User HMI - Hospitality 33
User HMI - Commercial 34
Other Functions 34
Customizable Color Options 37
Setpoint Adjustment 38
Service Views 39
Test Outputs Screen 42
Language Selection 44
Appendix A: Terminal Correspondence 45
®
Network Settings 11
®
Network Settings 14
®
Instance Number 15
2
User Interface Guide
VT8300 Series
HMI Display
The below shows a typical user interface for the hospitality industry. The User HMI is configurable and allows display functions such as Date,
Time, Humidity, Outdoor Temperature, and Setpoint to be enabled or disabled by setting various parameters.
Date
Occupancy Status
Indoor Temperature
Indoor Humidity
Outdoor Temperature
System Mode
Short Network
Message
Time
System Status
Fan Status
Up Arrow
Increase Temperature Setpoint
Actual Setpoint
Down Arrow
Decrease Temperature
Setpoint
Help
Fan Mode
Temperature Units
Language Selection
General Notes
1. When any change is made to a parameter, the value is automatically saved in memory when the next
parameter is selected or another page is opened.
2. Arrows auto-increment/decrement at higher speed when holding button for more than 0.5 second.
3. All objects related to humidity do not display on HMI when Controller is ordered without built-in humidity sensor.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Touch and hold this point
for 3 seconds to enter setup mode
Note: If a configuration/installer
password is activated to prevent
unauthorised access to the
configuration menu parameters, a
password entry prompt shows to
prevent access to device
configuration components.
3
Enter BACnet® & ZigBee® network settings (only if ZigBee is detected)
Enter parameter configuration menu
Enter setpoint and display settings
Enter status and service view
Enter output testing mode
Enable selected language(s)*
Return to
home screen
Note: The following menus show according to context:
- ZigBee menu shows if ZigBee card detected.
- Network choice inside does not show if no network is available
Discover ModeThe Controller
becomes discoverable on the wireless
ZigBee® network for 1 minute (this
button is hidden if ZigBee® settings are
not configured)
General Note:
Adjustable parameter
Nonadjustable parameter
Indicates invisible conditional
field. Appears based only
on model or presence of a
ZigBee® card
*only available in recent versions of firmware
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Note: The Schedule menu screen is directly
accessible from the main display if the Schedule Menu
configuration parameter is enabled. See Configuration
Parameters Screen 8/9 for more information.
Touch and hold this
point for 3 seconds
to enter the Schedule
Menu screen.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The Clock settings screen allows the device’s internal time settings to be changed, including current time, standard day, month, year
and weekday options, as well as choice between a 12 hour AM / PM display or a 24 hour display.
5
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Time Format
Current time display format
Default value: AM-PM
Time
Current time display setting
Default value: Begins at 12:00 AM at initial power up.
Year
Default value: 2000
Month
Default value: Jan.
Day
Default value: 01
Weekday
Default value: Sunday
Choice between 12 hour AM - PM time format or 24 hour time
format.
AM-PM
24 Hours
Note: Changing the value of this parameter automatically changes
the format of the displayed value of the Time parameter directly
below.
Standard time display, 12 hour AM-PM or 24 hour; format is
determined by the Time Format parameter value.
Current year
Current month
Current day
Current day of the week
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
There are 7 different schedule setting screens, one for each day of the week, titled accordingly. Each day can have different scheduled
events where the room controller is set to Occupied status or back to Unoccupied status and use the appropriate setpoints, back and
forth up to 3 times per day.
Screen title is identified by
day of the week (Sunday
through Saturday)
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Occupied
Default value: None
Unoccupied
Default value: None
Defines a time when the room controller is automatically set to use
the Occupied setpoint.
Note: There are 3 separate Occupied parameter entries
Defines a time when the room controller is automatically set to use
the Unoccupied setpoint.
Note: There are 3 separate Unoccupied parameter entries
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
When ZigBee wireless sensors are set up to communicate with a Room Controller, the functioning of each such sensor is described in
a separate Zone screen, up to a maximum of 10 Zones. Select the appropriate type of sensor based on the required functioning using
the up and down arrow keys.
Up to 10 separate
wireless sensors can
be configured, each
with its own Zone
screen
Identical to ZigBee
settings display
parameter, see
page 11
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Set function to
Describe function of specified wireless sensor
Default value: None
Status
Current status of information received from the sensor
Read only
Battery
Current status of sensor battery, if any.
Read only
Paired
Sensor pairing state
Read only
Only last 4 digits
in HEX shown
None: No sensor function configured for this zone
Door: Sensor is a door contact switch
Window: Sensor is a window contact switch
Motion: Sensor is a motion sensor
Status: Updates the BACnet status of the sensor, but no action is
taken by the internal logic of the controller.
Remove: Selecting this function clears the zone of the settings for
the attached sensor. However, the sensor will automatically try to
reconnect with the room controller unless it is manually reset as
well.
Close: Sensor in closed state (door/window only)
Open: Sensor in opened state (door/window only)
No motion: Sensor detects no motion (motion sensor only)
Motion: Sensor detects motion (motion sensor only)
None: No status information received from sensor.
Low: Battery power level is low, replacement or recharge will be
needed soon
Normal: Battery power level is in the normal range, replacement or
recharge is not currently needed.
None: Sensor does not use a battery
No: Sensor is not paired with the room controller
Yes: Sensor is paired with the room controller
Invalid: Sensor cannot be paired.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
if not init theninit=truedelay=0endif ME.BV1==1 thenME.BO98=1delay=60
2/3 LUA
Debug log:
Program cmd
Program status
Program error
Run
Running
No error
VT8300 Series
LUA SETTINGS
The LUA settings screens show information about any custom LUA script uploaded to the controller. LUA scripts are not programmable
on the controllers, and so must be uploaded to the controllers.
The title of the LUA script
is shown here
The body of the LUA
script is shown here
9
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Program cmd
Default value: Run
Program status
Read only
Program error
Read only
Run: The LUA script is activated and will run continuously until
deactivated.
Stop: The LUA script is deactivated
Running: The LUA script is current active
Halted: The LUA script has been stopped and is not active.
Idle: The LUA script is running but is not currently taking any
actions
Waiting: The LUA script is running and waiting for a response.
No error: No errors in the LUA script are detected.
Syntax: A syntax error in the LUA script is detected
Runtime: A runtime error has occurred while running the LUA
script.
Memory: The device has run out of memory for the script
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The LUA settings include six generic parameters that do not have predefined values. These can be used to represent LUA script variables.
They are user configurable in their default state, but when they are assigned a value by a LUA script they become read only, and the
display colour of the parameter changes to red. These parameters are also modifiable through BACnet as Analog Values (AVs). These
parameters can be configured to receive information from ZigBee sensors.
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Parameter A
Default value: 0
Default value can be changed by user
Parameter B
Default value: 0
Default value can be changed by user
Parameter C
Default value: 0
Default value can be changed by user
Parameter D
Default value: 0
Default value can be changed by user
Parameter E
Default value: 0
Default value can be changed by user
Parameter F
Default value: 0
Default value can be changed by user
5
A parameter defined by a LUA
script displays in red text.
The default value is normally 0,
but it can be user-configured to
use a different default value.
AV25
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV26
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV27
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV28
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV29
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV30
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
ZigBee Pro set-up screen shows when a ZigBee card is detected in the model. Select the desired parameter and
use the up or down arrow to set the parameter to the desired value.
ZigBee® Pro short address. The address is generated
once the device joins a ZigBee® network
Only last 4 digits in HEX show
Status of controller detecting a ZigBee®
network. Shows Online when successfully connected
to a network.
11
Previous Next
Page Page
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Com address
Terminal Equipment
Controller networking address
Default value = 254
Range value = 0 - 254
Change Value
Down.
Back to Setup Page
Communication Address
For wireless models, the use of COM address is not mandatory.
The extended IEEE ZigBee® node address is used to identify the
device on the network.
The COM address is an optional way to identify a device on the
network.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
ZigBeePan ID
Personal Area Network
Identification
Default value = 0
Range value = 0 - 1000
ZigBee channel
Channel selection
Default value = 10
Range value = 10 - 25
User Interface Guide
VT8300 Series
ZigBee Pro PAN ID
Links specific Terminal Equipment Controllers to
specific ZigBee® Pro coordinators. For every Terminal Equipment
Controller reporting to a coordinator. Ensure set the SAME
channel value both on the coordinator and the Terminal Equipment
Controller(s).
Default value of 0 is NOT a valid PAN ID. The valid range of
available PAN ID is from 1 to 1000.
Range 1 to 500 for centralized networked applications using a
ZigBee® Pro Coordinator.
Range 501 to 1000 is for stand-alone applications where each
controller is its own coordinator for stand alone installation of
wireless door and window switches.
ZigBee channel
This parameter links specific Terminal Equipment Controllers to
specific ZigBee® Pro coordinators. For every Terminal Equipment
Controller reporting to a coordinator, ensure you set the SAME
channel value both on the coordinator and the Terminal Equipment
Controller(s).
Using channels 15 and 25 is recommended.
The default value of 10 is NOT a valid channel. The valid range of
available channel is from 11 to 25.
ZigBee status
Read only
ZigBee status
The following read only messages show in this field:
• (Not Det): ZigBee® Pro module not detected
• (Pwr On): ZigBee® Pro module detected but not configured
• (No NWK): ZigBee® Pro configured but no network joined
• (Joined): ZigBee® Pro network joined
• (Online): Communicating
Note: The following menus shows according to context:
1. If ZigBee Pro card is detected, ZigBee configuration menus automatically show.
2. Bacnet menus show if the model supports BACnet.
3. Network choice inside the Setup screen does not show if no network is available.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
BACnet network set-up screen shows when BACnet is detected in model. Select desired parameter and use up or down arrow to set
parameter to desired value.
254 value sets BACnet®
network Offline. Choose different
Imperial or
Metric units
Baud rate
settings
value to activate Online
Language setting
Displays BACnet status,
Offline or Online
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Comm address
Terminal Equipment Controller
networking address
Default value = 254
Range: 0 to 254
Network units
Default value = Imperial
Network lang
Default value = English
Baud rate
Default value = Auto
Communication Address
For BACnet® MS-TP models, the valid range is from 1 to 127.
Default value of 254 disables BACnet® communication for the Terminal
Equipment Controller.
Measurement Units
(Imperial): network units shown as Imperial units.
(SI): network units shown as International Metric units.
Language Settings
Choice of network language/object names transmitted over network.
All available choices: (English, French, and Spanish).
The default BACnet® instance number is generated by the model number and COM address of the controller. For example, The instance
number of a VT8300A5B00 with a COM address of 57 is generated as “83057”.
The default instance number appears first. To change the instance number, use number pad and press Accept and save.
Press Reset to automatic instance addressing to reset to automatic instance addressing.
Instance number of controller
Baud rate
settings
15
Reset to automatic
instance addressing
Accept and save
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
These parameters are only displayed on
models with built in humidity
sensor
PARAMETER DETAILS SCREEN 3/7
Configuration Parameters Default ValueSignificance and Adjustments
Standby time
Default value: 0.5 hours
Unocc. time
Default value: 0.0 hours
Standby Time
Time delay between the moment where the PIR cover detects
last movement in the area, and the time which the Terminal Equipment
Controller stand-by setpoints become active.
Range: 0.5 to 24.0 hours in 0.5 hours increments.
Unoccupied Time
Time delay between the moment where the Terminal Equipment
Controller toggles to stand-by mode, and the time which the Terminal
Equipment Controller unoccupied mode and setpoints become active.
Factory value 0.0 hours: Setting this parameter to its default value of
0.0 hours disables the unoccupied timer. This prevents the Terminal
Equipment Controller to drift from stand-by mode to unoccupied mode
when PIR functions are used.
Range: 0.0 to 24.0 hours in 0.5 hours increments.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
Temp. occ. time
Default value: 2 hours
Deh. hysteresis
Default value: 5% RH
21
Temporary Occupancy Time
Temporary occupancy time with occupied mode setpoints when override
function is enabled.
When Terminal Equipment Controller is in unoccupied mode, function is
enabled with either the menu or UI2 configured as remote override input.
Range: 0 - 24 hours.
Humidity Control Hysteresis
Used only if dehumidification sequence is enabled:
Range: 2 to 20% RH (models with humidity sensor only).
Deh. max. cool
Default value: 100%
Deh. lockout
Default value: Enabled
Maximum Dehumidification Cooling
Maximum cooling valve position when dehumidification is enabled. This
can be used to balance smaller reheat loads installed in regards to the
capacity of the cooling coil.
Range: 20 to 100 % (models with humidity sensor only).
Dehumidification Lockout
Typically toggled through the network. This variable enables or disables
dehumidification based on central network requirements from the BAS
front end.
Enabled = Dehumidification Authorized
Disabled = Dehumidification Not Authorized
Models with humidity sensor only.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
BO8 Out Time
Default value: 0 = 15 minutes
BO8 AuxOut
Aux contact function used for reheat if sequence is set to use
BO8 for reheat through network or local. Ignore this parameter.
Default value = Not Used
Output directly follows occupancy of the Terminal Equipment Controller.
1) Auxiliary NO: Occ or St-By = Contact Closed / Unoccupied =
Contact Opened
2) Auxiliary NC: Occ or St-By = Contact Opened / Unoccupied =
Contact Closed. Output to follow directly main occupancy and Fan on
command. Typically used for 2 position fresh air damper applications.
3) Auxiliary NO: Occ or St-By & Fan On = Contact Closed/Unoccupied
and Fan On or Off = Contact Opened
4) Auxiliary NC: Occ or St-By & Fan On = Contact Opened/
Unoccupied and Fan On or Off = Contact Closed
Floating Time
Maximum stroke time of floating valve actuator.
Range: 0.5 to 9.0 minutes in 0.5 minute increments
DA/RA
For Analog signals
Default value: DA signal
Direct Acting/Reserve Acting
Reverse Acting or Direct Acting signal for Analog Output signals
DA = 0 to 100 % = 0 to 10VDC
RA = 0 to 100 % = 10 to 0VDC
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
Prop. band
Default value: 3
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI
control loop.
Note: default value of 3.0 gives satisfactory operation in
most normal installation cases. The use of a superior proportional band
different than the factory one is normally warranted in applications where
Terminal Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall mounted unit
where Terminal Equipment Controller is installed between return and
supply air feeds and is directly influenced by the supply air stream of unit.
ValueEffective Proportional Band
FahrenheitCelsius
331.2
441.7
552.2
662.8
773.3
883.9
995.0
10105.6
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
Pipe no.
Default value: 4 pipes
Seq. operation
Default value: Sequence #1
Pipe Setting Type Installed
Defines type of system installed.
2 Pipes: limits number of sequences of operation available from
0 - 4. It also enables heat/cool operation from the same output.
4 Pipes: can access all sequences of operation from 0 - 2. Also enables
heat/cool operation from different output.
Sequence Operation
Selects initial sequence of operation required by installation type and
application.
System ModesSystem = 2 PipesSystem = 4 Pipes
Off - Cool0 = Cooling Only0 = Cooling Only
Off - Heat1 = Heating Only1 = Heating Only
Off - Auto - Heat -
Cool
Off - Heat3 = Heating With
Off - Auto - Heat -
CoolN/A
2 = Cooling With
Electric Reheat
Electric Reheat
2 = Cooling With
Electric Reheat
3 = Heating With
Electric Reheat
4 = Cooling and
Heating (2 modulating
outputs)
Off - Auto - Heat -
CoolN/A
5 = Cooling/Heating
(2 modulating outputs) with reheat
For 2 Pipe output applications, the system is
limited if configured for local changeover COS,
COC/NC or COC/NC. The current water temperature detected by the RU1 then limits the
system mode available for the local configuration or network write.
25
For Sequence 2 and 3, set PulsedHt to On to
enable pulsed electric reheat applications with
VT8300B and VT8300E
Purge Sample
Default value: 2 hours
Purge Sample
Time interval between valve samples. Opens valve for a short period adjusted by Purge open parameter to sample pipe temperature to decide
between heating or cooling mode.
Adjustable for 0 to 4 hours (0 = disable).
Purge Open
Default value: 2 minutes
Purge Open
Time valve opens to sample pipe temperature to decide between heating
or cooling mode.
Adjustable for 1 to 3 minutes.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The following shows you how to enter the password for the Installer and User
Installer Password
User Interface Guide
VT8300 Series
1. Installer password prompt shows only if password value is greater than 0000. A password value of 0000 disables installer
password but does not restrict access to configuration options.
2. Installer password prompt automatically disappears after 10 seconds if no value is entered.
3. An error code is automatically generated if incorrect password is entered.
4. Installer is permitted access to all Installer functions and menus when correct password is entered.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
1. User password prompt shows only if password value is greater than 0000. A password value of 0000 disables user password but
does not restrict access to local user functions.
2. User password prompt automatically disappears after 10 seconds if no value is entered.
3. User is permitted access to controller interface to change any allowed settings when correct password is entered.
4. Password lock resumes after 1 minute of non activity.
PASSWORD PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Main password
Default value: 0
User password
Default value: 0
Installers Password
Parameter sets a protective access password to prevent unauthorized
access to the configuration menu parameters. A default value of 0 does
not prompt a password or lock access to configuration menu.
Range: 0 to 9999.
Are You Sure
Parameter sets a protective access password to prevent User
unauthorized access to main screen adjustments. A default value of 0
does not prompt for a password.
Range: 0 to 9999.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Configuration Parameters Default ValueSignificance and Adjustments
Unocc. cool.
Default value: 26.5 °C (80 °F)
Standby cool.
Default value: 25.5 °C (78 °F)
Occ. cool.
Default value: 24.0 °C (74 °F)
Occ. heat.
Default value: 22.0 °C (72 °F)
Standby heat.
Default value: 20.5 °C (69 °F)
Unoccupied Cooling
Unoccupied cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby Cooling
The value of this parameter should be set
between occupied and unoccupied cooling setpoints. Ensure
difference between standby and occupied value can be recovered in
a timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occupied Cooling
Cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occupied Heating
Heating setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby Heating
The value of this parameter should be set between occupied and
unoccupied heating setpoints. Ensure difference between standby and
occupied value can be recovered in a timely fashion when movement is
detected in the zone.
Unocc. heat.
Default value: 16.5 °C (62 °F)
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Parameter only displayed on
models with built in humidity
sensor.
VT8300 Series
31
SETPOINT PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Default heat
Default value: 22.0 °C (73 °F)
Min. deadband
Default value: 1.5 °C (3 °F)
Max heating
Default value: 32 °C (90 °F)
Default Heat
Used for hospitality applications in stand-alone mode only. When devices
are in deep unoccupied mode, any movement detected
by PIR resets actual occupied set points to fresh room default setting.
Default setpoint is used to write to Heating setpoint when thermostat
goes to Unoccupied mode.
Cooling setpoint is set according to Min. deadband; 18.0 to 26.5 °C (65
to 80 °F).
Parameter is only used when Stand-by mode = Rel.
Minimum Deadband
Minimum deadband value between heating and cooling setpoints
applied only when any setpoints are modified.
Range: 1.0 to 2.5 °C, 0.5 °C increments (2, 3, 4 or 5 °F, 1.0 °F
increments).
Maximum Heating
Maximum occupied and unoccupied heating setpoint adjustment.
Min. cooling
Default value: 12.0 °C (54 °F)
Dehumidify
Default value: 50% RH
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The day/night setback button appears only in unoccupied mode from 7 to 11 in HMI Commercial.
If UI17 input is configured as “override”, the day/night setback button does not show.
Parameters are model dependent and may not appear on certain models.
Other Functions
• Setpoint adjustment
• System mode setting
• Unoccupied mode
override
• User help menu
Local humidity only shows on models with the humidity sensor present and when enabled by configuration property RH Display.
Outdoor temperature display is dependent on receiving a valid networked outdoor temperature value.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
In automatic mode, setpoint showing at the top of the set point bar located directly under the blue line
represents the actual occupied cooling setpoint.
During occupied setpoints adjustment, large digits are temporarily used to display the occupied Cooling
Setpoint or occupied Heating Setpoint. The actual setpoint is dependent on the last effective demand (heating or
cooling). The setpoint on top of the red line represents the actual occupied heating setpoint. The
differential between the occupied heating and cooling setpoint is defined by the minimum deadband
configuration parameter.
Normal temperature display resumes after setpoints are adjusted and the actual occupied heating and cooling
setpoints show in the setpoint bar.
VT8300 Series
PARAMETER DETAILS
Configuration Parameters Default ValueSignificance and Adjustments
Color
Default value: White
Main display
Default value: White
Standby screen
Default value: No
Automatic Heating/Cooling Mode
Color
Select user HMI colour.
Choices: Green, Blue, Brown, and Grey.
Main Display
Select default value displayed on main display as temperature or setpoint.
Choices: Temperature or setpoint.
Standby Screen
Selecting Yes shows a custom image after 2 minutes with no user activity on the touch screen.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Parameter only displayed on
models with built in humidity
sensor.
SETPOINT PARAMETER DETAILS
User Interface Guide
VT8300 Series
Configuration Parameters Default ValueSignificance and Adjustments
Language
Default value: English
°C or °F
Default value: °C
Low backlight
Default value: 60%
Night backlight
Default value: 5%
Language
Select language for main display.
Choices: English, French, Spanish, Chinese, and Russian
Temperature Units
Sets default local scale value when Terminal Equipment Controller powers up.
°C for Celsius.
°F for Fahrenheit.
Backlight Display
Set display backlight intensity after 2 minutes of keyboard inactivity.
Adjustable: 0 to 100%.
Night Backlight Display
Set display backlight intensity after 2 minutes of keyboard inactivity.
Adjustable: 0 to 100%.
Parameter only available for models with motion/light detectors. The
screen backlight progressively decreases down to this setting when
room is dark. This feature is used mostly in hospitality applications when
a darker non obtrusive lighting level is desired when room is dark.
RH display
Default value: Disabled
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The service view screens show the current status of certain points locally at the controller. These points can also be viewed through the
network. Service view allows service contractor to visualize the status of key functionality to correctly diagnose operational system issues.
Firmware Revision
Room Temperature
Changeover Temperature
Supply Temperature
Outdoor Temperature
Room Humidity
39
Parameter only displayed on
models with built in humidity
sensor.
Effective Occupancy
PI Cooling Demand
PI Heating Demand
Cooling Demand Limit
Heating Demand Limit
Supply Temperature
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The Model Number is the BACnet® device name automatically assigned when using the current BACnet®
addressing scheme based on the MAC address. The network can update and change the device BACnet® name. If changed, the new
updated BACnet® device name shows on the screen.
For example, when a VT8300U5500B thermostat with a MAC address of 41 is connected to a network, its default Device Name is
VT8300U5x00B-41 and its default BACnet Device ID is 83041.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Note 1: Cooling output can also be used for heating on two pipes systems.
Note 2: The test output screen allows manual override of specified outputs. When any BACnet® network priority array includes a value,
the status background shows in red. After any output state is overridden, the command is cancelled after 1 minute of screen inactivity
(auto exit to main screen) or when page is exited. Refer to the BACnet® integration guide for more details.
Note 3: Use high caution when manually enabling outputs so as to not cause damage to equipment. It is the responsibility of the Installer
or Service Contractor to insure safe operation during usage.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
Note: screen Test outputs are LIVE. Any output gets displayed immediately for any value change according to the following:
1. If any BACnet priority array (1 - 16) includes a value, the displayed state background shows in red.
2. When toggling a value on the screen, the output directly energizes according to the selected value.
3. You can override any output if you bypass the Bacnet array (1 - 16).
4. It is not possible to modify the set Bacnet array values.
5. After any output state gets modified, all overrides get cancelled after 1 minute of button inactivity, or if you scroll from one screen to
another screen.
CASE A: screen 2/2 display is dependent on Control type configuration. If mode is set to Floating or On/Off, binary options show.
CASE B: screen 2/2 display is dependent on Control type configuration. If mode is set to Analog, analog options show.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
All languages are enabled by default, which means that they will be accessible to users cycling through languages on the display
settings menu screen. To change the language selection settings, touch a language on the screen and then use the arrow buttons to
disable or enable it. The English language is always enabled.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150
The terminals of an VT8300 are identified differently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7000
series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8300 Room Controller.
VT7000VT8300
Terminal nameTerminal IDTerminal nameTerminal ID
Binary Input 1BI1Universal Input 16UI16
Binary Input 2BI2Universal Input 17UI17
Universal Input 3UI3Universal Input 19UI19
Sensor CommonScomTerminal 18 CommonCOM
Remote SensorRSUniversal Input 20UI20 - RS
Sensor CommonScomTerminal 21 CommonCOM
Mix/Supply SensorMSUniversal Input 22UI22 - SS
45
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514 ) 3 21- 4150