Economizer Mode and Fresh Air Measurement Station30
Economizer Mode and CO2 Level Control31
Economizer Mode, CO2 Level Control and Fresh Air Measurement Station32
Specications33
Drawing & Dimensions34
1 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 2
InstallatIon
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
• Open unit by pulling on the bottom
side of Terminal Equipment Controller
(Fig. 1).
• Remove wiring terminals from sticker.
• Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an air
discharge grill.
4. Should not be affected by direct sun
radiation.
5. Nothing should restrict vertical air
circulation to the Terminal Equipment
Controller.
Installation
1. Swing open the Terminal Equipment
Controller PCB to the left by pressing
the PCB locking tabs (Fig. 2).
2. Pull out cables 6” out from the wall.
3. Wall surface must be at and clean.
4. Insert cable in the central hole of the
base.
5. Align the base and mark the location
of the two mounting holes on the
wall. Install proper side of base up.
6. Install anchors in the wall.
7. Insert screws in mounting holes on
each side of the base (Fig. 2).
8. Gently swing back the circuit board
on the base and push on it until the
tabs lock it.
9. Strip each wire 1/4 inch from end.
Fig. 1
Location of PCB retaining tabs
Fig. 2
Re-install terminal blocks
Fig. 3
2 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 3
10. Insert each wire according to wiring diagram.
11. Gently push excess wiring back into hole (Fig. 3).
12. Re-Install wiring terminals in their correct locations (Fig. 3).
13. Re-install the cover (top side rst) and gently push extra wire length back into the
hole in the wall.
14. Install security screw.
• If replacing an existing Terminal Equipment Controller, label the wires
before removal of the Terminal Equipment Controller.
• Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
• A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
• All VT7000 series Terminal Equipment Controllers are designed for
use as operating controls only and are not safety devices. These
instruments have undergone rigorous tests and verication prior to
shipping to ensure proper and reliable operation in the eld. Whenever
a control failure could lead to personal injury and/or loss of property,
it becomes the responsibility of the user / installer / electrical system
designer to incorporate safety devices (such as relays, ow switch,
thermal protections, etc…) and/or an alarm system to protect the entire
system against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.
3 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 4
Theoryof operaTion
The VT76X6E series uses a Viconics proprietary adaptive logic algorithm to control the
space temperature. This algorithm controls the heating or air conditioning system to
minimize overshoot while still providing comfort. It provides exceptional accuracy due to
its unique PI time proportioning control algorithm, which virtually eliminates temperature
offset associated with traditional, differential-based On-Off thermostats.
Fig.2 - On-Off mechanical control vs PI electronic control.
Features overview
• 7 day schedule models, 2 or 4 events.
• C02 control logic based on fresh air volume or fresh air damper position.
• Fresh air damper output for building CO2 level control.
• Gas, oil or electric system compatibility.
• Remote outdoor sensing capability for added exibility.
- System mode heating and cooling lockout.
• Remote discharge air sensor input for monitoring and control purpose.
- System efciency feedback.
- Discharge high limit heating lockout.
- Discharge low limit cooling lockout.
• Remote return air sensor input that replaces internal on board sensor.
- System efciency feedback.
• Password protected conguration menu and lockable keypads for security.
• Automatic smart fan operation saves energy during unoccupied periods.
• Non volatile EEPROM memory prevents loss of parameters during power shortage.
• Congurable SPST output relay on scheduling models for lighting, exhaust fan or
fresh air control.
• 6 hour typical reserve time for clock in case of power loss.
Easy conguration and self-binding operation
• Easy conguration without using any special software or additional tools.
• Can be used as stand-alone or with BACnet™ MS-TP supervision controller for
monitoring purposed.
• Truly scalable in terms of supported number of zones and RTU units.
4 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 5
Model CharT
Product Selector
Please refer to the following matrix when ordering
Example:
VT765 6 E 5500W
Wireless communication
Factory installed PIR cover
IAQ Control
With Economizer
Local Scheduling
Please note, not all combinations and variants are available. Refer to the Viconics price list for a complete selection listing of all available models.
Network ready
• All Viconics VT7600 series Terminal Equipment Controllers are designed for standalone (Network Ready) operation.
• They can be fully integrated into your choice of automation systems using the
available communication adapter options.
• If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
eld retrotted with the following communication adapters:
1 – Cool 2Y2Output for cooling / compressor stage number 2.
2 – Cool 1Y1Output for cooling / compressor stage number 1.
3 - FanGOutput for the fan.
4 - 24 V ~ HotRC
5 - 0 V ~ ComC
6 – Heat Switch
Leg
7 – Heat 1W1Output for heating stage number 1.
8 – Heat 2W2Output for heating stage number 2.
9 – Economizer
Output
10 – Analog
Heat Output
11 – RSRS
12 – MSMSDischarge air temperature sensor input
13 – AI1AI10-10 VDC analog input for CO2 transmitter
14 – ScomScomReference input for AI, RS, OS and DS
15 – OSOSOutside air temperature sensor input
16 –AI2AI20-10 VDC analog input for airow transmitter
Terminal
Identication
Power supply of controller, hot side (Delivered from the
RTU).
Power supply of controller, common side. Also used
as reference for the analog BPD output when used
(Delivered from the RTU).
24 VAC switched leg for the heating stages.
• If heating stages are part or RTU, install a jumper
RH
EC0-10 VDC analog fresh air damper / economizer output.
AO0-10 VDC analog heating output.
across RC & RH.
• If heating stages are part of separate equipment with a different power supply, feed external
switched power leg through RH without installing a
jumper across RC & RH.
Return air temperature sensor input. Used when communication is lost. If remote sensor fails, thermostat will
use its on-board sensor to control.
Description
Screw terminal arrangement and wiring
Controller terminals:
6 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 7
typIcal applIcatIons
Main outputs wiring
Wiring notes:
Note 1: If the same power source is used for the heating stages, install
jumper across RC & RH. Maximum current is 2.0 amps.
Note 2: Economizer and all analog outputs and inputs use a half bridge
rectier. Reference of the control signal is the common of the
power supply of the Terminal Equipment Controller. (Terminal C).
Note 3: Electromechanical contacts are to be used with the digital inputs.
Electronic triacs cannot be used as mean of switching for the
input. The switched leg to the input for the input to activate is
terminal C (common)
Note 4: The transformer of the unit provides power to the Terminal Equip-
ment Controller and the additional loads that will be wired to the
Terminal Equipment Controller.
7 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 8
Remote sensor accessories
Model no.Description
S2020E1000
S2060A1000
S2000D1000Duct mounted temperature sensor
Remote mount temperature sensors use 10K type 2 NTC thermistors.
Temperature vs. resistance chart for 10 Kohm NTC thermistor
S2000D1000; remote duct mounted temperature sensor c/w junction box.
This sensor can be used for:
• Remote return air temperature
sensing with the sensor mounted on
the return air duct.
• Outside air temperature sensing with
the sensor installed in the fresh air
plenum.
• Supply air temperature sensing.
Fig.10 – Remote Duct Mounted Temperature Sensor
S2060A1000; remote averaging duct mounted temperature sensor c/w junction box.
This sensor can be used for:
• Remote averaging return air temperature sensing with the sensor mounted on
the return air duct.
• Outside air temperature averaging sensing with the sensor installed in the fresh
air plenum.
• Supply air temperature averaging sensor for economizer models with the sensor
in the mixing plenum.
8 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 9
S2020E1000; outdoor air temperature sensor
This sensor can be used for:
• Outside air temperature sensing with the sensor installed directly exposed to the
elements.
• Sensor uses a water resistant NEMA 4 ABS enclosure for outdoor applications.
WIRING S2000D1000, S2060A1000 and S2020E1000
Remote wiring 1 sensorRemote wiring 4 sensors
confIguratIonand status dIsplay InstructIons
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There
is a low backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the current status of the system.
Each item is scrolled sequentially with the back lighting in low level mode. Pressing
any key will cause the back lighting to come on to high level.
Manual scrolling of each menu item is achieved by pressing the Yes (scroll) key
repetitively. The last item viewed will be shown on the display for 30 seconds before
returning to automatic scrolling. Temperature is automatically updated when scrolling
is held.
Sequence of auto-scroll status display:
CLOCK
STATUS
Monday
12:00 AM
9 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
SYSTEM
MODE
Sys mode
auto
Sys mode
off
Sys mode
heat
Sys mode
cool
SCHEDULE
STATUS
Occupied
Occupied HoldSetClock
UnoccupDAS alarm
OUTDOOR
TEMPERATURE
Outdoor
x.x °C or °F
ALARMS
Frost ON
FA alarm
High CO
2
Page 10
Outdoor air temperature
• Outdoor air temperature display is only enabled when outdoor air temperature
sensor is connected.
• A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.
• A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts
and economizer function are automatically disabled.
Alarms
• If alarms are detected, they will automatically be displayed at the end of the
status display scroll.
• During an alarm message display, the back lit screen will light up at the same
time as the message and shut off during the rest of the status display.
• Two alarms maximum can appear at any given time.
• The priority for the alarms is as follows:
Sequence of manual-scroll status display:
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The last item viewed will be shown on the display for 30 seconds before
returning to automatic scrolling. Temperature is automatically updated when scrolling
is held.
Clock StatusSystem
Mode
Monday
12:00 AM
Sys Mode
Off
Sys Mode
Schedule
Status
Outdoor
Temperature
OccupiedOutdoor
xx.x °C or °F
UnoccupiedSetClock
Auto
Sys Mode
OverrideDAS Alarm
Cool
Sys Mode
Heat
Frost ON
SetClock
DAS Alarm
Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6 °C (42 °F).
Indicates that the clock needs to be reset. There has been a power
failure which has lasted longer than 6 hours.
Indicates that the discharge air temperature is either too low or too
high.
FA AlarmIndicates that the Fresh Air Level is either too low or too high.
High CO2
10 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Indicates that the CO2 Level value is higher than the Max CO2
parameter value.
Alarms
(if detected)
Frost ON
FA Alarm
High CO2
Page 11
user inTerfaCe
When any of the fan is ON, the FAN LED will illuminate
When heating & reheat is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate
User conguring instructions menu
The VT76X6E series of controllers feature an intuitive,
menu-driven, back-lit LCD display that walks users
and installers through the conguring steps, making
the conguring process extremely simple. This menu
is typically accessed by the user to set the parameters
such as the clock time set, the schedule time events
and the system mode.
It is possible to bring up the user menu at any time
by depressing the MENU key. The status display
automatically resumes after exiting the user-conguring menu.
If the user pauses at any given time during conguring, Auto Help text is displayed to
help and guide the user through the usage and conguring of the controller.
Press yes key to change cooling temperature setpoint
Ex.:
Use the up or down arrow to adjust cooling setpoint
Local keypad interface
Each of the sections in the menu is accessed and congured using 5 keys on the
Terminal Equipment Controller cover.
The priority for the alarms is as follows:
The YES key is used to conrm a selection, to move onto the next menu
item and to manually scroll through the displayed information.
The NO key is used when you do not desire a parameter change, and to
advance to the next menu item. Can also be used to toggle between heating and cooling setpoints.
The MENU key is used to access the Main User Menu or exit the menu.
The down arrow key is used to decrease temperature setpoint and to adjust
the desired values when conguring the Terminal Equipment Controller.
The up arrow key is used to increase temperature setpoint and to adjust the
desired values when conguring the Terminal Equipment Controller.
11 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 12
When left unattended for 45 seconds, the display will resume automatic status display
scrolling.
To turn on the back light, press any key on the front panel. The back lit display will turn
off when the Terminal Equipment Controller is left unattended for 45 seconds
Sequence of user menu:
OVERRIDE
RESUME
SYSTEM MODE
SETTING
SCHEDULES
SETTING
CLOCK
SETTING
Override schd
Y/N
Appears only
in unoccupied
mode
Cancel ovrd
Y/N
Appears only
in override
mode
Sys mode set
Y/N
Schedule set
Y/N
Clock set
Y/N
A) Override an unoccupied period
Override
schd Y/N
This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12
hours).
B) Resume regular scheduling
Cancel
ovrd Y/N
This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in Unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to
resume the regular setpoints & scheduling.
C) Temperature setpoints
Permanent setpoint changes
Temperat
set Y/N
This menu permits the adjustment of all permanent temperature setpoints (occupied
and unoccupied) as well as the desired temperature units (°F or °C). Permanent
setpoints are written to RAM and EEPROM.
12 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 13
Cooling
setpoint
Occupied
mode
Heating
setpoint
Occupied
mode
Cooling
setpoint
Unoccupied
mode
Heating
setpoint
Unoccupied
mode
°F or °C
display
setting
Cooling
set? Y/N
Cooling
70.0 °F
No next →
Yes down
↓
Use ▲▼
To set
value
Heating
set? Y/N
Heating
68.00 °F
No next →
Yes down
Use ▲▼ keys to set value, Yes key to conrm
Use ▲▼
↓
To set
value
Unocc CL
set? Y/N
Unocc
CL
80.0 °F
No next →
Yes down
↓
Use ▲▼
To set
value
Unocc HT
set? Y/N
Unocc
HT
60.0 °F
No next →
Yes down
↓
Use ▲▼
To set
value
°F or °C
set? Y/N
Units
°F
No next →
Yes down
↓
Use ▲▼
To set
value
Temporary setpoint changes
Temporary setpoints can be modied through the Up arrow key (▲) and the Down
arrow keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the Terminal
Equipment Controller and its setpoint.
The Up (▲) arrow key will increment the setpoint by 0.5 degree (F or C).
The Down (▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Press the Yes key to accept the new setpoint.
Local changes to the heating or cooling setpoints made by the user directly using the
up or down arrow are temporary.
They will remain effective for the duration specied by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu
D) System mode setting
Sys mode
set Y/N
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to conrm
Sys mode
auto
Sys mode
cooling
Sys mode
heating
Sys mode
emergency
Sys mode
off
Automatic mode
Automatic changeover mode between heating and cooling operation
Cooling mode
Cooling operation mode only
Heating mode
Heating operation mode only
Emergency heat mode ( heat pump models only ) Forced auxiliary
heat operation mode only
Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost
protection at 50 °F ( 10 °C ) is enabled
13 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 14
E) Fan mode setting
Fan mode
set Y/N
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to conrm.
Fan mode
On
Fan mode
Auto
On fan mode
Fan is on continuously, even when system mode is OFF.
Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied periods.
Fan mode
Smart
Smart fan mode
During occupied periods, fan is on continuously. In unoccupied
mode, fan cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on all stand-alone (Network Ready) scheduling models or if DI1
or DI2 is set to RemNSB on stand-alone non-scheduling models.
F) Schedule set (2 events)
Scheduling can have 2 or 4 events per day. This is set in the conguration menu as
per parameter (2/4 event)
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specic schedules if needed.
• 2 events can be scheduled per day.
• Occupied and unoccupied periods can be set for each day.
Monday timer
Schedule set
Monday
set? Y/N
Occupied
Day? Y/N
Occupied
00:00 AM
Unoccup
00:00 AM
14 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
No next →
Yes down ↓
No next →
Yes down ↓
Use ▲▼
To set value
Use ▲▼
To set value
Tuesday timer
Wednesday timer
Schedule set
Tuesday
set? Y/N
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Unoccup
00:00 AM
No next →
Yes down ↓
No next →
Yes down ↓
Yes next →
No down ↓
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Wednesda
set? Y/N
Occupied
Day? Y/N
Copy Y/N
Previous
Occupied
00:00 AM
Unoccup
00:00 AM
Schedule set
No next →
Yes down ↓
No next →
Yes down ↓
Yes next →
No down ↓
Use ▲▼
To set value
Use ▲▼
To set value
Other days are
identical
Selects the day to be pro-
grammed
or modied
Yes = Daily schedules will be
accessed
No = Unoccupied mode
all day
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Sets Event # 1 Occupied time
Will activate occupied
setpoints
Sets Event # 2 Unoccupied
time
Will activate unoccupied
setpoints
Page 15
Typical examples of a 2 event ofce schedule
Ex. #1 Ofce building closed all weekend
EventPeriod #1 - Event #1Period #1 - Event #2
OccupiedUnoccupied
Setpoint
Monday7.00 AM6.00 PMDay time only
Tuesday7.00 AM6.00 PMDay time only
Wednesday7.00 AM6.00 PMDay time only
Thursday7.00 AM6.00 PMDay time only
Friday7.00 AM6.00 PMDay time only
Saturday12.00 PM *12.00 PM *Unoccupied
Sunday12.00 PM *12.00 PM *Unoccupied
Cool
72 °F
Heat
70 °F
Cool
80 °F
Heat
62 °F
Daily
Occupancy
* Programming consecutive events to the same time will cause the thermostat to choose
the last event as the time at which it will set its schedule. In the above example, the
thermostat will control to the unoccupied set point until 7:00 AM Monday.
Ex. #2 Ofce building open all weekend
EventPeriod #1 - Event #1Period #1 - Event #2
OccupiedUnoccupied
Setpoint
Monday7.00 AM6.00 PMDay time only
Tuesday7.00 AM6.00 PMDay time only
Wednesday7.00 AM6.00 PMDay time only
Thursday7.00 AM6.00 PMDay time only
Friday7.00 AM6.00 PMDay time only
Saturday12.00 AM11.59 PM **Occupied
Sunday12.00 AM11.59 PM **Occupied
Cool
72 °F
Heat
70 °F
Cool
80 °F
Heat
62 °F
Daily
Occupancy
** To program a day as occupied for 24 hours, set that day Occupied time to 12:00 AM and
Unoccupied time to 11:59 PM There will be a 1 minute unoccupied period every night at
11:59 PM with this schedule conguration.
15 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Note: 12:00 PM = Noon
12:00 AM = Midnight
Page 16
G) Schedule set (4 events)
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specic schedules if needed.
• 4 events can be scheduled per day.
• Occupied and Unoccupied periods can be set for each day.
• Scheduling the 3rd. & 4th. Events to the same time will cancel the last period.
Monday timer
Schedule set
Monday
set? Y/N
Occupied
Day? Y/N
Occupied
00:00 AM
Unoccup
00:00 AM
Occupie2
00:00 AM
Unoccu2
00:00 AM
No next →
Yes down ↓
No next →
Yes down ↓
To set value
To set value
To set value
To set value
Tuesday timer
Schedule set
Tuesday
set? Y/N
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes key to copy previous day, No key to set new time value for each day
Use ▲▼
Use ▲▼
Use ▲▼
Use ▲▼
Occupied
00:00 AM
Unoccup
00:00 AM
Occupie2
00:00 AM
Unoccu2
00:00 AM
No next →
Yes down ↓
No next →
Yes down ↓
Yes next →
No down ↓
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Use ▲▼
To set value
Use ▲▼ to set value, Yes key to conrm
Wednesday timer
Schedule set
Wednesda
set? Y/N
Occupied
Day? Y/N
Copy Y/N
Previous
Occupied
00:00 AM
Unoccup
00:00 AM
Occupie2
00:00 AM
Unoccu2
00:00 AM
No next →
Yes down ↓
No next →
Yes down ↓
Yes next →
No down ↓
Use ▲▼
To set value
Use ▲▼
To set value
Use ▲▼
To set value
Use ▲▼
To set value
Other days are
identical
Selects the day to be pro-
grammed
or modied
Yes = Daily schedules will be
accessed
No = Unoccupied mode
all day
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Sets Event # 1
Occupied time
Will activate occupied
setpoints
Sets Event # 2
Unoccupied time
Will activate unoccupied
setpoints
Sets Event # 3
Occupied time
Will activate occupied
setpoints
Sets Event # 4
Unoccupied time
Will activate unoccupied
setpoints
16 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 17
Ex. #1 Four event retail establishment schedule
EventPeriod #1 -
Event #1
Period #1 -
Event #2
Period #2 -
Event #3
Period #2 -
Event #4
Occupied Unoccupied Occupied Unoccupied
Cool
Heat
Setpoint
Monday7.00 AM5.00 PM12.00 PM * 12.00 PM *Day time only
Tuesday7.00 AM5.00 PM12.00 PM * 12.00 PM *Day time only
Wednesday7.00 AM5.00 PM12.00 PM * 12.00 PM *Day time only
* Programming events to the same time will cancel the last period and leave the controller
in unoccupied mode
Ex. #2 Residential
EventPeriod #1 -
Event #1
Period #1 -
Event #2
Period #2 -
Event #3
Period #2 -
Event #4
Occupied Unoccupied Occupied Unoccupied
Cool
Heat
Setpoint
Monday6:00 AM8:00 AM4:00 PM10:00 PM Day/evening time only
Tuesday6:00 AM8:00 AM4:00 PM10:00 PM Day/evening time only
Wednesday6:00 AM8:00 AM4:00 PM10:00 PM Day/evening time only
Thursday6:00 AM8:00 AM4:00 PM10:00 PM Day/evening time only
Friday6:00 AM8:00 AM4:00 PM11:30 PM Day/evening time only
Saturday8:00 AM **8:00 AM **8:00 AM ** 11:59 PM **Day time only
Sunday12:00 AM ** 12:00 AM ** 12:00 AM ** 11:59 PM **Occupied all day
72 °F
70 °F
Cool
80 °F
Heat
62 °F
Cool
72 °F
Heat
70 °F
Cool
80 °F
Heat
62 °F
Daily
Occupancy
** Programming consecutive events to the same time will cause the controller to choose
the last event as the time at which it will set its schedule. In the above example for
Saturday, the controller will control to the occupied set point from 8:00 AM until 11:59
PM. Since it is desired to be in occupied mode throughout the night, then it is neces-
sary to program the rst event on Sunday at 12:00 AM. The controller will force a one
minute unoccupied period for a one minute period (between 11:59 PM and 12:00 AM on
Saturday).
17 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 18
H) Clock/Day Settings
Clock
set Y/N
This section of the menu permits the user to set the time and day.
Time settingDay settingTime format setting
Time
set? Y/N
Time
0:00
No next →
Yes down
↓
Use ▲▼
To set value
Day
set? Y/N
Day
Monday
I) Schedule hold
Schedule
hold Y/N
• This menu will only appear on stand-alone (Network Ready) Terminal Equipment
Controller, i.e. without a BACnet® Echelon® module.
• This section of the menu permits the user to set a permanent schedule hold, which
bypasses the internal Terminal Equipment Controller scheduling.
• The permanent schedule hold function is typically used for nonscheduled events
that extend for various periods of time.
• Enabling a permanent occupied or permanent unoccupied schedule hold will cancel any active override.
• The use of temporary setpoints during permanent hold is permitted. The duration
of the temporary setpoint is as set per the TOccTime parameter.
• Ex. 3 hours
Use ▲▼ to set value, yes key to conrm
No next →
Yes down
↓
Use ▲▼
To set value
12/24hrs
set? Y/N
12/24hrs
12 hrs
No = exit
Yes down ↓
Use ▲▼
To set value
18 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 19
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Conguration parameters
menu access password
Default value = 0
Range is: 0 to 1000
Com addr Thermostat
networking address
Default value = 254
Range is: 0 to 254
PAN ID
Personal Area Network
Identication
Default value = 0
Range is: 0 to 500
This parameter sets a password access to prevent
unauthorized access to the conguration menu parameters. A default value of “0” will not prompt a password
or lock the access to the conguration menu.
Range is: 0 to 1000
Conditional parameter to BACnet MS-TP models
(VT76xxX5x00B)
Conditional parameter to Wireless models
(VT76xxX5x00W)
This parameter will only appear when a BACnet or wireless network adapter is present. If the thermostat is installed as a stand-alone unit or with an Echelon adapter,
this parameter will not be used or displayed
- For BACnet MS-TP models valid range to use is
from 1 to 127. Default value of 254 disables BACnet
communication for the thermostat.
- For wireless models valid range is 0 to 254 with a
maximum of 30 thermostat per VWG
Conditional parameter to Wireless models
VT76xxX5x00W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit
or with a BACnet® or Echelon® adapter, this parameter
will not be used or displayed.
This parameter (Personal Area Network Identication)
is used to link specic Terminal Equipment Controllers
to a single specic Schneider-Electric wireless gateway
(VWG). For every Terminal Equipment Controller reporting to a gateway (maximum of 30 Terminal Equipment
Controllers per gateway), be sure you set the SAME
PAN ID value both on the gateway and the Terminal
Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID. The valid
range of available PAN ID is from 1 to 500.
19 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 20
Channel
Channel selection
Default value = 10
Range is: 10 to 26
AI1
Analog input no.1 con-
guration
Default value = None
FA Range
FA range upper limit
value
Default value = 0 CFM
Conditional parameter to Wireless models
VT76xxX5x00W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit
or with a BACnet® or Echelon® adapter, this parameter
will not be used or displayed.
This parameter (Channel) is used to link specic
Terminal Equipment Terminal Equipment Controllers
to specic Viconics wireless gateway(s) (VWG). For
every Terminal Equipment Terminal Equipment Controller reporting to a gateway (maximum of 30 Terminal
Equipment Controllers per gateway), be sure you set
the SAME channel value both on the gateway and the
Terminal Equipment Controller(s).
Viconics recommends using only channels 15 and
25.
The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26
None, No function will be associated with the input
CO2, the 0-10VDC input value is used as a 0-2000ppm
CO2 level:
0 VDC = 0ppm
10VDC = 2000ppm
Sets the upper limit of the CFM range. This parameter
should be set based on the rooftop unit size. If set to 0
CFM, the fresh air damper control will be based on the
Min/Max CO2 and Min/Max Pos values. See Damper
Position section for more details.
0 to 20 000 CFM (0 to 9438 L/s), 10 or 100 incre-
ments
MenuScro
Menu scroll
Default value = On=
Scroll active
Removes the scrolling display and displays the room
temperature/humidity to the user. With this option
enabled, no mode, schedule and outdoor temperature
status is given.
▪ On = Scroll active▪ Off = Scroll not active
Lockout
Keypad lockout levels
Default value = 0 No
lock
20 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
0 = No lock
1 = Low level
2 = High level
Page 21
USER KEY FUNCTIONS
LEVEL
Resume/
Override scheduling
Permanent Occupied and
0
1
2
pwr del
Power-up delay
Default value = 10 seconds
Frost pr
Frost protection enabled
Default value = Off
arrows
Clock setting
Unoccupied Setpoints
Temporary setpoints using
System mode setting
Fan mode setting
Schedules setting
On initial power up of the Terminal Equipment Controller
(each time 24 VAC power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start
up multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds
Off: no room frost protection
On: room frost protection enabled in all system mode at: 42
°F (5.6 °C)
Frost protection is enabled even in system Off mode
Off or On
On heat pump models the system mode will be forced to
EMERGENCY mode if frost protection is activated
Permanent hold
Heat max
Maximum heating setpoint
limit
Default value = 90 °F (32 °C)
Proportional band setting
Default value 2 = 2.0 °F
(1.1 °C)
Adjust the proportional band used by the Terminal Equipment Controller PI control loop.
Note that the default value of 2.0 °F (1.1 °C) gives
satisfactory operation in most normal installation
cases. The use of a proportional band different than
the factory one is normally warranted in applications where
the Terminal Equipment Controller location is problematic
and leads to unwanted cycling of the unit. A typical example
is a wall mounted unit where the Terminal Equipment
Controller is installed between the return and supply air
feeds and is directly inuenced by the supply air stream of
the unit.
VALUE
°F SCALE
PBAND
°C SCALE
PBAND
22 F1.1 C
33 F1.7 C
44 F2.2 C
55 F2.8 C
66 F3.3 C
77 F3.9 C
88 F4.4 C
Anticycle
Minimum On-Off
operation time for stages
Default value = 2
minutes
Heat cph
Heating stages cycles
per hour Default value =
4 C.P.H.
22 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Minimum On-Off operation time of cooling & heating stages.
IMPORTANT, anti-short cycling can be set to 0 minutes for
equipment that posses their own anti cycling timer. Do not
use this value unless the equipment is equipped with such
internal timer. Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes
Anti-short cycling can be set to 0 minutes for equipment that
posses their own anti cycling timer. Do not use that value
unless the equipment is equipped with such internal timer.
Failure to do so can damage the equipment.
Will set the maximum number of heating stage cycles per
hour under normal control operation. It represents the maximum number of cycles that the equipment will turn ON and
OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of
control at the expense of wearing mechanical components
faster.
3, 4, 5, 6,7 & 8 C.P.H.
For multi stage models, heat cph applies to W1 & W2
For heat pump models, heat cph applies to W1 only
(Emergency heat )
Page 23
Cool cph
Cooling stages cycles
per hour Default value =
4 C.P.H.
Will set the maximum number of cooling stage cycles
per hour under normal control operation. It represents
the maximum number of cycles that the equipment will
turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy
of control at the expense of wearing mechanical components faster.
3 or 4 C.P.H.
For multi stage models, cool cph applies to Y1 & Y2
For heat pump models, cool cph applies to Y1 &
Y2 in cooling and heating independently of the
reversing valve position
Deadband
Minimum deadband
Default value = 2.0 °F
(1.1 °C)
The minimum deadband value between the heating and
cooling setpoints. When modied, it will take effect only
when any of the setpoints are modied again.
Range is: 2, 3, or 4 °F, 1.0 °F increments (1.0 to 2.0 °C,
0.5 °C increments)
Fan cont
Fan control
Default value = On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in
all cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating
stages (terminals W1 & W2) are solicited, will not be
energized. The fan in this case will be controlled by the
equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the
fan always on.
ON OR OFF
For multi stage models, fan control applies to W1 &
W2
For heat pump models, fan control applies to W1
only (Emergency heat)
Fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds after the
call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will leave
the fan always on.
Off or On
TOccTime
Temporary occupancy
time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints
when override function is enabled.
When the Terminal Equipment Controller is in unoccupied mode, function is enabled with either the menu or
UI2 congured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Cal RS
Room temperature
sensor calibration
Default value = 0.0 °F
Offset that can be added/subtracted to the actual displayed room temperature
± 5.0 °F, (± 2.5 °C)
or °C
23 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 24
Cal OS
Outside air temperature
sensor
calibration
Default value = 0.0 °F
or °C
Offset that can be added/subtracted to the actual displayed outdoor temperature.
± 5.0 °F, (± 2.5 °C)
H stage
Number of heating
stages.
Applicable to 2 stage
models only
Default value = 2
stages
C stage
Number of cooling
stages
Default value = 2
stages
H lock
Outside air temperature
heating lockout
Default value = 120 °F
(49 °C)
C lock
Outside air temperature
mechanical cooling
lockout.
Default value = -40 °F
(-40 °C)
Will revert the operation of 2 stages Terminal Equipment Controller to single stage operation only when the
second heating step is not needed.
1 or 2 stages
For heat pump models, H stage is limited to 1 stage
only (W1 – Aux. Heat)
Will revert the operation of 2 stage Terminal Equipment
Controller to single stage operation only when the second cooling step is not needed.
1 or 2 stages
Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS (outside air temperature sensor) is connected.
From -15 °F up to 120 °F (-26 °C up to 49 °C)
Disables cooling stage operation based on outdoor air
temperature.
On economizer model, free cooling will not be disabled
by this function.
Function will only be enabled if OS (outside air temperature sensor) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
Unocc TM
Unoccupied Timer value
Default 0.5 hours
Time delay between the moment where the Terminal
Equipment Controller toggles from occupied to unoccupied after the last movement has been detected by the
PIR.
Range is: 0.5 to 24.0 hours in 0.5 hour increments
24 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 25
2/4event
Number of events
conguration
Default value = 2 event
Prog rec
Progressive recovery
enabled
Default value = Off
Progressive recovery is
automatically disabled
if DI 1 and / or DI 2 are
congured remote NSB
Min SH
Only valid if HT Type
is set to Analog
Minimum supply heat
temperature setpoint
Default value = 64 °F
(18 °C)
Chngstpt
Changeover setpoint
Default value = 55 °F
(13.0 °C)
2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
Off, = no progressive recovery
The occupied schedule time is the time at which the
system will restart.
On, = progressive recovery active.
The occupied schedule time is the time at which the desired occupied temperature will be attained. The Terminal
Equipment Controller will automatically optimize the
equipment start time.
In any case, the latest a system will restart is 10 minutes
prior to the occupied period time.
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or Temporary Override).
From 50 °F up to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)
In Cooling mode.
The outside air temperature value at which the cooling
will be switched over from mechanical (compressor) to
free cooling (economizer)
14 to 70 °F (-10.0 to 21.0 °C)
25 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 26
C mech
Mechanical cooling
allowed
Default value = Off
In Cooling mode.
Allows the operation of the mechanical cooling if the
free cooling ( economizer ) cannot maintain the cooling
setpoint.
Off Typically applies when the MS ( mixed air temperature sensor ) is installed after the mechanical cooling
refrigeration coils. In this case, mechanical cooling will
never operate at the same time as free cooling.
On Typically applies when the MS ( mixed air temperature sensor ) is installed before the mechanical cooling
refrigeration coils in the mixing plenum. In this case,
mechanical cooling is allowed when the free cooling
( economizer operation ) cannot maintain the cooling
setpoint.
Off or On
mix stpt
Mixed air setpoint
Default value = 55 °F
(13.0 °C)
SH lock
Only valid if HT Type is
set to Analog
Outside air temperature
supply heat lockout
Default value = 32 °F
(0 °C)
Dis HL
Discharge air
temperature high limit
Default: 120°
Dis LL
Discharge air
temperature low limit
Default: 45°F
Free cooling mixed air setpoint when economizer mode
is enabled.
50 to 90 °F (10.0 to 32.0 °C)
Disables heating operation based on outdoor air temperature.
From –15 °F up to 120 °F (-26 °C up to 49 °C)
(increments: 5° or 50°)
Discharge air high temperature value at which the heating stages will be locked out.
70°F to 150°F (21°C to 65°C)
(increments: 0.5° or 5°)
Discharge air low temperature value at which the cooling
stages will be locked out.
35 to 65°F (2.0°C to 19.0°C)
(increments: 0.5° or 5°)
26 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 27
Min Pos
Minimum Fresh Air
Damper/Economizer
Position
Default value = 0%
Minimum fresh air damper position. Effective only in
Occupied mode (Fan is ON). This value is also used to
determine the fresh air damper position based on the
Min/Max CO2 and Min/Max Pos values set. See Fresh Air
Damper Position section for more details.
0% to 100%, 1 or 10 increments
Max Pos
Maximum Fresh Air
Damper/Economizer
Position
Default value = 100%
Min FA
Minimum Fresh Air
Value
Default value = 0 CFM
Max FA
Maximum Fresh Air
Value
Default value = 0 CFM
Maximum fresh air damper position. Effective only in Occupied mode (Fan is ON). This value is used to determine the fresh air damper position based on the Min/Max
CO2 and Min/Max Pos values set. See Fresh Air Damper
Position section for more details.
0% to 100%, 1 or 10 increments
Minimum fresh air required. Effective only in Occupied
mode (Fan is ON). This value is used to determine the
fresh air damper position based on the Min/Max CO2 and
Min/Max FA values (if FA Range is set to other than 0
CFM). See Fresh Air Damper Position section for more
details.
0 to 20 000 CFM (0 to 9438 L/s) (the value set cannot
exceed the value of FA Range parameter), 10 or 100
increments
Maximum fresh air allowed. Effective only in Occupied
mode (Fan is ON). This value is used to determine the
fresh air damper position based on the Min/Max CO2 and
Min/Max FA values set (if FA Range is set to other than
0 CFM). See Fresh Air Damper Position section for more
details.
0 to 20 000 CFM (0 to 9438 L/s) (the value set cannot
exceed the value of FA Range parameter), 10 or 100
increments
Min CO
Minimum CO2 Level
2
Default value = 800
ppm
Minimum CO2 Level required. Effective only in Occupied
mode (Fan is ON). This value is used to determine the
fresh air damper position based on the Min/Max CO2 and
Min/Max Pos values set. See Fresh Air Damper Position
section for more details.
0 to 2000 ppm, 10 or 100 increments
27 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 28
Max CO
Maximum CO2 Level
2
Default value = 1200
ppm
MS dis
Display mixed air temperature, only if sensor is
installed.
CO2 Level
Display CO2 Level, only
if a CO2 transmitter is
installed at AI1 input.
Maximum CO2 Level allowed. Effective only in Occupied
mode (Fan is ON). This value is used to determine the fresh
air damper position based on the Min/Max CO2 and Min/Max
Pos values set. See Fresh Air Damper Position section for
more details.
0 to 2000 ppm, 10 or 100 increments
Used as diagnostic / service help to troubleshoot and diagnose economizer operation.
Used as diagnostic / service help to troubleshoot and diagnose IAQ control operation
28 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 29
fresh air daMper ConTrol sequenCes
The fresh air damper can be controlled through more than one sequence to achieve
different control strategies such as free cooling (economizer mode), minimum fresh air
control and CO2 level control. Here are the control sequences available:
Note: For the sequences mentioned below, the following conditions must be
met in order for the sequences to be performed as stated:
- Max Pos parameter value must be greater than Min Pos Parameter value.
- Mac CO2 parameter value must be greater than Min CO2 Parameter value.
- Max FA parameter value must be greater than Min FA Parameter value.
Economizer Control Mode Only
If the fresh air damper is to be used only for free cooling purposes (economizer mode,
without fresh air measurement station or CO2 control), only the Min Pos parameter
and the free cooling sequence will be active.
- The FA Range parameter should be set to 0 CFM. (Default Value = 0 CFM)
- Set the Chngstpt parameter to desired value which free cooling is enabled.
(Default Value = 55°F)
If the outside air temperature is greater than the changeover setpoint, then normal
mechanical cooling will be used. If the outside air temperature is less than or equal
to the changeover setpoint, then free cooling will be enabled and mechanical cooling
stages will be locked out.
29 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 30
Economizer Mode and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and minimum fresh air volume control (economizer mode and fresh air measurement station, but without CO2
level control), only the Min FA parameter and the free cooling sequence will be active.
- The FA Range parameter should be set to a value higher than 0 CFM (0 CFM
disables the fresh air control).
- Min FA (minimum fresh air) parameter should be set to the desired level.
The FA Range parameter value should be set to the maximum capacity of the fresh
air measurement station. Therefore the relationship between air volumes and input
signals can be established. For example, if the fresh air station capacity is 10000
CFM, set FA Range to 10000.
This will set the relationship of 0 VDC = 0 CFM and 10VDC = 10000 CFM.
30 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 31
Economizer Mode and CO2 Level Control
If the fresh air damper is to be used for both free cooling and CO2level control (economizer mode and CO2 level control, but without fresh air measurement station), only
the Min Pos, Max Pos, Min CO2and Max CO2 parameters as well as the free cooling
sequence will be active.
- The FA Range parameter should be set to 0 CFM.
- Set AI1 parameter to CO2 (0 VDC = 0ppm ; 10VDC = 2000ppm)
- Min Pos, Max Pos, Min CO2 and Max CO2 parameters should be set accord-
ing to the required setting.
Current CO2 Level
The highest value between free cooling demand output and interpolation output for
the fresh air setpoint will be the output to the fresh air damper.
31 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 32
Economizer Mode, CO2 Level Control and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and CO2 level control with
a fresh air measurement station, only the Min FA, Max FA, Min CO2 and Max CO2
parameters as well as the free cooling sequence will be active.
- The FA Range parameter should be set to something other than 0 CFM.
- Use an air ow transmitter to read fresh air level with AI2 input (0-5 VDC
input)
- Min FA, Max FA, Min CO2 and Max CO2 parameters should be set according
to the required setting.
Current CO2 Level
The highest value between free cooling demand output and interpolation output for
the fresh air setpoint based on the CO2 level will be the output to the fresh air damper.
32 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 33
specIfIcatIons
Terminal Equipment Controller power requirements: 19-30 VAC 50 or 60 Hz; 2 VA Class 2
Operating conditions: 0 °C to 50 °C (32 °F to 122 °F)
Storage conditions: -30 °C to 50 °C (-22 °F to 122 °F)
Sensor: Local 10 K NTC thermistor
Resolution: ± 0.1 °C (± 0.2 °F)
Temperature control accuracy: ± 0.5 ° C (± 0.9 °F) @ 21 °C (70 °F)
Occ, Stand-By and Unocc cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F)
Occ, Stand-By and Unocc heating setpoint range: 4.5 °C to 32 °C (40 °F to 90 °F)
Room and outdoor air temperature display range: -40 °C to 50 °C (-40 °F to 122 °F)
Proportional band for room temperature control: Factory default: Cooling & Heating:
CO2 and airow analog inputs: 0 to 10 VDC input across Scom, AI1
Analog heat & economizer analog outputs rating: 0-10 VDC into 2KW resistance min.
Analog heat & economizer analog output accuracy:
Wire gauge: 18 gauge maximum, 22 gauge
Approximate shipping weight: 0.75 lb ( 0.34 kg )
Agency Approvals all models: UL: UL 873 (US) and CSA C22.2 No.
Agency Approvals all models: FCC: Compliant to CFR 47, Part 15,
Agency Approvals Wireless models: FCC: Compliant to: Part 15, Subpart
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS
SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT
CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
0% to 95% R.H. non-condensing
0% to 95% R.H. non-condensing
typical calibrated
Maximum, 3 Amp. In-rush.
1.8°C (3.2°F)-(Adjustable)
and AI2.
± 3% typical
24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003
(Canada)
Subpart B, Class A (US)
CE : EMC Directive 89/336/EEC
(Europe Union)
C-Tick: AS/NZS CISPR 22 Compli-
ant (Australia / New Zealand) Supplier Code Number N10696
B
Please check with your local government for instruction on disposal of this product.
33 | PIR Ready VT7600 Series-Installation Guide
028-0363-02
Page 34
Drawing & DiMensions
Viconics Technologies Inc.
9245 Langelier Blvd. I St-Leonard I Quebec I Canada I H1P 3K9