Wiring 6
Screw terminal arrangement 7
Main outputs wiring 7
Typical applications 7
Remote sensor accessories 8
Configuring and Status Display Instructions 11
Status display 12
User Interface 13
User configuring instructions menu 13
Local keypad interface 14
Occupied setpoints adjustments 15
Installer Configuration Parameter Menu 22
Troubleshooting guide 32
All models 32
Specifications 34
Drawing & Dimensions 35
1 | PIR Ready VT76xxW Series-Installation Guide
Page 2
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment
Controller (fig. 1).
Remove wiring terminals from sticker.
Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an
air discharge grill.
4. Should not be affected by direct
sun radiation.
5. Nothing should restrict vertical
air circulation to the Terminal
Equipment Controller.
Installation
1. Swing open the Terminal
Equipment Controller PCB to
the left by pressing the PCB
locking tabs (fig. 2).
2. Pull out cables 6” out from the
wall.
3. Wall surface must be flat and
clean.
4. Insert cable in the central hole
of the base.
5. Align the base and mark the
location of the two mounting
holes on the wall. Install base in
the proper orientation. Arrow on
base should be facing up.
6. Install anchors in the wall.
7. Insert screws in mounting holes
on each side of the base (fig. 2).
8. Gently swing back the circuit
board on the base and push on
it until the tabs lock it.
9. Strip each wire 1/4 inch from
end.
2 | PIR Ready VT76xxW Series-Installation Guide
Page 3
10. Insert each wire according to wiring diagram.
When replacing an existing Terminal Equipment Controller, label the
wires before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure
proper and reliable operation in the field. Whenever a control failure
could lead to personal injury and/or loss of property, it becomes the
responsibility of the user / installer / electrical system designer to
incorporate safety devices (such as relays, flow switch, thermal
protections, etc…) and/or an alarm system to protect the entire system
against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into
the hole in the wall.
14. Install security screw.
THEORY OF OPERATION
The VT7600 uses a Viconics proprietary adaptive logic algorithm to control the space
temperature. This algorithm controls the heating / air conditioning system to minimize
overshoot while still providing comfort. It provides exceptional accuracy due to its unique
PI time proportioning control algorithm, which virtually eliminates temperature offset
associated with traditional, differential-based on/off Terminal Equipment Controllers.
Fig.2 - On/Off mechanical control vs PI electronic control.
Features overview
7 day schedule models, 2 or 4 events
Built-in dehumidification control function with local ambient humidity sensing
Selectable single or dual compressor stages
Remote indoor averaging sensing capability
Temperature averaging with 2, 3, 4, 9 or 16 sensors
System mode lock out
3 | PIR Ready VT76xxW Series-Installation Guide
Page 4
Remote discharge air temperature sensor input for monitoring purpose
Remote water temperature sensor input for monitoring purpose
Lockable keypads for tamper proofing. No need for a separate guards
Anti short cycle and minimum on/off run time protection. Reduces wear and
maximizes life span of mechanical equipment.
2 configurable digital inputs for added flexibility. Each input can be configured as the
following:
None: No function will be associated with the input
Service: a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Filter: a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitor filters
Rem NSB: remote NSB timer clock input. Will disable the internal scheduling of
the Terminal Equipment Controller. The scheduling will now be set as per the
digital input. The menu part related to scheduling is disabled and no longer
accessible. It provides low cost setback operation via occupancy sensor or from
a dry contact
RemOVR: temporary occupancy contact. Disables all override menu function of
the Terminal Equipment Controller. . The override function is now controlled by a
manual remote momentarily closed contact. When configured in this mode, the
input operates in a toggle mode.
With this function enabled it is now possible to toggle between unoccupied &
occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
Fan lock: used in conjunction with a local air flow sensor connected to the input.
Locks out the Terminal Equipment Controller heating and cooling action and
displays a local alarm if no air flow is detected 10 seconds after the fan (G
terminal) is energized.
Configurable smart fan operation saves energy during night mode
Non volatile EEPROM memory prevents loss of parameters during power shortage
Built in default profile set-up for easier start up and commissioning
Configurable SPST output relay for lighting, exhaust fan or fresh air control
6 hour typical reserve time for clock in case of power loss on scheduling models
4 | PIR Ready VT76xxW Series-Installation Guide
Page 5
MODEL CHART
Network ready
All Viconics VT7600 series Terminal Equipment Controllers are designed for
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7600N5000B, Terminal Equipment Controller BACnet™ MS-TP®
communication adapter
o VCM7600N5000W Terminal Equipment Controller wireless Zigbee™
communication adapter
5 | PIR Ready VT76xxW Series-Installation Guide
Page 6
TERMINAL,IDENTIFICATION AND FUNCTION
Water Source HeatPump
Part Number
VT7652W
VT7600W
Schedule
Yes
No
Top left terminal block
Y2 X X
Y1 X X G X X RC X X C X X Top right terminal block
DEH X X
O/B X X
Bottom terminal block
Aux X X
DI1 X X
DI2 X X
RS X X
Scom X X
WS X X
MS X X
Wiring
6 | PIR Ready VT76xxW Series-Installation Guide
Page 7
Screw terminal arrangement
VT7600W5X00(X)
Water Source Heat pump / Without Schedule
AU
D1
D2
RS
Scom
WS
MS
Y2
Y1 G RC
C
DEH
O/B
5 pole left top connector
2 pole left top connector
7 pole bottom connector
Main outputs wiring
Wiring notes:
Note 1: Electromechanical contacts are to be used with the digital inputs. Electronic triacs
cannot be used as mean of switching for the input. The switched leg to the input for
the input to activate is terminal C (common)
Note 2: The transformer of the unit provides power to the Terminal Equipment Controller
and the additional loads that will be wired to the Terminal Equipment Controller.
TYPICAL APPLICATIONS
7 | PIR Ready VT76xxW Series-Installation Guide
Page 8
Remote sensor accessories
MODEL NO.
DESCRIPTION
S3010W1000
Wall mounted temperature sensor
S3020W1000
Wall mounted temperature sensor+override button and occupancy status
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
WIRING EXAMPLE OF SINGLE REMOTE ROOM SENSOR:
AU
D1
RS
Scom
C
D2
ScomRSScom
RS
C
DI
Aux
ScomRSScom
RS
OR
VT7600 Series
1x S3020W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
S3010W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
Dip switch
settingfor:
1sensor
S2-1= ONS2-2= ON
1
2
ON
Dip switch
setting for:
1 sensor
S2-1 = ON
S2-2 = ON
Remote mount temperature sensors use 10K NTC thermistor.
This sensor can be used for:
Various averaging combinations
Optional occupancy led
Optional override key
Wall mounted sensor
8 | PIR Ready VT76xxW Series-Installation Guide
Page 9
WIRING EXAMPLES OF 2 REMOTE ROOM SENSORS FOR AVERAGING APPLICATIONS:
WIRING EXAMPLES OF 3 REMOTE ROOM SENSORS FOR AVERAGING APPLICATIONS:
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
-40
-40
324.3197
-20
-4
94.5149 0
32
32.1910
20
68
12.4601
40
104
5.3467
-39
-38
303.6427
-19
-2
89.2521 1
34
30.6120
21
70
11.9177
41
106
5.1373
-38
-36
284.4189
-18 0 84.3147 2
36
29.1197
22
72
11.4018
42
108
4.9373
-37
-35
266.5373
-17 1 79.6808 3
37
27.7088
23
73
10.9112
43
109
4.7460
-36
-33
249.8958
-16 3 75.3299 4
39
26.3744
24
75
10.4443
44
111
4.5631
-35
-31
234.4009
-15 5 71.2430 5
41
25.1119
25
77
10.0000
45
113
4.3881
-34
-29
219.9666
-14 7 67.4028 6
43
23.9172
26
79
9.5754
46
115
4.2208
-33
-27
206.5140
-13 9 63.7928 7
45
22.7861
27
81
9.1711
47
117
4.0607
-32
-26
193.9703
-12
10
60.3980 8
46
21.7151
28
82
8.7860
48
118
3.9074
-31
-24
182.2686
-11
12
57.2044 9
48
20.7004
29
84
8.4190
49
120
3.7607
-30
-22
171.3474
-10
14
54.1988
10
50
19.7390
30
86
8.0694
50
122
3.6202
-29
-20
161.1499
-9
16
51.3692
11
52
18.8277
31
88
7.7360
51
124
3.4857
Notes for averaging applications:
S3010W1000 and S3020W1000
can be mixed matched.
S3010W1000 and S3020W1000
are to be wired in parallel.
Respect the dip switch setting in
each remote sensor.
AU
D1
RS
Scom
C
D2
ScomRSScom
RS
C
DI
Aux
ScomRSScom
RS
C
DI
Aux
AU
D1
RS
Scom
C
D2
ScomRSScom
RS
ScomRSScom
RS
C
DI
Aux
VT7600 Series
2x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
1x S3010W1000 and 1x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
Dip switch
settingfor:
2sensors
S2-1= OFFS2-2= ON
Temperature vs. resistance chart for 10 Kohm NTC thermistor
9 | PIR Ready VT76xxW Series-Installation Guide
Page 10
-28
-18
151.6239
-8
18
48.7042
12
54
17.9636
32
90
7.4182
52
126
3.3568
-27
-17
142.7211
-7
19
46.1933
13
55
17.1440
33
91
7.1150
53
127
3.2333
-26
-15
134.3971
-6
21
43.8268
14
57
16.3665
34
93
6.8259
54
129
3.1150
-25
-13
126.6109
-5
23
41.5956
15
59
15.6286
35
95
6.5499
55
131
3.0016
-24
-11
119.3244
-4
25
39.4921
16
61
14.9280
36
97
6.2866
56
133
2.8928
-23
-9
112.5028
-3
27
37.5056
17
63
14.2629
37
99
6.0351
57
135
2.7886
-22
-8
106.1135
-2
28
35.6316
18
64
13.6310
38
100
5.7950
58
136
2.6886
-21
-6
100.1268
-1
30
33.8622
19
66
13.0307
39
102
5.5657
59
138
2.5926
1 2
ON
Location of dip
S3010W1000 remote wall mounted
temperature sensor, dip switch location
S2000D1000, remote duct mounted temperature
sensor c/w junction box.
This sensor can be used for:
Remote return air temperature sensing with the
sensor mounted on the return air duct.
Outside air temperature sensing with the
sensor installed in the fresh air plenum.
Supply air temperature sensor
S2060A1000, remote averaging duct mounted temperature sensor c/w junction box.
This sensor can be used for:
Remote averaging return air temperature sensing with the sensor mounted on the return
air duct.
Outside air temperature averaging sensing with the sensor installed in the fresh air
plenum.
Mixed air temperature averaging sensor for economizer models with the sensor in the
mixing plenum.
10 | PIR Ready VT76xxW Series-Installation Guide
Page 11
WIRING S2000D1000, S2060A1000 AND S2020E1000
Remote wiring 1 sensor Remote wiring 4 sensors
10 K
10 K
10 K
10 K
10 K
Scom
MS
Scom
OS
Scom
RS
or
or
ScomMSScom
OS
Scom
RS
or
or
(
Schedule
set? Y/N
Sys mode
set? Y/N
Clock
set? Y/N
Temperat
set? Y/N
Schedule
hold Y/N
Exit
menu Y/N
Unocc HT
set? Y/N
°F/°C
set? Y/N
Heating
set? Y/N
Unocc CL
set? Y/N
Cooling
set? Y/N
°C
°F
Exit?
Y/N
Temperature
Temperature
Temperature
Temperature
MENU
12/24hrs
set? Y/N
12 / 24
Time
set? Y/N
Time
Day
set? Y/N
Day
Fan mode
set? Y/N
On
Smart
Auto
Sunday
set? Y/N
Saturday
set? Y/N
Friday
set? Y/N
Thursday
set? Y/N
Wednesda
set? Y/N
Tuesday
set? Y/N
Monday
set? Y/N
Exit?
Y/N
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Occupied
day? Y/N
Occupied
12:00 pm
Time
Unoccup
12:00 pm
Time
Resume
Occ Hold
Uno Hold
Exit?
Y/N
off
heat
cool
auto
Override
schd Y/N
Cancel
ovrd Y/N
If status is:
Unoccupied
If status is:
Temporary Occupied Time,
Appears on stand-alone
models only
User menu flow chart:
NOTE: Prompts may not all be present depending on model selected
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
11 | PIR Ready VT76xxW Series-Installation Guide
Page 12
Status display
ROOM
TEMPERATURE
CLOCK
STATUS
SYSTEM
MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C
or °F
XX % RH
Monday
12:00
AM
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
Service
Sys mode
off
Occupied
hold
Frost
ON
Sys mode
heat
Unoccup
SetClock
Sys mode
cool
Unoccup
hold
Filter
Fan lock
The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the actual status of the system.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any
key will cause the back light to come on to high level.
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively.
The last item viewed will be shown on the display for 30 seconds before returning to
automatic scrolling. Temperature is automatically updated when scrolling is held.
Sequence of auto-scroll status display:
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time.
The priority for the alarms is as follows:
12 | PIR Ready VT76xxW Series-Installation Guide
Page 13
Frost ON
Indicates that the heating is energized by the low limit frost protection room
temperature setpoint 5.6 °C ( 42 °F )
SetClock
Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours
Service
Indicates that there is a service alarm as per one of the configurable digital
input ( DI1 or DI2 )
Filter
Indicates that the filters are dirty as per one of the configurable digital input (
DI1 or DI2 )
Fan lock
Indicates that the heating and cooling action are locked out due to a defective
fan operation
When any of the fan is ON, the FAN LED will illuminate
When heating is ON, the HEAT LEDwill illuminate
When cooling is ON, the COOL LED will illuminate
LED
OPERATION
HEATPUMP
MODELS
Fan LED on
When G Fan terminal
operates
Heating LED
on
When Y1 terminal
operates in heating
mode
Cooling LED
on
When Y1 terminal
operates in cooling
mode
Three status LEDs on the Terminal Equipment Controller cover are used to indicate the
status of the fan, a call for heat, or a call for cooling.
USER INTERFACE
User configuring instructions menu
The VT7600 series of Terminal Equipment
Controller feature an intuitive, menu-driven, back-lit
LCD display that walks users through the
configuring steps, making the configuring process
extremely simple. This menu is typically accessed
by the user to set the parameters such as
temperature and time events, system mode, fan
mode, etc.
It is possible to bring up the user menu at any time by depressing the MENU key. The
status display automatically resumes after exiting the user-configuring menu.
13 | PIR Ready VT76xxW Series-Installation Guide
Page 14
If the user pauses at any given time during configuring, Auto Help text is displayed to help
Ex.:
Press yes key to change cooling temperature setpoint
Use the up or down arrow to adjust cooling setpoint
The YES key is used to confirm a selection, to move onto the next menu item
and to manually scroll through the displayed information.
The NO key is used when you do not desire a parameter change, and to
advance to the next menu item. Can also be used to toggle between heating
and cooling setpoints.
The MENU key is used to access the Main User Menu or exit the menu.
The down arrow key is used to decrease temperature setpoint and to adjust
the desired values when configuring the Terminal Equipment Controller.
The up arrow key is used to increase temperature setpoint and to adjust the
desired values when configuring the Terminal Equipment Controller.
and guide the user through the usage and configuring of the Terminal Equipment
Controller.
Local keypad interface
Each of the sections in the menu is accessed and configured using 5 keys on the
Terminal Equipment Controller cover.
The priority for the alarms is as follows:
When left unattended for 45 seconds, the display will resume automatic status display
scrolling.
To turn on the back light, press any key on the front panel. The back lit display will turn off
when the Terminal Equipment Controller is left unattended for 45 seconds
14 | PIR Ready VT76xxW Series-Installation Guide
Page 15
Sequence of user menu:
OVERRIDE
RESUME
TEMPERATURE
SETPOINTS
SYSTEM
MODE
SETTING
FAN
MODE
SETTING
SCHEDULES
SETTING
CLOCK
SETTING
SCHEDULE
HOLD
Override
schd Y/N
Temperat
Set Y/N
Sys
mode
set
Y/N
Fan
mode
set Y/N
Schedule
set Y/N
Clock
set Y/N
Schedule
hold Y/N
Appears
only in
unoccupied
mode
Appears
only on
stand-alone
(Network
Ready)
models
Cancel
ovrd Y/N
Appears
only in
override
mode
DEFAULT TEMPERATURE SETPOINTS:
DEFAULT MODES:
Occupied cooling setpoint = 24 °C (75 °F)
System mode = Auto
Occupied heating setpoint = 22 °C (72 °F)
Fan mode = Smart (for models with a
communication module
or scheduling network
ready models)
Fan mode = Auto (for non-scheduling
network ready models)
Unoccupied cooling setpoint = 28 °C (82°F)
Unoccupied heating setpoint = 18 °C (65°F)
DEFAULT SCHEDULES:
Fahrenheit scale
Monday through Sunday
Setpoint type = permanent
Occupied time is: 12 00 AM
Unoccupied time is: 11:59 PM
Occupied setpoints adjustments
There is a default profile set in the Terminal Equipment Controller from the factory.
This enables the Terminal Equipment Controller to operate as a non-scheduling unit in
day mode operation at start up.
There will be a 1 minute unoccupied period every night at 11:59 PM with this default
configuration.
15 | PIR Ready VT76xxW Series-Installation Guide
Page 16
A) Override an unoccupied period
Override
schd Y/N
Cancel
ovrd Y/N
Temperat
set Y/N
COOLING
SETPOINT
OCCUPIED
MODE
HEATING
SETPOINT
OCCUPIED
MODE
COOLING
SETPOINT
UNOCCUPIED
MODE
HEATING
SETPOINT
UNOCCUPIED
MODE
°F OR °C
DISPLAY
SETTING
Cooling
set? Y/N
No next
Yes down
Heating
set? Y/N
No next
Yes down
Unocc CL
set? Y/N
No next
Yes down
Unocc HT
set? Y/N
No next
Yes down
°F or °C
set? Y/N
No next
Yes down
Use ▲▼ keys to set value, Yes key to confirm
Cooling
70.0 °F
Use ▲▼
To set
value
Heating
68.00 °F
Use ▲▼
To set
value
Unocc CL
80.0 °F
Use ▲▼
To set
value
Unocc HT
60.0 °F
Use ▲▼
To set
value
Units
°F
Use ▲▼
To set
value
This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode. The unoccupied mode is enabled either by the internal timer scheduling or by a
remote NSB contact via DI1 or DI2.
If DI1 or DI2 is configured to operate as a remote temporary override contact, this menu
will be disabled.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12 hours).
B) Resume regular scheduling
This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in Unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to resume
the regular setpoints & scheduling.
C) Temperature setpoints
Permanent setpoint changes
This menu permits the adjustment of all permanent temperature setpoints (occupied and
unoccupied) as well as the desired temperature units (°F or °C). Permanent setpoints are
written to RAM and EEPROM.
Temporary setpoint changes
Temporary setpoints can be modified through the Up arrow key (▲) and the Down arrow
keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the Terminal
Equipment Controller and its setpoint.
The Up (▲) arrow key will increment the setpoint by 0.5 degree (F or C).
The Down (▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Press the Yes key to accept the new setpoint.
16 | PIR Ready VT76xxW Series-Installation Guide
Page 17
Local changes to the heating or cooling setpoints made by the user directly using the up
Sys mode
set Y/N
Sys mode
auto
Automatic mode
Automatic changeover mode between heating and cooling operation
Sys mode
cooling
Cooling mode
Cooling operation mode only
Sys mode
heating
Heating mode
Heating operation mode only
Sys mode
off
Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection
at 50 °F ( 10 °C ) is enabled
Fan mode
set Y/N
Fan mode
On
On fan mode
Fan is on continuously, even when system mode is OFF.
Fan mode
Auto
Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied
periods.
Fan mode
Smart
Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan
cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on
all stand-alone (Network Ready) scheduling models or if DI1 or DI2 is set
to RemNSB on stand-alone non-scheduling models.
or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu
D) System mode setting
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to confirm
E) Fan mode setting
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm
17 | PIR Ready VT76xxW Series-Installation Guide
Page 18
F) Schedule set (2 events)
Schedule
set Y/N
MONDAY TIMER
SCHEDULE SET
TUESDAY
TIMER
SCHEDULE SET
WEDNESDAY
TIMER
SCHEDULE SET
OTHER DAYS ARE
IDENTICAL
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
Event
Period #1 - Event #1
Period #1 - Event #2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
7.00 AM
6.00 PM
Day time only
Tuesday
7.00 AM
6.00 PM
Day time only
Wednesday
7.00 AM
6.00 PM
Day time only
Thursday
7.00 AM
6.00 PM
Day time only
Friday
7.00 AM
6.00 PM
Day time only
Saturday
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
Unoccupied
Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per
parameter (2/4event)
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specific schedules if needed.
2 events can be scheduled per day.
Occupied & unoccupied periods can be set for each day.
Typical examples of a 2 event office schedule:
Ex. #1 Office building closed all weekend
* Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the
above example, the Terminal Equipment Controller will control to the unoccupied set
point until 7:00 AM Monday.
18 | PIR Ready VT76xxW Series-Installation Guide
Page 19
Ex. #2 Commercial building which is occupied all weekend
Event
Period #1 - Event
#1
Period #1 - Event
#2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
8.00 AM
5.00 PM
Day time only
Tuesday
8.00 AM
5.00 PM
Day time only
Wednesday
8.00 AM
5.00 PM
Day time only
Thursday
8.00 AM
5.00 PM
Day time only
Friday
8.00 AM
5.00 PM
Day time only
Saturday
12.00 AM **
11.59 PM **
Occupied
Sunday
12.00 AM **
11.59 PM **
Occupied
Schedule
set Y/N
Monday timer
Schedule set
Tuesday timer
Schedule set
Wednesday timer
Schedule set
Other days are identical
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied
setpoints
Use ▲▼ to set value, Yes key to confirm
Occupie2
00:00 AM
Use ▲▼
To set
value
Occupie2
00:00 AM
Use ▲▼
To set
value
Occupie2
00:00 AM
Use ▲▼
To set
value
Sets Event # 3 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup2
00:00 AM
Use ▲▼
To set
value
Unoccup2
00:00 AM
Use ▲▼
To set
value
Unoccup2
00:00 AM
Use ▲▼
To set
value
Sets Event # 4 Unoccupied time
Will activate unoccupied
setpoints
Use ▲▼ to set value, Yes key to confirm
Note: 12:00 PM = Noon
** To schedule a day as occupied for 24 hours, set that day occupied time to 12:00 AM
and Unoccupied time to 11:59 PM There will be a 1 minute unoccupied period every
night at 11:59 PM with this schedule configuration.
G) Scheduleset (4 events)
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each
day can be tailored to specific schedules if needed.
4 events can be scheduled per day.
Occupied & Unoccupied periods can be set for each day.
Scheduling the 3rd. & 4th. Events to the same time will cancel the last period.
19 | PIR Ready VT76xxW Series-Installation Guide
Page 20
Ex. #1 Four event retail establishment schedule
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72°F
70°F
80°F
62°F
72°F
70 °F
80°F
62 °F
Occupancy
Monday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Tuesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Wednesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Thursday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Friday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Saturday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72°F
70°F
80°F
62°F
72°F
70°F
80°F
62°F
Occupancy
Monday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Tuesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Wednesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Thursday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Friday
6:00 AM
8:00 AM
4:00 PM
11:30 PM
Day/evening
time only
Saturday
8:00 AM *
8:00 AM *
8:00 AM *
11:59 PM *
Day time
only
Sunday
12:00 AM *
12:00 AM *
12:00 AM *
11:59 PM *
Occupied all
day
* Scheduling events to the same time will cancel the last period and leave the Terminal
Equipment Controller in unoccupied mode
Ex. #2 Residential
* Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the above
example for Saturday, the Terminal Equipment Controller will control to the occupied set
point from 8:00 AM until 11:59 PM. Since it is desired to be in occupied mode throughout
the night, then it is necessary to schedule the first event on Sunday at 12:00 AM. The
Terminal Equipment Controller will force a one minute unoccupied period for a one minute
period (between 11:59 PM and 12:00 AM on Saturday).
20 | PIR Ready VT76xxW Series-Installation Guide
Page 21
H) Clock/Day Settings
Clock
set Y/N
Time setting
Day setting
Time format setting
Time
set? Y/N
No next
Yes down
Day
set? Y/N
No next
Yes down
12/24hrs
set? Y/N
No = exit
Yes down
Time
0:00
Use ▲▼
To set value
Day
Monday
Use ▲▼
To set value
12/24hrs
12 hrs
Use ▲▼
To set value
Schedule
hold Y/N
Schedule
resume
Resume regular scheduling cancels the permanent hold and re-enables
the regular scheduling as set per internal schedule or as per remote NSB
via one of the DI’s configured as remote NSB.
This action can also by accomplished by using the Resume menu.
Any temporary setpoint that are active will be left active for the duration of
the period as set per the TOccTime parameter.
Schedule
occ hold
Hold permanent occupied forces the Terminal Equipment Controller into
a permanent occupied mode using the occupied setpoints. All timed
scheduling functions are by-passed.
The PERMANENT OCCUPIED status will appear in the automatic status
scroll. To resume to regular scheduling, user must scroll to the Schedule
Hold menu and select the Schedule resume option.
This section of the menu permits the user to set the time and day.
J) Schedule hold
This menu will only appear on stand-alone (Network Ready) Terminal
Equipment Controller, i.e. without a BACnet™ / Echelon™ module.
This section of the menu permits the user to set a permanent schedule
hold, which bypasses the internal Terminal Equipment Controller
scheduling.
The permanent schedule hold function is typically used for non-
scheduled events that extend for various periods of time.
Enabling a permanent occupied or permanent unoccupied schedule hold
will cancel any active override.
The use of temporary setpoints during permanent hold is permitted. The
duration of the temporary setpoint is as set per the TOccTime parameter.
Ex. 3 hours
Use ▲▼ to set value, yes key to confirm
21 | PIR Ready VT76xxW Series-Installation Guide
Page 22
Schedule
uno hold
Hold permanent unoccupied forces the Terminal Equipment Controller
into a permanent unoccupied mode using the unoccupied setpoints. All
timed scheduling functions are by-passed.
The PERMANENT UNOCCUPIED status will appear in the automatic
status scroll. To resume to regular scheduling, user must scroll to the
Schedule Hold menu and select the Schedule resume option.
INSTALLER CONFIGURATION PARAMETER MENU
Configuration can be done through the network or locally at the Terminal Equipment
Controller.
To enter configuration, press and hold the middle button “Menu” for 8 seconds
If a password lockout is active, “Password” is prompted. Enter password value using the
“up” and “down” arrows and press “Yes” to gain access to all configuration properties of
the Terminal Equipment Controller. A wrong password entered will prevent local access to
the configuration menu.
Once in the configuration menu, press the “No” button repetitively to scroll between all the
available parameters.
When the desired parameter is displayed, press “Yes” to adjust it to the desired value
using “up” and “down” arrows. Once set, press “Yes” to scroll to the next parameter.
22 | PIR Ready VT76xxW Series-Installation Guide
Page 23
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value = 0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Com Addr
Terminal Equipment
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet™ MS-TP models
(VT76xxW5x00B)
Conditional parameter to Wireless models
(VT76xxW5x00W)
This parameter will only appear when a BACnet™ or
wireless network adapter is present. If the Terminal
Equipment Controller is installed as a stand-alone
(Network Ready) unit or with an Echelon™ adapter, this
parameter will not be used or displayed
-For BACnet™ MS-TP models, the valid range to is from
1 to 127. Default value of 254 disables BACnet™
communication for the Terminal Equipment Controller.
For wireless models valid range is 0 to 254 with a
maximum of 30 Terminal Equipment Controllers per
VWG
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 1000
Conditional parameter to Wireless models
(VT76xxW5x00W)
This parameter will only appear when a wireless
network adapter is present. If the Terminal
Equipment Controller is installed as a stand-alone
(Network Ready) unit or with a BACnet™ or
Echelon™ adapter, this parameter will not be used or
displayed
This parameter (Personal Area Network
Identification) is used to link specific Terminal
Equipment Controllers to a single specific Viconics
wireless gateway ( VWG ) For every Terminal
Equipment Controller reporting to a gateway
( maximum of 30 Terminal Equipment Controllers per
gateway ), be sure you set the SAME PAN ID value
both at the gateway and the Terminal Equipment
Controller(s).
The default value of 0 is NOT a valid PAN ID.
23 | PIR Ready VT76xxW Series-Installation Guide
Page 24
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models
(VT76xxW5x00W)
This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone (Network
Ready) unit or with a BACnet™ or Echelon™ adapter,
this parameter will not be used or displayed
This parameter (Channel) is used to link specific
Terminal Equipment Controllers to specific Viconics
wireless gateway(s) (VWG) For every Terminal
Equipment Controller reporting to a gateway
(maximum of 30 Terminal Equipment Controllers per
gateway), be sure you set the SAME channel value
both at the gateway and the Terminal Equipment
Controller(s).
Viconics recommends using only the usage of
channels 15 and 25 only.
The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26
Get From
Terminal Equipment Controller
Get From another device
configuration utility
Default value = 0
Range is: 0 to 254
Conditional parameter to Wireless models
VT76xxW5x00W
Entering a MAC address enables an automatic routine
that automatically fetches all the required configuration
properties of the current device from another already
configured device an copies the same required
configured property values.
If a value other than the default value of 255 is entered,
user will then be prompted to exit the Configuration
Menu thus leaving all other parameter configuration to
be copied from the referenced Terminal Equipment
Controller MAC address.
Ex.: If you are currently configuring MAC12 and the
settings matches exactly the settings of ZN MAC5,
then enter 5 as the current parameter value.
If the process is successful and all required
configuration properties have been copied, the
value will revert back to 255
If the process is NOT successful and all required
configuration properties have NOT been copied
( either the reference device is NOT the same
model number or is offline or does not exists ) the
value will revert back to 254 to indicate the failure
of the process
Leaving the Get From parameter to 255 means that
every configuration parameters will be set
manually.
24 | PIR Ready VT76xxW Series-Installation Guide
Page 25
DI 1
Digital input no.1
configuration
Open contact input =
function not energized
Closed contact input =
function energized
Default Value = None
(None) : No function will be associated with the input
(Rem NSB): remote NSB timer clock input. Will disable the
internal scheduling of the Terminal Equipment Controller. The
scheduling will now be set as per the digital input. The time is
still displayed as information, but the menu part related to
scheduling is disabled and no longer accessible.
Open contact = occupied setpoints
Closed contacts = unoccupied setpoints
(RemOVR): Temporary override remote contact. Disables all
override menu function of the Terminal Equipment Controller.
The override function is now controlled by a manual remote
momentarily closed contact. When configured in this mode, the
input operates in a toggle mode. With this function enabled it is
now possible to toggle between unoccupied & occupied
setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time. When Override is enabled, an
Override status message will be displayed
(Filter): a back-lit flashing Filter alarm will be displayed on the
Terminal Equipment Controller LCD screen when the input is
energized
(Service): a back-lit flashing Service alarm will be displayed on
the Terminal Equipment Controller LCD screen when the input is
energized
(Fan lock): a back-lit flashing Fan lock alarm will be displayed
on the Terminal Equipment Controller LCD screen when the
input is not energized. Used in conjunction with a local airflow
sensor connected to the input. Locks out the Terminal
Equipment Controller heating and cooling action if no airflow is
detected 10 seconds after the fan ( G terminal ) is energized.
Open contact = no airflow
Closed contacts = airflow present
DI 2
Digital input no. 2
configuration
Default value = None
Same as above. It is possible to configure both inputs to have
the same function.
MenuScro
Menu scroll
Default value = On = Scroll active
Removes the scrolling display and only present the room
temperature/humidity to the user. With this option enabled, no
status is given of mode, schedule and outdoor temperature.
On = Scroll active
Off = Scroll not active
25 | PIR Ready VT76xxW Series-Installation Guide
Page 26
lockout Keypad lockout levels
Default value = 0 No lock
0 = No lock
1 = Low level
2 = High level
USER KEY FUNCTIONS
LEVEL
Resume/
Override scheduling
Permanent Occupied and
Unoccupied Setpoints
Temporary setpoints using
arrows
System mode setting
Fan mode setting
Schedules setting
Clock setting
Permanent hold
0
1
2
pwr del
Power-up delay
Default value = 10 seconds
On initial power up of the Terminal Equipment Controller
(each time 24 Vac power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds
Frost pr
Frost protection enabled
Default value = Off
Off: no room frost protection
On: roomfrost protection enabled in all system mode at:
42 °F ( 5.6 °C )
Frost protection is enabled even in system Off mode
Off or On
heat max
Maximum heating setpoint
limit
Default value = 90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
26 | PIR Ready VT76xxW Series-Installation Guide
Page 27
Pband
Proportional Band
setting
Default value 2 = 2.0 °F ( 0.6 °C )
Adjust the proportional band used by the Terminal Equipment
Controller PI control loop.
Note that the default value of 2.0 °F ( 1.1 °C ) gives
satisfactory operation in most normal installation cases.
The use of a superior proportional band different than
the factory one is normally warranted in applications where the
Terminal Equipment Controller location is problematic and leads
to unwanted cycling of the unit. A typical example is a wall
mounted unit where the Terminal Equipment Controller is installed
between the return and supply air feeds and is directly influenced
by the supply air stream of the unit.
Value
F scale
Pband
C scale
Pband
2
2 F
1.1 C
3
3 F
1.7 C
4
4 F
2.2 C 5 5 F
2.8 C
6
6 F
3.3 C
7
7 F
3.9 C 8 8 F
4.4 C
Anticycle
Minimum on/off
operation time for
stages
Default value = 2
minutes
Minimum On/Off operation time of cooling & heating stages.
IMPORTANT, anti-short cycling can be set to 0 minutes for
equipment that posses their own anti cycling timer. Do not use this
value unless the equipment is equipped with such internal timer.
Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes
Anti-short cycling can be set to 0 minutes for equipment that
posses their own anti cycling timer. Do not use that value unless
the equipment is equipped with such internal timer. Failure to do
so can damage the equipment.
% RH disp
Local RH Display
Default value = Off
Enables the display of humidity below the room temperature on the
display
On = Display %RH
Off = No display of %RH
cool cph
Heatpump stages
cycles per hour
Default value = 4
C.P.H.
Will set the maximum number of heatpump stage cycles per hour
under normal control operation. It represents the maximum number of
cycles that the equipment will turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3 or 4 C.P.H.
27 | PIR Ready VT76xxW Series-Installation Guide
Page 28
deadband
Minimum deadband
Default value = 2.0 °F ( 1.1 °C )
Minimum deadband value between the heating and cooling
setpoints. If modified, it will be applied only when any of the
setpoints are modified.
2, 3 or 4 °F ( 1.0 to 2.0 °C )
fan cont
Fan control
Default value = On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in all cases
will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating stages
(terminals W1 & W2) are solicited, will not be energized. The fan in
this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan
always on.
ON OR OFF
For multi stage models, fan control applies to W1 & W2
For heat pump models, fan control applies to W1 only
(Emergency heat)
fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds after the call for
heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will leave the fan
always on.
Off or On
ToccTime
Temporary
occupancy time
Default value = 3 hours
Temporary occupancy time with occupied mode setpoints when
override function is enabled
When the Terminal Equipment Controller is in unoccupied mode,
function is enabled with either the menu or DI1 or DI2 configured
as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours
Cal RS
Room air temperature
sensor calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual displayed room
temperature
± 5.0 °F ( ± 2.5 °C )
Cal RH
Humidity sensor
calibration
Default value = 0 %RH
Offset that can be added/subtracted to the actual displayed
humidity by ± 15.0 %RH.
Range is : ± 15.0 %RH
28 | PIR Ready VT76xxW Series-Installation Guide
Page 29
HP stage
Number of heatpump
stages
Default value = 2 stages
Will revert the operation of 2 stage Terminal Equipment
Controller to single stage operation only when the second
compressor step is not needed.
1 or 2 stages
H lock
Outside air temperature
heating lockout
Default value = 120 °F ( 49 °C )
Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS ( outside air temperature
network value ) is received.
From -15 °F up to 120 °F ( -26 °C up to 49 °C )
C lock
Outside air temperature
mechanical cooling
lockout.
Default value = -40 °F ( -40 °C )
Disables cooling stage operation based on outdoor air
temperature.
Function will only be enabled if OS ( outside air temperature
network value ) is received.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
Unocc TM
Unoccupied Timer value
Default 0.5 hours
Time delay between the moment where the Terminal
Equipment Controller toggles from occupied to unoccupied after
the last movement has been detected by the PIR.
Range is: 0.5 to 24.0 hours in 0.5 hour increments
2/4event
Number of events
configuration
Default value = 2 event
2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
29 | PIR Ready VT76xxW Series-Installation Guide
Page 30
aux cont
Auxiliary contact
configuration
Default value = N.O. normally open
This contact can be used to energize peripheral devices such
as: lighting equipment, exhaust fans, economizers, etc.
This contact will operate in parallel with the internal
occupied/unoccupied schedule of the Terminal Equipment
Controller or the remote NSB contact if DI1 or DI2 is used.
When the system is in OFF mode, the contact will remain in its
unoccupied status independently of the occupied / unoccupied
schedule.
Configured
Contact
occupied status
Contact
unoccupied status
N.O.
Closed
Opened
N.C.
opened
Closed
Prog rec
Progressive recovery
enabled
Default value = Off
Progressive recovery is
automatically disabled if
DI 1 and / or DI 2 are
configured remote NSB
Off, = no progressive recovery
The occupied schedule time is the time at which the system will
restart.
On, = progressive recovery active.
The occupied schedule time is the time at which the desired
occupied temperature will be attained. The Terminal Equipment
Controller will automatically optimize the equipment start time.
In any case, the latest a system will restart is 10 minutes prior
to the occupied period time.
Re valve
Reversing valve operation
O/B
Default value = O
Heat pump reversing valve operation
O will energize the valve in cooling operation.
B will energize the valve in heating operation
O OR B
30 | PIR Ready VT76xxW Series-Installation Guide
Page 31
Dhu set
Dehumidification setpoint
Default is 50 % RH
Used only if dehumidification sequence is enabled:
Range is: 30-95% RH
DHumiLCK
Dehumidification lockout
Default value:
Restrict
Enables, restricts or disables the dehumidification sequence.
Dhu Disa: Dehumidification disabled
Restrict: will restrict the dehumidification process based on
the following:
- System mode = Needs to be Cool or Auto ( currently
operating in cooling only )
- Low ambient room temperature protection enabled
Dhu Enab: will not restrict the dehumidification process:
- System mode = Needs to be Cool, Heat or Auto
There is no ambient room temperature protection enabled
Dhu OALK
Dehumidification outside air
temperature lockout
Default value = 32°F (0°C)
Outside air temperature under which the dehumidification
sequence is disabled.
Only valid if an outdoor air sensor is connected at the
Terminal Equipment Controller or a network value is
transmitted to the Terminal Equipment Controller.
From –40°F up to 122°F (-40°C to 50°C)
DehuHyst
Dehumidification
Hysteresys
Default = 5 % RH
Humidity control hysteresis. Used only if dehumidification
sequence is enabled:
Range is: 2 to 20% RH
MS dis
Display mixed air
temperature
Economizer model only,
only if sensor is installed
Used as diagnostic / service help to troubleshoot and
diagnose economizer operation.
31 | PIR Ready VT76xxW Series-Installation Guide
Page 32
TROUBLESHOOTING GUIDE
Symptom
Possible Cause
Corrective Action
No display on the
Terminal
Equipment
Controller
Absent or incorrect
supply voltage
1. Check power supply voltage between C
& RC to be from 19-30 VAC
2. Check for tripped fuse or circuit breaker
Overloaded power
transformer
Verify that the transformer used is
powerful enough (enough VA’s) to supply
all controlled devices including the
Terminal Equipment Controller
Keyboard menu
does not access
all functions
Keyboard locked
Change configuration parameter
LOCKOUT to value “0” to access all levels
of the menu
Temperature
setpoints revert to
original value
after a certain
time period
Temporary setpoint
option selected
1. The Terminal Equipment Controller
needs to be in Permanent setpoint
mode for the new setpoint to be kept
and memory and used all the time
2. Go to the Set temperature menu.
3. The last prompt is setpoint type. Set it
to Permanent setpoint
Terminal
Equipment
Controller will not
call for heating
Wrong mode selected
Select heating mode
Terminal Equipment
Controller in
Unoccupied mode
Select Occupied Hold in Schedule hold or
Override to force the Terminal Equipment
Controller Occupied heating setpoint
Anticycle delay active
Wait, the anticycling period will end and
the equipment will start
Heating setpoint is
satisfied
Raise the Heating setpoint
Heating lockout
attained
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter H Lock
to value 120 °F ( 49 °C ) to by-pass
lockout
Wiring error
1. Start the Fan by forcing the Fan ON
mode
2. Put a jumper across terminals RH &
W1. The heating should come ON. If it
does not, verify wiring and check if a
jumper is required between RC & RH
Terminal
Equipment
Controller will not
call for cooling
Wrong mode selected
Select cooling mode
Terminal Equipment
Controller in
Unoccupied mode
Select Occupied Hold in Schedule hold or
Override to force the Terminal Equipment
Controller Occupied cooling setpoint
Anticycle delay active
Wait, the anticycling period will end and
the equipment will start
Cooling setpoint is
satisfied
Lower the cooling setpoint
Cooling lockout
attained
1. Mode is locked out based on outside air
temperature
2. Change configuration parameter C Lock
to value -40 °F ( -40 °C ) to by-pass
lockout
All models
32 | PIR Ready VT76xxW Series-Installation Guide
Page 33
Wiring error
1. Start the Fan by forcing the Fan ON
mode
2. Put a jumper across terminals RC & Y1.
The cooling should come ON. If it does
not, verify wiring
The Terminal
Equipment
Controller will not
turn on the fan
Wrong mode selected
1. Start the Fan by forcing the Fan ON
mode
2. Put a jumper across terminals RC & G.
The fan should come ON. If it does not,
verify wiring
Wiring error
Digital display
shows missing
digits or erratic
segments
Defective display
Replace Terminal Equipment Controller
33 | PIR Ready VT76xxW Series-Installation Guide
Page 34
SPECIFICATIONS
Terminal Equipment Controller power
requirements:
Operating conditions:
Storage conditions:
Temperature sensor:
Temperate sensor resolution:
Temperature control accuracy:
Contact output rating
Occ, Stand-By and Unocc cooling setpoint range:
Occ, Stand-By and Unocc heating setpoint range:
Room and outdoor air temperature display range:
Proportional band for room temperature control:
Digital inputs:
Wire gauge:
Approximate shipping weight:
Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
19-30 VAC 50 or 60 Hz; 2 VA Class 2
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Local 10 K NTC thermistor
± 0.1 °C ( ± 0.2 °F )
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F )
typical calibrated
Relay output: 30 VAC, 1 Amp.
Maximum, 3 Amp. In-rush.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F )
Cooling & Heating: Default: 1.1°C
( 2°F )
Dry contact across terminal DI1,
DI2
18 gauge maximum, 22 gauge
0.75 lb ( 0.34 kg )
UL: UL 873 (US) and CSA C22.2 No.
24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
FCC: Compliant to CFR 47, Part 15,
Subpart B, Class A (US)
CE : EMC Directive 89/336/EEC
(Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant
(Australia / New Zealand) Supplier
Code Number N10696
FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Please check with your local government for instruction on disposal of this product.
34 | PIR Ready VT76xxW Series-Installation Guide
Page 35
DRAWING &DIMENSIONS
Viconics Technologies Inc.
Tel.:Fax:Toll free:
www.viconics.com
35 | PIR Ready VT76xxW Series-Installation Guide
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.