Viconics VTR7300 Integration Manual

CONTENTS
Installation 2
Location 2 Installation 2
Operation Overview 3 Model Chart 5
Network ready 6
Terminal, Identification and Function 6 Communication wiring to VC3xxxX Relay Pack 6
Network wiring topology 7
VC3xxx LED Operation 7
Wiring of local inputs to VTR73xxA Terminal Equipment Controller 8
Configuring and Status Display Instructions 8
Status display 8
User Interface 10
Local keypad interface 10 Dual occupied setpoints adjustment 11 Single occupied setpoints adjustment 11 Unoccupied and stand-by setpoints adjustments 11 Mode button menu sequence. 11
Installer Configuration Parameter Menu 12
Configuration interface 13
1 | PIR Ready VTR7300 Series-Installation Guide
INSTALLATION
Remove the security screw on the bottom of Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment Controller (fig. 1).
Remove wiring terminals from sticker.  Please read the FCC ID and IC label
installed in the cover upon removal of cover for the wireless products.
Location
1. Should not be installed on an outside wall.
2. Must be installed away from any direct heat source.
3. Should not be installed near an air discharge grill.
4. Should not be affected by direct sun radiation.
5. Nothing should restrict vertical air circulation to the Terminal Equipment Controller.
Installation
1. Swing open the Terminal Equipment Controller PCB to the left by pressing the PCB locking tabs (fig. 2).
2. Pull out cables 6” out from the wall.
3. Wall surface must be flat and clean.
4. Insert cable in the central hole of the base.
5. Align the base and mark the location of the two mounting holes on the wall. Install proper side of base up.
6. Install anchors in the wall.
7. Insert screws in mounting holes on each side of the base (fig. 2).
8. Gently swing back the circuit board on the base and push on it until the tabs lock it.
9. Strip each wire 1/4 inch from end.
10. Insert each wire according to wiring diagram.
11. Gently push excess wiring back into hole (fig. 3).
2 | PIR Ready VTR7300 Series-Installation Guide
If replacing an existing Line Voltage FCU Thermostat, label the wires
before removal of the thermostat.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VTR7300 series controls are designed for use as operating controls
only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into the hole in the wall.
14. Install security screw.
OPERATION OVERVIEW
The VC3xxxX Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single master VTR73xxA Terminal Equipment Controller.
Fan operation can be configured and wired for the following:
3 Speed configuration using 3 fan relays ( Low - Med - High ) 2 Speed configuration using 2 fan relays ( Low - High ) 3 Speed configuration with auto fan speed mode using 3 fan relays
( Low - Med - High - Auto )
2 Speed configuration with auto fan speed mode using 2 fan relays
The VTR7300 Controller can be configured for typical 2 or 4 pipe heating / cooling FCU (Fan Coil Unit) applications.
2 or 4 pipe only operation can be configured and wired for the following:
3 | PIR Ready VTR7300 Series-Installation Guide
( Low - High - Auto )
Single fan speed configuration.
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover
2 or 4 pipe only with electric reheat can be configured and wired for the following:
o Cooling only o Heating only o Cooling / Heating with network or local auto changeover o On-Off electric reheat only o Cooling with On-Off or modulating VDC pulsed electric reheat
( model dependent )
o Heating with On-Off or modulating VDC pulsed electric reheat
( model dependent )
o Cooling / Heating with network or local changeover with On-Off
or modulating VDC pulsed electric reheat ( model dependent )
The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal
Equipment Controller.
The VTR73xxA Controller controls the VC3xxxX Relay Pack(s) via a simple
communication bus.
A maximum of 10 VC3xxxX Relay Pack can be used under a single VTR73xxA
Terminal Equipment Controller.
3 wires minimum are required between the VTR73xxA Controller and the first
VR7300 Relay Pack.
The 3 wire functions are known as the following:
o 1 Tx / Rx Communication o 2 Power Hot 7.0 VDC 4 Watts maximum ( required for the
VTR73xxA Controller power )
o 3 Power common
Commands for fan speed and valve operation are issued from the VTR73xxA
Terminal Equipment Controller to the VC3xxxX Relay Pack(s)
4 | PIR Ready VTR7300 Series-Installation Guide
MODEL CHART
5 | PIR Ready VTR7300 Series-Installation Guide
Network ready
TERMINAL
IDENTIFICATION
ALL VTR73XXA5X00(X)
TERMINAL EQUIPMENT CONTROLLER
Terminal 3
Tx – Rx Communication
Terminal 4
Power Hot 7.0 VDC
Terminal 5
Power Common
Terminal 13
BI 1 ( Configurable )
Terminal 14
Scom
Terminal 15
BI 2 ( Configurable )
All Viconics VTR7300 series Terminal Equipment Controllers are designed for
stand-alone operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7000V5000W, Terminal Equipment Controller wireless
communication adapter
o VCM7300T5000B, Terminal Equipment Controller BACnet™ MS-TP
communication adapter
TERMINAL, IDENTIFICATION AND FUNCTION
COMMUNICATION WIRING TO VC3XXXX RELAY PACK
Only ONE VC3xxxX Relay Pack with remote monitoring inputs can be used under a single VTR73xxA Controller. All other slave units must be VC3xxxX Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxX Relay Packs can be used for a single VTR73xxA Terminal Equipment Controller.
6 | PIR Ready VTR7300 Series-Installation Guide
From the VTR73xxA to the first VC3xxxX Relay Pack
Condition of the Status LED
Cause
Solution
2 short blinks
No communication between
the VTR73xxA and the VC3xxxX relay pack. The VC3xxxX Relay Pack will
resume its output “no
communication active” status
Check communication
wiring and or power cycle the controllers
2 short blinks and a
longer blink
Normal communication
between the VTR73xxA and
the VC3xxxX relay pack.
N/A
0.2
2.5
0.6
0.4
0.0
1.0
5.0 sec
Power On
Online to
VTR73xxA
Uses existing or new field wires A minimum of 3 wires are required 14-22 Ga Solid or Stranded. Shield not
necessary.
From the first VC3xxxX to all other slave VC3xxxX Relay Pack(s)
Uses existing or new field wires A minimum of 2 wires are required 14-22 Ga Solid or Stranded. Shield not
necessary.
Connect only wires #1 Power Common and #2 Tx/Rx Communication
Network wiring topology
VC3XXX LED OPERATION
7 | PIR Ready VTR7300 Series-Installation Guide
LED / Time (Status operation)
Wiring of local inputs to VTR73xxA Terminal Equipment Controller
ROOM &
HUMIDITY
SYSTEM MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C or °F XX % RH
Sys mode auto
Occupied
Outdoor x.x °C or °F
Service
If humidity display enabled
Sys mode cool
Stand-By
Network value only
Filter
RoomTemp x.x °C or °F
Sys mode heat
Unoccup
n/a
Window
If humidity display is not enabled
Sys mode off
Override
n/a
Low Batt
VTR73xxA
Terminal Controller
13
- BI 1
14
- Scom 15
- BI 2
Local BI 1 Input by configuration:
- None (monitoring only)
-
Remote motion detector: Motion NO or Motion NC
- Remote Night Setback: RemNSB
Local BI 2 Input by configuration:
- None (monitoring only)
- Door contact: DoorDry
- Window contact Window:
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The VTR73xxA Terminal Equipment Controller features a two-line, eight-character display. There is a low-level backlight that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display that shows the status of the system. There is an option in the configuration menu to lockout the scrolling display and to only display the room temperature and conditional outdoor temperature to the user. With this option enabled, no local status of mode, occupancy and relative humidity is shown.
Each item scrolls individually with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic status display scrolling.
To activate the back light to high level, press any key on the front panel. The back light display will return to low level when the Terminal Equipment Controller is left unattended for 45 seconds.
Sequence of auto-scroll status display:
8 | PIR Ready VTR7300 Series-Installation Guide