The VT7600 PI thermostat family is specifically designed for single stage
and multi-stage control of heating/cooling equipment such as rooftop and
self-contained units. The product features an intuitive, menu-driven, back-lit
LCD display which walks users through the programming steps, making the
process extremely simple. Accurate temperature control is achieved due to
the product’s PI time proportional control algorithm, which virtually eliminates
temperature offset associated with traditional, differential-based thermostats.
All models contain two digital inputs, which can be set by the user to monitor
filter status, activate a remote temporary occupancy switch, and/or used as
a general purpose service indicator. In addition, depending on the model, up
to three remote sensor inputs are available. All models contain a SPST
auxiliary switch, which can be used to control lighting or disable the
economizer function and a discharge air sensor input. For more advanced
applications, an economizer control logic has been integrated onto the
thermostat for use with proportional damper economizer actuators.
The additional following documentation is available on www.viconics.com
• Information on the LON models (VT76xxX1000E), is available on document ITG-VT7600-LON-Exx
• Information on the BACnet models (VT76xxX1000B), is available on document ITG-VT7600-BAC-Exx
• Information on the Wireless models (VT76xx0X1000W), is available on documents: ITG-VWG-40-BAC-
Exx and LIT-VWG-40-SETUP-Exx
Models available
Model (programmable) VT7652A1000 VT7652B1000 VT7656B1000 VT7652H1000
Model (non-programmable) VT7600A1000 VT7600B1000 VT7605B1000 VT7600H1000
Features and benefits
Application 1 Heat / 1 Cool 2 Heat / 2 Cool
2 Heat / 2 Cool
with economizer
3 Heat / 2 Cool
heat pump
FeaturesBenefits
• PI time proportioning algorithm ⇒ Increased comfort , accuracy, and energy savings
• Economizer output (0-10 V d.c.) (on economizer models
⇒ Increase flexibility and functionality
⇒ Can be used for all types of establishments
⇒ Excellent retrofit opportunities
• Low/High balance point (on heat pump models onl
• 3 Heat/2 Cool (on heat pump models only) ⇒ Support single and two stages heat pump with one
⇒ Protect and optimize systems performances
auxiliary heat stage
028-0132R8_LIT-VT7600-E08.doc
www.viconics.com / sales@viconics.com
Theory of operation
The VT7600 uses a Viconics proprietary adaptive
logic algorithm to control the space temperature. This
algorithm controls the heating / air conditioning system
to minimize overshoot while still providing comfort. It
provides exceptional accuracy due to its unique PI
time proportioning control algorithm, which virtually
eliminates temperature offset associated with
traditional, differential-based on/off thermostats.
Fig.2 - On/Off mechanical control vs PI electronic control.
Features overview
• 7 day programmable models, 2 or 4 events
• Gas/oil or electric system compatibility for all type
of applications
• Remote indoor averaging sensing capability
• Temperature averaging with 2, 3, 4, 9 or 16
sensors
• Remote outdoor sensing capability for added
flexibility
- System mode lock out
- Heat pump balance point settings
• Remote discharge air sensor input for monitoring
purpose
- System efficiency feedback
• Lockable keypads for tamper proofing. No need for
thermostat guards
• Automatic frost protection to prevents costly freeze
damage
• Anti short cycle and minimum on/off run time
protection. Reduces wear and maximizes life span
of mechanical equipment.
• 2 programmable digital inputs for added flexibility.
Each input can be programmed as the following:
- None: No function will be associated with the
input
- Service: a backlit flashing Service alarm will be
displayed on the thermostat LCD screen when
the input is energized. It can be tied in to the AC
unit control card, which provides an alarm in
case of malfunction.
- Filter: a backlit flashing Filter alarm will be
displayed on the thermostat LCD screen when the
input is energized. It can be tied to a differential
pressure switch that monitor filters
- Rem NSB: remote NSB timer clock input. Will
disable the internal scheduling of the thermostat.
The scheduling will now be set as per the digital
input. The menu part related to scheduling is
disabled and no longer accessible. It provides low
cost setback operation via occupancy sensor or
from a dry contact
- RemOVR: temporary occupancy contact. Disables
all override menu function of the thermostat. . The
override function is now controlled by a manual
remote momentarily closed contact. When
configured in this mode, the input operates in a
toggle mode.
With this function enabled it is now possible to
toggle between unoccupied & occupied setpoints
for the amount of time set by parameter
(TOccTime) temporary occupancy time.
• Programmable smart fan operation saves
energy during night mode
• Non volatile EEPROM memory prevents loss of
parameters during power shortage
• Built in default profile set-up for easier start up
and commissioning
• Configurable SPST output relay on
programmable models for lighting, exhaust fan
or fresh air control
• 6 hour typical reserve time for clock in case of
power loss
• 0 to 10 Vdc economizer output for more retrofit
opportunities
- Built in dry bulb economizer logic using
outdoor temperature sensor
- Input for supply/mixed air temperature sensor
Heat pump model specific features
• Selectable single or dual stage compressor
stages
• High balance point:
Locks out auxiliary heating when outside air
temperature is above this value
• Low balance point:
Locks out heat pump compressor operation
when outside air temperature is below this value
• Comfort/economy mode:
In economy mode, heat pump use is maximized
before turning On auxiliary heating
• Compressor/auxiliary interlock:
Adds flexibility by locking out heat pump
operation during auxiliary heating to prevent high
pressure trip when the coil is downstream of the
auxiliary heat source.
2
Installation
3
• Remove security screw on the bottom of thermostat cover.
• Open up by pulling on the bottom side of thermostat.
• Remove Assembly and remove wiring terminals from sticker. (Fig. 3)
• Please note the FCC ID and IC label installed in the cover upon
removal of cover for the wireless products.
A) Location:
1- Should not
be installed on an outside wall.
2- Must be installed away from any heat source.
3- Should not be installed near an air discharge grill.
4- Should not be affected by direct sun radiation.
5- Nothing must restrain vertical air circulation to the thermostat.
B) Installation:
1- Swing open the thermostat PCB to the left by pressing the PCB
locking tabs. (Fig. 4)
2- Pull out cables 6” out of the wall.
3- Wall surface must be flat and clean.
4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two mounting holes
on the wall. Install proper side of base up.
6- Install anchors in the wall.
7- Insert screws in mounting holes on each side of the base.
(Fig. 4)
8- Gently swing back the circuit board on the base and push on it
until the tabs lock it.
10- Strip each wire 1/4 inch.
11- Insert each wire according to wiring diagram.
13- Gently push back into hole excess wring (Fig. 5)
14- Re-Install wiring terminals in correct location. (Fig. 5)
15- Reinstall the cover (top side first) and gently push back extra
wire length into the hole in the wall.
16- Install security screw.
• If replacing an old thermostat, label the wires before
removal of the old thermostat.
• Electronic controls are static sensitive devices.
Discharge yourself properly before manipulation and
installing the thermostat.
• Short circuit or wrong wiring may permanently damage
the thermostat or the equipment.
• Anti-short cycling can be set to 0 minutes for equipment
that posses their own anti cycling timer. Do not use that
value unless the equipment is equipped with such
internal timer. Failure to do so can damage the
equipment.
• All VT7600 series thermostats are to be used only as
operating controls. Whenever a control failure could
lead to personal injury and/or loss of property, it
becomes the responsibility of the user to add safety
devices and/or alarm system to protect against such
catastrophic failures.
Fig.3
Fig.4
Fig.5
Location of PCB retaining tabs
Re-install terminal blocks
Thermostat assembly
(VT7300F1000 shown)
Fig.6
p
Y2Y
Wiring
4
Terminal identification
Multistage 1H / 1CHeat Pum
Part Number VT7656B VT7605B VT7652B VT7600B VT7652A VT7600A Part Number VT7652H VT7600H
Programmable Yes No Yes No Yes No Programmable Yes No
Top left terminal block Top left terminal block
Y2 X X X X Y2 X X
Y1 X X X X X X Y1 X X
G X X X X X X G X X
RC X X X X X X RC X X
C X X X X X X C X X
Top right terminal block Top right terminal block
RH X X X X X X RH X X
W1 X X X X X X W1 X X
W2 X X X X O/B X X
Bottom terminal block Bottom terminal block
Econo X X
Aux X X X X X X Aux X X
DI1 X X X X X X DI1 X X
DI2 X X X X X X DI2 X X
RS X X X X X X RS X X
Scom X X X X X X Scom X X
OS X X X X X X OS X X
MS X X X X X X MS X X
Screw terminal arrangement
5 pole left top connector
3 pole left top connector
1GRC C
RH W1
W2
O/B
8 pole bottom connector
EC AU
D1
D2 RS
Scom
OS MS
Wiring notes:
Note 1: If the same power source is used for the heating stages, install jumper across RC & RH. Maximum current is 2.0
Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure the
Note 3: Economizer output uses a half bridge rectifier. Reference of the control signal is the common of the power supply
Note 4: Electromechanical contacts are to be used with the digital inputs. Electronic triacs cannot be used as mean of
Note 5: The transformer of the unit provides power to the thermostat and the additional loads that will be wired to the
amps.
relay parameter (Aux cont ) to the N.O. setting. A second relay can be added for additional functionality of the
occupancy output.
of the thermostat. (terminal C)
switching for the input. The switched leg to the input for the input to activate is terminal C ( common )
Thermostat internal wiring
System wiring
Jumper J1
Fan
Cool
24 Vac
T1
VT7652H1000
Heat pump / Programmable
Heat
Stage 1
Heat
Stage 2
0-10 Vdc
Com24V
Auxiliary
Output
Remote
Room
Sensor
Remote
Outdoor
Sensor
Field contacts
Thermostat Terminals - VT7652H1000
Y2
Y1RCG
DI1 DI2AU
C
RH
Scom
OSRS
Remote
Mixed Air
Sensor
W1
MS
O/B
Digital Input #1
Digital Input #2
ScomRS
Remote
Room
Sensor
Field contacts
Remote
Outdoor
Sensor
MSOS
Remote
Mixed Air
Sensor
Y2
Compressor
Stage 2
Y1
Compressor
Stage 1
Thermo stat internal wiring
System wiring
Jumper J1
G
Fan
Jumper J1
See note 1
(previous
page)
RCCRH
24 Vac
T1
W1
Auxiliary
Heat
O/BAU
Reversing
Valve
DI1DI2
Auxiliary
Output
r
Remote sensor accessories
Model no. Description
S3010W1000 Wall mounted temperature sensor
S3020W1000 Wall mounted temperature sensor with override button and occupancy status LED
S2020E1000 Outdoor temperature sensor
S2060A1000 Averaging temperature sensor
S2000D1000 Duct mounted temperature sensor
Remote mount temperature sensors use 10K NTC thermistors.
• This sensor can be used for:
• 3 thermistors with 2 dip switches are provided with each sensor for various
averaging combinations
• Optional occupancy led
• Optional override key
Wiring example of single remote room sensor:
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
1x S3020W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
ScomRSScom
RS
Aux
C
DI
S3010W1000
Remote wiring 1 sensor
S2-1 = ON / S2-2 = ON
OR
ScomRSScom
RS
Fig.8 – S3020W1000
wall mounted sensor
ON
2
1
S2-1 = ON
S2-2 = ON
Dip switch
setting for:
1 senso
6
Wiring examples of 2 remote room sensors for averaging applications:
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
2x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
ScomRSScom
RS
Aux
C
DI
ScomRSScom
RS
Aux
C
DI
1x S3010W1000 and 1x S3020W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
ScomRSScom
RS
Aux
C
DI
ScomRSScom
RS
Notes for averaging applications:
• S3010W1000 and S3020W1000 can be
• S3010W1000 and S3020W1000 are to
• Respect the dip switch setting in each
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
mixed matched.
be wired in parallel.
remote sensor.
Wiring examples of 3 remote room sensors for averaging applications:
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
2x S3010W1000 and 1x S3020W1000
Remote wiring 3 sensors
S2-1 = OFF / S2-2 = OFF
ScomRSScom
RS
Aux
C
DI
ScomRSScom
RS
ScomRSScom
RS
VT7600 Series
Thermostat
Scom
RS
AU
C
D1
D2
1x S3010W1000 and 2x S3020W1000
Remote wiring 3 sensors
S2-1 = OFF / S2-2 = OFF
ScomRSScom
RS
Aux
2x S3010W1000
Remote wiring 2 sensors
S2-1 = OFF / S2-2 = ON
ScomRSScom
RS
ScomRSScom
RS
Dip switch
setting for:
2 sensors
ScomRSScom
RS
Aux
C
DI
C
DI
ScomRSScom
RS
Dip switch
setting for:
3 sensors
ON
2
1
ON
1
S2-1 = OFF
S2-2 = ON
S2-1 = OFF
-
2
=
Temperature vs resistance chart for 10 Kohm NTC thermistor