2 pipe systems cooling and/or heating 6
4 pipe systems cooling and heating 7
2 pipe systems cooling or heating with reheat 8
Remote Sensor Accessories 9
Wiring example of single remote room sensor 9
Wiring examples of 2 remote room sensors 10
Wiring examples of 2 remote room sensors 10
Home Screen Display 11
How to Enter Setup Screen 12
2
INSTALLATION
Preparation
• Remove the security screw (if any) on the bottom of the Terminal Equipment
Controller cover.
• Open unit by pulling on bottom side of the Terminal Equipment Controller
(Fig. 1).
• Read FCC ID and IC label installed in cover before installing any wireless
product.
• Ensure correct side of base faces up.
Location
1. Do not install on outside wall.
2. Do not install in areas with direct heat source.
3. Do no install near any air discharge grill.
4. Do not install in areas exposed to direct sunlight.
5. Ensure Controller has sufficient air circulation.
6. Ensure wall surface is flat and clean.
Installation
1. Pull cables 15 cm ( 6” ) out from wall.
2. Align base and mark location of two mounting holes on wall.
3. Install anchors in wall.
4. Insert cable in central hole of base.
5. Insert screws in mounting holes on each side of base.
6. Strip each wire 1/4” ( 0.6 cm) from end.
7. Insert each wire and screw according to wiring chart.
8. Gently push excess wiring back into hole.
9. Gently align cover to top of base and snap in place from bottom.
10. Install security screw.
Installation Guide
Figure-1 Ope n the cover
Figure-2 Install the bas e
VT8300 Series
• If replacing an existing Line Voltage FCU Controller, label wires
before removal of Controller.
• Electronic controls are static sensitive devices. Discharge
yourself correctly before manipulating and installing Controller.
• A short circuit or wrong wiring may permanently damage
Controller or equipment.
• All VT8300 ® series controls are designed for use as operating
controls only and are not safety devices. Tampering with the
devices or unintended application of the devices will result in a
void of warranty.
• This device must be installed to provide a separation distance
of at least 8in (40cm) from all persons and must not be
collocated or operating in conjunction with any other antenna
Figure-3 Reinstall cover
or transmitter.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0
Universal input #16 can be configured for the following binary
functions:
1. (None): No function will be associated with the input
2. (Rem NSB): remote NSB timer clock input. The scheduling will now be
set as per the binary input. It provides low cost setback operation via a dry
contact.
Contact opened = Occupied
Contact closed = Unoccupied
3. (Motion NO) and (Motion NC): Advanced PIR occupancy functions using
a normally open (NO) or normally closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APP-PIRSE8xxx. This document will provide the installers and system designers with
detailed examples on applications, parameter configuration information,
sequence of operation, troubleshooting and diagnostic help required for the
proper usage of the onboard PIR sensor.
4. (Window) EMS: Forces the system to disable any current heating or cooling
action by the Terminal Equipment Controller. The mode stays the same and
the current setpoints are the same occupied setpoints. Only the outputs
are disabled. There is a Door/Window alarm displayed on the Terminal
Equipment Controller to indicate to the local tenant that the door/window
needs to be closed for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm
Contact closed = System enabled
Universal input #17 can be configured for the following binary
functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or an onboard
PIR sensor is used. With this sequence enabled, the occupancy is now
dictated through those 2 inputs. Any motion detected will set the zone
to occupied status. The zone will remain permanently in occupied mode
until the door contact switch opens momentarily. The Terminal Equipment
Controller will then go in stand-by mode. If more movements are detected,
the occupied mode will resume. While the door is opened, any movements
detected by the remote PIR sensor or the onboard PIR sensor will be
ignored. Use a Normally Closed contact switching device.
4. (Filter): a Filter alarm short text message will be
displayed on the Terminal Equipment Controller
screen when the input is energized. It can be
tied to a differential pressure switch that monitor
filters
Contact opened = No alarm
Contact closed = Alarm displayed
5. (Service): a Service alarm short text message
will be displayed on the Terminal Equipment
Controller screen when the input is energized. It
can be tied in to the AC unit control card, which
provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Universal input #19 can be configured for
the following functions:
1. (None): No function will be associated with the
input
2. (COC/NH) Change over dry contact.
Normally Heat: Used for hot / cold air / water
change over switching in 2 pipe systems.
Contact closed = Cold air/water present
Contact opened = Hot air/water present
Only used and valid if Room Controller is set
up for a 2 pipe system.
3. (COC/NC) Change over dry contact.
Normally Cool: Used for hot / cold air / water
change over switching in 2 pipe systems.
Contact closed = Hot air/water present
Contact opened = Cold air/water
present
Only used and valid if Room Controller is set
up for a 2 pipe system.
4. (COS) Change over analog sensor: Used for
hot / cold air / water change over switching in 2
pipe systems.
Contact opened = Door opened
Contact closed = Door closed
3. (RemOVR): temporary occupancy remote override contact. This function
disables the central button override function on the Terminal Equipment
Controller. The override function is now controlled by a manual remote
momentarily closed contact. When configured in this mode, the input
operates in a toggle mode. It is now possible to toggle between unoccupied
& occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0
S3020W1000Wall mounted temperature sensor with override button and occupancy status
LED
The VT8300 room controller is compatible with remote mount temperature sensors using 10K type 2 NTC thermistors.
Note:
If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting
the sensor(s) in the RS terminal will re-activate the internal sensor.
Features:
• Each sensor can be configured for various averaging combinations
• Optional occupancy led
• Optional override key
Wiring example of single remote room sensor:
9
VT8300
Series Controller
Common
UI 20
BO8
24 Vac Com
UI17
S3020W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
OR
RS
Aux
C
DI
S3010W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
RS
Dip switch
setting for:
1 sensor
ON
1 2
S2-1 = ON
S2-2 = ON
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0
Note: User HMI is configurable and allows display functions such as Date, Time,
Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by
setting various parameters.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0
Touch and hold this point
for 3 seconds to enter set-up mode
Note: If a configuration/installer
password is activated to prevent
unauthorised access to the
configuration menu parameters, a
password entry prompt shows to
prevent access to device configuration
components.
For more information on using and
configuring the functions of the HMI,
refer to the following document:
VT8300 Series
Terminal Equipment Controller
User Interface Guide
Return to
home screen
Enter BACnet
Enter parameter configuration menu
Enter setpoint & display settings
Enter status and service view
Enter output testing mode
Enter language selection
Discover ModeThe Controller
becomes discoverable on the wireless
ZigBee® network for 1 minute (this
button is hidden if ZigBee® settings are
not configured)
®
& ZigBee® network settings
General Note:
Adjustable parameter
Non-adjustable parameter
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0
The terminals of a VT8300 are identified differently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7000
series and the VT8300 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room
Controller with a VT8300 Room Controller.
VT7000VT8300
Terminal nameTerminal IDTerminal nameTerminal ID
Binary Input 1BI1Universal Input 16UI16
Binary Input 2BI2Universal Input 17UI17
Universal Input 3UI3Universal Input 19UI19
Sensor CommonScomTerminal 18 CommonCOM
Remote SensorRSUniversal Input 20UI20 - RS
Sensor CommonScomTerminal 21 CommonCOM
Mix/Supply SensorMSUniversal Input 22UI22 - SS
13
APPENDIX B: POWER OUTAGE CLOCK RESET
In the event of a power outage, VT8300 Room Controllers retain the correct time as long as the duration of the power outage is
not prolonged. Depending on the duration of the power outage, the Room Controllers internal clock may need to be updated
or reset completely. The following table gives an indication of the expected clock performance after a power outage of a given
duration.
Outage duration Room Controller behaviour
0 - 24 hoursClock functions are normal
24 - 36 hoursClock accuracy not guaranteed, time may need to be adjusted
36 - 72 hoursClock no longer increments and will need to be adjusted when power is
restored.
72+ hoursClock functions are fully reset, and will need to be reinitialized as per a
new installation.
Viconics Technologies Inc. | 9245 La ngeli er Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel : (514) 321-5660 | Fa x: ( 514) 32 1-415 0