User HMI - Hospitality 23
User HMI - Commercial 23
Other Functions 24
Customizable Color Options 25
Setpoint Adjustment 26
Service Views 29
Test Outputs Screen 31
Language Selection 32
2
HOME SCREEN DISPLAY
Date
Occupancy Status
Room Indoor
Temperature
Room Indoor Humidity
Outdoor Temperature
User Interface Guide
Hospitality user interface shown
VTR8300 Series
Time
System Status
Fan Status
Up Arrow
Raise Temperature Setpoint
Actual Setpoint
Down Arrow
Lower Temperature Setpoint
Help
Enter help screen
System Mode
Select system mode
Fan Mode
Select fan mode
Language
Select preferred language
Temperature Units
Select Celsius or Fahrenheit units
Short Network Message
Note: User HMI's are configurable, as such the following display functions can be enabled or disabled by setting
various parameters: Date, time, humidity, outdoor temperature, setpoint, buttons, etc.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Touch and hold this point
for 3 seconds to enter setup mode
Note: If a configuration / installer
password is activated to prevent
unauthorised access to the
configuration menu parameters, a
password entry prompt will appear
to prevent access to the device
configuration components.
SETUP SCREEN DISPLAY
Return to
home screen
Discover Mode The Controller will
become discoverable on the wireless
ZigBee® network for 1 minute (this
button is hidden if ZigBee® settings are
not configured)
Note: The "Network" button will not be displayed if
no BACnet® or ZigBee® card is installed.
Enter BACnet® & ZigBee® network settings
Enter parameter configuration menu
Enter setpoint & display settings
Enter status and service view
Enter output testing mode
Enable selected language(s)*
General Note:
Adjustable parameter
Nonadjustable parameter
Indicates invisible conditional
field. Appears based only
on model or presence of a
ZigBee® card
*only available in recent versions of firmware
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
ZIGBEE NETWORK SETTINGS(IF ZIGBEE NETWORK CARD IS INSTALLED)
Page 1 of 2
Note: To change the value of
a parameter, simply press on
the parameter name or value
and then use the arrow keys
to change the value.
User Interface Guide
ZigBee® Pro short address.
The address is generated
once the device joins a
ZigBee® network.
Only the last 4 digits in HEX
are showed
Status of controller
detecting a ZigBee®
network. Will display
Online when connected
successfully to network.
VTR8300 Series
PARAMETER DETAILS
Configuration parameters
default value
COM address
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254
ZigBee® Pan ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 1000
Previous
Page
Significance and adjustments
For wireless models, the use of the COM address is not mandatory. The
extended IEEE ZigBee® node address is used to identify the device on the
network.
The COM address is an optional useful way to identify a device on the
network.
This parameter (PAN ID) is used to link specific Terminal Equipment
Controllers to specific ZigBee® coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.
The valid range of available PAN ID is from 1 to 1000.
Next
Page
Back to
Setup Page
Change Value
( see note )
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
028-6045 -01 April 2014
Range 1 to 500 for centralized networked applications using a ZigBee®
Coordinator.
Range 501 to 1000 is for stand-alone applications where there is no
ZigBee® Coordinator.
Channel selection
Default value = 10
Range is: 10 to 25
ZigBee® status
( read only )
Significance and adjustments
This parameter (Channel) is used to link specific Terminal Equipment
Controllers to specific ZigBee® coordinators. For every Terminal Equipment
Controller reporting to a coordinator, be sure you set the SAME channel
value both on the coordinator and the Terminal Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 25.
( Not Det ): ZigBee® module not detected
( Pwr On ): ZigBee® module detected but not configured
( No NWK ): ZigBee® configured but no network joined
( Joined ): ZigBee® network joined
( Online ): Communicating
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Note: The display will return to the home screen when no activity is detected for 1 minute.
PARAMETER DETAILS (CONT'D)
Configuration parameters
default value
Permit join
Default value = On
Significance and adjustments
Changing this value to "Off" will lockout any new ZigBee® devices from
joining the network through this controller.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
"254" value will set BACnet®
network "Offline". To activate
"Online", choose a different
value
Indicates the controller
status on the network
PARAMETER DETAILS
Configuration parameters
default value
COM address
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254
Network units
Default value = Imperial
Network lang.
Default value = English
Baud rate
Default value = Auto
Significance and adjustments
For BACnet® MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet® communication for the Terminal
Equipment Controller.
(Imperial): Network units shown as “imperial” units.
(Si): Network units shown as “international metric” units.
Choice of network language / object names that will be transmitted over
the network.
Other choices: (French) (Spanish).
(Auto): Will automatically detect the BACnet® MS/TP baud rate.
Other choices: (115200) (76800) (57600) (38400) (19200) (9600).
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Note: The default BACnet® instance
number is generated by the model
number and COM address of the
controller.
Example: The instance number of a
VTR8300A500Bwith a COM address
of 57 will be generated as "83057".
User Interface Guide
Instance number
of the controller.
The default instance number
will appear first. To change
the instance number, use the
number pad and then press
to save changes made.
To reset to automatic instance
addressing, press
VTR8300 Series
Back to
Setup Page
Accept. and save
Reset to automatic
instance addressing
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
Binary input no.1 configuration
Default value = None
Significance and adjustments
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Rem NSB): Remote NSB timer clock input. The scheduling will now be
set as per the binary input. It provides low cost setback operation via a dry
contact.
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions using a
Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APPPIR-Guide-Exx. This document will provide the installers and system
designers with detailed examples on applications, parameter configuration
information, sequence of operation, troubleshooting and diagnostic help
required for the proper usage of the PIR accessory covers.
(Window) EMS: Forces the system to disable any current heating or
cooling action by the Terminal Equipment Controller. The mode stays the
same and the current setpoints are the same Occupied setpoints. Only
the outputs are disabled. There is a Door/Window alarm displayed on the
Terminal Equipment Controller to indicate to the local tenant that the door/
window needs to be closed for cooling or heating to resume.
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Door Dry): Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or a PIR
accessory cover is used.
With this sequence enabled, the occupancy is now dictated through those
2 inputs. Any motion detected will set the zone to occupied status. The
zone will remain permanently in occupied mode until the door contact
switch opens momentarily. The Terminal Equipment Controller will then
go in stand-by mode. If more movements are detected, the occupied
mode will resume. While the door is opened, any movements detected by
the remote PIR sensor or the PIR accessory cover will be ignored. Use a
Normally Closed contact switching device.
• Contact opened = Door opened
• Contact closed = Door closed
(Override): A temporary close contact on input BI 2 will override temporally
to occupied mode.
(None): No function will be associated with the input. Input can be used for
remote network monitoring.
(Filter): "Filter alarm" will be displayed on the Terminal Equipment Controller
LCD screen when the input is energized. It can be tied to a differential
pressure switch that monitor filters.
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): "Service alarm" will be displayed on the Terminal Equipment
Controller LCD screen when the input is energized. It can be tied in to the
AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
(COC/NH) Change over dry contact. Normally Heat: Used for hot / cold
water or air change over switching in 2 pipe systems.
Contact closed = Cold water or air present
Contact opened = Hot water or air present
Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No )
set as 2 pipes.
(COC/NC) Change over dry contact. Normally Cool: Used for hot / cold
water or air change over switching in 2 pipe systems.
Contact closed = Hot water present
Contact opened = Cold water present
Only used and valid if system is setup as 2 pipes. Parameter (Pipe No )
set as 2 pipes.
(COS) Change over analog sensor: Used for hot / cold water or air change
over switching in 2 pipe systems.
Only used and valid if system is setup as 2 pipes. Parameter (Pipe No )
set as 2 pipes.
If water temperature is > 26 °C ( 78 °F )= Hot water present
If water temperature is < 24 °C ( 75 °F )= Cold water present
Viconics Technologies Inc. I Sma ll Building S ystems I 9245 Langelier Blvd. Saint- Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660 I ww w.viconics.com