Viconics VT8300 Series Installation Manual

Page 1
VT8300 Series Installation Guide
24 Vac Low Voltage
Commercial and Hotel/Lodging HVAC Fan Coil Applications for 1, 2, 3-speed or ECM motors
Page 2
• If replacing an existing Room Controller, label wires before removal of Controller.
• Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Room Controller.
• A short circuit or wrong wiring may permanently damage Room Controller or equipment.
• This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be located or operating in conjunction with any other antenna or transmitter.
LOCATION
• Do not install on outside wall.
• Do not install behind a door.
• Do not install in areas with direct heat source.
• Do not install near any air discharge grill.
• Do not install in areas exposed to direct sunlight.
• Ensure Room Controller has sufficient natural air circulation.
• Ensure wall surface is flat and clean.
• Ensure external thermal sensor wirings are away from noisy electrical sources.
• Install 1.3 to 1.5 meter (52 to 60 inches) above the floor.
CLEANING THE ROOM CONTROLLER
• Use a soft, pre-moistened lint-free cloth for cleaning.
• Avoid getting moisture in openings.
• Do not spray anything directly on the Room Controller or use compressed air.
• Do not use caustic/corrosive products, ammonia, solvents or any cleaning product containing alcohol or grit.
• Never use tools directly on the touchscreen.
• Never use paint on the Room Controller.
• Do not drop or crush the Room Controller, or allow it to come into contact with liquids.
• Do not use a damaged device (such as one with a cracked screen).
• Performance can be affected if the glass on the screen is broken.
Failure to comply with these recommendations will result in damage to the unit and void the manufacturer’s warranty.
Page 3
INSTALLATION
Installation
1. Remove security screw (if any) on bottom of Room Controller cover.
2. Open unit by pulling on bottom side of Room Controller (Figure 1).
3. Read FCC ID and IC label installed in cover before installing any wireless product.
4. Ensure correct side of base faces up.
3
5. Pull cables 6in (15cm) out from wall.
6. Align base and mark location of two mounting holes on wall (Figure 2).
7. Install anchors in wall.
8. Insert cable in central hole of base.
9. Insert screws in mounting holes on each side of base.
10. Strip each wire 1/4in (0.6cm) from end.
11. Insert each wire and screw according to wiring chart (see following pages).
12. Gently push excess wiring back into hole.
13. Gently align cover to top of base and snap in place from bottom (Figure 3).
14. Install security screw.
Figure 1 Open the cover
Figure 2 Install the base
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Figure 3 Reinstall cover
Page 4
4
TERMINAL IDENTIFICATION AND FUNCTION
Terminal identification for 3-Speed Fan System
Fan Type - 3-Speed
Control Type On/Off Floating Analog
1- BO1 Not used Not used Not used
2- BO2 Fan-L Fan-L Fan-L
3- BO3 Fan-M Fan-M Fan-M
4- BO4 Fan-H Fan- H Fan-H
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 Normally Close Heat Valve Close Heat Valve Not used
11- UO11 Normally Open Cool Valve Open Cool Valve Analog Heat Valve
12- U O12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- U I17 UI17 Function
18- Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21- Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 5
Terminal identification for ECM Fan System
Fan Type - ECM
Control Type On/Off Floating Analog
1- BO1 Normally Close Heat Valve Close Heat valve Not used
2- BO2 Not used Not used Not used
3- BO3 Not used Not used Not used
4- BO4 ECM Fan Star t ECM Fan Star t ECM Fan Star t
5- RC / 24 V~ Hot 24 V~ Hot 24 V~ Hot 24 V~ Hot
6- C / 24 V~ Com 24 V~ Com 24 V~ Com 24 V~ Com
7- RH Aux Heat Aux Heat Aux Heat
8- BO8 Aux Heat Aux Heat Aux Heat
9- UO9 Normally Close Cool Valve Close Cool Valve Not used
10- UO10 Analog ECM Fan Analog ECM Fan Analog ECM Fan
11- UO11 Normally Open Cool Valve Open Cool Valve Analog Heat valve
12- U O12 Normally Open Heat Valve Open Heat Valve Analog Cool Valve
13- RS485 + RS485 +
14- RS485 - RS485 -
15- RS485 Ref RS485 Ref
16- UI16 UI16 Function
17- U I17 UI17 Function
18- Scom Common
19- UI19 UI19 Function
20- UI20 Remote Room Sensor
21- Scom Common
22- UI22 Remote Supply Sensor
23- UI23 Not used
24- UI24 Not used
5
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 6
6
Wiring - Single or Multispeed Motor
Power and Fan
3 Speed 2 Speed Single Speed
LOW LOW
LOW LOW
MED
MED
HIGH HIGH
BO8 Auxiliary Output Wiring
Dry contact to end device 24 V~ maximum 24 Vac power to relay
RC (24 Vac)
C (Common)
R
RH
BO8 - Aux Heat
RC (24 Vac)
C (Common)
RH
BO8 - Aux Heat
HIGHHIGH HIGH
HIGH
24 Vac
Transformer
R
Wiring ECM Motor
Power and Fan
4
BO4 - Fan H
RC (24 Vac)
C (Common)
UO10 ECM Fan
24Vac signal to start fan (optional)
0 - 10Vdc signal
Relay Coil
24Vac
Transformer
-
+
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 7
Main Outputs Wiring
2 Pipe Applications
Com 24Vac
Com
4 Pipe Applications
2 Pipe Applications 4 Pipe Applications
Com 24Vac
Com 24Vac
Com Open Close
Com Open
Com 24Vac
Com 24Vac
Com Open Close
Com 24 Vac
0-10 Vdc
Com
Com 24Vac
Com 24Vac
Com Open Close
Com Open Close
Com 24Vac
Com 24Vac
Com Open Close
Com Open Close
7
2 Pipe Applications 4 Pipe Applications
Control type = On-Off
UO9
UO11
UO11
UO9
UO12
Heating / Cooling valve
OR
Com 24Vac
UO10 NC
UO12 NO
UO09 NC
UO11 NO
Com
OR
OR
24Vac
Com 24Vac
Heating valve
Cooling valve
Floating control
Heating / Cooling valve
Com Open Close
UO12
UO10
UO11
UO9
Com Open Close
Com Open Close
Heating valve
Cooling valve
Analog control
Heating / Cooling valve
Com 24Vac 0-10Vdc
UO11
UO12
Com 24 Vac
0-10 Vdc
Com 24 Vac
0-10 Vdc
Heating valve
Cooling valve
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 8
8
1 2
REMOTE SENSOR ACCESSORIES
Model no. Description
S3010W1031 Wall mounted temperature sensor
S3020W1031 Wall mounted temperature sensor with override button and occupancy status LED
The VT8300 Room Controller is compatible with remote mount temperature sensors using 10K type 2 NTC thermistors.
Note: If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in the RS terminal will re-activate the internal sensor.
Features:
• Each sensor can be configured for various averaging combinations
• Optional occupancy led
• Optional override key
Wiring example of single remote room sensor
VT8300
Series Controller
Common
UI 20
BO8
24 Vac Com
UI17
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%)
ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm ºC ºF Kohm
-40 -40 324.3197 -20 -4 94.5149 0 32 32.1910 20 68 12.4601 40 104 5.3467
-35 -31 234.4009 -15 5 71.2430 5 41 25.1119 25 77 10.0000 45 113 4.3881
-30 -22 171.3474 -10 14 54.1988 10 50 19.7390 30 86 8.0694 50 122 3.6202
-25 -13 126.6109 -5 23 41.5956 15 59 15.6286 35 95 6.5499 55 131 3.0016
S3020W1031
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
OR
RS
Aux
C
DI
Dip switch setting for:
1 sensor
S3010W1031
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
RS
ON
S2-1 = ON
S2-2 = ON
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 9
HOME SCREEN DISPLAY
9
Hospitality User Interface Shown
Date
Occupancy Status
Indoor Temperature
Indoor Humidity
Outdoor Temperature
System Mode
Short Network
Message
Time System Status
Fan Status
Up Arrow Increase Temperature Setpoint
Actual Setpoint
Down Arrow Decrease Temperature Setpoint
Help
Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters.
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Fan Mode
Temperature Units
Language Selection
Page 10
10
HOW TO ENTER SET-UP SCREEN
SET-UP SCREEN DISPLAY
1/2 Setup
Touch and hold this point for 3 seconds to enter set-up mode
Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components.
For more information on using and configuring the functions of the HMI, refer to the VT8300 User Interface
Guide
Network
Configuration
Setpoints - Display
Service View
Test Outputs
Language Selection
Return to home screen
Enter BACnet® & ZigBee® network settings
Enter parameter configuration menu
Enter setpoint & display settings
Enter status and service view
Enter output testing mode
Enter language selection
General Note:
Adjustable parameter
Nonadjustable parameter
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Page 11
APPENDIX A TERMINAL CORRESPONDENCE
The terminals of a VT8300 are identified differently and have a wider range of possible functions compared to those of any of the VT7300 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the VT7300 series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7300 Room Controller with a VT8300 Room Controller.
VT7300 VT8300
Terminal name Terminal ID Terminal name Terminal ID
Binary Input 1 BI1 Universal Input 16 UI16
Binary Input 2 BI2 Universal Input 17 UI17
Universal Input 3 UI3 Universal Input 19 UI19
Sensor Common Scom Terminal 18 Common COM
Remote Sensor RS Universal Input 20 UI20 - RS
Sensor Common Scom Terminal 21 Common COM
Mix/Supply Sensor MS Universal Input 22 UI22 - SS
11
APPENDIX B POWER OUTAGE CLOCK RESET
In the event of a power outage, VT8300 Room Controllers retain the correct time as long as the duration of the power outage is not prolonged. Depending on the duration of the power outage, the Room Controllers internal clock may need to be updated or reset completely. The following table gives an indication of the expected clock performance after a power outage.
Outage duration Room Controller behaviour
0 - 24 hours Clock functions are normal
24 - 36 hours Clock accuracy not guaranteed, time may need to be adjusted
36 - 72 hours Clock no longer increments and must adjusted when power is
restored
72+ hours Clock functions are fully reset, and must be reinitialized as per a new
installation
Viconics Technologie s Inc. www.viconics.com sales@viconics.com
028-0429-05 November 2018
Loading...