Viconics VTR8300 Application Guide

Fan Coil Unit (FCU) Application Guide
VTR8300 Series Room Controllers
TABLE OF CONTENTS
VTR8300 and SCs | Fan coil terminal equipment controllers 2 VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wireless door switch 4 VTR8350A5000 -VC3404E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, dehumidification, 2-position valves 6 VTR8300A5000 - VC3504E5000: Heating/cooling with changeover sensor: 2-pipe fan coil unit with 3-speed fan and wireless window switch 8 VTR8350A5000 - VC3400E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan and dehumidification, 2-position valves 10 VTR8300A5500 - VC3514E5000: Heating/cooling: 2-pipe fan coil unit with 3-speed fan and fresh air damper, 2-position valves 12 VTR8300A5000 -VC3500E5000 -VC3300E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack 14 VTR8300A5000 - VC3504E5000: Cooling and electric heat: 2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch 16 VTR8300A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves with wired door switch 18 Appendix A - Passive infra-red (PIR) motion detector cover specifications 20 Appendix B - option network wiring if communicating models are used 21 Appendix C - controllers’ occupancy sequence of operation schematic 21 Appendix D - SED Series - wireless door & window switch 22 Appendix E - VTR8300 controller & VC3000 relay pack 23
2
VTR8300 Fan Coil ControllerApplication Guide
OVERVIEW
VTR8300 & Relay Pack
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the VTR8300 terminal equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers.
The VTR8300 Line Voltage Fan Coil Terminal Equipment Controller and SC3000 Relay Pack can be configured to handle a broad variety of applications covering all the standard implementations necessary for controlling line-voltage HVAC systems.
In addition to controlling heating, cooling and fan activity, depending on the model the VTR8300 can handle wireless networking and switches, passive infrared (PIR) occupancy detection using either onboard or remote sensors, and dehumidification control. The applications described here cover all these features, and in combination with the VTR8300’s advanced scheduling and occupancy controls can provide the functionality for any required line-voltage HVAC implementation.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300 Fan Coil ControllerApplication Guide
VTR8300 AND SCS | FAN COIL TERMINAL EQUIPMENT CONTROLLERS
Commercial interface (local override)
Power
Part Number Description Humidity PIR Cover Communication
VTR8300A0Axx
VTR8300A0Bxx
VTR8300A0Pxx
VTR8300A5Axx
VTR8300A5Bxx
VTR8300A5Pxx
VTR8350A0Axx
VTR8350A0Bxx
VTR8350A0Pxx
VTR8350A5Axx
VTR8350A5Bxx
VTR8350A5Pxx
Stand-alone fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Wireless fan coil terminal equipment controller
Stand-alone fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Wireless fan coil terminal equipment controller
Stand-alone fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Wireless fan coil terminal equipment controller
Stand-alone fan coil terminal equipment controller
BACnet® fan coil terminal equipment controller
Wireless fan coil terminal equipment controller
No No Stand-alone
No No BACnet
®
No No ZigBee® Pro Wireless
No Yes Stand-alone
No Yes BACnet
®
Yes Yes ZigBee® Pro Wireless
Yes No Stand-alone
Yes No BACnet
®
Yes No ZigBee® Pro Wireless
Yes Yes Stand-alone
Yes Yes BACnet
®
Yes Yes ZigBee® Pro Wireless
3
Transformer relay packs for fan coil units
Power
Part Number Description
SC3500E5045
SC3504E5045
SC3514E5045
SC3400E5045
SC3404E5045
SC3300E5045
1 heat/cool output, 1 cool output, and 3 fan outputs
1 heat/cool output, 1 cool output, 3 fan outputs, and four inputs
1 heat/cool output, 1 cool output, 3 fan outputs, Occupancy output (7Vdc), and four inputs
1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs
1 heat/cool output, 1 Modulating pulsed Vdc output for SSR electric reheat control, and 3 fan outputs
3 slave fan outputs
Wireless accessories for VTR8300 Series
Power
Part Number Description
SED-DOR-P-5045 Wireless door switch
SED-WIN-P-5045 Wireless window switch
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
4
VTR83X0AXPXX WITH SC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH
VTR8300 Fan Coil ControllerApplication Guide
VTR8300
Onboard PIR Sensor
AND / OR
Remote PIR Sensor
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
Heating Coil
2 POSITION
HEATING VALVE
SC3500E5000
Refer to the Wireless Door and Window Switch Installation Guide for the door pairing procedure.
Door Switch
SED-DOR-P-5000
Configuration Parameter Name
Configuration Settings
Fan Menu L-M-H-A Fan cont. heat. On BI2 Door Dry Pulsed heating Off Pipe no. 4 Seq. operation Ht - Cl
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
SC3500E5000
VTR8300
7 VDC
Tx / Rx
Com
VTR8300 Fan Coil ControllerApplication Guide
1
Tx/Rx
2
7 Vdc
Com
3
5
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closed.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closed.
Wireless Door Switch
Wireless door switch automatically toggles occupancy.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Can be configured for 2-pipe systems (without changeover).
• Binary inputs can be configured to control occupancy via door
or window contact, remote motion sensor, or remote night setback.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
6
VTR8300 Fan Coil ControllerApplication Guide
VTR8350AXXXX WITH SC3404E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8300
Configuration parameter name
Fan
Airflow Direction
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
SC3404E5000
Configuration settings
SSR
SOLID STATE RELAY
(GENERIC)
Fan menu L-M-H-A Fan cont. heat On Pulsed heating On Pipe no. 2 Seq. operation Ht-Cl
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
SC3404E5000
VTR8300
7 VDC
Tx / Rx
Com
VTR8300 Fan Coil ControllerApplication Guide
1
Tx/Rx
2
7 Vdc
Com
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
Heat -
10
Heat +
7
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
SOLIDSTATE RELAY (4-32Vdc)
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door
or window contact, remote night setback, or provide alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
8
VTR8300 Fan Coil ControllerApplication Guide
VTR8300AXPXX WITH SC3504E5000 RELAY: HEATING/COOLING WITH CHANGEOVER SENSOR 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND WIRELESS WINDOW SWITCH
Window Switch
SED-WIN-P-5000
Fan
Airflow Direction
Cooling / Heating Coil Supply Sensor
VTR8300
AND / OR
Onboard PIR Sensor
SC3504E5000
Configuration Parameter Name
Fan Menu L-M-H-A Fan cont On BI1 Window RUI1 COS Pipe No 2 Seq. operation Cool
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Configuration Settings
SENSOR
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300
7 VDC
Tx / Rx
Com
VTR8300 Fan Coil ControllerApplication Guide
9
SC3504E5000
1
Tx/Rx
2
7 Vdc
Com
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wireless Window Switch
Wireless window switch automatically locks out heating/cooling when window is opened.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Remote wall mount or duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
10
VTR8300 Fan Coil ControllerApplication Guide
VTR8350AXXXX WITH SC3400E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, DEHUMIDIFICATION AND 2-POSITION VALVES
VTR8300
Fan
Airflow Direction
SC3400E5000
Cooling Coil Electric Heating
2 POSITION
COOLING VALVE
SSR
SOLID STATE RELAY
(GENERIC)
Configuration parameter name
Configuration settings
Fan menu L-M-H-A Fan cont. heat. On Pulsed Heating On Pipe No 2 Seq. operation Cool-Rht
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300 Fan Coil ControllerApplication Guide
11
SC3400E5000
VTR8300
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
Com
SCom
SOLIDSTATE RELAY (4-32Vdc)
1
2
3
9
10
(-)
(+)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus configuration defined deadband value.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Options
• BACnet® and Wireless communication models available (see
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Appendix B for network wiring).
• Binary inputs can be configured to control occupancy via door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
12
VTR8300 Fan Coil ControllerApplication Guide
VTR8300AXXXX WITH SC3514E5000 RELAY: HEATING/COOLING 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN, FRESH AIR DAMPER AND 2-POSITION VALVES
Fresh Air
DAMPER
VTR8300
Return Air
Fan
Airflow Direction
SC3514E5000
Cooling / Heating Coil Supply Sensor
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
Supply Sensor: 10K Ohm type 2.
Changeover Sensor: 10K Ohm type 2.
SENSOR
Configuration Parameter Name
Configuration Settings
Fan menu L-M-H-A Fan cont. heat On BI1 Window RUI1 COS Pulsed Heating Occ Out Pipe no. 2 Seq. operation Cool
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300
BACnet+
BACnet-
Tx / Rx
BACnet REF
UI 16 - BI1
VTR8300 Fan Coil ControllerApplication Guide
Com
7 VDC
UI 17 - BI2
SCom
7Vdc RELAY COIL
1
2
3
4
5
6
7
8
9
13
SC3514E5000
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
OCC -
Sequence of Operation and Wiring
Occupied Mode
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Setpoints revert to those defined by occupied cooling and heating. The occupancy output opens fresh air damper to minimum position.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling. The fresh air damper closes.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Remote wall mount or return duct sensor ready.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
14
VTR8300 Fan Coil ControllerApplication Guide
VTR8300AXXXX WITH SC3500E5000 AND SC3300E5000 RELAYS: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH SLAVE RELAY PACK
Airflow Direction
Fan
Cooling Coil
Heating Coil
VTR8300
SC3300E5000
Configuration Parameter Name
Fan menu L-M-H-A Fan cont. heat On Pipe No 4 Seq. operation Ht-Cl
Configuration Settings
2 POSITION
COOLING VALVE
SC3500E5000
2 POSITION
HEATING VALVE
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300 Fan Coil ControllerApplication Guide
15
SC3500E5000T
VTR8300
BACnet+
BACnet-
BACnet REF
7 VDC
Tx / Rx
UI 16 - BI1
UI 17 - BI2
Com
SCom
1
2
3
SC3300E5000
1
2
3
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Can be configured for 2-pipe systems without changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
16
VTR8300 Fan Coil ControllerApplication Guide
VTR8300AXPXX WITH SC3504E5000 RELAY: COOLING AND ELECTRIC HEAT 2-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED WINDOW SWITCH
Window Switch
SED-WIN-P-5000
Fan
Airflow Direction
Cooling / Heating Coil Supply Sensor
VTR8300
AND / OR
Onboard PIR Sensor
SC3504E5000
Configuration Parameter Name
Fan menu L-M-H-A
Fan cont. heat On
BI1 Window
RUI1 COS
Pipe no. 2
Seq. operation Cool
2 POSITION
COOLING VALVE / HEATING VALVE
C/O
SENSOR
SENSOR
Changeover Sensor: 10K Ohm type 2
Supply Sensor: 10K Ohm type 2
Configuration Settings
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300
BACnet+
BACnet-
Tx / Rx
BACnet REF
UI 16 - BI1
Com
7 VDC
UI 17 - BI2
SCom
VTR8300 Fan Coil ControllerApplication Guide
17
SC3504E5000
1
Tx/Rx
2
7 Vdc
Com
3
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
BI1 (Window)
SCom
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
If supply water temperature is less than 24°C (75F), valve opens to maintain room temperature, else the valve closes.
On Call for Heat
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes.
Supply Air Sensor
Only used for monitoring. Shows automatically if sensor is connected.
Wired Window Switch
The window switch automatically locks out heating/cooling when window opens.
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Remote wall mount or duct sensor ready.
• Can be configured for 2-pipe systems with changeover.
• Binary inputs can be configured to control occupancy via door
or window contact, remote night setback, or provide alarms for service or filter monitoring.
• Universal input can be configured for changeover sensor.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
18
VTR8300 Fan Coil ControllerApplication Guide
VTR8300AXPXX WITH SC3500E5000 RELAY: HEATING/COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRED DOOR SWITCH
VTR8300
Onboard PIR Sensor
AND / OR
Remote PIR Sensor
Fan
Airflow Direction
Cooling Coil
2 POSITION
COOLING VALVE
SC3500E5000
Heating Coil
2 POSITION
HEATING VALVE
Door Switch
SED-DOR-P-5000
Configuration Parameter Name
Configuration Settings
Fan menu L-M-H-A Fan cont. heat On BI2 Door Dry Pipe No 4 Seq. Operat Ht-Cl
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300
VTR8300 Fan Coil ControllerApplication Guide
7 VDC
Tx / Rx
Com
1
2
3
19
SC3500E5000
Tx/Rx
7 Vdc
Com
BACnet+
BACnet-
BACnet REF
UI 16 - BI1
UI 17 - BI2
SCom
BI2 (Door)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
SCom
Options
• BACnet® and Wireless communication models available (see Appendix B for network wiring).
• Models available with factory installed PIR sensor.
• Can be configured for 2-pipe systems without changeover.
• Binary inputs can be configured to control occupancy via
door or window contact, remote motion sensor, remote night setback, or provide alarms for service or filter monitoring.
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes.
Door Switch
Door switch automatically toggles occupancy.
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
20
Typical Consumption PIR Thermos tat Consum ption Savings
VTR8300 Fan Coil ControllerApplication Guide
APPENDIX A - PASSIVE INFRA-RED (PIR) MOTION DETECTOR COVER SPECIFICATIONS
PIR cover sequence of operation
Initially, the controller is in Stand-by mode. Stand-by setpoints are used at the controller. As soon as the PIR detects motion, the Occupancy status switches to Occupied and the Stand-By Time timer is reset. The Occupied setpoints are used. If no motion is detected in the room for the entire Stand-By Time duration (adjustable parameter), the room then switches to Stand-by mode and stand-by setpoints are used. While in Stand-by mode, if no motion is detected for the entire Unoccupied Time period (adjustable parameter), the room switches to Unoccupied mode and uses its Unoccupied setpoints. While in Stand-By or Unoccupied mode, any motion will switch the room back to Occupied mode.
Typical Detection Pattern for PIR Lens
Recommended installation height for PIR sensor:
4 - 5 ft. / 1.2-1.5 m
Sensor Ranges
A = 20 ft. / 6.1 m B = 14 ft. / 4.3 m C = 11 ft. / 3.4 m
Horizontal Angles (Typical)
Transverse motion: 4-5 ft/s
O
40
A
/ 1.5 m/s
Center
Vertical Angle (Typical)
O
30
Energy savings
The PIR can maximize your energy saving from 10-30% by relaxing temperature set points in unoccupied zones during scheduled periods.
B
C
20
O
O
20
20
20
O
O
B
C
Center
Typical Savings of 10-30%
85 80
75 70
65 60 55
50 45
40 35
30 25
Ener gy Us age (K Wh)
20
15 10
5 0
0 2
4 6 8 10 12 14 16 18 20 22 24
Time of Day (EST)
50%
40%
Saving Percentage
30%
20%
10%
0%
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300 Fan Coil ControllerApplication Guide
Setpoints
e
Stand-by timer reset
Unoccupied timer reset
21
BACnet® communication
wiring
BACnet
thermostat
1
BACnet
thermostat
2
BACnet
thermostat
3
Notes:
- Wiring should be daisy chained
- Respect polarity
- If using 2 conductors shielded wires, connect the shield of each feed together on the back of the controller. ONLY ground the shield at one location. DO NOT connect the shield to the ref terminal.
+
-
ref
+
-
ref
+
-
ref
Wireless Communication
No communication wires required
APPENDIX C - CONTROLLERS’ OCCUPANCY SEQUENCE OF OPERATION SCHEMATIC
26.5°C
Unoccupied cool
Stand-by cool
Occupied cool
Occupied heat
Stand-by heat
noccupied heat
Deadband
Movement detected
-
24.5°C 76°F
22°C 72°F
70°F 21°C 21°C
Stand-by
time
Into Stand-by mode
-
Deadband
66°F
19°C
Unoccupied
time
Into Unoccupied
mode
80°F
Deadband
62°F
16.5°C
22°C 72°F
70°F
Tim
Next movement
detected
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
22
LED (switch side)
Hidden Switch
Pull Tab
VTR8300 Fan Coil ControllerApplication Guide
APPENDIX D - SED SERIES - WIRELESS DOOR & WINDOW SWITCH
®
Wireless ZigBee
Wireless door switches used with an onbaord or remote PIR sensor provide advanced local occupancy routines allowing for increased energy savings during occupied hours without sacrificing occupant comfort.
Wireless window switches are used to monitor exterior windows and or patio and balcony doors being opened or closed. This prevents unnecessary energy consumption by the tenants.
Fan Coil Terminal Equipment Controllers with SED Series ZigBee network ready mode with or without integration to a central management system to allow for advanced functions such as central reservation and occupancy functions.
A combination of up to twenty SED Series door and or window switches can be used simultaneously with a single Fan Coil Terminal Equipment Controller.
The SED Series switches are factory delivered with 2 AAA batteries and are ready to be installed, configured and used right out of the box. Due to the extremely small current consumption of the switches, the expected battery life is approximately 10 years and is equivalent to the battery shelf life.
No tools are required for commissioning or servicing the door switch. A very simple interface with an on­board LED & hidden switch provides all the required functions for local interaction. Local information for battery life and connectivity (heartbeat) are provided at the Fan Coil Terminal Equipment Controller local display through the ZigBee security tamper proof screw and self tapping mounting screws.
Pro door & window switch
®
wireless switches can be used in
®
wireless network. Each switch is factory supplied with a magnet, a locking
Model selection
Window Switch Door Switch
SED-WIN-P-5045 SED-DOR-P-5045
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.
VTR8300 Fan Coil ControllerApplication Guide
APPENDIX E - VTR8300 CONTROLLER & SC3000 RELAY PACK
Product overview
The VTR8300 Fan Coil Controller offers a new cost-effective solution for upgrading line-voltage fan coil unit thermostats. The VTR8300 terminal Equipment Fan Coil Unit Controllers are available as BACnet wireless ZigBee
®
Pro networked models.
No previous building automation training is required for the easy installation and commissioning process. Installation can be completed in approximately fifteen minutes, reducing costs and providing increased savings.
The SC3000 Series Line Voltage Switching Transformer Relay Pack Controllers has been designed for silent control of typical high voltage fan coil device loads (90 to 277 VAC multi-voltages capable).
It uses advanced microprocessor-based circuitry with a built-in transformer that eliminates all typical required peripheral components when automating a Fan Coil unit with traditional building automation systems.
The SC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR8300 Terminal Equipment Controller.
A single VTR8300 Terminal Equipment Controller can control up to 10x SC3000 Series Relay Pack. The SC3000 Series Relay Packs are line-powered units.
The extremely compact unit locally contains all the relay outputs for fan switching and valve control. Models are also available for extra monitoring / control inputs of the Fan Coil Units.
®
MSTP or
23
Typical fan coil unit setup
Typical Fan Coil Unit
Low Voltage Connections to VTR8300 Controller
H C
1
Tx/Rx
2
7 Vdc
Power
Com
3
Supply
SC3404E5000
4
RUI 1
5
SCom
6
RBI 2
7
SS
8
RS
9
Heat -
10
Heat +
90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb Amb. Temp. 50oC
FAN LOW
1/2 HP
FAN
or 13A
MED
Max
FAN HIGH
5A
COOL
Max
WHITE
BLACK
RED
BLUE
BROWN
YELLOW
Electrical
Cabinet
1
Tx/Rx
2
7 Vdc
Power
Com
3
Supply
4
RUI 1
xxx-xxxx-xx
SCom
5
WHITE
6
RBI 2
90-277 Vac - 50/60 Hz 1/2HP + 5A Max Comb. or 13A+ 5A Max Comb
7
SS
Amb. Temp. 50oC
BLACK
8
RS
FAN
RED
LOW
1/2 HP
9
Heat -
FAN
or 13A
BLUE
MED
Max
10
Heat +
FAN
BROWN
HIGH
5A
YELLOW
COOL
Max
C C
Daisy chained topology
Mixed daisy chained and Star topology
Star topology
Viconics Technologies Inc. | 9245 Langelier B lvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax : (514 ) 3 21-4150
028-6047-03 www.viconics.com | sales@viconics.com February 2015
© 2015 Viconics Technologies Inc. All rights reserved.