Viconics VTR7300 Application Guide

HVAC Application Manual
VTR73XXA Series Fan Coil Terminal Equipment Controller
VC3XXXX Series Line Voltage Switching Relay Packs
Product overview
The VTR73XX Series Fan Coil Terminal Equipment Controller features a backlit LCD display with dedicated function menu buttons for simple operation. Accurate temperature control is achieved due to the product’s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based Terminal Equipment Controllers. All models feature configurable System and Fan button functions to meet all possible applications The VTR73XX Terminal Equipment Controllers are powered and communicate with the associated VC3000 Series Relay Pack(s) using only 3 wires.
2 types of interfaces for the user can be ordered. The VC73x5 models are typically used for hotel and lodging applications where the middle button of the interface is for the user to select the local displayed scale in ºF or ºC. The VC73x0 models are typically used for commercial and institution applications where the middle button of the interface is defined for the local unoccupied override function.
The VTR73XX Terminal Equipment Controllers are also compatible with the new Viconics PIR cover accessories. Terminal Equipment Controllers equipped with a PIR cover provide advanced active occupancy logic, which will automatically switch occupancy levels from Occupied to Stand-By and Unoccupied as required by local activity being present or not. This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort. All Terminal Equipment Controllers can be ordered with or without a factory installed PIR cover ( see ordering notes below ).
The compatible VC3000 Series Line Voltage Switching Relay Pack(s) operate as slave unit(s) under the control of a single master VTR73XX Terminal Equipment Controller. A single VTR73XX Terminal Equipment Controller can control up to 10 VC3000 Series Relay Pack. The VC3000 Series Relay Packs are line-powered units. They locally contain all the relay outputs for fan switching and valve control. Models are also available for extra monitoring / control inputs of the Fan Coil Units.
For Commercial and Lodging HVAC Fan Coil Applications
(Issue Date: March 29, 2010 – 028-6021_R00)
VTR73x5X Lodging VTR73x0X Commercial
VC3000 Series Relay Pack
The additional following documents are available at: www.viconics.com
PIR application information and examples, are available on document: APP-PIR-Guide-Exx
PIR cover installation information is available on document: PIR Cover Installation-Exx
Information on the LON models (VTR73xxX5x00E), is available on document ITG-VTR73-PIR-LON-Exx
Information on the BACnet models (VTR73xxX5x00B), is available on document ITG-VTR73-PIR-BAC-Exx
Information on the Wireless models (VTR3xxX5x00W), is available on documents: ITG-VWG-40-BAC-Exx and LIT-VWG-40-SETUP-Exx
VTR73XXA models available
Viconics part number VTR7300A5x00(x) VTR7350A5x00(x) VTR7305A5x00(x) VTR7355A5x00(x) Primary market
User interface definition
On board %RH sensor
For dehumidification strategy
Ordering Information Notes: The (X) at the end of the model number represents available communication options:
X = none for Stand-alone X = E for Echelon
X = B for BACnet MS-TP X = W for Wireless
The Terminal Equipment Controllers can be ordered with a factory installed PIR cover. Please use (5500) extension instead of the (5000) only extension. The Terminal Equipment Controllers ordered without a PIR cover can be retrofitted with a separate PIR accessory cover afterwards if required.
Ordering examples:
A VTR7305AW5500B is for a wall mounted Terminal Equipment Controller with a hotel / lodging interface with a factory mounted PIR cover and an MS-TP BACnet communication interface.
A VTR7350A5000W is for a wall mounted Terminal Equipment Controller with a commercial / institution interface and a wireless communication interface. The Terminal Equipment Controller can be retrofitted with a separate PIR accessory cover afterwards if required.
028-xxxx R0_APP-VTR73XXA-PIR-E04.doc www.viconics.com / sales@viconics.com
Commercial and institution applications Hotels and lodging applications
None Yes None Yes
VC3xxxX relay pack models available
Applications
Fan control Monitoring inputs Control types
Ordering Information Notes:
Please refer to the “Operation overview” section for related information on VTR73xxA and VC3xxxX arrangements and possible combinations.
Ordering examples:
VC3500E5000 VC3504E5000 VC3400E5000 VC3404E5000 VC3300E5000
2 pipes 2 pipes with reheat 4 pipes
Up to 3 speed Up to 3 speed Up to 3 speed Up to 3 speed Up to 3 speed None 4 FCU remote inputs None 4 FCU remote inputs None
On-Off line switched valve output control
- 1 heat / cool output
- 1 cool output
- 3 fan outputs
More than one VC3xxxX Relay Pack can be used for a single VTR73xxA Terminal Equipment Controller.
Only one VC3x4X Relay Pack with monitoring inputs can be used for a single VTR73xxA Terminal Equipment Controller
A VC3500E5000 is for a 90 to 277 Vac powered FCU mounted Relay Pack with the following outputs:
o Three 90 to 277 Vac switching fan relay outputs o Two 90 to 277 Vac switching valve relay outputs
A VC3504E5000 is for a 90 to 277 Vac powered FCU mounted Relay Pack with the following inputs and outputs:
o One configurable universal input o One configurable binary input o One dedicated discharge air temperature monitoring input o One dedicated return air temperature control input o Three 90 to 277 Vac switching fan relay outputs o Two 90 to 277 Vac switching valve relay outputs
A VC3300E5000 is for a 90 to 277 Vac powered FCU mounted Relay Pack with the following outputs:
o Three 90 to 277 Vac switching fan relay outputs
2 pipes 2 pipes with reheat 4 pipes
On-Off line switched valve output control
- 1 heat / cool output
- 1 cool output
- 3 fan outputs
2 pipes 2 pipes with modulating pulsed reheat
On-Off line switched valve output control
- 1 heat / cool output
- 1 Modulating pulsed
Vdc output for SSR electric reheat control
- 3 fan outputs
2 pipes 2 pipes with modulating pulsed reheat
On-Off line switched valve output control
- 1 heat / cool output
- 1 Modulating pulsed
Vdc output for SSR electric reheat control
- 3 fan outputs
Slave Fan Unit
Slave fan control only
Slave fan control only
3 fan outputs
Features and benefits
Features VTR73xxA Terminal Equipment Controller
Benefits
Models available with internal humidity sensing Increased occupant comfort through dehumidification
Advanced occupancy functions Through the network or smart local occupancy sensing
Ready for PIR accessory cover Fully integrated advanced occupancy functionality
Configurable sequences of operation Single model meets more applications
Configurable fan functions button Meets more applications with a single model
Unique configuration setup utility ⇒ Minimizes parameter tampering
Multi level lockable keypad
Auto Fan speed mode
Tamper proof, no need for Terminal Equipment Controller
guards
Increased occupant comfort in cooling mode by reducing
humidity and offer less fan noise in all mode of operation
Features VC3xxxX Relay Pack Benefits
Universal line powered from 90 to 277 Vac
Line switching from 90 to 277 Vac No pilot duty relay required
2 configurable inputs Adds functionality
Dedicated discharge air temperature monitoring Adds functionality
Dedicated return air temperature control Return air temperature control where application dictates
Pulsed Vdc output for SSR electric reheat
No external transformer needed One model fits all voltage requirements
Advanced modulating electric heat control on specific
models
2
Operation overview
The VC3xxxX Series Line Voltage Switching Relay Pack(s) operate as slave unit(s) under the control of a single master VTR73xxA Terminal Equipment Controller.
A) Each application below represents typical 3 speed FCU fan motor applications. Fan operation can be configured and wired for the following:
o 3 Speed configuration using 3 fan relays ( Low – Med - High ) o 2 Speed configuration using 2 fan relays ( Low - High ) o 3 Speed configuration with Auto fan speed mode using 3 fan relays ( Low – Med - High ) o 2 Speed configuration with Auto fan speed mode using 2 fan relays ( Low - High ) o Single fan speed configuration.
B) Each application below represents typical 2 or 4 pipe heating / cooling FCU applications. 2 or 4 pipe only operation can be configured and wired for the following:
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover
2 or 4 pipe only with electric reheat can be configured and wired for the following:
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover o On-Off electric reheat only o Cooling with On-Off or modulating Vdc pulsed electric reheat ( model dependent ) o Heating with On-Off or modulating Vdc pulsed electric reheat ( model dependent ) o Cooling / Heating with network or local changeover with On-Off or modulating Vdc pulsed electric reheat ( model
Operation Concept
dependent )
The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller.  The VTR73xxA Controller operates the VC3xxxX Relay Pack(s) via a simple communication bus.  A maximum of 10 VC3xxxX Relay Pack can be used under a single VTR73xxA Terminal Equipment Controller.  3 wires minimum are required between the VTR73xxA Controller and the first VR7300 Relay Pack.  The 3 wire functions are as follow:
o 1 Tx / Rx Communication o 2 Power Hot 7.0 Vdc 4 Watts maximum ( required for the VTR73xxA Controller power ) o 3 Power common
Commands for fan speed and valve operation are issued from the VTR73xxA Terminal Equipment Controller to the
VC3xxxX Relay Pack(s)
FCU Remote inputs for monitoring and control. Remote inputs are read at the VC3xxxX Relay Pack ( models with
inputs only ). The present value of these inputs are read by the VTR73xxA Terminal Equipment Controller for it’s internal operation
o RUI1 can be configured for:
o RBI2 can be configured for:
o SS is dedicated to a discharge air sensor ( Auto Detect ) o RS is dedicated to a remote return air sensor ( Auto Detect )
None = no functions associated COS = for a local 2 pipes system Change Over thermistor sensor COC NO = for a local 2 pipes system Change Over Normally Opened dry contact thermostat COC NC = for a local 2 pipes system Change Over Normally Closed dry contact thermostat Service = A local and / or networked service alarm Filter = A local and / or networked dirty filter alarm
None = no functions associated Service = A local and / or networked service alarm Filter = A local and / or networked dirty filter alarm
3
VTR73xxA Occupancy function remote inputs. All wiring for those remote inputs is located at the wall VTR73xxA
Terminal Equipment Controller.
o BI1 can be configured for:
None = no functions associated Motion NO = for a remote normally opened contact PIR motion sensor Motion NC = for a remote normally closed contact PIR motion sensor Rem NSB = for usage with a remote on-off contact device for the occupancy function. A typical application
is a room tenant card holder, which force the occupancy if the card is inserted in the holder.
Window = A local and / or networked window opened alarm. The system heating and cooling actions are
also locked out.
o BI2 can be configured for:
None = no functions associated DoorDry = for usage of a PIR and entrance door switch for lodging occupancy routine
All communication wires ( if needed ) are located at the VTR73xxA Terminal Equipment Controller
Typical one to one set-up
4
Local Inputs at VTR7300 Controller
Special optional local funct ion(s):
- Remote motion detector(s)
- Window contacts
- Occupancy card holder
Existing or New Field VTR7300 Wires
3 minimum required 14-22 Ga
Solid or Str anded
Optional FCU Monitori n g Inputs
- Changeover sensor or contact
Model Dependent
- Service or Filter alarms
- Supply air sensor
- Return air sensor
Existing or New Communication Field Wires
- BACnet MS-TP
- LON TP-FT 10
- Wireless ( No wires )
High Voltage in cabinet wiring
- Line powered 90 to 277 Vac
- Line switching of fan & valves 90 to 277 V ac
- Isolated heating output for electric reheat
Line Voltag e Power
Line Voltage Va l v e s
- 2 pipes or 4 pipes applications
- Isolated line switching for electric reheat
H
C
Line Voltag e Fa n
- Configurable
- Up to 3 speed fan control
- Auto fan speed
Typical line wiring one to one setup
Line Voltage Electrical Ratings
Power supply
Fan line voltage contact Wire connections ½ HP Maximum Valve line voltage
contact Yellow wire connection 10A maximum Valve line voltage
contact Orange wire
connections 10A maximum
VC3500E5000 VC3504E5000 VC3400E5000 VC3404E5000 VC3300E5000
Slave Fan Unit
- 90 to 277 Vac universal all models
- Black Hot L1 Power Vac ( Switches: Brown, Blue, Red & Yellow )
- White Neutral Power Vac
3 Fan Speed Control Wires
Brown, Blue, Red 4 Pipes Cool output
Or 2 Pipes Heat / Cool
output 4 Pipes Heat output Isolated dry contact
output Or 2 Pipes reheat
output
3 Fan Speed Control Wires
Brown, Blue, Red 4 Pipes Cool output
Or 2 Pipes Heat / Cool
output 4 Pipes Heat output Isolated dry contact
output Or 2 Pipes reheat
output
3 Fan Speed Control Wires
Brown, Blue, Red 2 Pipes Heat / Cool
output
N/A N/A N/A
3 Fan Speed Control Wires
Brown, Blue, Red 2 Pipes Heat / Cool
output
3 Fan Speed Control Wires
Brown, Blue, Red N/A
5
VC3504E
Relay Pack
Brown - High Speed Blue - Medium Speed Red - Low Speed
Orange - Heating Valve
Yellow - Cooling Valve
For 2 pipe applications use cooling valve yellow wire connection
Orange - Electric Reheat
For electric reheat applications where current draw is under above 10 A use a line powered coil pilot duty relay or contactor for the heating element in place o f the heating va lv e
M
3 Speed
Applications
M
2 Speed
Applications
V
V
R
M
Single Speed
Applications
Black - Hot Power Orange - Connected to Black Hot White - Neutral
Fan Spee d Arrang ement By Configuration
Typical master slave applications with single or multiple fan(s)
Basic single FCU applications
o One fan motor under 1/2HP
o One, Two (or more) fan motors where each fan
motor is more than 1/2HP
o ( Pilot duty application )
o Two (or more) fan motors where
o Two (or more) fan motors where:
each fan motor is under 1/2HP totalling under
1/2HP combined
each fan motor is under 1/2HP totalling more than
1/2HP combined
6
Advanced single FCU applications
o One fan motor under 1/2HP
o One, Two (or more) fan motors where each fan
motor is more than 1/2HP
o ( Pilot duty application )
o Two (or more) fan motors where
each fan motor is under 1/2HP totalling under
o Two (or more) fan motors where:
each fan motor is under 1/2HP totalling more than
1/2HP combined
7
1/2HP combined
Basic multiple FCU applications
o One fan motor per FCU under 1/2HP
o Two (or more) fan motors per FCU where
each fan motor is under 1/2HP totalling under
o
1/2HP combined
Two (or more) fan motors per FCU where:
each fan motor is under 1/2HP totalling more than
1/2HP combined
9
o One, Two (or more) fan motors per FCU where each fan motor is more than 1/2HP o ( Pilot duty application )
Loading...
+ 19 hidden pages