Viconics VTR7300 Series Installation Manual

Page 1
1 | 028-0298-09 November 2015
CONTENTS
Installation 2
Location 2 Installation 2
Operation Overview 3
Network ready 4
Terminal, Identification and Function 5 Communication wiring to VC3xxxX Relay Pack 5
Network wiring topology 6
VC3xxx LED Operation 6
Wiring of local inputs to VTR73xxA Room Controller 6
Configuring and Status Display Instructions 7
Status display 7
User Interface 9
Local keypad interface 9
VTR7300 Series
For Commercial and Lodging HVAC
Fan Coil Applications
November 2015
Page 2
2 | 028-0298-09 November 2015
INSTALLATION
Remove security screw on bottom of Room Controller cover.
Open unit by pulling on bottom side of
Room Controller (fig. 1).
Remove wiring terminals from sticker.  Read FCC ID and IC label installed in
the cover.
Location
1. Should not be installed on outside wall.
2. Must be installed away from any direct heat source.
3. Should not be installed near an air discharge grill.
4. Should not be affected by direct sun radiation.
5. Nothing should restrict vertical air circulation to Room Controller.
Installation
1. Swing open Room Controller PCB to left by pressing PCB locking tabs (fig.
2).
2. Pull out cables 6” out from wall. Ensure wall surface is flat and clean.
3. Insert cable in central hole of base.
4. Align base and mark location of two mounting holes on wall ensuring to install proper side of base up.
5. Install anchors in wall.
6. Insert screws in mounting holes on each side of base (fig. 2).
7. Gently swing back circuit board on base and push until tabs lock.
8. Strip each wire 1/4 inch from end.
9. Insert each wire according to wiring diagram.
10. Gently push excess wiring back into hole (fig. 3).
11. Re-Install wiring terminals in correct locations (fig. 3).
12. Re-install cover (top side first) and gently push extra wire length back into hole in wall.
13. Install security screw.
Page 3
3 | 028-0298-09 November 2015
OPERATION OVERVIEW
The VC3xxxX Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR73xxA Room Controller.
Fan operation can be configured and wired for the following:
3 Speed configuration using 3 fan relays ( Low - Med - High ) 2 Speed configuration using 2 fan relays ( Low - High ) 3 Speed configuration with auto fan speed mode using 3 fan relays
(Low - Med - High - Auto)
2 Speed configuration with auto fan speed mode using 2 fan relays
(Low - High - Auto)
Single fan speed configuration.
The VTR7300 Controller can be configured for typical 2 or 4 pipe heating / cooling FCU (Fan Coil Unit) applications.
2 or 4 pipe only operation can be configured and wired for the following:
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover
If replacing an existing Line Voltage FCU Thermostat, label the wires
before removal of the thermostat.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Room Controller.
A short circuit or wrong wiring may permanently damage the Room
Controller or the equipment.
All VTR7300 series controls are designed for use as operating controls
only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
Page 4
4 | 028-0298-09 November 2015
2 or 4 pipe only with electric reheat can be configured and wired for the following:
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover o On-Off electric reheat only o Cooling with On-Off or modulating VDC pulsed electric reheat
(model dependent)
o Heating with On-Off or modulating VDC pulsed electric reheat
(model dependent)
o Cooling / Heating with network or local changeover with On-Off
or modulating VDC pulsed electric reheat (model dependent)
The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Room
Controller.
The VTR73xxA Controller controls the VC3xxxX Relay Pack(s) via a simple
communication bus.
A maximum of 10 VC3xxxX Relay Pack can be used under a single VTR73xxA
Room Controller.
3 wires minimum are required between the VTR73xxA Controller and the first
VR7300 Relay Pack.
The 3 wire functions are known as the following:
o 1 Tx / Rx Communication o 2 Power Hot 7.0 VDC 4 Watts maximum ( required for the
VTR73xxA Controller power)
o 3 Power common
Commands for fan speed and valve operation are issued from the VTR73xxA
Room Controller to the VC3xxxX Relay Pack(s)
Network ready
All Viconics VTR7300 series Room Controllers are designed for stand-alone
operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Room Controllers can be field
retrofitted with the following communication adapters:
o VCM7000V5000W, Room Controller wireless communication adapter o VCM7300T5000B, Room Controller BACnet™ MS-TP communication
adapter
Page 5
5 | 028-0298-09 November 2015
TERMINAL, IDENTIFICATION AND FUNCTION
TERMINAL
IDENTIFICATION
ALL VTR73XXA5X00(X)
ROOM CONTROLLER
Terminal 3
Tx – Rx Communication
Terminal 4
Power Hot 7.0 VDC
Terminal 5
Power Common
Terminal 13
BI 1 ( Configurable )
Terminal 14
Scom
Terminal 15
BI 2 ( Configurable )
COMMUNICATION WIRING TO VC3XXXX RELAY PACK
Only ONE VC3xxxX Relay Pack with remote monitoring inputs can be used under a single VTR73xxA Controller. All other slave units must be VC3xxxX Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxX Relay Packs can be used for a single VTR73xxA Room Controller.
From the VTR73xxA to the first VC3xxxX Relay Pack
Uses existing or new field wires A minimum of 3 wires are required 14-22 Ga Solid or Stranded. Shield not
necessary.
From the first VC3xxxX to all other slave VC3xxxX Relay Pack(s)
Uses existing or new field wires A minimum of 2 wires are required 14-22 Ga Solid or Stranded. Shield not
necessary.
Connect only wires #1 Power Common and #2 Tx/Rx Communication
Page 6
6 | 028-0298-09 November 2015
Network wiring topology
VC3XXX LED OPERATION
LED / Time (Status operation)
Wiring of local inputs to VTR73xxA Room Controller
Condition of the Status LED
Cause
Solution
2 short blinks
No communication between
the VTR73xxA and the VC3xxxX relay pack. The VC3xxxX Relay Pack will
resume its output “no
communication active” status
Check communication
wiring and or power cycle the controllers
2 short blinks and a
longer blink
Normal communication
between the VTR73xxA and
the VC3xxxX relay pack.
N/A
0.2
2.5
0.6
0.4
0.0
1.0
5.0 sec
Power On
Online to
VTR73xxA
13
- BI 1
14
- Scom
15
- BI 2
Local BI 1 Input by configuration:
- None (monitoring only)
-
Remote motion detector: Motion NO or Motion NC
- Remote Night Setback: RemNSB
Local BI 2 Input by configuration:
-
None (monitoring only)
-
- Window contact Window:
Page 7
7 | 028-0298-09 November 2015
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The VTR73xxA Room Controller features a two-line, eight-character display. There is a low-level backlight that is always active and can only be seen at night.
When left unattended, the Room Controller has an auto scrolling display that shows the status of the system. There is an option in the configuration menu to lockout the scrolling display and to only display the room temperature and conditional outdoor temperature to the user. With this option enabled, no local status of mode, occupancy and relative humidity is shown.
Each item scrolls individually with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic status display scrolling.
To activate the back light to high level, press any key on the front panel. The back light display will return to low level when the Room Controller is left unattended for 45 seconds.
Sequence of auto-scroll status display:
ROOM &
HUMIDITY
SYSTEM MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C or °F XX % RH
Sys mode auto
Occupied
Outdoor x.x °C or °F
Service
If humidity display enabled
Sys mode cool
Stand-By
Network value only
Filter
RoomTemp x.x °C or °F
Sys mode heat
Unoccup
n/a
Window
If humidity display is not enabled
Sys mode off
Override
n/a
Low Batt
% RH display is conditional to:
(Humidity display is model and configuration dependent)
Model with RH sensor built in Display function can be enabled with RH display parameter. Displayed range is
10 to 90 % RH
Outdoor air temperature
Display is only enabled when outdoor air temperature network variable is
received.
Occupancy status
Occupied, Stand-By, Unoccupied and Override status are displayed on the
scrolling display.
Page 8
8 | 028-0298-09 November 2015
Alarms
If alarms are detected, they will automatically be displayed at the end of the
scrolling status display.
When an alarm message is displayed, the backlit screen will illuminate at the
same time as the message and shut off during the rest of the status display.
A maximum of two alarms can appear at any given time. The priority for the
alarms are as follows:
Three status LED’s on the Room Controller cover are used to indicate the status of the fan (any speed), a call for heat, or a call for cooling.
Fan coil models
When any of the fan speeds are ON, the FAN LED will illuminate
When heating & reheat is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate
Service
Indicates that there is a service alarm as per one of the configurable binary inputs ( BI2 )
Filter
Indicates that the filters are dirty as per one of the configurable binary inputs ( BI2 )
Window
Indicates that the outside window or door is opened and that the Room Controller has cancelled any cooling or heating action ( BI1 )
Low Batt
Indicates that attached wireless switching devices (Door or window contact) have a low battery condition.
(Only functional when used with a wireless communication adapter)
Page 9
9 | 028-0298-09 November 2015
USER INTERFACE
Unoccupied mode override
An Override can be made on commercial models during an unoccupied period. If the Override option is enabled in the lockout configuration, pressing the middle override button will resume occupied setpoints for a time specified by the parameter ToccTime”.
Local keypad interface
Is used to toggle between the different system modes available as per sequence and menu selected.
Repetitively pressing the button will toggle between all the available modes.  Available menus are dependent on selected sequence of operation.
Is used to toggle between the different fan modes available as per the
sequence and menu selected
Repetitively pressing the button will toggle between all the available modes  Available menus are dependent on selected sequence of operation and menu
selected for Fan
Hotel and lodging applications. Toggles the local user temperature scale
between °F and °C
Commercial and institutional applications. Set a local unoccupied timed
override to occupied mode
In cooling mode only the cooling setpoint is displayed,  In heating mode only the heating setpoint is displayed  In auto mode, (See below)
In cooling mode only the cooling setpoint is displayed,  In heating mode only the heating setpoint is displayed  In auto mode, (See below)
Page 10
10 | 028-0298-09 November 2015
Viconics Technologies Inc.
Tel.: Fax: Toll free:
www.viconics.com
Loading...