VTR8300 and SCs | Fan coil terminal equipment controllers 2
VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil
unit with 3-speed fan, 2-position valves with wireless door switch 4
VTR8350A5000 -VC3404E5000: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan, dehumidification, 2-position valves 6
VTR8300A5000 - VC3504E5000: Heating/cooling with changeover sensor:
2-pipe fan coil unit with 3-speed fan and wireless window switch 8
VTR8350A5000 - VC3400E5000: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan and dehumidification, 2-position valves 10
VTR8300A5500 - VC3514E5000: Heating/cooling: 2-pipe fan coil unit
with 3-speed fan and fresh air damper, 2-position valves 12
VTR8300A5000 -VC3500E5000 -VC3300E5000: Heating/cooling:
4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack 14
VTR8300A5000 - VC3504E5000: Cooling and electric heat:
2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch 16
VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit
with 3-speed fan, 2-position valves with wired door switch 18
Appendix A - Passive infra-red (PIR) motion detector cover specifications 20
Appendix B - option network wiring if communicating models are used 21
Appendix C - controllers’ occupancy sequence of operation schematic 21
Appendix D - SED Series - wireless door & window switch 22
Appendix E - VTR8300 controller & VC3000 relay pack 23
2
VTR8300 Fan Coil ControllerApplication Guide
OVERVIEW
VTR8300 & Relay Pack
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the VTR8300 terminal
equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature
controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power
supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire
costly pilot relays and transformers.
The VTR8300 Line Voltage Fan Coil Terminal Equipment Controller and SC3000 Relay Pack can be configured to handle a broad variety of
applications covering all the standard implementations necessary for controlling line-voltage HVAC systems.
In addition to controlling heating, cooling and fan activity, depending on the model the VTR8300 can handle wireless networking
and switches, passive infrared (PIR) occupancy detection using either onboard or remote sensors, and dehumidification control. The
applications described here cover all these features, and in combination with the VTR8300’s advanced scheduling and occupancy controls
can provide the functionality for any required line-voltage HVAC implementation.
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve
closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled
in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Options
•BACnet® and Wireless communication models available (see
Appendix B for network wiring).
•Remote wall mount or return duct sensor ready.
•Can be configured for 2-pipe systems with changeover.
•Binary inputs can be configured to control occupancy via door
or window contact, remote night setback, or provide alarms for
service or filter monitoring.
•Universal input can be configured for changeover sensor.