User HMI - Hospitality 23
User HMI - Commercial 23
Other Functions 24
Customizable Color Options 25
Setpoint Adjustment 26
Service Views 29
Test Outputs Screen 31
Language Selection 32
2
HOME SCREEN DISPLAY
Date
Occupancy Status
Room Indoor
Temperature
Room Indoor Humidity
Outdoor Temperature
User Interface Guide
Hospitality user interface shown
VTR8300 Series
Time
System Status
Fan Status
Up Arrow
Raise Temperature Setpoint
Actual Setpoint
Down Arrow
Lower Temperature Setpoint
Help
Enter help screen
System Mode
Select system mode
Fan Mode
Select fan mode
Language
Select preferred language
Temperature Units
Select Celsius or Fahrenheit units
Short Network Message
Note: User HMI's are configurable, as such the following display functions can be enabled or disabled by setting
various parameters: Date, time, humidity, outdoor temperature, setpoint, buttons, etc.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Touch and hold this point
for 3 seconds to enter setup mode
Note: If a configuration / installer
password is activated to prevent
unauthorised access to the
configuration menu parameters, a
password entry prompt will appear
to prevent access to the device
configuration components.
SETUP SCREEN DISPLAY
Return to
home screen
Discover Mode The Controller will
become discoverable on the wireless
ZigBee® network for 1 minute (this
button is hidden if ZigBee® settings are
not configured)
Note: The "Network" button will not be displayed if
no BACnet® or ZigBee® card is installed.
Enter BACnet® & ZigBee® network settings
Enter parameter configuration menu
Enter setpoint & display settings
Enter status and service view
Enter output testing mode
Enable selected language(s)*
General Note:
Adjustable parameter
Nonadjustable parameter
Indicates invisible conditional
field. Appears based only
on model or presence of a
ZigBee® card
*only available in recent versions of firmware
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
ZIGBEE NETWORK SETTINGS(IF ZIGBEE NETWORK CARD IS INSTALLED)
Page 1 of 2
Note: To change the value of
a parameter, simply press on
the parameter name or value
and then use the arrow keys
to change the value.
User Interface Guide
ZigBee® Pro short address.
The address is generated
once the device joins a
ZigBee® network.
Only the last 4 digits in HEX
are showed
Status of controller
detecting a ZigBee®
network. Will display
Online when connected
successfully to network.
VTR8300 Series
PARAMETER DETAILS
Configuration parameters
default value
COM address
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254
ZigBee® Pan ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 1000
Previous
Page
Significance and adjustments
For wireless models, the use of the COM address is not mandatory. The
extended IEEE ZigBee® node address is used to identify the device on the
network.
The COM address is an optional useful way to identify a device on the
network.
This parameter (PAN ID) is used to link specific Terminal Equipment
Controllers to specific ZigBee® coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.
The valid range of available PAN ID is from 1 to 1000.
Next
Page
Back to
Setup Page
Change Value
( see note )
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
Range 1 to 500 for centralized networked applications using a ZigBee®
Coordinator.
Range 501 to 1000 is for stand-alone applications where there is no
ZigBee® Coordinator.
Channel selection
Default value = 10
Range is: 10 to 25
ZigBee® status
( read only )
Significance and adjustments
This parameter (Channel) is used to link specific Terminal Equipment
Controllers to specific ZigBee® coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 25.
( Not Det ): ZigBee® module not detected
( Pwr On ): ZigBee® module detected but not configured
( No NWK ): ZigBee® configured but no network joined
( Joined ): ZigBee® network joined
( Online ): Communicating
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Note: The display will return to the home screen when no activity is detected for 1 minute.
PARAMETER DETAILS (CONT'D)
Configuration parameters
default value
Permit join
Default value = On
Significance and adjustments
Changing this value to "Off" will lockout any new ZigBee® devices from
joining the network through this controller.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
"254" value will set BACnet®
network "Offline". To activate
"Online", choose a different
value
Indicates the controller
status on the network
PARAMETER DETAILS
Configuration parameters
default value
COM address
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254
Network units
Default value = Imperial
Network lang.
Default value = English
Baud rate
Default value = Auto
Significance and adjustments
For BACnet® MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet® communication for the Terminal
Equipment Controller.
(Imperial): Network units shown as “imperial” units.
(Si): Network units shown as “international metric” units.
Choice of network language / object names that will be transmitted over
the network.
Other choices: (French) (Spanish).
(Auto): Will automatically detect the BACnet® MS/TP baud rate.
Other choices: (115200) (76800) (57600) (38400) (19200) (9600).
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Note: The default BACnet® instance
number is generated by the model
number and COM address of the
controller.
Example: The instance number of a
VTR8300A500Bwith a COM address
of 57 will be generated as "83057".
User Interface Guide
Instance number
of the controller.
The default instance number
will appear first. To change
the instance number, use the
number pad and then press
to save changes made.
To reset to automatic instance
addressing, press
VTR8300 Series
Back to
Setup Page
Accept. and save
Reset to automatic
instance addressing
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Binary input no.1 configuration
Default value = None
Significance and adjustments
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Rem NSB): Remote NSB timer clock input. The scheduling will now be
set as per the binary input. It provides low cost setback operation via a dry
contact.
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions using a
Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APPPIR-Guide-Exx. This document will provide the installers and system
designers with detailed examples on applications, parameter configuration
information, sequence of operation, troubleshooting and diagnostic help
required for the proper usage of the PIR accessory covers.
(Window) EMS: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode stays the
same and the current setpoints are the same Occupied setpoints. Only
the outputs are disabled. There is a Door/Window alarm displayed on the
Terminal Equipment Controller to indicate to the local tenant that the door/
window needs to be closed for cooling or heating to resume.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Door Dry): Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or a PIR
accessory cover is used.
With this sequence enabled, the occupancy is now dictated through those
2 inputs. Any motion detected will set the zone to occupied status. The
zone will remain permanently in occupied mode until the door contact
switch opens momentarily. The Terminal Equipment Controller will then
go in stand-by mode. If more movements are detected, the occupied
mode will resume. While the door is opened, any movements detected by
the remote PIR sensor or the PIR accessory cover will be ignored. Use a
Normally Closed contact switching device.
• Contact opened = Door opened
• Contact closed = Door closed
(Override): A temporary close contact on input BI 2 will override temporally
to occupied mode.
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Filter): "Filter alarm" will be displayed on the Terminal Equipment Controller
LCD screen when the input is energized. It can be tied to a differential
pressure switch that monitor filters.
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): "Service alarm" will be displayed on the Terminal Equipment
Controller LCD screen when the input is energized. It can be tied in to the
AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
(COC/NH) Change over dry contact. Normally Heat: Used for hot / cold
water or air change over switching in 2 pipe systems.
Contact closed = Cold water or air present
Contact opened = Hot water or air present
Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No )
set as 2 pipes.
(COC/NC) Change over dry contact. Normally Cool: Used for hot / cold
water or air change over switching in 2 pipe systems.
Contact closed = Hot water present
Contact opened = Cold water present
Only used and valid if system is setup as 2 pipes. Parameter (Pipe No )
set as 2 pipes.
(COS) Change over analog sensor: Used for hot / cold water or air change
over switching in 2 pipe systems.
Only used and valid if system is setup as 2 pipes. Parameter (Pipe No )
set as 2 pipes.
If water temperature is > 26 °C ( 78 °F )= Hot water present
If water temperature is < 24 °C ( 75 °F )= Cold water present
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Remote Binary input
no.2 configuration
Default value = None
Occupancy cmd
Significance and adjustments
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Filter): "Filter alarm" will be displayed on the Terminal Equipment Controller
LCD screen when the input is energized. It can be tied to a differential
pressure switch that monitor filters.
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): "Service alarm" will be displayed on the Terminal Equipment
Controller LCD screen when the input is energized. It can be tied in to the
AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
(Loc Occ): Occupancy is determined by local sequences
(Occupied): Force occupied mode
(Unoccup): Force unoccupied mode
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Enables Auto menu
for Mode button
Default value = On
Fan menu
Mode button menu
configuration
Default is: On-Auto
Significance and adjustments
Enables Auto function for the mode button
For sequences 2, 4 & 5 only
On = Auto active (Off-Cool-Heat-Auto)
Off = auto not active (Off-Cool-Heat)
Menu presented are dependent on model used and sequence of operation
selected.
(L-M-H): 3 Speed configuration using 3 fan relays.
(L-H): 2 Speed configuration using 2 fan relays.
(L-M-H-A): 3 Speed configuration with Auto fan speed mode using 3 fan
relays.
(Auto Mode operation is dependent on Auto Fan parameter).
(L-H-A): 2 Speed configuration with Auto fan speed mode using 2 fan
relays.
(Auto Mode operation is dependent on Auto Fan parameter).
(On-Auto): Single Speed configuration. Auto is for Fan on demand / On is
On all the time.
Auto fan func.
Auto Fan Function
Default value: AS
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
(AS): Auto Speed during occupied periods. Fan is always on during
occupied periods.
(AS AD): Auto Speed / Auto Demand during occupied periods.
(On): the controller in all cases will always control the fan (terminals LowMed—Hi Fan Speed). Valid in any fan sequences and all the available fan
modes.
(Off Auto): the controller in all cases will disable the fan (any terminals LowMed—Hi Fan Speed). ONLY when the local fan mode is set to Auto. Valid
in all fan sequences with auto mode.
(Off All): the controller in all cases will disable the fan (any terminals LowMed—Hi Fan Speed). When the local fan mode is set to ANY mode. Valid
in all fan sequences and all local fan modes.
Choose which standby setpoints are used for control.
(Abs): “Absolute” Standby entered values are used for standby mode.
(Offset): “Offset” Occupied setpoints +/- “Standby diff.” is used for standby
mode.
When “Standby mode” is “Relative”, standby setpoints are calculated as:
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
These parameters are model
dependent and may not appear
on certain models.
User Interface Guide
VTR8300 Series
PARAMETER DETAILS
Configuration parameters
default value
Standby time
Default 0.5 hours
Unocc. time
Default 0.0 hours
Temp. occ. time
Default value = 2 hours
Deh. hysteresis
Default value = 5 % RH
Significance and adjustments
Time delay between the moment where the PIR cover detected the
last movement in the area and the time which the Terminal Equipment
Controller stand-by setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5 hours increments.
Time delay between the moment where the Terminal Equipment Controller
toggles to stand-by mode and the time which the Terminal Equipment
Controller unoccupied mode and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its default value
of 0.0 hours disables the unoccupied timer. This prevents the Terminal
Equipment Controller to drift from stand-by mode to unoccupied mode
when PIR functions are used.
Range is: 0.0 to 24.0 hours in 0.5 hours increments.
Temporary occupancy time with occupied mode setpoints when override
function is enabled.
When the Terminal Equipment Controller is in unoccupied mode, function
is enabled with either the menu or UI2 configured as remote override input.
Range is: 0 to 24 hours in 1 hour increments.
Humidity control hysteresis. Used only if dehumidification sequence is
enabled:
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Maximum cooling valve position when dehumidification is enabled. This
can be used to balance smaller reheat loads installed in regards to the
capacity of the cooling coil.
Range is: 20 to 100 %.
(Models with humidity sensor only).
Dehumidification lockout, typically toggled through the network.
This variable enables or disables dehumidification based on central
network requirements from the BAS front end.
Enabled = Dehumidification Authorized
Disabled = Dehumidification Not Authorized
(Models with humidity sensor only).
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Cooling output cycles per hour. Will set the maximum number cycles per
hour under normal control operation. It represents the maximum number
of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the
expense of wearing mechanical components faster.
Range is: 3, 4, 5, 6,7 & 8 C.P.H.
Heating output cycles per hour. Will set the maximum number cycles per
hour under normal control operation. It represents the maximum number
of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the
expense of wearing mechanical components faster.
Range is: 3, 4, 5, 6,7 & 8 C.P.H.
Set’s the type of valve used for cooling
NC = Valve is normally closed when no power is present.
NO = Valve is normally opened when no power is present.
Set’s the type of valve used for heating.
NC = Valve is normally closed when no power is present.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
NO = Valve is normally opened when no power is present.
Proportional band setting. Adjusts the proportional band used by the
Terminal Equipment Controller PI control loop.
Warning: Note that the default value of 3.0 gives satisfactory operation
in most normal installation cases. The use of a superior proportional band
different than the factory one is normally warranted in applications where
the Terminal Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall mounted unit
where the Terminal Equipment Controller is installed between the return
and supply air feeds and is directly influenced by the supply air stream of
the unit.
Effective
Proportional band
Value °F °C
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6
Pulsed heating
Default Value = Off
VDC output configuration. VC3000 series model dependent.
Off = Regular On-Off control for VC350xE models only.
Can be used with 2 & 4 pipes applications.
On = VDC SSR electric heat 10 second pulsed time base modulation for
SC340xE models only.
Can only be used with 2 pipes system only.
Occ Out = VDC Occupancy output follows local device occupancy for
SC3514E model only.
Occupied & Temporary Occupied = Contact closed
Stand-By & Unoccupied = Contact opened
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
System type installation: Number of pipes. Defines the type of system
installed.
Selects the initial sequence of operation required by the installation type
and the application.
2 Pipes4 Pipes
Cooling onlyCooling only
Heating onlyHeating only
Cooling with electric reheatHeating / Cooling
Heating with electric reheat---
Electric reheat only---
For 2 Pipe output applications, the system access is limited if RUI 1 is
configured for local changeover COS, COC/NC or COC/NC. The current
water temperature detected by the RUI 1 then limits the system mode
available for the local configuration or network write.
For sequence “electric reheat”, set PulsedHt to "On" to enable pulsed
electric reheat applications with SC3400E & SC3404E.
Time interval between valve samples. Will open valve for a short period
(adjusted by “Purge open” parameter to sample pipe temperature (to
decide between heating or cooling mode).
Purge open
Default is: 2 min
Adjustable for 0 to 4 hrs.
(0 = disable this function).
Time the valve will open to sample pipe temperature (to decide between
heating or cooling mode).
Adjustable for 1 to 3 min.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Parameter only displayed on
models with built in humidity
sensor.
19
PARAMETER DETAILS
Configuration parameters
default value
Main password
Default value = 0
User password
Default value = 0
Calib. temp.
Default value = 0.0 °C or °F
Calib. humid.
Default value = 0 %RH
Significance and adjustments
Installer’s password. This parameter sets a protective access password
to prevent unauthorized access to the configuration menu parameters. A
default value of “0” will not prompt a password or lock the access to the
configuration menu.
Range is: 0 to 9999.
User’s password. This parameter sets a protective access password to
prevent user unauthorized access to main screen adjustments. A default
value of “0” will not prompt for a password.
Range is: 0 to 9999.
Room temperature sensor calibration. Offset that can be added/
subtracted to actual displayed room temperature.
Range is: ± 2.5 °C, 0.1 °C increments ( ± 5.0 °F, 0.1 °F increments ).
Humidity sensor calibration. Offset that can be added/subtracted to actual
displayed humidity.
Range is : ± 15.0 %RH.
(Models with humidity sensor only).
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Answering “Yes” to these two questions and pressing the “Accept” button,
will erase all values to factory’s default values except networked related
values:
COM address, ZigBee® Pan ID, ZigBee® channel, Network units, Network
lang., Baud rate, BACnet® instance, Device name.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Standby cooling setpoint. The value of this parameter should be set
between the occupied and unoccupied cooling setpoints. Make sure that
the difference between the stand-by and occupied value can be recovered
in a timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range is: 12.0 to 37.5 °C ( 54 to 100 °F ).
Cooling setpoint range is:
12.0 to 37.5 °C ( 54 to 100 °F ).
Heatling setpoint range is:
12.0 to 37.5 °C ( 54 to 100 °F ).
Stand-by heating setpoint. The value of this parameter should be set
between the occupied and unoccupied heating setpoints. Make sure that
the difference between the stand-by and occupied value can be recovered
in a timely fashion when movement is detected in the zone.
Unocc. heat.
Default value = 16.5 °C
( 62 °F )
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
Stand-by heating setpoint range is: 4.5 to 32.0 °C ( 40 to 90 °F ).
Parameter only displayed on
models with built in humidity
sensor.
User Interface Guide
VTR8300 Series
PARAMETER DETAILS
Configuration parameters
default value
Default heat
Default value = 22.0 °C
( 73 °F )
Min. deadband
Default value = 1.5 °C
( 3.0 °F )
Max heating
Default value = 32.0 °C
( 90.0 °F )
Min. cooling
Default value = 12.0 °C
( 54.0 °F )
Significance and adjustments
This function is used for hospitality applications in stand-alone mode only.
When the devices is in deep unoccupied mode, any movement detected
by the PIR will reset the actual occupied set points to the “fresh room”
default setting.
This default setpoint is used to write to the “Heating setpoint” when the
thermostat goes to “Unoccupied” mode. Cooling setpoint will be set
according to the “Min. deadband”. 18.0 to 26.5 °C ( 65 to 80 °F ).
This parameter is only used when “Stand-by mode” = “Rel”.
Minimum deadband value between the heating and cooling setpoints.
It will be applied only when any of the setpoints are modified.
Range is: 1.0 to 2.5 °C, 0.5 °C increments ( 2, 3, 4 or 5 °F,
1.0 °F increments ).
Maximum occupied & unoccupied heating setpoint adjustment.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
Dehumidification setpoint. Used only if dehumidification sequence is
enabled:
These parameters are model dependent and may not appear on certain models.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
These parameters are model dependent and may not appear on certain models.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
RH Display = Configuration + model dependent
Outdoor Temp = When set by network
25
If main display parameter
is set to "setpoint",
the setpoint value will
display as shown:
On/Off will display
when the sequence
of operation is set to
heating or cooling only
Heating only
Time and Date will
display only if it has
been properly set
(from the network)
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Cooling mode or cooling only
sequence of operation
In Cooling mode, the setpoint displayed in the bar is the
current occupied cooling setpoint.
During occupied setpoint adjustment, the large digits are
temporarily used to display the occupied cooling setpoint
while it is adjusted.
Normal temperature display resumes after the setpoint
is adjusted and the actual occupied cooling setpoint is
displayed in the setpoint bar.
Heating mode or heating only
sequence of operation
VTR8300 Series
In Heating mode, the setpoint displayed in the bar is the
current occupied heating setpoint.
During occupied setpoint adjustment, the large digits are
temporarily used to display the occupied heating setpoint.
Normal temperature display resumes after the setpoint
is adjusted and the actual occupied heating setpoint is
displayed in the setpoint bar.
Automatic Heating / Cooling mode
In automatic mode, the setpoint displayed at the top
of the set point bar located directly under the blue line
represent the actual occupied cooling setpoint.
During occupied setpoints adjustment, the large digits
are temporarily used to display the occupied “Cooling
Setpoint” or occupied “Heating Setpoint”. The actual
setpoint is dependent on the last effective demand
(heating or cooling).
Normal temperature display resumes after the setpoints
are adjusted and the actual occupied heating and
cooling setpoints are displayed in the setpoint bar.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Select default value displayed on main display: Temperature or setpoint.
Default value = Temp.
Choices: Temperature or setpoint.
Disp. cust. img.
Default value = No
Selecting "Yes" will display a custom image after 2 minutes of touch
screen inactivity.
Customisablecolour options
BlueGreenDark Grey
GreyWhite
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Parameter only displayed on
models with built in humidity
sensor.
User Interface Guide
VTR8300 Series
PARAMETER DETAILS
Configuration parameters
default value
Language
Default value = English
°C or °F
Default value = °C
Low backLight
Default value is 60%
Night backLight
Default value = 5%
RH display
Default value = Disabled
Significance and adjustments
Select language for main display.
Choices: English, French, Spanish, Chinese.
This sets the default value when the Terminal Equipment Controller powers
up.
°C for Celsius scale.
°F for Fahrenheit scale.
Set the display’s backlight intensity after 2 minutes of keyboard inactivity.
Adjustable from: 0 to 100%.
Set the display’s backlight intensity after 2 minutes of keyboard inactivity.
Adjustable from: 0 to 100%.
(This parameter is only available for models with motion/light detectors.
The screen backlight will progessively decrease down to this setting when
room is dark).
Enables the display of humidity below the room temperature on the display
(On): Display %RH.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
The service view screens show the current status of certain points locally at the
controller. These points can also be viewed through the network.
Firmware revision
of the controller
Changeover temperature
Outdoor temperature
29
Room temperature
Supply temperature
Room Humidity
Effective occupancy
PI cooling demand
PI heating demand
Cooling demand limit
Heating demand limit
Parameter only displayed on
models with built in humidity
sensor.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Parameter only displayed on
models with built in humidity
sensor.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Note: This represents
BACnet® device name
automatically assigned
using the current BACnet®
MAC address.
The network can
update and change the
device BACnet® name.
If changed, the new
updated BACnet® device
name will be shown
VTR8300 Series
31
TEST OUTPUTS SCREEN
1/1 Test outputs
Cooling output
( see note 1 )
High speed
fan output
Low speed
fan output
Note 1: Cooling output can also be used for heating on two pipes systems.
See note 2
Heating output
Medium speed
output
Pulsed heating
demand
Note 2: The test output screen allows manual override of specified outputs. When any BACnet® network
priority array includes a value, the status background is shown in red. After any output state is overridden, the
command is cancelled after 1 min of screen inactivity (auto exit to main screen) or when page is exited. Please
refer to the BACnet® integration guide for more details.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
All languages are enabled by default, which means that they will be accessible to users cycling through languages on the
display settings menu screen. To change the language selection settings, touch a language on the screen and then use the
arrow buttons to disable or enable it. The English language is always enabled.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com