VTR8300 and SCs | Fan coil terminal equipment controllers 2
VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil
unit with 3-speed fan, 2-position valves with wireless door switch 4
VTR8350A5000 -VC3404E5000: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan, dehumidification, 2-position valves 6
VTR8300A5000 - VC3504E5000: Heating/cooling with changeover sensor:
2-pipe fan coil unit with 3-speed fan and wireless window switch 8
VTR8350A5000 - VC3400E5000: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan and dehumidification, 2-position valves 10
VTR8300A5500 - VC3514E5000: Heating/cooling: 2-pipe fan coil unit
with 3-speed fan and fresh air damper, 2-position valves 12
VTR8300A5000 -VC3500E5000 -VC3300E5000: Heating/cooling:
4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack 14
VTR8300A5000 - VC3504E5000: Cooling and electric heat:
2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch 16
VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit
with 3-speed fan, 2-position valves with wired door switch 18
Appendix A - Passive infra-red (PIR) motion detector cover specifications 20
Appendix B - option network wiring if communicating models are used 21
Appendix C - controllers’ occupancy sequence of operation schematic 21
Appendix D - SED Series - wireless door & window switch 22
Appendix E - VTR8300 controller & VC3000 relay pack 23
2
VTR8300 Fan Coil ControllerApplication Guide
OVERVIEW
VTR8300 & Relay Pack
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the VTR8300 terminal
equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature
controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power
supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire
costly pilot relays and transformers.
The VTR8300 Line Voltage Fan Coil Terminal Equipment Controller and SC3000 Relay Pack can be configured to handle a broad variety of
applications covering all the standard implementations necessary for controlling line-voltage HVAC systems.
In addition to controlling heating, cooling and fan activity, depending on the model the VTR8300 can handle wireless networking
and switches, passive infrared (PIR) occupancy detection using either onboard or remote sensors, and dehumidification control. The
applications described here cover all these features, and in combination with the VTR8300’s advanced scheduling and occupancy controls
can provide the functionality for any required line-voltage HVAC implementation.
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve
closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled
in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Options
•BACnet® and Wireless communication models available (see
Appendix B for network wiring).
•Remote wall mount or return duct sensor ready.
•Can be configured for 2-pipe systems with changeover.
•Binary inputs can be configured to control occupancy via door
or window contact, remote night setback, or provide alarms for
service or filter monitoring.
•Universal input can be configured for changeover sensor.
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled
in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Options
•BACnet® and Wireless communication models available (see
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Appendix B for network wiring).
•Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night
setback, or provide alarms for service or filter monitoring.
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve
closed and dehumidification is disabled.
VTR8300AXXXX WITH SC3500E5000 AND SC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT
WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
Airflow Direction
Fan
Cooling Coil
Heating Coil
VTR8300
SC3300E5000
Configuration
Parameter Name
Fan menuL-M-H-A
Fan cont. heatOn
Pipe No 4
Seq. operationHt-Cl
Typical ConsumptionPIR Thermos tat Consum ption Savings
VTR8300 Fan Coil ControllerApplication Guide
APPENDIX A - PASSIVE INFRA-RED (PIR) MOTION DETECTOR COVER SPECIFICATIONS
PIR cover sequence of operation
Initially, the controller is in Stand-by mode. Stand-by setpoints are used at the controller. As soon as the
PIR detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The
Occupied setpoints are used. If no motion is detected in the room for the entire Stand-By Time duration
(adjustable parameter), the room then switches to Stand-by mode and stand-by setpoints are used. While in
Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the
room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied
mode, any motion will switch the room back to Occupied mode.
Typical Detection Pattern for PIR Lens
Recommended installation
height for PIR sensor:
4 - 5 ft. / 1.2-1.5 m
Sensor Ranges
A = 20 ft. / 6.1 m
B = 14 ft. / 4.3 m
C = 11 ft. / 3.4 m
Horizontal Angles (Typical)
Transverse motion: 4-5 ft/s
O
40
A
/ 1.5 m/s
Center
Vertical Angle (Typical)
O
30
Energy savings
The PIR can maximize
your energy saving from
10-30% by relaxing
temperature set points in
unoccupied zones during
scheduled periods.
- If using 2 conductors shielded wires, connect the shield
of each feed together on the back of the controller. ONLY
ground the shield at one location. DO NOT connect the
shield to the ref terminal.
+
-
ref
+
-
ref
+
-
ref
Wireless Communication
No communication wires required
APPENDIX C - CONTROLLERS’ OCCUPANCY SEQUENCE OF OPERATION SCHEMATIC
APPENDIX D - SED SERIES - WIRELESS DOOR & WINDOW SWITCH
®
Wireless ZigBee
Wireless door switches used with an onbaord or remote PIR sensor provide advanced local occupancy
routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort.
Wireless window switches are used to monitor exterior windows and or patio and balcony doors being opened
or closed. This prevents unnecessary energy consumption by the tenants.
Fan Coil Terminal Equipment Controllers with SED Series ZigBee
network ready mode with or without integration to a central management system to allow for advanced
functions such as central reservation and occupancy functions.
A combination of up to twenty SED Series door and or window switches can be used simultaneously with a
single Fan Coil Terminal Equipment Controller.
The SED Series switches are factory delivered with 2 AAA batteries and are ready to be installed, configured
and used right out of the box. Due to the extremely small current consumption of the switches, the expected
battery life is approximately 10 years and is equivalent to the battery shelf life.
No tools are required for commissioning or servicing the door switch. A very simple interface with an onboard LED & hidden switch provides all the required functions for local interaction. Local information for
battery life and connectivity (heartbeat) are provided at the Fan Coil Terminal Equipment Controller local
display through the ZigBee
security tamper proof screw and self tapping mounting screws.
Pro door & window switch
®
wireless switches can be used in
®
wireless network. Each switch is factory supplied with a magnet, a locking
APPENDIX E - VTR8300 CONTROLLER & SC3000 RELAY PACK
Product overview
The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit
thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet
wireless ZigBee
®
Pro networked models.
No previous building automation training is required for the easy installation and commissioning process.
Installation can be completed in approximately fifteen minutes, reducing costs and providing increased
savings.
The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers has been designed for silent
control of typical high voltage fan coil device loads (90 to 277 VAC multi-voltages capable).
It uses advanced microprocessor-based circuitry with a built-in transformer that eliminates all typical required
peripheral components when automating a Fan Coil unit with traditional building automation systems.
The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the
control of a single master VTR8300 Terminal Equipment Controller.
A single VTR8300 Terminal Equipment Controller can control up to 10x SC3000 Series Relay Pack. The
SC3000 Series Relay Packs are line-powered units.
The extremely compact unit locally contains all the relay outputs for fan switching and valve control. Models
are also available for extra monitoring / control inputs of the Fan Coil Units.
®
MSTP or
23
Typical fan coil unit setup
Typical Fan Coil Unit
Low Voltage Connections
to VTR8300 Controller
H C
1
Tx/Rx
2
7 Vdc
Power
Com
3
Supply
SC3404E5000
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
Heat -
10
Heat +
90-277 Vac - 50/60 Hz
1/2HP + 5A Max Comb. or
13A+ 5A Max Comb
Amb. Temp. 50oC
FAN
LOW
1/2 HP
FAN
or 13A
MED
Max
FAN
HIGH
5A
COOL
Max
WHITE
BLACK
RED
BLUE
BROWN
YELLOW
Electrical
Cabinet
1
Tx/Rx
2
7 Vdc
Power
Com
3
Supply
4
RUI 1
xxx-xxxx-xx
SCom
5
WHITE
6
RBI 2
90-277 Vac - 50/60 Hz
1/2HP + 5A Max Comb. or
13A+ 5A Max Comb