-P-5045
SED-MTH-G-5045
SED-WLS-G-5045
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 97
97
Deployment
Placement of the Room Controller must be given consideration. It is recommended to install the Room Controller as close to a door
as possible (but not so as to be blocked by the door), or in an area with high occupant movement.
Ideally the Room Controller should be installed 5 feet (1.5 meters) above the floor surface to ensure maximum detection range is
achieved. As well, Room Controller placement should ensure the occupant crosses the lens beam in a perpendicular path within the
prescribed detection zone.
Example of Recommended Deployment
The below shows Room Controllers installed in ideal locations for two rooms.
The examination room shows one Room Controller installed adjacent to the door. In this area of the room, occupant traffic is high and
ensures the occupant will almost always cross the PIR detection path laterally and within the detection range.
The waiting room shows one Room Controller installed beside a door in the middle of the room. As shown in the diagram below,
occupant traffic is high in several areas of the room including the entrance, waiting room, access to the door and activity around the
reception desk. Moreover, for each case aforementioned, occupant movement almost always moves lateral to the PIR, which ensures
detection by the PIR, as well as respecting the PIR detection range of 20 feet (6 meters) at 140°, and 16 feet (5 meters) between 15°
to 30° laterally.
Recommended Installation
Viconics Technologies Inc. www.viconics.comsales@viconics.com
028-0444-06November 2018
Page 98
98
Example of Non-Recommended Deployment
The below shows four Room Controllers (two for each room) installed in non-ideal locations for the two rooms.
The examination room shows one Room Controller installed in a low traffic area near the door, and a second Room Controller installed
on the wall directly opposite the door. For the Room Controller installed in the corner wall, the PIR could be blocked by the opened
door, while occupant traffic cold also be minimal in this area of the room. For the second Room Controller installed opposite the door,
the PIR detection could fall outside the specified detection zone, while at the same time most occupant movement would be not be
lateral to the PIR, thereby not respecting optimal crossing patterns for PIR detection.
The waiting room shows one Room Controller installed in the corner of the room, and a second Room Controller installed beside the
reception area. For the Room Controller installed in the corner, the opening/closing of the door creates high probability that the
PIR would get blocked, and therefore, occupancy going undetected. For the Room Controller installed beside the reception area,
occupant traffic could fall outside the detection zone, and the receptionist would often be below the 5 foot recommended installation
height for the Room Controller.