User configuring instructions menu 11
Local keypad interface 11
Discharge Air Control 27
Specifications 28
Drawing & Dimensions 29
1 | PIR Ready VT7600 Series-Installation Guide
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment
Controller (fig. 1).
Remove wiring terminals from sticker.
Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an
air discharge grill.
4. Should not be affected by direct
sun radiation.
5. Nothing should restrict vertical
air circulation to the Terminal
Equipment Controller.
Installation
1. Swing open the Terminal
Equipment Controller PCB to
the left by pressing the PCB
locking tabs (fig. 2).
2. Pull out cables 6” out from the
wall.
3. Wall surface must be flat and
clean.
4. Insert cable in the central hole
of the base.
5. Align the base and mark the
location of the two mounting
holes on the wall. Install base in
the proper orientation. Arrow on
base should be facing up.
6. Install anchors in the wall.
7. Insert screws in mounting holes
on each side of the base (fig. 2).
8. Gently swing back the circuit
board on the base and push on
it until the tabs lock it.
9. Strip each wire 1/4 inch from
end.
2 | PIR Ready VT7600 Series-Installation Guide
10. Insert each wire according to wiring diagram.
When replacing an existing Terminal Equipment Controller, label the
wires before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
A short circuit or improper wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure
proper and reliable operation in the field. Whenever a control failure
could lead to personal injury and or loss of property, it becomes the
responsibility of the user or installer or electrical system designer to
incorporate safety devices (such as relays, flow switch, thermal
protections, etc…) and or an alarm system to protect the entire system
against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into
the hole in the wall.
14. Install security screw.
THEORY OF OPERATION
The VT76X6F series uses a Viconics proprietary adaptive logic algorithm to control the
space temperature. This algorithm controls the heating and or air conditioning system to
minimize overshoot while still providing comfort. It provides exceptional accuracy due to
its unique PI time proportioning control algorithm, which virtually eliminates temperature
offset associated with traditional, differential-based on/off thermostats.
Fig.2 - On/Off mechanical control vs. PI electronic control.
3 | PIR Ready VT7600 Series-Installation Guide
Features overview
7 day schedule models, 2 or 4 events.
Remote outdoor sensing capability for added flexibility.
- System mode heating and cooling lockout.
-
Remote discharge air sensor input for monitoring and control purpose.
- System efficiency feedback.
- Discharge high limit heating lockout.
- Discharge low limit cooling lockout.
- Minimum supply air temperature.
Remote return air sensor input that replaces internal on board sensor.
Password protected configuration menu and lockable keypads for security.
Two configurable digital input for added flexibility. The input can be configured as the
following:
None: No function will be associated with the input.
Service: a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Filter: a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitors filters.
RemNSB: remote NSB timer clock input. Will disable the internal scheduling of
the Terminal Equipment Controller. The scheduling will now be set as per the
digital input. The menu part related to scheduling is disabled and no longer
accessible. It provides low cost setback operation via occupancy sensor or from
a dry contact.
RemOVR: temporary occupancy contact. Disables all override menu function of
the Terminal Equipment Controller. . The override function is now controlled by a
manual remote momentarily closed contact. When configured in this mode, the
input operates in a toggle mode.
With this function enabled it is now possible to toggle between unoccupied &
occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
Automatic smart fan operation saves energy during unoccupied periods.
Non volatile EEPROM memory prevents loss of parameters during power shortage.
Configurable SPST output relay on scheduling models for lighting, exhaust fan or
fresh air control.
6 hour typical reserve time for clock in case of power loss.
Easy configuration and self-binding operation
Easy configuration without using any special software or additional tools.
Can be used as stand-alone or with BACnet™ MS-TP supervision controller for
monitoring purposed.
Truly scalable in terms of supported number of zones and RTU units.
4 | PIR Ready VT7600 Series-Installation Guide
MODEL CHART
Network ready
All Viconics VT7600 series Terminal Equipment Controllers are designed for
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7600N5000B, Terminal Equipment Controller BACnet™ MS-TP®
communication adapter
o VCM7600N5000W Terminal Equipment Controller wireless Zigbee™
communication adapter
5 | PIR Ready VT7600 Series-Installation Guide
TERMINAL,IDENTIFICATION AND FUNCTION
Terminal Use
Terminal
Identification
Description
1 – Y2 2nd cooling
Y2
Second cooling stage output.
2 – Y1 1st cool
Y1
First cooling stage output.
3 – G Fan
G
Fan output.
4 – RC 24VAC hot
RC
Power supply of thermostat, hot side.
5 – C 24VAC com
C
Power supply of thermostat, common side.
9 – AO analog
heat
AO
Analog 0 – 10 VDC heating output.
10 – Auxiliary
output
AUX
Auxiliary output used to disable economizer
minimum position or control lighting during
unoccupied periods.
11 – DI 1
DI 1
Configurable extra digital input. See
parameter section for more information.
12 – DI 2
DI 2
Configurable extra digital input. See
parameter section for more information.
13 – RS
RS
Remote temperature sensor input.
14 - Scom
Scom
Reference input for DI 1, RS, OS & DS.
15 - OS
OS
Outside air temperature sensor input.
16 - DS
MS
Discharge air temperature sensor input.
Aux
DI1
DI2
RS
SCom
OS
MS
G
Y1
Y2CRC
VT76XXF Controller Terminals
AO
Screw terminal arrangement and wiring
6 | PIR Ready VT7600 Series-Installation Guide
TYPICAL APPLICATIONS
Main outputs wiring
Wiring notes:
Note 1: If the same power source is used for the heating stages, install jumper across RC &
RH. Maximum current is 2.0 amps.
Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside
the equipment, configure the relay parameter (Aux cont) to the N.O. setting. A
second relay can be added for additional functionality of the occupancy output.
Note 3: The analog outputs and inputs use a half bridge rectifier. Reference of the control
signal is the common of the power supply of the Terminal Equipment Controller.
(Terminal C)
Note 4: Electromechanical contacts are to be used with the digital inputs. Electronic triacs
cannot be used as mean of switching for the input. The switched leg to the input for
the input to activate is terminal C (common)
Note 5: The transformer of the unit provides power to the t Terminal Equipment Controller
and the additional loads that will be wired to the Terminal Equipment Controller.
7 | PIR Ready VT7600 Series-Installation Guide
Remote sensor accessories
Model no.
Description
S2020E1000
Outdoor temperature sensor
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
-40
-40
324.3197
-20
-4
94.5149
0 32
32.1910
20
68
12.4601
40
104
5.3467
-39
-38
303.6427
-19
-2
89.2521
1 34
30.6120
21
70
11.9177
41
106
5.1373
-38
-36
284.4189
-18 0 84.3147
2 36
29.1197
22
72
11.4018
42
108
4.9373
-37
-35
266.5373
-17 1 79.6808
3 37
27.7088
23
73
10.9112
43
109
4.7460
-36
-33
249.8958
-16 3 75.3299
4 39
26.3744
24
75
10.4443
44
111
4.5631
-35
-31
234.4009
-15 5 71.2430
5 41
25.1119
25
77
10.0000
45
113
4.3881
-34
-29
219.9666
-14 7 67.4028
6 43
23.9172
26
79
9.5754
46
115
4.2208
-33
-27
206.5140
-13 9 63.7928
7 45
22.7861
27
81
9.1711
47
117
4.0607
-32
-26
193.9703
-12
10
60.3980
8 46
21.7151
28
82
8.7860
48
118
3.9074
-31
-24
182.2686
-11
12
57.2044
9 48
20.7004
29
84
8.4190
49
120
3.7607
-30
-22
171.3474
-10
14
54.1988
10
50
19.7390
30
86
8.0694
50
122
3.6202
-29
-20
161.1499
-9
16
51.3692
11
52
18.8277
31
88
7.7360
51
124
3.4857
-28
-18
151.6239
-8
18
48.7042
12
54
17.9636
32
90
7.4182
52
126
3.3568
-27
-17
142.7211
-7
19
46.1933
13
55
17.1440
33
91
7.1150
53
127
3.2333
-26
-15
134.3971
-6
21
43.8268
14
57
16.3665
34
93
6.8259
54
129
3.1150
-25
-13
126.6109
-5
23
41.5956
15
59
15.6286
35
95
6.5499
55
131
3.0016
-24
-11
119.3244
-4
25
39.4921
16
61
14.9280
36
97
6.2866
56
133
2.8928
-23
-9
112.5028
-3
27
37.5056
17
63
14.2629
37
99
6.0351
57
135
2.7886
-22
-8
106.1135
-2
28
35.6316
18
64
13.6310
38
100
5.7950
58
136
2.6886
-21
-6
100.1268
-1
30
33.8622
19
66
13.0307
39
102
5.5657
59
138
2.5926
Fig.10 – Remote Duct Mounted Temperature Sensor
Remote mount temperature sensors use 10K NTC thermistor.
Temperature vs. Resistance Chart for 10 Kohm NTC Thermistor
(R
= 10K±3% - B
25°C
= 3975K±1.5%)
25/85°C
S2000D1000; remote duct mounted temperature sensor c/w junction box.
This sensor can be used for:
Remote return air temperature
sensing with the sensor
mounted on the return air duct.
Outside air temperature sensing
with the sensor installed in the
fresh air plenum.
Supply air temperature sensing.
S2060A1000; remote averaging duct mounted temperature sensor c/w junction
box.
This sensor can be used for:
Remote averaging return air temperature sensing with the sensor mounted on
the return air duct.
Outside air temperature averaging sensing with the sensor installed in the
8 | PIR Ready VT7600 Series-Installation Guide
fresh air plenum.
Supply air temperature averaging sensor for economizer models with the
WIRING S2000D1000, S2060A1000 and S2020E1000
Remote wiring 1 sensor Remote wiring 4 sensors
CLOCK
STATUS
SYSTEM
MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
Monday
12:00
AM
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
Service
Sys mode
off
Occupied
hold
Frost ON
Sys mode
heat
Unoccup
SetClock
Sys mode
cool
Filter
Fan lock
DAS Alrm
10 K
10 K
10 K
10 K
10 K
Scom
DS
Scom
OS
Scom
RS
or
or
Scom
DS
Scom
OS
Scom
RS
or
or
sensor in the mixing plenum.
S2020E1000; outdoor air temperature sensor
This sensor can be used for:
Outside air temperature sensing with the sensor installed directly exposed to
the elements.
Sensor uses a water resistant NEMA 4 ABS enclosure for outdoor
applications.
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a low
level backlight that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display that
shows the current status of the system.
Each item is scrolled sequentially with the back lighting in low level mode. Pressing any key will
cause the back light to come on to high level.
Manual scrolling of each menu item is achieved by pressing the Yes (scroll) key repetitively.
The last item viewed will be shown on the display for 30 seconds before returning to automatic
scrolling. Temperature is automatically updated when scrolling is held.
Sequence of auto-scroll status display:
9 | PIR Ready VT7600 Series-Installation Guide
Outdoor air temperature
Clock Status
System
Mode
Schedule
Status
Outdoor
Temperature
Alarms
(if detected)
Monday
Sys Mode
Occupied
Outdoor
Service
12:00 AM
Off xx.x °C or °F
DAS Alrm
Sys Mode
Unoccupied
SetClock
Auto Filter
Sys Mode
Cool
Override
Fan lock
Frost ON
Sys Mode
Heat
Frost ON
Indicates that the heating is energized by the low limit frost protection room
temperature setpoint 5.6 °C (42 °F)
SetClock
Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours
Service
Indicates that there is a service alarm as per one of the configurable digital
input (DI1 or DI2)
Filter
Indicates that the filters are dirty as per one of the configurable digital input
(DI1 or DI2)
Fan lock
Indicates that the heating and cooling action are locked out due to a defective
fan operation
DAS
Alarm
Indicates that the discharge air temperature is either too low or too high.
Outdoor air temperature display is only enabled when outdoor air temperature sensor is
connected.
A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.
A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time.
The priority for the alarms is as follows:
Sequence of manual-scroll status display:
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The
last item viewed will be shown on the display for 30 seconds before returning to automatic
scrolling. Temperature is automatically updated when scrolling is held.
10 | PIR Ready VT7600 Series-Installation Guide
When any of the fan is ON, the FAN LED will illuminate
When heating is ON, the HEAT LEDwill illuminate
When cooling is ON, the COOL LED will illuminate
Ex.:
Press yes key to change cooling temperature setpoint
Use the up or down arrow to adjust cooling setpoint
The YES key is used to confirm a selection, to move onto the next menu item
and to manually scroll through the displayed information.
The NO key is used when you do not desire a parameter change, and to
advance to the next menu item. Can also be used to toggle between heating
and cooling setpoints.
The MENU key is used to access the Main User Menu or exit the menu.
The down arrow key is used to decrease temperature setpoint and to adjust
the desired values when configuring the Terminal Equipment Controller.
The up arrow key is used to increase temperature setpoint and to adjust the
desired values when configuring the Terminal Equipment Controller.
USER INTERFACE
User configuring instructions menu
The VT76X6FX series of controllers feature an intuitive,
menu-driven, back-lit LCD display that walks users and
installers through the configuring steps, making the
configuring process extremely simple. This menu is
typically accessed by the user to set the parameters
such as the clock time set, the schedule time events
and the system mode.
It is possible to bring up the user menu at any time by
depressing the MENU key. The status display automatically resumes after exiting the
user-configuring menu.
If the user pauses at any given time during configuring, Auto Help text is displayed to
help and guide the user through the usage and configuring of the controller.
Each of the sections in the menu is accessed and configured using 5 keys on the
controller cover. The priority for the alarms is as follows:
Local keypad interface
11 | PIR Ready VT7600 Series-Installation Guide
When left unattended for 45 seconds, the display will resume automatic status
Override
Resume
System mode
setting
Schedules
setting
Clock setting
Override
schd Y/N
Sys mode
set Y/N
Schedule
set Y/N
Clock
set Y/N
Appears only in
unoccupied mode
Cancel
ovrd Y/N
Appears only in
override mode
Override
schd Y/N
Cancel
ovrd Y/N
display scrolling.
To turn on the back light, press any key on the front panel. The back lit display will
turn off automatically after 45 seconds.
Sequence of user menu:
A) Override an unoccupied period
This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode. The unoccupied mode is enabled either by the internal timer scheduling or by a
remote NSB contact via DI1 or DI2.
If DI1 or DI2 is configured to operate as a remote temporary override contact, this menu
will be disabled.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12 hours).
B) Resume regular scheduling
This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in Unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to resume
the regular setpoints & scheduling.
12 | PIR Ready VT7600 Series-Installation Guide
C) Temperature setpoints
Temperat
set Y/N
COOLING
SETPOINT
OCCUPIED
MODE
HEATING
SETPOINT
OCCUPIED
MODE
COOLING
SETPOINT
UNOCCUPIED
MODE
HEATING
SETPOINT
UNOCCUPIED
MODE
°F OR °C
DISPLAY
SETTING
Cooling
set? Y/N
No next
Yes down
Heating
set? Y/N
No next
Yes down
Unocc CL
set? Y/N
No next
Yes down
Unocc HT
set? Y/N
No next
Yes down
°F or °C
set? Y/N
No next
Yes down
Use ▲▼ keys to set value, Yes key to confirm
Cooling
70.0 °F
Use ▲▼
To set
value
Heating
68.00 °F
Use ▲▼
To set
value
Unocc CL
80.0 °F
Use ▲▼
To set
value
Unocc HT
60.0 °F
Use ▲▼
To set
value
Units
°F
Use ▲▼
To set
value
Sys mode
set Y/N
Sys mode
auto
Automatic mode
Automatic changeover mode between heating and cooling operation
Sys mode
cooling
Cooling mode
Cooling operation mode only
Sys mode
heating
Heating mode
Heating operation mode only
Sys mode
emergency
Emergency heat mode ( heat pump models only )
Forced auxiliary heat operation mode only
Sys mode
off
Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection
at 50 °F ( 10 °C ) is enabled
Permanent setpoint changes
This menu permits the adjustment of all permanent temperature setpoints (occupied and
unoccupied) as well as the desired temperature units (°F or °C). Permanent setpoints are
written to RAM and EEPROM.
Temporary setpoint changes
Temporary setpoints can be modified through the Up arrow key (▲) and the Down arrow
keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the Terminal
Equipment Controller and its setpoint.
The Up (▲) arrow key will increment the setpoint by 0.5 degree (F or C).
The Down (▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Press the Yes key to accept the new setpoint.
Local changes to the heating or cooling setpoints made by the user directly using the up
or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu
D) System mode setting
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to confirm
13 | PIR Ready VT7600 Series-Installation Guide
E) Fan mode setting
Fan mode
set Y/N
Fan mode
On
On fan mode
Fan is on continuously, even when system mode is OFF.
Fan mode
Auto
Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied
periods.
Fan mode
Smart
Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan
cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on
all stand-alone (Network Ready) scheduling models or if DI1 or DI2 is set
to RemNSB on stand-alone non-scheduling models.
Schedule
set Y/N
MONDAY TIMER
SCHEDULE SET
TUESDAY
TIMER
SCHEDULE SET
WEDNESDAY
TIMER
SCHEDULE SET
OTHER DAYS ARE
IDENTICAL
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm
F) Scheduleset (2 events)
Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per
parameter (2/4event)
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specific schedules if needed.
2 events can be scheduled per day.
Occupied & unoccupied periods can be set for each day.
14 | PIR Ready VT7600 Series-Installation Guide
Typical examples of a 2 event office schedule:
Event
Period #1 - Event #1
Period #1 - Event #2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
7.00 AM
6.00 PM
Day time only
Tuesday
7.00 AM
6.00 PM
Day time only
Wednesday
7.00 AM
6.00 PM
Day time only
Thursday
7.00 AM
6.00 PM
Day time only
Friday
7.00 AM
6.00 PM
Day time only
Saturday
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
Unoccupied
Event
Period #1 - Event
#1
Period #1 - Event
#2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
8.00 AM
5.00 PM
Day time only
Tuesday
8.00 AM
5.00 PM
Day time only
Wednesday
8.00 AM
5.00 PM
Day time only
Thursday
8.00 AM
5.00 PM
Day time only
Friday
8.00 AM
5.00 PM
Day time only
Saturday
12.00 AM **
11.59 PM **
Occupied
Sunday
12.00 AM **
11.59 PM **
Occupied
Note: 12:00 PM = Noon
Ex. #1 Office building closed all weekend
* Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the
above example, the Terminal Equipment Controller will control to the unoccupied set
point until 7:00 AM Monday.
Ex. #2 Commercial building which is occupied all weekend
** To schedule a day as occupied for 24 hours, set that day occupied time to 12:00 AM
and Unoccupied time to 11:59 PM There will be a 1 minute unoccupied period every
night at 11:59 PM with this schedule configuration.
15 | PIR Ready VT7600 Series-Installation Guide
G) Schedule set (4 events)
Schedule
set Y/N
Monday timer
Schedule set
Tuesday timer
Schedule set
Wednesday timer
Schedule set
Other days are identical
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied
setpoints
Use ▲▼ to set value, Yes key to confirm
Occupie2
00:00 AM
Use ▲▼
To set
value
Occupie2
00:00 AM
Use ▲▼
To set
value
Occupie2
00:00 AM
Use ▲▼
To set
value
Sets Event # 3 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup2
00:00 AM
Use ▲▼
To set
value
Unoccup2
00:00 AM
Use ▲▼
To set
value
Unoccup2
00:00 AM
Use ▲▼
To set
value
Sets Event # 4 Unoccupied time
Will activate unoccupied
setpoints
Use ▲▼ to set value, Yes key to confirm
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each
day can be tailored to specific schedules if needed.
4 events can be scheduled per day.
Occupied & Unoccupied periods can be set for each day.
Scheduling the 3rd. & 4th. Events to the same time will cancel the last period.
16 | PIR Ready VT7600 Series-Installation Guide
Ex. #1 Four event retail establishment schedule
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72°F
70°F
80°F
62°F
72°F
70 °F
80°F
62 °F
Occupancy
Monday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Tuesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Wednesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Thursday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Friday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Saturday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72°F
70°F
80°F
62°F
72°F
70°F
80°F
62°F
Occupancy
Monday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Tuesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Wednesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Thursday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Friday
6:00 AM
8:00 AM
4:00 PM
11:30 PM
Day/evening
time only
Saturday
8:00 AM *
8:00 AM *
8:00 AM *
11:59 PM *
Day time
only
Sunday
12:00 AM *
12:00 AM *
12:00 AM *
11:59 PM *
Occupied all
day
* Scheduling events to the same time will cancel the last period and leave the Terminal
Equipment Controller in unoccupied mode
Ex. #2 Residential
* Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the above
example for Saturday, the Terminal Equipment Controller will control to the occupied set
point from 8:00 AM until 11:59 PM. Since it is desired to be in occupied mode throughout
the night, then it is necessary to schedule the first event on Sunday at 12:00 AM. The
Terminal Equipment Controller will force a one minute unoccupied period for a one minute
period (between 11:59 PM and 12:00 AM on Saturday).
17 | PIR Ready VT7600 Series-Installation Guide
H) Clock/Day Settings
Clock
set Y/N
Time setting
Day setting
Time format setting
Time
set? Y/N
No next
Yes down
Day
set? Y/N
No next
Yes down
12/24hrs
set? Y/N
No = exit
Yes down
Time
0:00
Use ▲▼
To set value
Day
Monday
Use ▲▼
To set value
12/24hrs
12 hrs
Use ▲▼
To set value
Schedule
hold Y/N
This section of the menu permits the user to set the time and day.
J) Schedule hold
This menu will only appear on stand-alone (Network Ready) Terminal
Equipment Controller, i.e. without a BACnet™ / Echelon™ module.
This section of the menu permits the user to set a permanent schedule
hold, which bypasses the internal Terminal Equipment Controller
scheduling.
The permanent schedule hold function is typically used for non-
scheduled events that extend for various periods of time.
Enabling a permanent occupied or permanent unoccupied schedule hold
will cancel any active override.
The use of temporary setpoints during permanent hold is permitted. The
duration of the temporary setpoint is as set per the TOccTime parameter.
Ex. 3 hours
Use ▲▼ to set value, yes key to confirm
18 | PIR Ready VT7600 Series-Installation Guide
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value = 0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Com addr Thermostat
networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models
(VT76xxX5x00B)
Conditional parameter to Wireless models
(VT76xxX5x00W)
This parameter will only appear when a BACnet or
wireless network adapter is present. If the thermostat is
installed as a stand-alone unit or with an Echelon
adapter, this parameter will not be used or displayed
- For BACnet MS-TP models valid range to use is
from 1 to 127. Default value of 254 disables BACnet
communication for the thermostat.
- For wireless models valid range is 0 to 254 with a
maximum of 30 thermostat per VWG
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 1000
Conditional parameter to Wireless models
(VT76xxX5x00W)
This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone (Network
Ready) unit or with a BACnet™ or Echelon™ adapter,
this parameter will not be used or displayed
This parameter (Personal Area Network Identification)
is used to link specific Terminal Equipment Controllers
to a single specific Viconics wireless gateway ( VWG )
For every Terminal Equipment Controller reporting to
a gateway ( maximum of 30 Terminal Equipment
Controllers per gateway ), be sure you set the SAME
PAN ID value both at the gateway and the Terminal
Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.
19 | PIR Ready VT7600 Series-Installation Guide
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models
(VT76xxX5x00W)
This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone (Network
Ready) unit or with a BACnet™ or Echelon™ adapter,
this parameter will not be used or displayed
This parameter (Channel) is used to link specific
Terminal Equipment Controllers to specific Viconics
wireless gateway(s) (VWG) For every Terminal
Equipment Controller reporting to a gateway
(maximum of 30 Terminal Equipment Controllers per
gateway), be sure you set the SAME channel value
both at the gateway and the Terminal Equipment
Controller(s).
Viconics recommends using only the usage of
channels 15 and 25 only.
The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26
20 | PIR Ready VT7600 Series-Installation Guide
DI 1
Digital input no.1 configuration
Open contact input = function
not energized
Closed contact input = function
energized
Default value = None
None, No function will be associated with the input
Rem NSB, remote NSB timer clock input. Will disable the
internal scheduling of the thermostat. The scheduling will
now be set as per the digital input. The time is still
displayed as information, but the menu part related to
scheduling is disabled and no longer accessible.
all override menu function of the thermostat. The override
function is now controlled by a manual remote
momentarily closed contact. When configured in this
mode, the input operates in a toggle mode. With this
function enabled it is now possible to toggle between
unoccupied & occupied setpoints for the amount of time
set by parameter (TOccTime) temporary occupancy time.
When Override is enabled, an Override status message
will be displayed
Filter, a back-lit flashing Filter alarm will be displayed
on the thermostat LCD screen when the input is
energized
Service, a back-lit flashing Service alarm will be
displayed on the thermostat LCD screen when the
input is energized
Fan lock, a back-lit flashing Fan lock alarm will be
displayed on the thermostat LCD screen when the input is
not energized. Used in conjunction with a local airflow
sensor connected to the input. Locks out the thermostat
heating and cooling action if no airflow is detected 10
seconds after the fan ( G terminal ) is energized.
Open contact = no airflow
Closed contacts = airflow present
DI 2
Digital input no.2 configuration
Open contact input = function
not energized
Closed contact input = function
energized
Default value = None
Same as above. It is possible to configure both inputs to
have the same function.
MenuScro
Menu scroll
Default value = On = Scroll
active
Removes the scrolling display and only present the room
temperature/humidity to the user. With this option
enabled, no status is given of mode, schedule and
outdoor temperature.
On = Scroll active
Off = Scroll not active
21 | PIR Ready VT7600 Series-Installation Guide
Lockout Keypad lockout levels
Default value = 0 No lock
0 = No lock
1 = Low level
2 = High level
USER KEY FUNCTIONS
LEVEL
Resume/
Override scheduling
Permanent Occupied and
Unoccupied Setpoints
Temporary setpoints using
arrows
System mode setting
Fan mode setting
Schedules setting
Clock setting
Permanent hold
0
1
2
pwr del
Power-up delay
Default value = 10 seconds
On initial power up of the Terminal Equipment Controller
(each time 24 VAC power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds
Frost pr
Frost protection enabled
Default value = Off
Off: no room frost protection
On: roomfrost protection enabled in all system mode at:
42 °F ( 5.6 °C )
Frost protection is enabled even in system Off mode
Off or On
On heat pump models the system mode will be forced to
EMERGENCY mode if frost protection is activated
heat max
Maximum heating setpoint
limit
Default value = 90 °F (32 °C )
Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 2 °C )
Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
22 | PIR Ready VT7600 Series-Installation Guide
Pband
Proportional Band setting
Default value 2 = 2.0 °F ( 0.6 °C )
Adjust the proportional band used by the Terminal
Equipment Controller PI control loop.
Note that the default value of 2.0 °F ( 1.1 °C )
gives satisfactory operation in most normal
installation cases. The use of a superior
proportional band different than the factory one is normally
warranted in applications where the Terminal Equipment
Controller location is problematic and leads to unwanted
cycling of the unit. A typical example is a wall mounted
unit where the Terminal Equipment Controller is installed
between the return and supply air feeds and is directly
influenced by the supply air stream of the unit.
Value F scale
Pband
C scale
Pband
2
2 F
1.1 C
3
3 F
1.7 C 4 4 F
2.2 C
5
5 F
2.8 C
6
6 F
3.3 C 7 7 F
3.9 C
8
8 F
4.4 C
Anticycle
Minimum on/off operation
time for stages
Default value = 2 minutes
Minimum On/Off operation time of cooling & heating
stages.
IMPORTANT, anti-short cycling can be set to 0 minutes for
equipment that posses their own anti cycling timer. Do not
use this value unless the equipment is equipped with such
internal timer. Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes
Anti-short cycling can be set to 0 minutes for equipment
that posses their own anti cycling timer. Do not use that
value unless the equipment is equipped with such internal
timer. Failure to do so can damage the equipment.
Min SH
Minimum supply heat
temperature setpoint
Default value = 64 °F (18 °C)
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or Temporary
Override).
From 50 °F up to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)
23 | PIR Ready VT7600 Series-Installation Guide
cool cph
Cooling stages cycles per hour
Default value = 4 C.P.H.
Will set the maximum number of cooling stage cycles per
hour under normal control operation. It represents the
maximum number of cycles that the equipment will turned
on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy
of control at the expense of wearing mechanical
components faster.
3 or 4 C.P.H.
For multi stage models, cool cph applies to Y1 & Y2
For heat pump models, cool cph applies to Y1 & Y2 in
cooling and heating independently of the reversing
valve position
deadband
Minimum deadband
Default value = 2.0 °F (1.1 °C)
Minimum deadband value between the heating and
cooling setpoints. If modified, it will be applied only
when any of the setpoints are modified.
2, 3 or 4 °F ( 1.0 to 2.0 °C )
fan cont
Fan control
Default value = On
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller
in all cases will always control the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating
stages (terminals W1 & W2) are solicited, will not be
energized. The fan in this case will be controlled by the
equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave
the fan always on.
ON OR OFF
For multi stage models, fan control applies to W1 &
W2
For heat pump models, fan control applies to W1
only (Emergency heat)
fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds after
the call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will leave
the fan always on.
Off or On
ToccTime
Temporary occupancy time
Default value = 3 hours
Temporary occupancy time with occupied mode
setpoints when override function is enabled
When the Terminal Equipment Controller is in
unoccupied mode, function is enabled with either the
menu or DI1 or DI2 configured as remote override
input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours
Cal RS
Room air temperature sensor
calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual displayed
room temperature
± 5.0 °F ( ± 2.5 °C )
24 | PIR Ready VT7600 Series-Installation Guide
Cal OS
Outside air temperature sensor
calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual displayed
outside air temperature
± 5.0 °F ( ± 2.5 °C )
SH lock
Outside air temperature supply
heat lockout
Default value = 32 °F (0 °C)
Disables heating operation based on outdoor air
temperature.
Please refer to the Viconics Zoning System Guide for
recommended settings.
From –15 °F up to 120 °F (-26 °C up to 49 °C)
(increments: 5° or 50°)
C stage
Number of cooling stages
Default value = 2 stages
Will revert the operation of 2 stage Terminal Equipment
Controller to single stage operation only when the
second cooling step is not needed.
1 or 2 stages
H lock
Outside air temperature heating
lockout
Default value = 120 °F ( 49 °C )
Disables heating stage operation based on outdoor air
temperature.
Function will only be enabled if OS (outside air
temperature sensor) is connected.
From -15 °F up to 120 °F ( -26 °C up to 49 °C )
C lock
Outside air temperature
mechanical cooling lockout.
Default value = -40 °F ( -40 °C )
Disables cooling stage operation based on outdoor air
temperature.
On economizer model, free cooling will not be disabled
by this function.
Function will only be enabled if OS (outside air
temperature sensor) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
Unocc TM
Unoccupied Timer value
Default 0.5 hours
Time delay between the moment where the Terminal
Equipment Controller toggles from occupied to
unoccupied after the last movement has been detected
by the PIR.
Range is: 0.5 to 24.0 hours in 0.5 hour increments
2/4event
Number of events configuration
Default value = 2 event
2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
25 | PIR Ready VT7600 Series-Installation Guide
aux cont
Auxiliary contact configuration
Default value = N.O. normally open
This contact can be used to energize peripheral devices
such as: lighting equipment, exhaust fans,
economizers, etc.
This contact will operate in parallel with the internal
occupied/unoccupied schedule of the Terminal
Equipment Controller or the remote NSB contact if DI1
or DI2 is used.
When the system is in OFF mode, the contact will
remain in its unoccupied status independently of the
occupied / unoccupied schedule.
Configured
Contact
occupied
status
Contact
unoccupied
status
N.O.
Closed
Opened
N.C.
opened
Closed
Prog rec
Progressive recovery enabled
Default value = Off
Progressive recovery is
automatically disabled if DI 1 and
/ or DI 2 are configured remote
NSB
Off, = no progressive recovery
The occupied schedule time is the time at which the
system will restart.
On, = progressive recovery active.
The occupied schedule time is the time at which the
desired occupied temperature will be attained. The
Terminal Equipment Controller will automatically
optimize the equipment start time.
In any case, the latest a system will restart is 10
minutes prior to the occupied period time.
Dis HL
Discharge air temperature high
limit
Default: 120°F
Discharge air high temperature value at which the
heating output will be locked out.
70°F to 150°F (21°C to 65°C)
(increments: 0.5° or 5°)
Dis LL
Discharge air temperature low
limit
Default: 45°F
Discharge air low temperature value at which the
cooling stages will be locked out.
35°F to 65°F (2.0°C to 19.0°C)
(increments: 0.5° or 5°)
MS dis
Display mixed air temperature
Economizer model only, only if
sensor is installed
Used as diagnostic / service help to troubleshoot and
diagnose economizer operation.
26 | PIR Ready VT7600 Series-Installation Guide
DISCHARGE AIR CONTROL
The Viconics VT7600F controller has the ability to maintain a minimum heating supply
temperature by using an analog 0-10VDC proportional output instead of using the staging
outputs which will cause the unit to cycle. Using a full proportional output to maintain the
minimum heating supply temperature can increase cost savings and less wear and tear
on HVAC equipment.
The desired minimum setpoint temperature value can be set under the Min SH parameter
and the following conditions must apply:
- The system mode is heating.
- The occupancy mode is in Occupied or Temporary Override.
- The OA temperature value is below SH lockout parameter value.
27 | PIR Ready VT7600 Series-Installation Guide
SPECIFICATIONS
Terminal Equipment Controller power
requirements:
Operating conditions:
Storage conditions:
Sensor:
Resolution:
Temperature control accuracy:
Contact output rating
Occ, Stand-By and Unocc cooling setpoint range:
Occ, Stand-By and Unocc heating setpoint range:
Room and outdoor air temperature display range:
Digital inputs:
Analog outputs rating (BPD & AO)
Analog outputs accuracy (BPD & AO)
Wire gauge:
Approximate shipping weight:
Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
19-30 VAC 50 or 60 Hz; 2 VA Class 2
RC to RH jumper 2.0 Amps 48VA max.
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Local 10 K NTC thermistor
± 0.1 °C ( ± 0.2 °F )
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F )
typical calibrated
Relay outputs: 30 VAC, 1 Amp.
Maximum, 3 Amp. In-rush.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F )
Dry contact across terminal DI1
0 to 10 VDC into 2K resistance min
± 3% typical
18 gauge maximum, 22 gauge
0.75 lb ( 0.34 kg )
UL: UL 873 (US) and CSA C22.2 No.
24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
FCC: Compliant to CFR 47, Part 15,
Subpart B, Class A (US)
CE : EMC Directive 2004/108/EC
(Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant
(Australia / New Zealand) Supplier
Code Number N10696
FCC: Compliant to: Part 15, Subpart B,
Class (US)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION
Please check with your local government for instruction on disposal of this product
28 | PIR Ready VT7600 Series-Installation Guide
DRAWING &DIMENSIONS
Viconics Technologies Inc.
Tel.:Fax:Toll free:
www.viconics.com
29 | PIR Ready VT7600 Series-Installation Guide
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.