The VT76x7 PI thermostat family is specifically designed for single stage
and multi-stage control of heating/cooling equipment such as rooftop and
self-contained units with humidifier and/or dehumidifier. The product features
an embedded complete humidity solution with an intuitive, menu-driven,
backlit LCD display that walks users through the programming steps, making
the process extremely simple. Accurate temperature & relative humidity
control is achieved due to the product’s PI time proportional control
algorithm, which virtually eliminates temperature offset associated with
traditional, differential-based thermostats.
All models contain one digital input, which can be set by the user to monitor
filter status, activate a remote temporary occupancy switch, and/or used as
a general purpose service indicator. The two models contain a SPST
auxiliary switch, which can be used to control lighting or disable the
economizer function and a discharge air sensor input.
The additional following documentation is available on www.viconics.com
• Information on the LON models (VT76x7B1000E), is available on document ITG-VT76x7-LON-Exx
• Information on the BACnet models (VT76x7B1000B), is available on document ITG-VT76x7-BAC-Exx
• Information on the Wireless models (VT76x7B1000W), is available on documents: ITG-VWG-40-
Fig.1 - VT76x7 thermostat
BAC-Exx and LIT-VWG-40-SETUP-Exx
Models Avalable
Ordering Information Notes:
(X) model number represents available communication options: X = none for Stand-alone,
Features and benefits
X = B for BACnet MS-TP, X = E for Echelon and X = W for Wireless
⇒ Simplifies installation and reduce installation costs
colder climates
⇒ Can be used for all types of establishments
028-0174 R5_LIT-VT76x7-E05.doc
www.viconics.com / sales@viconics.com
Page 2
Theory of operation
The VT7600 uses a Viconics proprietary adaptive
logic algorithm to control the space temperature. This
algorithm controls the heating / air conditioning system
to minimize overshoots while still providing comfort. It
provides exceptional accuracy due to its unique PI
time proportioning control algorithm, which virtually
eliminates temperature offset associated with
traditional, differential-based on/off thermostats.
Fig.2 - On/Off mechanical control vs PI electronic control.
Features overview
• 7 day programmable models, 2 or 4 events
• Gas/oil or electric system compatibility for all type
of applications
• Internal RH sensor and remote RH input with
humidification and dehumidification sequence of
operation embedded
• Remote outdoor sensing capability for added
flexibility
- System mode lock out
- Humidity setpoint reset
• High limit input to prevent over-humidification
• Lockable keypads for tamper proofing. No need for
thermostat guards
• Automatic frost protection to prevents costly freeze
damage
• Anti short cycle and minimum on/off run time
protection. Reduces wear and maximizes life span
of mechanical equipment.
• Programmable digital input for added flexibility. The
input can be programmed as the following:
- None: No function will be associated with the
input
- Service: a backlit flashing Service alarm will be
displayed on the thermostat LCD screen when
the input is energized. It can be tied in to the AC
unit control card, which provides an alarm in
case of malfunction.
- Filter: a backlit flashing Filter alarm will be
displayed on the thermostat LCD screen when the
input is energized. It can be tied to a differential
pressure switch that monitor filters
- Rem NSB: remote NSB timer clock input. Will
disable the internal scheduling of the thermostat.
The scheduling will now be set as per the digital
input. The menu part related to scheduling is
disabled and no longer accessible. It provides low
cost setback operation via occupancy sensor or
from a dry contact
- RemOVR: temporary occupancy contact. Disables
all override menu function of the thermostat. . The
override function is now controlled by a manual
remote momentarily closed contact. When
configured in this mode, the input operates in a
toggle mode.
With this function enabled it is now possible to
toggle between unoccupied & occupied setpoints
for the amount of time set by parameter
(TOccTime) temporary occupancy time.
• Programmable smart fan operation saves
energy during night mode
• Non volatile EEPROM memory prevents loss of
parameters during power shortage
• Built in default profile set-up for easier start up
and commissioning
• Configurable SPST output relay on
programmable models for lighting, exhaust fan
or fresh air control
• 6 hour typical reserve time for clock in case of
power loss
• 0 to 10 Vdc humidification output
- Built in proportional humidity controller
- Proportional humidity high limit when used
with the analog input for supply humidity
- Automatic humidity setpoint reset when
outside air temperature value is used.
2
Page 3
Installation
3
• Remove security screw on the bottom of thermostat cover.
• Open up by pulling on the bottom side of thermostat.
• Remove Assembly and remove wiring terminals from sticker.
(Fig. 3)
A) Location:
1- Should not
be installed on an outside wall.
2- Must be installed away from any heat source.
3- Should not be installed near an air discharge grill.
4- Should not be affected by direct sun radiation.
5- Nothing must restrain vertical air circulation to the thermostat.
B) Installation:
1- Swing open the thermostat PCB to the left by pressing the PCB
locking tabs. (Fig. 4)
2- Pull out cables 6” out of the wall.
3- Wall surface must be flat and clean.
4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two mounting holes
on the wall. Install proper side of base up.
6- Install anchors in the wall.
7- Insert screws in mounting holes on each side of the base.
(Fig. 4)
8- Gently swing back the circuit board on the base and push on it
until the tabs lock it.
10- Strip each wire 1/4 inch.
11- Insert each wire according to wiring diagram.
13- Gently push back into hole excess wring (Fig. 5)
14- Re-Install wiring terminals in correct location. (Fig. 5)
15- Reinstall the cover (top side first) and gently push back extra
wire length into the hole in the wall.
16- Install security screw.
• If replacing an old thermostat, label the wires before
removal of the old thermostat.
• Electronic controls are static sensitive devices.
Discharge yourself properly before manipulation and
installing the thermostat.
• Short circuit or wrong wiring may permanently damage
the thermostat or the equipment.
• Anti-short cycling can be set to 0 minutes for equipment
that posses their own anti cycling timer. Do not use that
value unless the equipment is equipped with such
internal timer. Failure to do so can damage the
equipment.
• All VT7000 series thermostats are to be used only as
operating controls. Whenever a control failure could
lead to personal injury and/or loss of property, it
becomes the responsibility of the user to add safety
devices and/or alarm system to protect against such
catastrophic failures.
Valid for both hight limit sensor (HL) or
main remote humidity sensor (HS) connections
24 Vac Power
To Thermostat
VH2020D1000
Remote wiring
1
Common
2
Power
0-10 Vdc
4
Page 6
User menu flow chart:
NOTE:
Prompts may not all be present depending on model selected
MENU
If statu s is:
Unoccupied
6
Overr i de
schd Y/ N
If statu s is:
Temporary Occupied Time,
Occupied hold or
Resume
schd Y/ N
Unoccupied hold
Temperat
set ? Y/ N
Humi d i t y
set ? Y/ N
Sys mode
set ? Y/ N
Off
Heat
Cool
Fan mode
set ? Y/ N
On
Smart
Auto
Auto
Dehumi di
set ? Y/ N
Humi d i f i
set ? Y/ N
Exi t ?
Y/ N
RH%RH%
Cooling
set ? Y/ N
Heat i ng
set ? Y/ N
Unocc CL
set ? Y/ N
Unocc HT
set ? Y/ N
Temperature Temperature Temperature Temperature
Schedul e
set ? Y/ N
°F/°C
set ? Y/ N
°C
°F
Cl o c k
set ? Y/ N
Ti me
set ? Y/ N
Time
Exi t ?
Y/ N
Schedul e
hol d Y/ N
Resume
Occ Hold
Uno Hold
Da y
set ? Y/ N
Day
On stand-alone
models only
Exi t ?
Y/ N
12/ 24hrs
set ? Y/ N
12 / 24
Exi t ?
Y/ N
Exi t ?
Y/ N
Sunday
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Sat u r day
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Fr i day
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Thur sday
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
We dnesda
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Tuesday
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Monday
set ? Y/ N
Occupi ed
day? Y/ N
Occupi ed
12: 00 pm
Time
Unoccup
12: 00 pm
Time
Page 7
Programming and status display instructions
1. Status display
The thermostat features a two-line, eight-character display. There is a low-level backlit level that is always active and can only
be seen at night. When left unattended, the thermostat has an auto scrolling display that shows the actual status of the
system. Each item is scrolled one by one with the backlighting off. Pressing any key will cause the backlit to come on.
Sequence of auto-scroll status display:
Room Temp &
Humidity
x.x °C or °F Monday Sys mode Occupied Outdoor Service
xx % RH 12.00 AM auto x.x °C or°F
If humidity display is
enabled
RoomTemp
x.x °C or °F
If humidity display is not
enabled
Sys mode emergenc
Clock status System mode Schedule status
Sys mode
off
Sys mode
heat
Sys mode
cool
Occupied
hold
Unoccup
Unoccup
hold
Override
Outdoor
temperature
Frost ON
SetClock
Filter
Alarms
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The last item viewed will be shown on the
display for 30 seconds before returning to automatic scrolling. Temperature is automatically updated when scrolling is held.
Outdoor air temperature display is only enabled when outdoor air temperature sensor is connected or a network value is
received.
• A maximum range status display of 50 °C (122 °F) indicates a shorted sensor. Associated functions, such as mode lockouts
are automatically disabled.
• A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened sensor or a sensor not connected.
Associated functions, such as mode lockouts are automatically disabled.
If alarms are detected, they will automatically be displayed at the end of the status display scroll. During an alarm message
display, the backlit screen will light up at the same time as the message and shut off during the rest of the status display. Two
alarms maximum can appear at any given time. The priority for the alarms is as follows:
Frost ON
SetClock
Service
Filter
Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6 °C (42 °F )
Indicates that the clock needs to be reset. There has been a power failure which has lasted longer than 6 hours
Indicates that there is a service alarm as per one of the programmable digital input (DI1 or DI2)
Indicates that the filters are dirty as per one of the programmable digital input (DI1 or DI2)
Three status LEDs on the thermostat cover are used to indicate the status of the fan, a call for heat, or a call for cooling.
• When the fan is on, the FAN LED will illuminate.
• When heating is on, the HEAT LED will illuminate.
• When cooling is on, the COOL LED will illuminate.
Fig.10 – VT7657 and VT7607 cover
7
Page 8
2. User programming instructions menu
The VT7600 series of thermostat feature an intuitive, menu-driven, backlit LCD display that walks users through the
programming steps, making the programming process extremely simple. This menu is typically accessed by the user to set the
parameters such as temperature and time events, system mode, fan mode, etc.
It is possible to bring up the user menu at any time by depressing the MENU key. The status display automatically resumes
after exiting the user-programming menu.
If the user pauses at any given time during programming, Auto Help text is displayed to help and guide the user through the
usage and programming of the thermostat.
Ex.:
Each of the sections in the menu are accessed and programmed using 5 keys on the thermostat cover.
The priority for the alarms is as follows:
When left unattended for 45 seconds, the display will resume automatic status display scrolling.
To turn on the backlit, press any key on the front panel. The backlit display will turn off when the thermostat is left unattended
for 45 seconds
Sequence of user menu:
Override
schd Y/N
Appears only in
unoccupied mode
Cancel
ovrd Y/N
Appears only in
override mode
There is a default profile set in the thermostat from the factory.
This enables the thermostat to operate as a non-programmable unit in day mode operation at start up.
Programmed default temperature and humidity setpoints:
Occupied cooling setpoint = 24 °C ( 75 °F )
Occupied heating setpoint = 22 °C ( 72 °F )
Unoccupied cooling setpoint = 28 °C ( 82 °F )
Unoccupied heating setpoint = 18 °C ( 65 °F )
Dehumidification setpoint = 70% RH
Humidification setpoint = 50% RH
Fahrenheit scale
Setpoint type = permanent
There will be a 1 minute unoccupied period every night at 11:59 PM with this default configuration.
Press yes key to change cooling temperature setpoint
Use the up or down arrow to adjust cooling setpoint
The YES key is used to confirm a selection, to move onto the next menu item and to manually scroll through the
displayed information.
The NO key is used when you do not desire a parameter change, and to advance to the next menu item. Can
also be used to toggle between heating and cooling setpoints.
The MENU key is used to access the Main User Menu or exit the menu.
The down arrow key is used to decrease temperature setpoint and to adjust the desired values when
programming and configuring the thermostat.
The up arrow key is used to increase temperature setpoint and to adjust the desired values when programming
and configuring the thermostat.
Override
Resume
Temperature
setpoints
Temperat
set Y/N
Humidity
setpoints
Humidity
set Y/N
System mode
setting
Sys mode
set Y/N
Fan mode
setting
Fan mode
set Y/N
Schedules
setting
Schedule
set Y/N
Clock
setting
Clock
set Y/N
Schedule hold
Schedule
hold Y/N
Appears only on
stand-alone models
Programmed default modes:
System mode = Auto
Fan mode = Smart (for models with a communication module or
programmable stand-alone models)
Fan mode = Auto (for non-programmable stand-alone models)
Programmed default schedules:
Monday through Sunday
Occupied time is: 12 00 AM
Unoccupied time is: 11:59 PM
Unoccupied time is: 11:59 PM
8
Page 9
A) Override an unoccupied period
Override
schd Y/N
This menu will appear only when the thermostat is in unoccupied mode. The unoccupied mode is enabled either by the internal
timer scheduling or by a remote NSB contact via DI.
If DI is configured to operate as a remote temporary override contact, this menu will be disabled.
Answering yes to this prompt will cause the thermostat to go into occupied mode for an amount of time equal to the parameter
“TOccTime” (1 to 12 hours).
B) Resume regular scheduling
Cancel
ovrd Y/N
This menu does not appear in regular operation. It will appear only when the thermostat is in Unoccupied override mode.
Answering “Yes” to this question will cause the thermostat to resume the regular programmed setpoints & scheduling.
C) Temperature setpoints
Permanent setpoint changes
Temperat
set Y/N
This menu permits the adjustment of all permanent temperature setpoints (occupied and unoccupied) as well as the desired
temperature units (°F or °C). Permanent setpoints are written to RAM and EEPROM
Cooling setpoint
Occupied mode
Cooling
set? Y/N
Use ▲▼ keys to set value, Yes key to confirm
Cooling
70.0 °F
Temporary setpoint changes
No next →
Yes down ↓
Use ▲▼
To set value
Temporary setpoints can be modified through the Up arrow key (▲) and the Down arrow keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the thermostat and its setpoint.
The Up (
The Down (
Press the Yes key to accept the new setpoint.
▲) arrow key will increment the setpoint by 0.5 degree (F or C).
▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Local changes to the heating or cooling setpoints made by the user directly using the up or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the
D) Humidity setpoints
Humidity
set Y/N
This menu permits the adjustment of humidification and dehumidification setpoints.
Dehumidification
setpoint
Dehumidi
set? Y/N
Use ▲▼ keys to set value, Yes key to confirm
Dehumidi
70 %
No next →
Yes down ↓
Use ▲▼
To set value
To prevent overlap, a minimum fixed deadband of 5% RH will always prevail between the humidification and dehumidification
setpoints. For example, if the humidification setpoint is 50% RH and the dehumidification setpoint is changed from 70% RH to
45% RH, the humidification setpoint will be modified to 45% RH by the thermostat.
Humidification process
Humidification process will only be allowed when the thermostat is in heating mode (System Mode = Heat or System Mode =
Auto and effective mode at the thermostat is heat). If there is a humidification demand and the fan is OFF, the fan is first turned
ON and the humidifier output is then activated.
Other than having the RH setpoint, the following events can stop the humidification process at any time: RH sensor is out of
range, System Mode is switched to Off or Cool and the System Mode = Auto but the room’s effective mode changes from Heat
to Cool
Heating setpoint
Occupied mode
Heating
set? Y/N
Heating
68.00 °F
No next →
Yes down ↓
Use ▲▼
To set value
Humidification
setpoint
Humidifi
set? Y/N
Humidifi
50 %
No next →
Yes down ↓
Use ▲▼
To set value
Cooling setpoint
Unoccupied mode
Unocc CL
set? Y/N
Unocc CL
80.0 °F
No next →
Yes down ↓
Use ▲▼
To set value
Heating setpoint
Unoccupied mode
Unocc HT
set? Y/N
Unocc HT
60.0 °F
Temperat set ? menu
No next →
Yes down ↓
Use ▲▼
To set value
°F or °C
display setting
°F or °C
set? Y/N
Units
°F
No next →
Yes down ↓
Use ▲▼
To set value
9
Page 10
Dehumidification process
10
If (Dhu LCK) Dehumidification Lockout Functions is set to On (Enabled):
Dehumidification process will only be allowed when the thermostat is in cooling mode (System Mode = Cool or System Mode =
Auto and effective mode at the thermostat is cool). If there is a dehumidification demand and the fan is OFF, the fan is first
turned ON and the dehumidification output is then activated.
Other than having reach the dehumidification setpoint, the following events can stop the dehumidification process at any time:
• RH sensor is out of range
• System Mode is switched to Off, Heat or System Mode = Auto and effective mode at the thermostat is Heat
• The room temp drops below the cooling setpoint minus the deadband value
• The Outside air temp is below the Dhu OALK parameter
If (Dhu LCK) Dehumidification Lockout Functions is set to Off (Disabled):
Other than having reach the dehumidification setpoint, the following events can stop the dehumidification process at any time:
• RH sensor is out of range
• System Mode is switched to Off
• The Outside air temp is below the Dhu OALK parameter
Dehumidification process is allowed when the thermostat operates in all system mode except Off. If there is a dehumidification
demand. If the fan is OFF, the fan is first turned ON and the dehumidification output is then activated.
There is NO active temperature lockout protection in this mode. If the dehumidification process causes the room temperature to
rise or fall, the thermostat will react by either activating the cooling or heating outputs based on it’s current system mode
settings.
E) System mode setting
Sys mode
set Y/N
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to confirm
Sys mode
auto
Sys mode
cooling
Sys mode
heating
Sys mode
off
F) Fan mode setting
Fan mode
set Y/N
Automatic mode
Automatic changeover mode between heating and cooling operation
Cooling mode
Cooling operation mode only
Heating mode
Heating operation mode only
Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection at 50 °F ( 10 °C ) is enabled
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm
Fan mode
On
Fan mode
Auto
Fan mode
Smart
On fan mode
Fan is on continuously, even when system mode is OFF.
Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied periods.
Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on all stand-alone programmable models
or if DI1 or DI2 is set to RemNSB on stand-alone non-programmable models
Page 11
G) Scheduleset (2 events)
Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per parameter (2/4event )
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each day can be tailored to specific
schedules if needed.
• 2 events can be programmed per day.
• Occupied & unoccupied periods can be set for each day.
Monday
set? Y/N
Monday timer
Schedule set
No next →
Yes down ↓
Tuesday timer
Schedule set
Tuesday
set? Y/N
No next →
Yes down ↓
Wednesday timer
Schedule set
Wednesda
set? Y/N
No next →
Yes down ↓
Other days are identical
Selects the day to be programmed or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next →
Yes down ↓
Occupied
Day? Y/N
No next →
Yes down ↓
Occupied
Day? Y/N
No next →
Yes down ↓
Yes = Daily schedules will be accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next →
No down ↓
Copy Y/N
Previous
Yes next →
No down ↓
Yes = Will copy previous day schedule
No = Daily schedules will be accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set value
Occupied
00:00 AM
Use ▲▼
To set value
Occupied
00:00 AM
Use ▲▼
To set value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set value
Unoccup
00:00 AM
Use ▲▼
To set value
Unoccup
00:00 AM
Use ▲▼
To set value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
Typical examples of a 2 event office schedule
Ex. #1 Office building closed all weekend
Event Period #1 - Event #1 Period #1 - Event #2
Occupied Unoccupied
Setpoint
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Cool Heat Cool Heat
72 °F 70 °F 80 °F 62 °F
7.00 AM 6.00 PM Day time only
7.00 AM 6.00 PM Day time only
7.00 AM 6.00 PM Day time only
7.00 AM 6.00 PM Day time only
7.00 AM 6.00 PM Day time only
12.00 PM * 12.00 PM * Unoccupied
12.00 PM * 12.00 PM * Unoccupied
Note: 12:00 PM = Noon
12:00 AM = Midnight
Daily
Occupancy
* Programming consecutive events to the same time will cause the thermostat to choose the last event as the time at which it
will set its schedule. In the above example, the thermostat will control to the unoccupied set point until 7:00 AM Monday.
Ex. #2 Commercial building which is occupied all weekend
Event Period #1 - Event #1 Period #1 - Event #2
Occupied Unoccupied
Setpoint
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Cool Heat Cool Heat
72 °F 70 °F 80 °F 62 °F
8.00 AM 5.00 PM Day time only
8.00 AM 5.00 PM Day time only
8.00 AM 5.00 PM Day time only
8.00 AM 5.00 PM Day time only
8.00 AM 5.00 PM Day time only
12.00 AM ** 11.59 PM ** Occupied
12.00 AM ** 11.59 PM ** Occupied
** To program a day as occupied for 24 hours, set that day Occupied time to 12:00 AM and Unoccupied time to 11:59 PM There will be a 1
minute unoccupied period every night at 11:59 PM with this schedule configuration.
Daily
Occupancy
11
Page 12
H) Scheduleset (4 events)
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each day can be tailored to specific
schedules if needed.
• 4 events can be programmed per day.
• Occupied & Unoccupied periods can be set for each day.
• Programming the 3 rd. & 4 th. events to the same time will cancel the last period.
Monday
set? Y/N
Monday timer
Schedule set
No next →
Yes down ↓
Tuesday
set? Y/N
Tuesday timer
Schedule set
No next →
Yes down ↓
Wednesday timer
Schedule set
Wednesda
set? Y/N
No next →
Yes down ↓
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next →
Yes down ↓
Occupied
Day? Y/N
No next →
Yes down ↓
Occupied
Day? Y/N
No next →
Yes down ↓
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next →
No down ↓
Copy Y/N
Previous
Yes next →
No down ↓
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set value
Occupied
00:00 AM
Use ▲▼
To set value
Occupied
00:00 AM
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set value
Unoccup
00:00 AM
Use ▲▼
To set value
Unoccup
00:00 AM
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to confirm
Occupie2
00:00 AM
Use ▲▼
To set value
Occupie2
00:00 AM
Use ▲▼
To set value
Occupie2
00:00 AM
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to confirm
Unoccup2
00:00 AM
Use ▲▼
To set value
Unoccup2
00:00 AM
Use ▲▼
To set value
Unoccup2
00:00 AM
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to confirm
Ex. #1 Four event retail establishment schedule
Event Period 1 - Event 1 Period 1 - Event 2 Period 2 - Event 3 Period 2 - Event 4
Setpoint Occupied Unoccupied Occupied Unoccupied
Cool Heat Cool Heat Cool Heat Cool Heat
* Programming events to the same time will cancel the last period and leave the thermostat in unoccupied mode
Ex. #2 Residential
Event Period 1 - Event 1 Period 1 - Event 2 Period 2 - Event 3 Period 2 - Event 4
Setpoint Occupied Unoccupied Occupied Unoccupied
Cool Heat Cool Heat Cool Heat Cool Heat
72 °F 70 °F 80 °F 62 °F 72 °F 70 °F 80 °F 62 °F
Monday 6:00 AM 8:00 AM 4:00 PM 10:00 PM
Tuesday 6:00 AM 8:00 AM 4:00 PM 10:00 PM
Wednesday 6:00 AM 8:00 AM 4:00 PM 10:00 PM
Thursday 6:00 AM 8:00 AM 4:00 PM 10:00 PM
Friday 6:00 AM 8:00 AM 4:00 PM 11:30 PM
Saturday 8:00 AM * 8:00 AM * 8:00 AM * 11:59 PM *
Sunday 12:00 AM * 12:00 AM * 12:00 AM * 11:59 PM *
* Programming consecutive events to the same time will cause the thermostat to choose the last event as the time at which it will
set its schedule. In the above example for Saturday, the thermostat will control to the occupied set point from 8:00 AM until
11:59 PM. Since it is desired to be in occupied mode throughout the night, then it is necessary to program the first event on
Sunday at 12:00 AM. The thermostat will force a one minute unoccupied period for a one minute period (between 11:59 PM and
12:00 AM on Saturday).
Other days are identical
Selects the day to be programmed or
modified
Yes = Daily schedules will be accessed
No = Unoccupied mode all day
Yes = Will copy previous day schedule
No = Daily schedules will be accessed
Sets Event # 1 Occupied time
Will activate occupied setpoints
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Sets Event # 3 Occupied time
Will activate occupied setpoints
Sets Event # 4 Unoccupied time
Will activate unoccupied setpoints
Daily
Occupancy
Day time only
Day time only
Day time only
Day/evening time only
Day/evening time only
Unoccupied
Unoccupied
Daily
Occupancy
Day/evening time only
Day/evening time only
Day/evening time only
Day/evening time only
Day/evening time only
Day time only
Occupied all day
12
Page 13
I) Clock/Day Settings
Clock
set Y/N
This section of the menu permits the user to set the time and day.
Time setting Day setting Time format setting
Time
set? Y/N
Time
0:00
No next →
Yes down ↓
Use ▲▼
To set value
Day
set? Y/N
Day
Monday
No next →
Yes down ↓
Use ▲▼
To set value
12/24hrs
set? Y/N
12/24hrs
12 hrs
J) Schedule hold
Schedule
hold Y/N
This menu
• This menu will only appear on stand-alone thermostat, e.i. without a BACnet / Echelon module.
• This section of the menu permits the user to set a permanent schedule hold, which bypasses the internal
thermostat scheduling.
• The permanent schedule hold function is typically used for non-scheduled events that extend for various periods
of time.
• Enabling a permanent occupied or permanent unoccupied schedule hold will cancel any active override.
• The use of temporary setpoints during permanent hold is permitted. The duration of the temporary setpoint is as
set per the TOccTime parameter. Ex. 3 hours
Use ▲▼ to set value, Yes key to confirm
Schedule
resume
Resume regular scheduling cancels the permanent hold and re-enables the regular
programming as set per internal scheduling or as per remote NSB via one of the DI’s
configured as remote NSB.
This action can also by accomplished by using the Resume menu.
Any temporary setpoint that are active will be left active for the duration of the period as set
Schedule
occ hold
per the TOccTime parameter.
Hold permanent occupied forces the thermostat into a permanent occupied mode using the
occupied setpoints. All timed scheduling functions are by-passed.
The PERMANENT OCCUPIED status will appear in the automatic status scroll. To resume
to regular scheduling, user must scroll to the Schedule Hold menu and select the Schedule
resume option..
Schedule
uno hold
Hold permanent unoccupied forces the thermostat into a permanent unoccupied mode
using the unoccupied setpoints. All timed scheduling functions are by-passed.
The PERMANENT UNOCCUPIED status will appear in the automatic status scroll. To
resume to regular scheduling, user must scroll to the Schedule Hold menu and select the
Schedule resume option..
No = exit
Yes down ↓
Use ▲▼
To set value
13
Page 14
Installer configuration parameter menu
Configuration can be done through the network or locally at the thermostat.
• To enter configuration, press and hold the middle button (Menu) for 8 seconds
• Press the same middle button repetitively to scroll between all the available parameters
• Use the up and down key to change the parameter to the desired value.
• To acknowledge and save the new value, press the middle button again.
• The next listed parameter is now displayed
Configuration
parameters
%RH disp
DI
Significance
Default value
Local RH Display
Default value = Off
Digital input no.1 configuration
14
Adjustments
Enables the display of humidity below the room
temperature on the display
On = Display %RH
Off = No display of %RH
None, No function will be associated with the input
Open contact input = function not
energized
Closed contact input = function
energized
Default value = None
Rem NSB, remote NSB timer clock input. Will disable
the internal scheduling of the thermostat. The
scheduling will now be set as per the digital input. The
time is still displayed as information, but the menu part
related to scheduling is disabled and no longer
accessible.
Open contact = occupied setpoints
Closed contacts = unoccupied setpoints
RemOVR Temporary override remote contact.
Disables all override menu function of the thermostat.
The override function is now controlled by a manual
remote momentarily closed contact. When configured
in this mode, the input operates in a toggle mode. With
this function enabled it is now possible to toggle
between unoccupied & occupied setpoints for the
amount of time set by parameter (TOccTime)
temporary occupancy time. When Override is enabled,
an Override status message will be displayed
Filter, a back-lit flashing Filter alarm will be displayed
on the thermostat LCD screen when the input is
energized
Service, a back-lit flashing Service alarm will be
displayed on the thermostat LCD screen when the
input is energized
Lockout
Pwr del
Level
0
1
2
Keypad lockout levels
Default value = 0 No lock
Resume/
Override
scheduling
Resume
sched Y/N
Yes access Yes access Yes access Yes access Yes access Yes access Yes access Yes access Yes access
Yes access No access Yes access No Access No access No access No access Yes access No access
No access No access No access No Access No access No access No access Yes access No access
Permanent
Occupied and
Unoccupied
Setpoints
Temperat
set Y/N
Temporary
setpoints
using arrows
Up key (▲)
Down key (▼)
Humidity
Setpoints
Humidity
set Y/N
Power-up delay
Default value = 10 seconds
0 = No lock
1 = Low level
2 = High level
System mode
setting
Sys mode
set Y/N
Fan mode
setting
Fan mode
set Y/N
Schedules
setting
Schedule
set Y/N
Clock setting
Clock
set Y/N
Permanent
hold
Schedule
hold Y/N
On initial power up of the thermostat (each time 24 Vac
power supply is removed & re-applied) there is a delay
before any operation is authorized (fan, cooling or
heating). This can be used to sequence start up
multiple units / thermostat in one location.
10 to 120 seconds
Page 15
Frost pr
Frost protection enabled
Default value = Off
On heat pump models the system
mode will be forced to EMERGENCY
mode if frost protection is activated
Heat max Maximum heating setpoint limit
Default value = 90 °F ( 32 °C )
Cool min Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )
Anticycle Minimum on/off operation time for
stages
Default value = 2 minutes
Anti-short cycling can be set to 0
minutes for equipment that posses
their own anti cycling timer. Do not use
that value unless the equipment is
equipped with such internal timer.
Failure to do so can damage the
equipment.
Heat cph Heating stages cycles per hour
Default value = 4 C.P.H.
Cool cph Cooling stages cycles per hour
Default value = 4 C.P.H.
Deadband Minimum deadband
Default value = 2.0 °F ( 1.1 °C )
Fan cont Fan control
Default value = On
Off: no room frost protection
On: roomfrost protection enabled in all system
mode at: 42 °F ( 5.6 °C )
Frost protection is enabled even in system Off
mode
Off or On
Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Minimum On/Off operation time of cooling &
heating stages.
IMPORTANT, anti-short cycling can be set to 0
minutes for equipment that posses their own anti
cycling timer. Do not
use this value unless the
equipment is equipped with such internal timer.
Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes
Will set the maximum number of heating stage
cycles per hour under normal control operation. It
represents the maximum number of cycles that
the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher
accuracy of control at the expense of wearing
mechanical components faster.
3, 4, 5, 6,7 & 8 C.P.H.
Will set the maximum number of cooling stage
cycles per hour under normal control operation. It
represents the maximum number of cycles that
the equipment will turned on and off in one hour.
Note that a higher C.P.H will represent a higher
accuracy of control at the expense of wearing
mechanical components faster.
3 or 4 C.P.H.
Minimum deadband value between the heating
and cooling setpoints. If modified, it will be applied
only when any of the setpoints are modified.
2, 3 or 4 °F ( 1.0 to 2.0 °C )
Fan control in heating mode.
When selecting On; the thermostat in all cases
will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan ( terminal G ), when
heating stages ( terminals W1 & W2 ) are
solicited, will not be energized. The fan in this
case will be controlled by the equipment fan limit
control.
Valid only for Auto fan mode. On fan mode will
leave the fan always on.
On or Off
15
Page 16
Fan del Fan delay
Default value = Off
Com Addr
Thermostat networking address
Default value = 4 Range is: 0 to 254
• For BACnet MS-TP models valid
range to use is from 1 to 127
• For wireless models valid range is 0
to 254 with a maximum of 30
thermostat per VGG
TOccTime Temporary occupancy time
Default value = 3 hours
Cal RS Room air temperature sensor calibration
Default value = 0.0 °F or °C
Cal OS Outside air temperature sensor
calibration
Default value = 0.0 °F or °C
H stage Number of heating stages. Applicable to
2 stage models only
Default value = 2 stages
C stage Number of cooling stages
2 stages model only
Default value = 2 stages
H lock Outside air temperature heating lockout
Default value = 120 °F ( 49 °C )
C lock Outside air temperature mechanical
cooling lockout.
Default value = -40 °F ( -40 °C )
2/4event Number of events configuration
Default value = 2 event
For scheduling model only VT7657B1000B
Fan delay extends fan operation by 60 seconds
after the call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will
leave the fan always on.
Off or On
Conditional parameter to BACnet MS-TP models
(VT76x7B1000B)
Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a BACnet or
wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with
an Echelon adapter, this parameter will not be used
or displayed
Temporary occupancy time with occupied mode
setpoints when override function is enabled
When the thermostat is in unoccupied mode,
function is enabled with either the menu or DI1 or
DI2 configured as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours
Offset that can be added/subtracted to actual
displayed room temperature
± 5.0 °F ( ± 2.5 °C )
Offset that can be added/subtracted to actual
displayed outside air temperature
± 5.0 °F ( ± 2.5 °C )
Will revert the operation of 2 stages thermostat to
single stage operation only when the second
heating step is not needed.
1 or 2 stages
Will revert the operation of 2 stage thermostat to
single stage operation only when the second
cooling step is not needed.
1 or 2 stages
Disables heating stage operation based on outdoor
air temperature.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -15 °F up to 120 °F ( -26 °C up to 49 °C )
Disables cooling stage operation based on outdoor
air temperature.
On economizer model, free cooling will not be
disabled by this function.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
2 events, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
16
Page 17
Aux cont
Auxiliary contact configuration
Default value = N.O. normally open
Prog rec Progressive recovery enabled
Default value = Off
Progressive recovery is automatically
disabled if DI is configured as Remote
NSB
For scheduling model only VT7657B1000B
RH LT
Reset RH lower outside temperature
setpoint
Default value = -20°F (-29°C)
RH HT Reset RH higher outside temperature
setpoint
Default value = 32°F (0°C)
HL Sp RH High limit setpoint
Default value = 85% RH
Dhu OALK Dehumidification outside air
temperature lockout
Default value = 32°F (0°C)
This contact can be used to energize peripheral
devices such as: lighting equipment, exhaust fans,
economizers, etc.
This contact will operate in parallel with the internal
occupied/unoccupied schedule of the thermostat or
the remote NSB contact if DI is used.
When the system is in OFF mode, the contact will
remain in its unoccupied status independently of the
occupied / unoccupied schedule.
Configured
Contact
occupied
status
Contact unoccupied
status
N.O. Closed Opened
N.C. opened Closed
Off, = no progressive recovery
The programmed occupied schedule time is the
time at which the system will restart.
On, = progressive recovery active.
The programmed occupied schedule time is the
time at which the desired occupied temperature will
be attained. The thermostat will automatically
optimize the equipment start time.
In any case, the latest a system will restart is 10
minutes prior to the occupied period time.
Minimum outside air temperature for RH setpoint
reset.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH HT & RE Sp.From –40°F up to 15°F (-40°C to –9.5°C)
Maximum outdoor air temperature for RH setpoint
reset.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH LT & RE SpFrom 20°F up to 55°F (-6.5°C to 13°C)
High humidity limit in the supply.
Only valid if a 0-10 Vdc sensor is connected at the
thermostat – otherwise this feature is disabled
automatically.
From 50% RH up to 90% RH
Outside air temperature under which the
dehumidification sequence is disabled.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat.
From –40°F up to 122°F (-40°C to 50°C)
17
Page 18
18
Dhu LCK Dehumidification Lockout Functions
Default value = On
Enables or disables the lockout functions for the
dehumidification control process of the output.
On: will restrict the dehumidification process based
on the following:
- System mode = Needs to be Cool or Auto (
currently operating in cooling only )
- Low ambient room temperature protection
enabled
Off: will not restrict the dehumidification process:
- System mode = Needs to be Cool, Heat or
Auto
- There is no ambient room temperature
protection enabled
DehuHyst Dehumidification hysterisys
Default value = 5% RH
Dehumidification control hysterisys.
Used only if dehumidification sequence is enabled.
From 2% RH up to 20% RH
RE Sp Reset humidity setpoint
Default value = 20% RH
The RH setpoint will be reset from the user setpoint
to this value when the RH LT outside air
temperature value is reached.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH LT & RE HT.
From 10% RH up to 90% RH
RH cal Humidity sensor calibration
Default value = 0 %RH
Offset that can be added/subtracted to actual
displayed humidity by ± 15.0 %RH.
This calibration applies to the internal humidity
sensor if no remote humidity sensor is connected.
This calibration applies to the remote humidity
sensor when one is connected.
From –15% RH up to 15% RH
Display
HL
Display the high limit sensor value Used as diagnostic / service help to troubleshoot
and diagnose sensor / humidifier operation
Note:
When the outside air sensor is not connected or is shorted, the thermostat bypasses:
• The heating lockout
• The cooling lockout
• The dehumidification lockout
• The humidity setpoint reset
Page 19
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
Wireless Model only
Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a wireless
network adapter is present. If the thermostat is
installed as a stand-alone unit or with a BACnet or
Echelon adapter, this parameter will not be used or
displayed
This parameter (Personal Area Network Identification)
is used to link specific thermostats to a single specific
Viconics wireless gateway ( VWG ) For every
thermostat reporting to a gateway ( maximum of 30
thermostats per gateway ), be sure you set the SAME
PAN ID value both at the gateway and the
thermostat(s).
The default value of 0 is NOT a valid PAN ID. The valid
range of available PAN ID is from 1 to 500
19
Channel
Get From
Channel selection
Default value = 10
Range is: 10 to 26
Thermostat Get From another
device configuration utility
Default value = 0
Range is: 0 to 254
Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a wireless
network adapter is present. If the thermostat is
installed as a stand-alone unit or with a BACnet or
Echelon adapter, this parameter will not be used or
displayed
This parameter (Channel) is used to link specific
thermostats to specific Viconics wireless gateway(s) (
VWG ) For every thermostat reporting to a gateway (
maximum of 30 thermostats per gateway ), be sure
you set the SAME channel value both at the gateway
and the thermostat(s).
Viconics recommends using only the 2 last
channels ( 25-2575MHz and 26-2580MHz )
The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26
Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter / function is not currently supported by the
wireless thermostats.
Page 20
Humidity setpoint reset by outside air temperature
45%
RH Set = 45%
40%
35%
RH HT = 32°F
30%
%RH Setpoint
25%
20%
RH LT = -20°F
-40°F
RE Sp = 20%
-20°F 0°F 20°F 40°F
Outside Air Temp.
Fig.11 – Humidity setpoint reset by outside air
temperature
High limit humidity sensor
100 %
Control
Output
Level
Fig.12 – High humidity limit vs Control output level curve
50 %
0 %
Maximum Supply Humidity
85 %
20
If an outdoor air sensor is connected at the thermostat
or a value is received from the network, it can be used
to reset the humidity setpoint during the cold season to
minimize condensation on windows and building
structures.
When the outdoor temperature falls below the selected
high temperature, parameter RH HT (32°F in the
example Figure 8), the humidity setpoint will start to
decrease. The lowest humidity setpoint will be reached
at selected low temperature, parameter RH LT (-20°F).
The setpoint decrease from original setpoint to the
lowest setpoint determined by the parameter RE Sp. In
the example, Figure 8, RE Sp was set to 20%, therefore
the humidity setpoint dropped from 45% to 20%.
If you don’t want to use this feature, set the RE Sp
parameter to 90% RH.
The VT76x7 series includes a high limit sequence. This
allows the use of a remote 0 to 10 Vdc humidity sensor to
limit the humidity in the supply air. If no sensor is detected at
the HL connector, this sequence is disabled at the
thermostat.
Note: this high limit function is not a safety device. For
critical situations, provide installation with normal protections
required to ensure a safe operation.
Page 21
Troubleshooting guide
Symptom Possible Cause Corrective Action
No display on the
thermostat
Absent or incorrect supply
voltage
1. Check power supply voltage between C & RC to be
from 19-30 Vac
2. Check for tripped fuse or circuit breaker
Overloaded power
transformer
Verify that the transformer used is powerful enough
(enough VA’s) to supply all controlled devices
including the thermostat
21
Keyboard menu does
not access all functions
Temperature setpoints
revert to original value
after a certain time
period
Thermostat will not call
for heating
Keyboard locked Change configuration parameter LOCKOUT to value
“0” to access all levels of the menu
Temporary setpoint option
selected
1. The thermostat needs to be in Permanent setpoint
mode for the new setpoint to be kept and memory
and used all the time
2. Go to the Set temperature menu.
3. The last prompt is setpoint type. Set it to
Permanent setpoint
Wrong mode selected Select heating mode
Thermostat in Unoccupied
mode
Select Occupied Hold in Schedule hold or Override to
force the thermostat Occupied heating setpoint
Anticycle delay active Wait, the anticycling period will end and the
equipment will start
Heating setpoint is satisfied Raise the Heating setpoint
Heating lockout attained 1. Mode is locked out based on outside air
temperature
2. Change configuration parameter H Lock to value
120 °F ( 49 °C ) to by-pass lockout
Wiring error 1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The
heating should come ON. If it does not, verify
wiring and check if a jumper is required between
RC & RH
Page 22
Symptom Possible Cause Corrective Action
Thermostat will not call
for cooling
Wrong mode selected Select cooling mode
Thermostat in Unoccupied
mode
Select Occupied Hold in Schedule hold or Override to
force the thermostat Occupied cooling setpoint
Anticycle delay active Wait, the anticycling period will end and the
equipment will start
Cooling setpoint is satisfied Lower the cooling setpoint
Cooling lockout attained 1. Mode is locked out based on outside air
temperature
2. Change configuration parameter C Lock to value 40 °F ( -40 °C ) to by-pass lockout
Wiring error 1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & Y1. The
cooling should come ON. If it does not, verify wiring
22
turn on the fan
Digital display shows
missing digits or erratic
segments
Thermostat will not call
for humidification
Thermostat will not call
for dehumidification
Wrong mode selected The thermostat will not
Wiring error
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & G. The fan
should come ON. If it does not, verify wiring
Defective display Replace thermostat
RH sensor is out of range Verify the remote RH sensor or the internal RH
sensor
System Mode in Cool or Off Change the system mode parameter to heat
System Mode in Auto but a
cooling demand at the
Wait: when a heating demand will occur at the
thermostat, humidification will resume
thermostat
High limit sensor is controlling
the humidifier output by
Wait: when the supply humidity will drop below the
high limit setpoint, humidification will resume.
forcing it to 0%
RH sensor is out of range Verify the remote RH sensor or the internal RH
sensor
System Mode in Heat or Off Change the system mode parameter to cool
System Mode in Auto but a
heating demand at the
Wait: when a cooling demand will occur at the
thermostat, dehumidification will resume
thermostat
Outside air temperature is
below the Dhu OALK
Change the Dhu OALK parameter to a value that will
enable the dehumidification, if desired.
parameter
Page 23
Specifications
Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA ( RC & C ) Class 2
RC to RH jumper 2.0 Amps 48 VA maximum
Operating conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions: -30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Temperature sensor: Local 10 K NTC thermistor
Resolution: Temperature: ± 0.1 °C (± 0.2 °F)
Humidity: ± 0.1%
Control accuracy: Temp: ± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typ. calibrated
Humidity: ± 5% RH from 20 to 0% RH at 50 to 90°F (10 to 32°C)
Humidification setpoint range: 10% RH to 90% RH
Dehumidification setpoint range: 15% RH to 95% RH
Occupied and unoccupied setpoint range cooling: 12.0 to 37.5 °C ( 54 to 100 °F )
Occupied and unoccupied setpoint range heating: 4.5 °C to 32 °C ( 40 °F to 90 °F )
Room and outdoor air temperature range -40 °C to 50 °C ( -40 °F to 122 °F )
Proportional band for room temperature control: Both outputs: 1.1°C ( 2.0°F )
Digital input: Relay dry contact only across C terminal to DI1
Analog high limit and remote humidity inputs
0 to 10 Vdc into 10KΩ input load
Contact output rating: Each relay output: ( Y1, Y2, G, W1, W2 & AU )
30 Vac, 1 Amp. maximum
30 Vac, 3 Amp. in-rush
Humidification analog output rating:
0 to 10 Vdc into 2KΩ resistance min.
Humidification analog output accuracy: ± 3% typical
Wire gauge 18 gauge maximum, 22 gauge recommended
Dimensions: 4.94” x 3.38” x 1.13”
Approximate shipping weight: 0.75 lb ( 0.34 kg )
Agency Approvals all models:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with
CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
Agency Approvals Stand-Alone, BACnet & LON models
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
CE: EMC Directive 89/336/EEC (Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand)
Supplier Code Number N10696
Agency Approvals Wireless models
FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Drawing & dimensions
Fig.13 – Thermostat dimensions
Important notice
operating controls only and
are not safety devices. These
instruments have undergone
rigorous tests and verifications
prior to shipment to ensure
proper and reliable operation
in the field. Whenever a
control failure could lead to
personal injury and/or loss of
property, it becomes the
responsibility of the user /
installer / electrical system
designer to incorporate safety
devices ( such as relays,
flow switch, thermal
protections, etc…) and/or
alarm system to protect the
entire system against such
catastrophic failures.
Tampering of the devices or
miss application of the device
will void warranty.
23
All VT7600
series
controls are
for use as
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.