Viconics VT8300 Interface Guide

VT8300 User Interface Guide
VT8300 Room Controller Series
Commercial and Hotel/Lodging HVAC Fan Coil Applications
1
CONTENTS
HMI Display 2 How to Enter Setup Screen 3 Setup Screen Display 3
Schedule Menu 4 Clock Settings 5 Schedule Settings 6 Occupancy Settings 7 Wireless Ecosystem Settings 8 LUA Settings 9
Network Settings 11
ZigBee BACnet BACnet
Configuration Parameters 16 Password Settings 28 Setpoints Settings 30 Display Settings 32
User HMI - Hospitality 33 User HMI - Commercial 34 Other Functions 34 Customizable Color Options 37 Setpoint Adjustment 38
Service Views 39 Test Outputs Screen 42 Language Selection 44 Appendix A: Terminal Correspondence 45
®
®
Network Settings 14
®
Instance Number 15
2
User Interface Guide
VT8300 Series
HMI Display
The below shows a typical user interface for the hospitality industry. The User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, and Setpoint to be enabled or disabled by setting various parameters.
Date
Occupancy Status
Indoor Temperature
Indoor Humidity
Outdoor Temperature
System Mode
Short Network
Message
Time System Status
Fan Status
Up Arrow Increase Temperature Setpoint
Actual Setpoint
Down Arrow Decrease Temperature Setpoint
Help
Fan Mode
Temperature Units
Language Selection
General Notes
1. When any change is made to a parameter, the value is automatically saved in memory when the next parameter is selected or another page is opened.
2. Arrows auto-increment/decrement at higher speed when holding button for more than 0.5 second.
3. All objects related to humidity do not display on HMI when Controller is ordered without built-in humidity sensor.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
1/2 Setup
Network
Configuration
Setpoints - Display
Service view
Test outputs
Language selection
VT8300 Series
Enter Set-up Screen
Touch and hold this point for 3 seconds to enter setup mode
Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components.
3
Enter BACnet® & ZigBee® network settings (only if ZigBee is detected)
Enter parameter configuration menu
Enter setpoint and display settings
Enter status and service view
Enter output testing mode
Enable selected language(s)*
Return to home screen
Note: The following menus show according to context:
- ZigBee menu shows if ZigBee card detected.
- Network choice inside does not show if no network is available
Discover Mode The Controller
becomes discoverable on the wireless
ZigBee® network for 1 minute (this
button is hidden if ZigBee® settings are not configured)
General Note:
Adjustable parameter
Nonadjustable parameter
Indicates invisible conditional
field. Appears based only
on model or presence of a
ZigBee® card
*only available in recent versions of firmware
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
4
2/2 Setup
Clock - Schedule
LUA
Wireless Ecosystem
Occupancy
Schedule Menu
Clock
Schedule
SET-UP SCREEN DISPLAY 2/2
Enter Schedule menu screen
Enter Wireless Ecosystem menu screen
Enter LUA script settings
User Interface Guide
VT8300 Series
SCHEDULE MENU SCREEN
Enter Clock settings
Enter Schedule settings
Enter Occupancy settings
Note: The Schedule menu screen is directly accessible from the main display if the Schedule Menu configuration parameter is enabled. See Configuration Parameters Screen 8/9 for more information.
Touch and hold this point for 3 seconds to enter the Schedule Menu screen.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
--:--
Clock
Time Format
AM-PM
Time
2014
Year
Month
Day
Weekday
01
Jan.
Sunday
VT8300 Series
CLOCK SETTINGS
The Clock settings screen allows the device’s internal time settings to be changed, including current time, standard day, month, year and weekday options, as well as choice between a 12 hour AM / PM display or a 24 hour display.
5
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Time Format
Current time display format Default value: AM-PM
Time
Current time display setting Default value: Begins at 12:00 AM at initial power up.
Year Default value: 2000
Month Default value: Jan.
Day Default value: 01
Weekday
Default value: Sunday
Choice between 12 hour AM - PM time format or 24 hour time format.
AM-PM 24 Hours
Note: Changing the value of this parameter automatically changes the format of the displayed value of the Time parameter directly below.
Standard time display, 12 hour AM-PM or 24 hour; format is determined by the Time Format parameter value.
Current year
Current month
Current day
Current day of the week
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
6
--:--
--:--
****day Schedule
Occupied
Unoccupied
--:--
--:--
Occupied
Unoccupied
--:--
--:--
Occupied
Unoccupied
User Interface Guide
VT8300 Series
SCHEDULE SETTINGS
There are 7 different schedule setting screens, one for each day of the week, titled accordingly. Each day can have different scheduled events where the room controller is set to Occupied status or back to Unoccupied status and use the appropriate setpoints, back and forth up to 3 times per day.
Screen title is identified by day of the week (Sunday through Saturday)
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Occupied Default value: None
Unoccupied
Default value: None
Defines a time when the room controller is automatically set to use the Occupied setpoint.
Note: There are 3 separate Occupied parameter entries
Defines a time when the room controller is automatically set to use the Unoccupied setpoint.
Note: There are 3 separate Unoccupied parameter entries
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
Occupancy
Occupancy cmd.
Loc occ.
VT8300 Series
OCCUPANCY SETTINGS
The occupancy settings screen allows you to determine how the Room Controller will determine whether it is functioning in Occupied or Unoccupied mode.
7
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Occupancy cmd
Default value: Local occ
Occupancy Command
Loc occ: occupancy is determined by local sequences.
Occupied: force occupied mode.
Unoccup: force unoccupied mode.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
8
Set function to
Status
1/10 Zone
Battery
No
Paired
0x0000
IEEE address
None
Closed
Normal
Permit join
On
Set function to
Status
10/10 Zone
Battery
No
Paired
0x0000
IEEE address
None
Closed
Normal
User Interface Guide
VT8300 Series
WIRELESS ECOSYSTEM
When ZigBee wireless sensors are set up to communicate with a Room Controller, the functioning of each such sensor is described in a separate Zone screen, up to a maximum of 10 Zones. Select the appropriate type of sensor based on the required functioning using the up and down arrow keys.
Up to 10 separate wireless sensors can be configured, each with its own Zone screen
Identical to ZigBee settings display parameter, see page 11
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Set function to
Describe function of specified wireless sensor Default value: None
Status
Current status of information received from the sensor Read only
Battery
Current status of sensor battery, if any. Read only
Paired
Sensor pairing state Read only
Only last 4 digits in HEX shown
None: No sensor function configured for this zone Door: Sensor is a door contact switch Window: Sensor is a window contact switch Motion: Sensor is a motion sensor Status: Updates the BACnet status of the sensor, but no action is
taken by the internal logic of the controller. Remove: Selecting this function clears the zone of the settings for
the attached sensor. However, the sensor will automatically try to reconnect with the room controller unless it is manually reset as well.
Close: Sensor in closed state (door/window only) Open: Sensor in opened state (door/window only) No motion: Sensor detects no motion (motion sensor only) Motion: Sensor detects motion (motion sensor only) None: No status information received from sensor.
Low: Battery power level is low, replacement or recharge will be
needed soon
Normal: Battery power level is in the normal range, replacement or recharge is not currently needed.
None: Sensor does not use a battery
No: Sensor is not paired with the room controller
Yes: Sensor is paired with the room controller
Invalid: Sensor cannot be paired.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
1/3 LUA
LUA program’s name:
User program
Program:
if not init then init=true delay=0 end if ME.BV1==1 then ME.BO98=1 delay=60
2/3 LUA
Debug log:
Program cmd
Program status
Program error
Run
Running
No error
VT8300 Series
LUA SETTINGS
The LUA settings screens show information about any custom LUA script uploaded to the controller. LUA scripts are not programmable on the controllers, and so must be uploaded to the controllers.
The title of the LUA script is shown here
The body of the LUA script is shown here
9
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Program cmd
Default value: Run
Program status
Read only
Program error
Read only
Run: The LUA script is activated and will run continuously until deactivated.
Stop: The LUA script is deactivated
Running: The LUA script is current active Halted: The LUA script has been stopped and is not active. Idle: The LUA script is running but is not currently taking any
actions
Waiting: The LUA script is running and waiting for a response.
No error: No errors in the LUA script are detected. Syntax: A syntax error in the LUA script is detected Runtime: A runtime error has occurred while running the LUA
script.
Memory: The device has run out of memory for the script
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
10
3/3 LUA
0
8
Param. B (AV26)
Param. C (AV27)
Param. D (AV28)
Param. E (AV29)
Param. F (AV30)
0
0
0
Param. A (AV25)
User Interface Guide
VT8300 Series
LUA GENERIC PARAMETERS
The LUA settings include six generic parameters that do not have predefined values. These can be used to represent LUA script variables. They are user configurable in their default state, but when they are assigned a value by a LUA script they become read only, and the display colour of the parameter changes to red. These parameters are also modifiable through BACnet as Analog Values (AVs). These parameters can be configured to receive information from ZigBee sensors.
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Parameter A
Default value: 0 Default value can be changed by user
Parameter B
Default value: 0 Default value can be changed by user
Parameter C
Default value: 0 Default value can be changed by user
Parameter D
Default value: 0 Default value can be changed by user
Parameter E
Default value: 0 Default value can be changed by user
Parameter F
Default value: 0 Default value can be changed by user
5
A parameter defined by a LUA script displays in red text.
The default value is normally 0, but it can be user-configured to use a different default value.
AV25
The value(s) of this parameter depends on what is assigned to it using the LUA script function
AV26
The value(s) of this parameter depends on what is assigned to it using the LUA script function
AV27
The value(s) of this parameter depends on what is assigned to it using the LUA script function
AV28
The value(s) of this parameter depends on what is assigned to it using the LUA script function
AV29
The value(s) of this parameter depends on what is assigned to it using the LUA script function
AV30
The value(s) of this parameter depends on what is assigned to it using the LUA script function
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
Com address
ZigBee Pan ID
1/2 ZigBee Network
ZigBee channel
0x0000
ZigBee short
0x0000
IEEE address
No NWK
ZigBee status
254
0
10
VT8300 Series
ZIGBEE PRO NETWORK SETTINGS
ZigBee Pro set-up screen shows when a ZigBee card is detected in the model. Select the desired parameter and use the up or down arrow to set the parameter to the desired value.
ZigBee® Pro short address. The address is generated once the device joins a ZigBee® network
Only last 4 digits in HEX show
Status of controller detecting a ZigBee® network. Shows Online when successfully connected to a network.
11
Previous Next Page Page
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Com address
Terminal Equipment Controller networking address Default value = 254 Range value = 0 - 254
Change Value Down.
Back to Setup Page
Communication Address
For wireless models, the use of COM address is not mandatory. The extended IEEE ZigBee® node address is used to identify the device on the network. The COM address is an optional way to identify a device on the network.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
12
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
ZigBee Pan ID Personal Area Network Identification Default value = 0 Range value = 0 - 1000
ZigBee channel
Channel selection Default value = 10 Range value = 10 - 25
User Interface Guide
VT8300 Series
ZigBee Pro PAN ID
Links specific Terminal Equipment Controllers to specific ZigBee® Pro coordinators. For every Terminal Equipment Controller reporting to a coordinator. Ensure set the SAME channel value both on the coordinator and the Terminal Equipment Controller(s).
Default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from 1 to 1000.
Range 1 to 500 for centralized networked applications using a ZigBee® Pro Coordinator.
Range 501 to 1000 is for stand-alone applications where each controller is its own coordinator for stand alone installation of wireless door and window switches.
ZigBee channel
This parameter links specific Terminal Equipment Controllers to specific ZigBee® Pro coordinators. For every Terminal Equipment Controller reporting to a coordinator, ensure you set the SAME channel value both on the coordinator and the Terminal Equipment Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of available channel is from 11 to 25.
ZigBee status
Read only
ZigBee status
The following read only messages show in this field:
(Not Det): ZigBee® Pro module not detected
(Pwr On): ZigBee® Pro module detected but not configured
(No NWK): ZigBee® Pro configured but no network joined
(Joined): ZigBee® Pro network joined
(Online): Communicating
Note: The following menus shows according to context:
1. If ZigBee Pro card is detected, ZigBee configuration menus automatically show.
2. Bacnet menus show if the model supports BACnet.
3. Network choice inside the Setup screen does not show if no network is available.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
2/2 ZigBee others
Door status
Closed
Door installed
No
Window status
Closed
Win. installed
No
Permit join
On
Battery alarm
Off
VT8300 Series
13
Door status if installed Window status if installed
Battery status of wireless switch
Note: Display returns to home screen when no activity is detected for 1 minute.
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Permit join
Default value = On
Indicates if door contact is installed Indicates if window contact is installed
Automatically allows
®
ZigBee
Pro devices to join the network through this controller.
Permit Join
Changing this value to Off prevents any new ZigBee® Pro devices from joining network through this controller.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
14
1/2 BACnet network
Baud rate
Auto
Network units
SI
Network lang.
English
BACnet status
Offline
COM address
254
User Interface Guide
VT8300 Series
BACNET NETWORK SETTINGS
BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set parameter to desired value.
254 value sets BACnet® network Offline. Choose different
Imperial or Metric units
Baud rate settings
value to activate Online
Language setting
Displays BACnet status, Offline or Online
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Comm address
Terminal Equipment Controller networking address Default value = 254 Range: 0 to 254
Network units
Default value = Imperial
Network lang
Default value = English
Baud rate
Default value = Auto
Communication Address
For BACnet® MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet® communication for the Terminal Equipment Controller.
Measurement Units
(Imperial): network units shown as Imperial units. (SI): network units shown as International Metric units.
Language Settings
Choice of network language/object names transmitted over network. All available choices: (English, French, and Spanish).
Baud Rate
(Auto): automatically detects BACnet® MS/TP baud rate.
Other choices: (115200, 76800, 57600, 38400, 19200, and 9600).
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
0830057
2/2 BACnet instance
VT8300 Series
BACNET INSTANCE NUMBER
The default BACnet® instance number is generated by the model number and COM address of the controller. For example, The instance number of a VT8300A5B00 with a COM address of 57 is generated as “83057”.
The default instance number appears first. To change the instance number, use number pad and press Accept and save.
Press Reset to automatic instance addressing to reset to automatic instance addressing.
Instance number of controller
Baud rate settings
15
Reset to automatic instance addressing
Accept and save
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
16
1/7 Configuration
UI 19
UI 17
UI 16
None
None
None
Occupancy src
Motion
Smart recovery
Off
Setpoint func.
Attach Stp
CONFIGURATION PARAMETERS SCREEN 1//7
User Interface Guide
VT8300 Series
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
UI 16
Universal input no.1 configuration Default value = None
UI 17
Universal input no.2 configuration Default value = None
Universal Input No. 1
None: no function associated with input
Rem NSB: remote NSB timer clock input. The scheduling gets set as
per the binary input and provides low cost setback operation via a dry contact.
Motion No and Motion NC: advanced PIR occupancy functions using a Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Window EMS: forces system to disable any current heating or
cooling action by Terminal Equipment Controller.
Universal Input No. 2
None: no function associated with input.
Door Dry: door contact and motion detector.
Override: temporary occupancy remote override contact.
Filter: backlit flashing filter alarm shows on the Terminal Equipment
Controller LCD screen when the input is energized.
Service: backlit flashing Service alarm shows on Terminal Equipment Controller LCD screen when input is energized.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 1/7
Configuration Parameters Default Value Significance and Adjustments
UI 19
Universal input no.3 configuration Default value = None
Occupancy cmd
Default value = Local
17
Universal Input No. 3
None: no function associated with input though input can be used
for remote network monitoring.
COC/NH: change over dry contact. Normally heat used for hot/cold water or air change over switching in 2 pipe systems.
COC/NC: change over dry contact. Normally cool used for hot/cold water or air change over switching in 2 pipe systems.
COS: change over sensor. Used for hot/cold water or air change over switching in 2 pipe systems.
Occupancy Command
Loc Occ: occupancy is determined by local sequences.
Occupied: force occupied mode.
Unoccup: force unoccupied mode.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
18
2/7 Configuration
Auto fan func.
Fan menu
Auto mode
AS
On-Auto
Enabled
Standy mode
Abs
Standby diff.
2.0 C
Mode button
Normal
CONFIGURATION PARAMETERS SCREEN 2/7
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 2/7
Configuration Parameters Default Value Significance and Adjustments
Auto mode
Enables Auto menu for Mode button Default value = On
Fan menu
Default value = Local
Auto fan func.
Auto Fan Function Default value: AS
Auto Mode
Enables auto function for the mode button
For sequences 2, 4, and 5 only
On = auto active (Off-Cool-Heat-Auto)
Off = auto not active (Off-Cool-Heat)
Fan Speeds
User fan menu presented is dependent on selected fan sequence of operation for the fan coil.
L-M-H: 3 Speed configuration using 3 fan relays.
L-H: 2 Speed configuration using 2 fan relays.
L-M-H-A: 3 Speed configuration with Auto fan speed mode using 3 fan
relays. Auto Mode operation is dependent on Auto Fan parameter.
L-H-A: 2 Speed configuration with Auto fan speed mode using 2 fan relays. Auto Mode operation is dependent on Auto Fan parameter.
On-Auto: single Speed configuration. Auto is for Fan on demand/On is On all the time.
Automatic Fan Function
Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
AS: auto Speed during occupied periods. Fan is always on during occupied periods.
AS/AD: auto Speed/Auto Demand during occupied periods.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 2/7
Configuration Parameters Default Value Significance and Adjustments
Standby mode
Default value: Abs
Standby diff.
Default value: 2 °C ( 3 °F )
19
Standby Mode
Choose which standby setpoints are used for control.
Abs: absolute Standby entered values are used for standby mode.
Offset: offset Occupied setpoints +/- Standby diff. used for standby
mode.
Standby Difference
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat”= Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
20
3/7 Configuration
Temp. occ. time
Unocc. time
Standby time
2.0 hrs
0.0 hrs
0.5 hrs
Deh hysteresis
5.0% RH
Deh. max cool
100%
Deh. lockout
Enabled
CONFIGURATION PARAMETERS SCREEN 3/7
User Interface Guide
VT8300 Series
These parameters are only displayed on models with built in humidity sensor
PARAMETER DETAILS SCREEN 3/7
Configuration Parameters Default Value Significance and Adjustments
Standby time
Default value: 0.5 hours
Unocc. time
Default value: 0.0 hours
Standby Time
Time delay between the moment where the PIR cover detects
last movement in the area, and the time which the Terminal Equipment
Controller stand-by setpoints become active.
Range: 0.5 to 24.0 hours in 0.5 hours increments.
Unoccupied Time
Time delay between the moment where the Terminal Equipment Controller toggles to stand-by mode, and the time which the Terminal Equipment Controller unoccupied mode and setpoints become active.
Factory value 0.0 hours: Setting this parameter to its default value of
0.0 hours disables the unoccupied timer. This prevents the Terminal Equipment Controller to drift from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours in 0.5 hours increments.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 3/7
Configuration Parameters Default Value Significance and Adjustments
Temp. occ. time
Default value: 2 hours
Deh. hysteresis
Default value: 5% RH
21
Temporary Occupancy Time
Temporary occupancy time with occupied mode setpoints when override function is enabled.
When Terminal Equipment Controller is in unoccupied mode, function is enabled with either the menu or UI2 configured as remote override input.
Range: 0 - 24 hours.
Humidity Control Hysteresis
Used only if dehumidification sequence is enabled:
Range: 2 to 20% RH (models with humidity sensor only).
Deh. max. cool
Default value: 100%
Deh. lockout
Default value: Enabled
Maximum Dehumidification Cooling
Maximum cooling valve position when dehumidification is enabled. This can be used to balance smaller reheat loads installed in regards to the capacity of the cooling coil.
Range: 20 to 100 % (models with humidity sensor only).
Dehumidification Lockout
Typically toggled through the network. This variable enables or disables dehumidification based on central network requirements from the BAS front end.
Enabled = Dehumidification Authorized
Disabled = Dehumidification Not Authorized
Models with humidity sensor only.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
22
4/7 Configuration
BO8 Out Time
Control Type
CPH
15 min
Floating
4
BO8 AuxOut
Not used
Floating Time
0.5 min
DA/RA
DA
CONFIGURATION PARAMETERS SCREEN 4/7
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 4/7
Configuration Parameters Default Value Significance and Adjustments
CPH
Default value: 4 CPH
Control Type
Control type for Triac models Default: Floating
Cooling Output Cycles/Hr
Sets maximum number cycles per hour under normal control operation. It represents the maximum number of cycles equipment turns ON and OFF in one hour.
A higher CPH represents a higher accuracy of control at the expense of wearing mechanical components faster.
Range: 3, 4, 5, 6,7 and 8 CPH.
Control Output for FCU Valves
Defines type of control output for type of valves installed for the FCU application
On/Off: normally opened or normally closed 24 VAC 2 position valves
Floating: modulating 3 wires control of 24 VAC floating valves
Analog: analog modulating control of 2-10 Vdc valves
Refer to proper control diagram according to selected control type outputs.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 4/7
Configuration Parameters Default Value Significance and Adjustments
BO8 Out Time
Default value: 0 = 15 minutes
BO8 AuxOut
Aux contact function used for reheat if sequence is set to use BO8 for reheat through network or local. Ignore this param­eter. Default value = Not Used
Floating Time
Floating actuator stroke timing value Default value: 1.5 minutes floating actuator timing
23
Reheat Output Time
Sets reheat output time base.
Valid only if reheat sequences are enabled.
0 = 15 minutes
1 = 10 seconds for solid state relays
Binary Output Terminal
Output directly follows occupancy of the Terminal Equipment Controller.
1) Auxiliary NO: Occ or St-By = Contact Closed / Unoccupied = Contact Opened
2) Auxiliary NC: Occ or St-By = Contact Opened / Unoccupied = Contact Closed. Output to follow directly main occupancy and Fan on command. Typically used for 2 position fresh air damper applications.
3) Auxiliary NO: Occ or St-By & Fan On = Contact Closed/Unoccupied and Fan On or Off = Contact Opened
4) Auxiliary NC: Occ or St-By & Fan On = Contact Opened/ Unoccupied and Fan On or Off = Contact Closed
Floating Time
Maximum stroke time of floating valve actuator.
Range: 0.5 to 9.0 minutes in 0.5 minute increments
DA/RA
For Analog signals Default value: DA signal
Direct Acting/Reserve Acting
Reverse Acting or Direct Acting signal for Analog Output signals
DA = 0 to 100 % = 0 to 10VDC
RA = 0 to 100 % = 10 to 0VDC
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
24
5/7 Configuration
Seq. operation
Pipe no.
Prop. band
Heat only
2
3.0
Purge sample
0.0 hrs
Purge open
1 min
CONFIGURATION PARAMETERS SCREEN 5/7
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 5/7
Configuration Parameters Default Value Significance and Adjustments
Prop. band
Default value: 3
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI control loop.
Note: default value of 3.0 gives satisfactory operation in
most normal installation cases. The use of a superior proportional band different than the factory one is normally warranted in applications where Terminal Equipment Controller location is problematic and leads to unwanted cycling of the unit. A typical example is a wall mounted unit where Terminal Equipment Controller is installed between return and supply air feeds and is directly influenced by the supply air stream of unit.
Value Effective Proportional Band
Fahrenheit Celsius
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 5/7
Configuration Parameters Default Value Significance and Adjustments
Pipe no.
Default value: 4 pipes
Seq. operation
Default value: Sequence #1
Pipe Setting Type Installed
Defines type of system installed.
2 Pipes: limits number of sequences of operation available from 0 - 4. It also enables heat/cool operation from the same output.
4 Pipes: can access all sequences of operation from 0 - 2. Also enables heat/cool operation from different output.
Sequence Operation
Selects initial sequence of operation required by installation type and application.
System Modes System = 2 Pipes System = 4 Pipes
Off - Cool 0 = Cooling Only 0 = Cooling Only
Off - Heat 1 = Heating Only 1 = Heating Only
Off - Auto - Heat -
Cool
Off - Heat 3 = Heating With
Off - Auto - Heat -
Cool N/A
2 = Cooling With
Electric Reheat
Electric Reheat
2 = Cooling With Electric Reheat
3 = Heating With Electric Reheat
4 = Cooling and Heating (2 modulating outputs)
Off - Auto - Heat -
Cool N/A
5 = Cooling/Heating (2 modulating out­puts) with reheat
For 2 Pipe output applications, the system is limited if configured for local changeover COS, COC/NC or COC/NC. The current water tem­perature detected by the RU1 then limits the system mode available for the local configura­tion or network write.
25
For Sequence 2 and 3, set PulsedHt to On to enable pulsed electric reheat applications with VT8300B and VT8300E
Purge Sample
Default value: 2 hours
Purge Sample
Time interval between valve samples. Opens valve for a short period ad­justed by Purge open parameter to sample pipe temperature to decide between heating or cooling mode.
Adjustable for 0 to 4 hours (0 = disable).
Purge Open
Default value: 2 minutes
Purge Open
Time valve opens to sample pipe temperature to decide between heating or cooling mode.
Adjustable for 1 to 3 minutes.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
26
6/7 Configuration
Calib. temp.
User password
Main password
0.0 C
0
0
Calib. humid.
0% RH
Schedule menu
Enabled
CONFIGURATION PARAMETERS SCREEN 6/7
Parameter only displayed on models with built in humidity sensor.
User Interface Guide
VT8300 Series
PARAMETER DETAILS SCREEN 6/7
Configuration Parameters Default Value Significance and Adjustments
Main password
Default value: 0
User Password
Default value: 0
Calib. temp.
Default value = 0.0 °C or °F
Calib. humid.
Default value = 0% RH
Main Password
Installer password. This parameter sets a protective access password to prevent unauthorized access to configuration menu param­eters.
Default value of 0 does not prompt a password or lock access configuration menu.
Range: 0 - 9999.
User Password
User password. This parameter sets a protective access password to prevent user unauthorized access to main screen adjustments.
Default value of 0 does not prompt a password.
Range: 0 - 9999.
Calibration Temperature
Room temperature sensor calibration. Offset can be added or subtracted to actual displayed room temperature.
Range: ± 2.5 °C, 0.5 °C increments ( ± 5.0 °F, 1.0 °F increments ).
Humidity Calibration
Humidity sensor calibration. Offset can be added or subtracted to actual displayed humidity.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
Range: ± 15.0 %RH (models with humidity sensor only).
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
7/7 Reinitialization
Push to accept:
Are you sure?
Erase all?
No
No
VT8300 Series
CONFIGURATION PARAMETERS SCREEN 7/7
27
PARAMETER DETAILS SCREEN 7/7
Configuration Parameters Default Value Significance and Adjustments
Erase all?
Default value: No
Are you sure?
Default value: No
Erase All
Answering Yes on both and pressing Accept button erases all values and changes to factory default values except the following network related values:
COM address
ZigBee® Pro Pan ID
ZigBee® Pro channel
Network units
Network language
Baud rate
BACnet® instance
Device name
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
28
Installer Password
...
.
01234
56789
Enter your password
Reset
PASSWORD SETTINGS
The following shows you how to enter the password for the Installer and User
Installer Password
User Interface Guide
VT8300 Series
1. Installer password prompt shows only if password value is greater than 0000. A password value of 0000 disables installer password but does not restrict access to configuration options.
2. Installer password prompt automatically disappears after 10 seconds if no value is entered.
3. An error code is automatically generated if incorrect password is entered.
4. Installer is permitted access to all Installer functions and menus when correct password is entered.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
User Password
...
.
01234
56789
Wrong code
User Password
VT8300 Series
29
1. User password prompt shows only if password value is greater than 0000. A password value of 0000 disables user password but does not restrict access to local user functions.
2. User password prompt automatically disappears after 10 seconds if no value is entered.
3. User is permitted access to controller interface to change any allowed settings when correct password is entered.
4. Password lock resumes after 1 minute of non activity.
PASSWORD PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Main password
Default value: 0
User password
Default value: 0
Installers Password
Parameter sets a protective access password to prevent unauthorized access to the configuration menu parameters. A default value of 0 does not prompt a password or lock access to configuration menu.
Range: 0 to 9999.
Are You Sure
Parameter sets a protective access password to prevent User unauthorized access to main screen adjustments. A default value of 0 does not prompt for a password.
Range: 0 to 9999.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
30
1/2 Setpoints
Occ. cool.
Standby cool.
Unocc. cool.
25.5 °C
24.0 °C
22.0 °C
20.5 °C
16.5 °C
26.5 °C
Occ. heat.
Standby heat.
Unocc. heat.
SETPOINT SETTINGS 1/2
User Interface Guide
VT8300 Series
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Unocc. cool.
Default value: 26.5 °C (80 °F)
Standby cool.
Default value: 25.5 °C (78 °F)
Occ. cool.
Default value: 24.0 °C (74 °F)
Occ. heat.
Default value: 22.0 °C (72 °F)
Standby heat.
Default value: 20.5 °C (69 °F)
Unoccupied Cooling
Unoccupied cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby Cooling
The value of this parameter should be set between occupied and unoccupied cooling setpoints. Ensure difference between standby and occupied value can be recovered in a timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occupied Cooling
Cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occupied Heating
Heating setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby Heating
The value of this parameter should be set between occupied and unoccupied heating setpoints. Ensure difference between standby and occupied value can be recovered in a timely fashion when movement is detected in the zone.
Unocc. heat.
Default value: 16.5 °C (62 °F)
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
Stand-by heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).
Unoccupied Heating
Unoccupied heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
2/2 Setpoints
Max. heating
Min. deadband
Default heat
1.5 °C
32.0 °C
12.0 °C
50.0 %RH
22.0 °C
Min. cooling
Dehumidify
SETPOINT SETTINGS 2/2
Parameter only displayed on models with built in humidity sensor.
VT8300 Series
31
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Default heat
Default value: 22.0 °C (73 °F)
Min. deadband
Default value: 1.5 °C (3 °F)
Max heating
Default value: 32 °C (90 °F)
Default Heat
Used for hospitality applications in stand-alone mode only. When devices are in deep unoccupied mode, any movement detected by PIR resets actual occupied set points to fresh room default setting.
Default setpoint is used to write to Heating setpoint when thermostat goes to Unoccupied mode.
Cooling setpoint is set according to Min. deadband; 18.0 to 26.5 °C (65 to 80 °F).
Parameter is only used when Stand-by mode = Rel.
Minimum Deadband
Minimum deadband value between heating and cooling setpoints applied only when any setpoints are modified.
Range: 1.0 to 2.5 °C, 0.5 °C increments (2, 3, 4 or 5 °F, 1.0 °F increments).
Maximum Heating
Maximum occupied and unoccupied heating setpoint adjustment.
Min. cooling
Default value: 12.0 °C (54 °F)
Dehumidify
Default value: 50% RH
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
Range: 4.5 to 32.0 °C (40 to 90 °F).
Minimum Cooling
Minimum occupied and unoccupied cooling setpoint adjustment.
Range: 12.0 to 37.5 °C (54 to 100 °F).
Dehumidify
Used only if dehumidification sequence is enabled: Range is: 30-95% RH (models with humidity sensor only).
© 2014 Viconics Technologies Inc. All rights reserved.
32
1/2 Display
Color
White
User HMI
0
Main display
Temp.
Standby screen
No
DISPLAY SETTINGS 1/2
User Interface Guide
VT8300 Series
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
User HMI
Default value: 0
Color
Default value: White
Main display
Default value: Temp.
Standby screen
Default value: No
User HMI
Select user HMI type.
Range: 0 to 11.
White
Change text colors according to set font colors.
Main Display
Shows temperature setpoint
Standby Screen
When the device is left unattended for 2 minutes background backlight dims to save screen life.
Installers can load a custom image for brand identification.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
User HMI for Hospitality
0 (Hospitality) 1 (Hospitality) 2 (Hospitality) 3 (Hospitality)
33
Setpoint adjustment
System mode setting
Fan mode setting
Local unit scale
Setpoint adjustment
System mode setting
Fan mode setting
User help menu
Local unit scale adjustment
Local user language
User help menu
Setpoint adjustment
User help menu
adjustment
Local user language
User help menu
Parameters are model dependent and may not appear on certain models.
4 (Hospitality) 5 (Hospitality) 6 (Hospitality) 7 (Commercial)
Fully locked interface with no user settings
Setpoint adjustment
System mode setting
User help menu
Setpoint adjustment
System mode setting
Fan mode setting
Local unit scale adjustment
User help menu
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
Setpoint adjustment
System mode setting
Fan mode setting
unoccupied mode overdrive
User help menu
© 2014 Viconics Technologies Inc. All rights reserved.
34
User Interface Guide
VT8300 Series
8 (Commercial) 9 (Commercial) 10 (Commercial) 11 (Commercial)
Setpoint adjustment
Unoccupied mode override
Local user language
Setpoint adjustment
Unoccupied mode override
User help menu
Setpoint adjustment
Unoccupied mode override
User help menu
User help menu
Note:
The day/night setback button appears only in unoccupied mode from 7 to 11 in HMI Commercial. If UI17 input is configured as “override”, the day/night setback button does not show.
Parameters are model dependent and may not appear on certain models.
Other Functions
Setpoint adjustment
System mode setting
Unoccupied mode override
User help menu
Local humidity only shows on models with the humidity sensor present and when enabled by configuration prop­erty RH Display.
Outdoor temperature display is dependent on receiving a valid networked outdoor temperature value.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
Heating only Configuration
Setpoint value shows if main display parameter is set to Setpoint.
On/Off icon is used instead of system mode icon when sequence of operation is set to either heating on or cooling only.
35
Time and Date show only when a network time synchronisation command is received.
Setpoint Adjustment for Cooling Mode
In Cooling mode, the setpoint displayed in the bar is the current occupied cooling setpoint.
During occupied setpoint adjustment, the large digits are temporarily used to show occupied cooling setpoint while it is adjusted.
Normal temperature display resumes after setpoint is adjusted and actual occupied cooling setpoint shows in setpoint bar.
Cooling mode or cooling only sequence of operation.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
36
User Interface Guide
Setpoint Adjustment for Heating Mode
In automatic mode, setpoint showing at the top of the set point bar located directly under the blue line represents the actual occupied cooling setpoint.
During occupied setpoints adjustment, large digits are temporarily used to display the occupied Cooling Setpoint or occupied Heating Setpoint. The actual setpoint is dependent on the last effective demand (heating or cooling). The setpoint on top of the red line represents the actual occupied heating setpoint. The differential between the occupied heating and cooling setpoint is defined by the minimum deadband configuration parameter.
Normal temperature display resumes after setpoints are adjusted and the actual occupied heating and cooling setpoints show in the setpoint bar.
VT8300 Series
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Color
Default value: White
Main display
Default value: White
Standby screen
Default value: No
Automatic Heating/Cooling Mode
Color
Select user HMI colour.
Choices: Green, Blue, Brown, and Grey.
Main Display
Select default value displayed on main display as temperature or set­point.
Choices: Temperature or setpoint.
Standby Screen
Selecting Yes shows a custom image after 2 minutes with no user activ­ity on the touch screen.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
CUSTOMIZABLE COLOR OPTIONS
37
White Green Blue
Brown Grey
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
38
Language
Night backLight
Units
Low backLight
English
5%
°C
60%
RH display
Disabled
2/2 Display
DISPLAY SETTINGS 2/2
Parameter only displayed on models with built in humidity sensor.
SETPOINT PARAMETER DETAILS
User Interface Guide
VT8300 Series
Configuration Parameters Default Value Significance and Adjustments
Language
Default value: English
°C or °F Default value: °C
Low backlight
Default value: 60%
Night backlight
Default value: 5%
Language
Select language for main display.
Choices: English, French, Spanish, Chinese, and Russian
Temperature Units
Sets default local scale value when Terminal Equipment Controller pow­ers up.
°C for Celsius. °F for Fahrenheit.
Backlight Display
Set display backlight intensity after 2 minutes of keyboard inactivity.
Adjustable: 0 to 100%.
Night Backlight Display
Set display backlight intensity after 2 minutes of keyboard inactivity.
Adjustable: 0 to 100%.
Parameter only available for models with motion/light detectors. The screen backlight progressively decreases down to this setting when room is dark. This feature is used mostly in hospitality applications when a darker non obtrusive lighting level is desired when room is dark.
RH display
Default value: Disabled
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
Relative Humidity Display
Enables display of humidity below room temperature on the display (On): Display %RH. (Off): Do not display %RH. *(models with humidity sensor only)
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
1/6 Service view
Room temp.
xx.x °C
Room humidity
xx.x %RH
Firmware rev.
1.0
xx.x °C
Supply temp.
xx.x °C
ChgOver temp.
xx.x °C
Outdoor temp.
2/6 Service view
PI heat. dem.
0%
0%
PI cool. dem.
Heat dem. limit
0.0%
0.0%
Cool. dem. limit
Effective occ.
Occupied
Supply temp.
xx.x °C
VT8300 Series
SERVICE SCREEN VIEWS
The service view screens show the current status of certain points locally at the controller. These points can also be viewed through the network. Service view allows service contractor to visualize the status of key functionality to correctly diagnose operational system issues.
Firmware Revision
Room Temperature
Changeover Temperature
Supply Temperature
Outdoor Temperature
Room Humidity
39
Parameter only displayed on models with built in humidity sensor.
Effective Occupancy
PI Cooling Demand
PI Heating Demand
Cooling Demand Limit
Heating Demand Limit
Supply Temperature
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
40
3/6 Service view
UI16 status
UI19 status
UI17 status
Activated
Not activ
Not activ
Filter alarm
Window alarm
Off
Off
Off
Service alarm
Local motion
On
4/6 Service view
Deh. status
Off
User Interface Guide
Universal Input Status
Universal Input Status
Universal Input Status
VT8300 Series
Window Alarm Status
Service Alarm Status
Filter Alarm Status
Local Motion Status
Dehumidification Status
Parameter only displayed on models with built in humidity sensor.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
UO9 Config
Binary
Binary
5/6 Service view
UO10 Config
UO11 Config
UO12 Config
Binary
Binary
6/6 Service view
Device name:
VT83xxAxxxx
VT8300 Series
41
Universal Output Configuration
Universal Output Configuration
Universal Output Configuration
Universal Output Configuration
Device Name / Model Number
The Model Number is the BACnet® device name automatically assigned when using the current BACnet® addressing scheme based on the MAC address. The network can update and change the device BACnet® name. If changed, the new updated BACnet® device name shows on the screen.
For example, when a VT8300U5500B thermostat with a MAC address of 41 is connected to a network, its default Device Name is VT8300U5x00B-41 and its default BACnet Device ID is 83041.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
42
BO2 Fan Low
BO4 Fan High
Off
Off
Off
BO3 Fan Med
BO8 Aux Output
Off
1/2 Test Outputs
TEST OUTPUTS
User Interface Guide
VT8300 Series
Note 1: Cooling output can also be used for heating on two pipes systems.
Note 2: The test output screen allows manual override of specified outputs. When any BACnet® network priority array includes a value,
the status background shows in red. After any output state is overridden, the command is cancelled after 1 minute of screen inactivity (auto exit to main screen) or when page is exited. Refer to the BACnet® integration guide for more details.
Note 3: Use high caution when manually enabling outputs so as to not cause damage to equipment. It is the responsibility of the Installer or Service Contractor to insure safe operation during usage.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
UO11 Binary
UO9 Binary
Off
Off
Off
UO10 Binary
UO12 Binary
Off
2/2 Test outputs
UO11 Analog
0 Vdc
0 Vdc
UO12 Analog
2/2 Test outputs
TEST OUTPUTS
VT8300 Series
CASE A CASE B
43
Note: screen Test outputs are LIVE. Any output gets displayed immediately for any value change according to the following:
1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red.
2. When toggling a value on the screen, the output directly energizes according to the selected value.
3. You can override any output if you bypass the Bacnet array (1 - 16).
4. It is not possible to modify the set Bacnet array values.
5. After any output state gets modified, all overrides get cancelled after 1 minute of button inactivity, or if you scroll from one screen to another screen.
CASE A: screen 2/2 display is dependent on Control type configuration. If mode is set to Floating or On/Off, binary options show.
CASE B: screen 2/2 display is dependent on Control type configuration. If mode is set to Analog, analog options show.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
44
Language selection
Chinese
Spanish
French
Enabled
Enabled
Enabled
Russian
Enabled
LANGUAGE SELECTION
User Interface Guide
VT8300 Series
All languages are enabled by default, which means that they will be accessible to users cycling through languages on the display settings menu screen. To change the language selection settings, touch a language on the screen and then use the arrow buttons to disable or enable it. The English language is always enabled.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
User Interface Guide
VT8300 Series
APPENDIX A: TERMINAL CORRESPONDENCE
The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the VT7000 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7000 series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller with a VT8300 Room Controller.
VT7000 VT8300
Terminal name Terminal ID Terminal name Terminal ID
Binary Input 1 BI1 Universal Input 16 UI16
Binary Input 2 BI2 Universal Input 17 UI17
Universal Input 3 UI3 Universal Input 19 UI19
Sensor Common Scom Terminal 18 Common COM
Remote Sensor RS Universal Input 20 UI20 - RS
Sensor Common Scom Terminal 21 Common COM
Mix/Supply Sensor MS Universal Input 22 UI22 - SS
45
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
028-0427-01 www.viconics.com | sales @viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
Loading...