Viconics VT7200 F 5000 E, VT7200 Series, VT7200 C 5000 E, VT7200 F 5500 E, VT7200 C 5500 E Installation Manual

...
Page 1
1 | PIR Ready VT7200 Series-Installation Guide
CONTENTS
Installation 2
Location 2 Installation 2
Configurable BI/UI inputs overview 3 Model Chart 5
Network ready 6
Terminal, Identification and Function 6
Wiring 7 Main outputs wiring 7 Typical applications 8 Remote sensor accessories 12
Configuring and Status Display Instructions 13
Status display 13
User Interface 15
Local keypad interface 15 Occupied setpoints adjustments 16 Unoccupied and stand-by setpoints adjustments 16 Mode button menu sequence 16 System mode function 16
Installer Configuration Parameter Menu 16
Configuration interface 17
Specifications 28 Drawing & Dimensions 29
PIR Ready VT7200 Series 24 VAC Low Voltage
Zoning Terminal Equipment Controller
Installation Guide
For Commercial HVAC Applications
May 3rd, 2012 / 028-0190-R8
Page 2
2 | PIR Ready VT7200 Series-Installation Guide
INSTALLATION
Remove the security screw on the bottom of Terminal Equipment Controller cover.
Open unit by pulling on the bottom side
of Terminal Equipment Controller (fig.
1).
Remove wiring terminals from sticker.  Please read the FCC ID and IC label
installed in the cover upon removal of cover for the wireless products.
Location
1. Should not be installed on an outside wall.
2. Must be installed away from any direct heat source.
3. Should not be installed near an air discharge grill.
4. Should not be affected by direct sun radiation.
5. Nothing should restrict vertical air circulation to the Terminal Equipment Controller.
Installation
1. Swing open the Terminal Equipment Controller PCB to the left by pressing the PCB locking tabs (fig.
2).
2. Pull out cables 6” out from the wall.
3. Wall surface must be flat and clean.
4. Insert cable in the central hole of the base.
5. Align the base and mark the location of the two mounting holes on the wall. Install proper side of base up.
6. Install anchors in the wall.
7. Insert screws in mounting holes on each side of the base (fig. 2).
8. Gently swing back the circuit board on the base and push on it until the tabs lock it.
9. Strip each wire 1/4 inch from end.
10. Insert each wire according to wiring diagram.
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
Page 3
3 | PIR Ready VT7200 Series-Installation Guide
13. Re-install the cover (top side first) and gently push extra wire length back into the hole in the wall.
14. Install security screw.
CONFIGURABLE BI/UI INPUTS OVERVIEW
Binary input #1 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Rem NSB): remote NSB timer clock input. The scheduling will now be set as
per the binary input. It provides low cost setback operation via a dry contact Contact opened = Occupied Contact closed = Unoccupied
3. (Motion NO) and (Motion NC): Advanced PIR occupancy functions using a Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor. Occupancy mode is now set as per applied PIR function and configuration. Application information and examples are available on document: APP-PIR- Guide-Exx. This document will provide the installers and system designers with detailed examples on applications, parameter configuration information, sequence of operation, troubleshooting and diagnostic help required for the proper usage of the PIR accessory covers
4. (Window) EMS: Forces the system to disable any current heating or cooling action by the Terminal Equipment Controller. The mode stays the same and the current setpoints are the same occupied setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the Terminal Equipment Controller to indicate to the local tenant that the door/window needs to be closed for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm Contact closed = System enabled
If replacing an existing Terminal Equipment Controller, label the wires
before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
Page 4
4 | PIR Ready VT7200 Series-Installation Guide
Binary input #2 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector: This configuration is only functional if binary input #1 is set to Motion NO or Motion NC or a PIR accessory cover is used. With this sequence enabled, the occupancy is now dictated through those 2 inputs. Any motion detected will set the zone to occupied status. The zone will remain permanently in occupied mode until the door contact switch opens momentarily. The Terminal Equipment Controller will then go in stand-by mode. If more movements are detected, the occupied mode will resume. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed contact switching device.
Contact opened = Door opened Contact closed = Door closed
3. (RemOVR): temporary occupancy remote override contact. This function disables the central button override function on the Terminal Equipment Controller. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode. It is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time.
4. (Filter): a backlit flashing Filter alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
Contact opened = No alarm Contact closed = Alarm displayed
5. (Service): a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold air / water change over switching in 2 pipe systems.
Contact closed = Cold air / water present Contact opened = Hot air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold air / water change over switching in 2 pipe systems.
Contact closed = Hot air / water present Contact opened = Cold air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
Page 5
5 | PIR Ready VT7200 Series-Installation Guide
4. (COS) Change over analog sensor: Used for hot / cold air / water change over switching in 2 pipe systems.
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
If temperature is > 77 °F = Hot air / water present If temperature is < 75 °F = Cold air / water present
5. (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
Only used for network reporting of the supply air temperature. Has no internal function in the Terminal Equipment Controller.
MODEL CHART
Page 6
6 | PIR Ready VT7200 Series-Installation Guide
Network ready
All Viconics VT7200 series Terminal Equipment Controllers are designed for
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7300V5000B, Terminal Equipment Controller BACnet™ MS-TP
communication adapter
o VCM7300V5000E, Terminal Equipment Controller Echelon™ Lontalk™
communication adapter
o VCM7000V5000W Terminal Equipment Controller wireless
communication adapter
TERMINAL, IDENTIFICATION AND FUNCTION
Viconics Part Numbers VT7200C5x00(x) Viconics number VT7200F5x00(x)
Description / Application 1 or 2 Floating outputs Description / application 1 or 2 Analog outputs
1 or 2 On/Off outputs
4- 24 V~ Hot 24 V~ Hot 4- 24 V~ Hot 24 V~ Hot
5- 0 V~ Com 24 V~ Com 5- 0 V~ Com 24 V~ Com
6- Aux BO 5 BO 5-Aux 6- Aux BO 5 BO 5-Aux
7- Aux BO 5 BO 5-Aux 7- Aux BO 5 BO 5-Aux
8- BO 3 Open Heat BO 3
9- BO 4 Close Heat BO 4 9- AO 2 Heat AO 2
10- BO 1 Open Cool BO 1 10- AO 1 Cool AO 1
11- BO 2 Close Cool BO 2 Not used Blank Blank
12- BI 1 BI 1 12- BI 1 BI 1
13- RS RS 13- RS RS
14- Scom Scom 14- Scom Scom
15- BI 2 BI 2 15- BI 2 BI 2
16- UI 3 COS / COC /SS UI 3 16- UI 3 COS / COC /SS UI 3
Page 7
7 | PIR Ready VT7200 Series-Installation Guide
Wiring
Main outputs wiring
Single output applications
Dual output applications
On-Off control VT7200C5x00(x)
Floating control VT7200C5x00(x)
Remote inputs ( All models )
BI 1
RS
Scom
BI 2
UI 3
OR
Contact
- Rem NSB
- Motion
- Window
Contact
- Door
- Remote Override
- Filter alarm
- service alarm
Remote wall sensor
- S3010W1000
- S3020W1000
SS ( supply sensor )
- S1010E1000
- S2000D1000
COS ( changeover sensor )
- S1010E1000
COC/NH
- Normally heat
- Closed contact = cold water
COC/NC
- Normally cool
- Closed contact = heat water
#4 24 V~ Hot
#5 24 V~ Com
#6
#7
#4 24 V~ Hot
#5 24 V~ Com
#6
#7
Auxiliary output
( All models )
- Dry contact to end device 24 V~ maximum
- 24 VAC power to relay
R
R
Heating / Cooling valve
24 VAC
Com
OR
24 V~ Hot
24 V~ Com
BO1
if N.O.
BO2
if N.C.
24 V~ Hot
24 V~ Com
BO3
if N.O.
BO4
if N.C.
BO1
if N.O.
BO2
if N.C.
24 Vac
Com
Heating valve
Cooling valve
24 Vac
Com
OR
OR
24 VAC
Com
Heating valve
Cooling valve
24 VAC
Com
OR
OR
Open
Com
Close
Heating / Cooling valve
24 V~ Hot
24 V~ Com
BO1
BO2
Open
Com
Close
Heating valve
Open
Com
Close
Cooling valve
24 V~ Hot
24 V~ Com
BO3
BO4
BO1
BO2
Page 8
8 | PIR Ready VT7200 Series-Installation Guide
Analog control VT7200F5x00(x)
Typical applications
Schematic
Wiring
Settings
Pressure dependent VAV cooling only:VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0  CntrltTyp = Floating  FL time = as per
actuator
SeqOpera = 0
Cooling only
Pressure dependent VAV cooling only: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0  RA/DA = as per
actuator
SeqOpera = 0
Cooling only
Heating / Cooling valve
Com
24 VAC
0-10 VDC
24 V~ Hot
24 V~ Com
AO 1
24 V~ Hot
24 V~ Com
AO 2
AO 1
Com
24 VAC
0-10 VDC
Heating valve
Cooling valve
Com
24 VAC
0-10 VDC
UI3 COS 0 V~ Com 24 V~ Hot
BO1 Open
BO2 Close
& Maximum
Position
the actuator
Modulating Floating
VAV Actuator
Analog VAV Actuator
& Maximum
Position
the actuator
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Minimum
Minimum
Adjusted on
Room Temperature Control
Adjusted on
Room Temperature Control
Page 9
9 | PIR Ready VT7200 Series-Installation Guide
Pressure dependent VAV cooling / heating with changeover: VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0  CntrltTyp = Floating  FL time = as per
actuator
If heat / cool auto­changeover with a local
discharge air temperature sensor set: SeqOpera = 0
Cooling only
UI3 = COS
Pressure dependent VAV cooling / heating with changeover: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0  RA/DA = as per
actuator
If heat / cool auto- changeover with a local discharge air temperature sensor set: SeqOpera = 0
Cooling only
UI3 = COS
Supply air
temperature sensor
UI3 COS 0 V~ Com 24 V~ Hot
BO1 Open BO2 Close
Changeover
Sensor
Room Temperature Control
& Maximum
Position
the actuator
Modulating Floating
VAV Actuator
0 to 10 VDC
Analog Actuator
Changeover
Sensor
Room Temperature Control
Minimum
& Maximum
Adjusted on
the actuator
Position
Supply air
temperature sensor
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Minimum
Adjusted on
Page 10
10 | PIR Ready VT7200 Series-Installation Guide
Pressure dependent VAV cooling / heating with changeover and reheat: VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0  CntrltTyp = Floating  FL time = as per
actuator
If heat / cool auto­changeover with a local
discharge air temperature sensor set: SeqOpera = 2
Cooling with Reheat
UI3 = COS
Pressure dependent VAV cooling / heating with changeover and reheat: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0  RA/DA = as per
actuator
If heat / cool auto­changeover with a local
discharge air temperature sensor set: SeqOpera = 2
Cooling with Reheat
UI3 = COS
Supply air
temperature sensor
1
C
UI3 COS
0 V~ Com
24 V~ Hot BO1 Open BO2 Close
BO5-Aux BO5-Aux
Sensor
Room Temperature Control
& Maximum
Position
Adjusted on
the actuator
Modulating Floating
VAV Actuator
Heating and/or Cooling
& On/Off Duct Heater
Minimum
Sensor
Analog
VAV Actuator
Heating and/or Cooling
& On/Off Duct Heater
& Maximum
Position
the actuator
Minimum
Adjusted on
Room Temperature Control
Supply air
temperature sensor
1
C
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
BO5-Aux
BO5-Aux
AO2
Changeover
Changeover
Page 11
11 | PIR Ready VT7200 Series-Installation Guide
Schematic
Wiring
Settings
Heating or cooling hydronic valve control: VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0  CntrltTyp = Floating  FL time = as per
actuator
If cooling only set:: SeqOpera = 0
Cooling only
If heating only set::
SeqOpera = 1
Heating only
Heating or cooling hydronic valve control: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0  RA/DA = as per
actuator
If cooling only set:: SeqOpera = 0
Cooling only
If heating only set::
SeqOpera = 1
Heating only
Cooling / heating with changeover hydronic valve control: VT7200C5x00(x) Floating actuator
Mandatory
Out1Conf = 2.0  CntrltTyp = Floating  FL time = as per
actuator
If heat / cool auto­changeover with a local
water temperature sensor set: SeqOpera = 0
Cooling only
UI3 = COS
UI3 COS 0 V~ Com 24 V~ Hot
BO1 Open BO2 Close
Supply water
temperature sensor
UI3 COS 0 V~ Com 24 V~ Hot
BO1 Open BO2 Close
Modulating Floating
Valve Cooling or Heating
Room Temperature
Control Thermostat
Analog Valve
Cooling or Heating
Room Temperature
Control Thermostat
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Modulating Floating Valve
Heating and/or Cooling
Optional Water
Supply Sensor
Room Temperature
Control Thermostat
Page 12
12 | PIR Ready VT7200 Series-Installation Guide
Cooling / heating with changeover hydronic valve control: VT7200F5x00(x) Analog actuator
Mandatory
Out1Conf = 2.0  RA/DA = as per
actuator
If heat / cool auto- changeover with a local water temperature sensor set: SeqOpera = 0
Cooling only
UI3 = COS
Remote sensor accessories
Model no.
Description
S3010W1000
Wall mounted temperature sensor
S3020W1000
Wall mounted temperature sensor with override key and occupancy
status LED
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
Remote mount temperature sensors use 10K NTC thermistor.
This sensor can be used for: Each sensor can be configured for various averaging combinations Optional occupancy led Optional override key
S3020W1000
Wall mounted sensor
Wiring example of single remote room sensor:
Dip switch
setting for:
1 sensor
S2-1 = ON
S2-2 = ON
S3020W1000
Remote wiring 1 sensor
S2=On,
S3=On
VT7200 Series
BO 5
BI 2
RS
Scom
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
OR
S3010W1000
Remote wiring 1 sensor
S2=On,
S3=On
24 Vac
Com
1
2
ON
Dip switch
setting for:
1 sensor
S2-1 = ON
S2-2 = ON
Analog Valve
Heating and/or Cooling
Optional Water
Supply Sensor
Room Temperature
Control Thermostat
Supply water
temperature sensor
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Page 13
13 | PIR Ready VT7200 Series-Installation Guide
Wiring examples of 2 remote room sensors for averaging applications:
Wiring examples of 3 remote room sensors for averaging applications:
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R
25°C
=
10K±3%, B
25/85°C
= 3975K±1.5%)
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
-40
-40
324.3197
-20
-4
94.5149
0 32
32.1910
20
68
12.4601
40
104
5.3467
-35
-31
234.4009
-15 5 71.2430
5 41
25.1119
25
77
10.0000
45
113
4.3881
-30
-22
171.3474
-10
14
54.1988
10
50
19.7390
30
86
8.0694
50
122
3.6202
-25
-13
126.6109
-5
23
41.5956
15
59
15.6286
35
95
6.5499
55
131
3.0016
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display that shows the actual status of the system. There is an option in the configuration menu to lockout the scrolling display and to only present the room temperature and conditional outdoor temperature to the user. With this option enabled, no local status is given of mode, occupancy and relative humidity.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level. When left unattended for 10
Notes for averaging applications:
S3010W1000 and S3020W1000 can
be mixed matched.
S3010W1000 and S3020W1000 are
to be wired in parallel.
Respect the dip switch setting in
each remote sensor.
Dip switch
setting for:
2 sensors
S2-1 = OFF
S2-2 = ON
Dip switch
setting for:
3 sensors
S2-1 = OFF S2-2 = OFF
1 x S3010W1000 and 1 x
S3020W1000
Remote wiring 2 sensors
S1=On,
S2=Off
Scom
RS
Scom
RS
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS C DI
Aux
2 x
S3020W1000
Remote wiring 2 sensors
S2=On,
S3=Off
Scom
RS
Scom
RS
C
DI
Aux
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS
C
DI
Aux
2 x S3010W1000
Remote wiring 2 sensors
S2=On,
S3=Off
Scom
RS
Scom
RS
VT7200 Series
RS
Scom
Scom
RS
Scom
RS
2x S3010W1000 and 1 x
S3020W1000
Remote wiring 3 sensors
S2=Off,
S3=Off
Scom
RS
Scom
RS
Scom
RS
Scom
RS
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS C DI
Aux
3x S3010W1000
Remote wiring 3 sensors
S2=Off,
S3=Off
Scom
RS
Scom
RS
Scom
RS
Scom
RS
VT7200 Series
RS
Scom
Scom
RS
Scom
RS
1
2
ON
Dip switch
setting for:
2 sensors
S2-1 = OFF
S2-2 = ON
1
2
ON
Dip switch
setting for:
3 sensors
S2-1 = OFF
Page 14
14 | PIR Ready VT7200 Series-Installation Guide
seconds after changes are made, the display will resume automatic status display scrolling.
To turn on the back light to high level, press any key on the front panel. The back lit display will return to low level when the Terminal Equipment Controller is left unattended for 45 seconds
Sequence of auto-scroll status display:
ROOM &
HUMIDITY
SYSTEM MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C or °F XX % RH
Sys mode
Occupied
Outdoor
Service
Auto
x.x °C or°F
Filter
Sys mode Cool
Stand-By
Window
Sys mode heat
Unoccup
Outdoor air temperature
Display is only enabled when outdoor air temperature network variable is received.
Occupancy Status
Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling
display.
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time. The priority for the alarms is as
follows:
Two status LED’s on the Terminal Equipment Control cover are used to indicate a call for heat or a call for cooling.
Service
Indicates that there is a service alarm as per one of the configured binary inputs ( BI2 )
Filter
Indicates that the filters are dirty as per one of the configured binary inputs ( BI2 )
Window
Indicates that the outside window or door is opened and that the Terminal Equipment Controller has cancelled any cooling or heating action ( BI1 )
Page 15
15 | PIR Ready VT7200 Series-Installation Guide
Zoning Models
When heating & reheat is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate
USER INTERFACE
Unoccupied mode override
An Override can be made during an unoccupied period. If the Override option is enabled in the lockout configuration pressing the Override button will resume occupied setpoints for a time specified by parameter ToccTime
Local keypad interface
Any setpoint change can be permanent or temporary based on configuration
parameter (Setpoint Type)
Any setpoint written through the network, will be permanent and cancel any
active temporary setpoints
Lockouts of access to certain functions is made with configuration parameter
(lockout)
An Override can be made during an unoccupied period. If the Override
option is enabled in the lockout configuration pressing the override key will resume occupied setpoints for a time specified by parameter ToccTime
In cooling mode only the cooling setpoint is displayed, In heating mode only the heating setpoint is displayed In auto mode, (See below)
In cooling mode only the cooling setpoint is displayed, In heating mode only the heating setpoint is displayed In auto mode, (See below)
Page 16
16 | PIR Ready VT7200 Series-Installation Guide
Occupied setpoints adjustments
Unoccupied and stand-by setpoints adjustments
Setting of the stand-by and unoccupied setpoints is done through the network or through configuration setup only.
Mode button menu sequence
Modes presented to the user are dependent on the sequence of operation selected. Default mode is shown in bold when sequence of operation parameter is changed.
System mode function
PLEASE NOTE THAT: Default system mode of operation is dependent on sequence of operation selected
Default mode is in bold when sequence of operation parameter is changed
The available mode can only be changed through the network since there is no local mode access
SEQUENCE SELECTED
MODE MENU
0 = Cooling Only
Off - Cool
1 = Heating Only
Off - Heat
2 = Cooling With Electric Reheat
Off – Auto – Heat – Cool
3 = Heating With Electric Reheat
Off - Heat
4 = Cooling and Heating ( 2 modulating outputs )
Off – Auto – Heat – Cool
5 = Cooling / Heating ( 2 modulating outputs) with reheat
Off – Auto – Heat – Cool
INSTALLER CONFIGURATION PARAMETER MENU
Configuration can be done through the network or locally at the Terminal Equipment Controller.
To enter configuration, press and hold the middle button (°C/°F or Override) for
8 seconds.
If a password lockout is active, “Password” is prompted. Enter password value
using the “up” and “down” arrows and press the middle button again to gain
COOLING
MODE
HEATING
MODE
OFF
MODE
AUTO MODE
Setpoint presented to user is the setpoint from
the last action taken by the Terminal Equipment Controller or the one currently in use.
Both heating and cooling setpoints are
changed simultaneously while respecting the minimum configured deadband
Cool XX.X
°F or °C
Heat
XX.X
°F or °C
No access to setpoint
Cool XX.X °F or °C and Heat XX.X °F or °C
Both heating & cooling setpoints change
simultaneously
Page 17
17 | PIR Ready VT7200 Series-Installation Guide
access to all configuration properties of the Terminal Equipment Controller. Entering a wrong password will prevent local access to the configuration menu.
Press the same middle button repetitively to scroll between all the available
parameters.
Use the up and down key to change the parameter to the desired value. To acknowledge and save the new value, press the middle button again. The next parameter will now be displayed.
Configuration interface
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters menu access password Default value = 0 Range is: 0 to 1000
This parameter sets a password access to prevent unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu. Range is: 0 to 1000
Com Addr
Terminal Equipment Terminal Equipment Controller networking address Default value = 254 Range is: 0 to 254
Conditional parameter to BACnet™ MS-TP models VT7200X5x00B
Conditional parameter to Wireless models VT7200X5x00W
For BACnet™ MS-TP models, the valid range is
from 1 to 127. Default value of 254 disables BACnet™ communication for the Terminal Equipment Controller. For wireless models, the valid range is 0 to 254 with a maximum of 30 Terminal Equipment Controller per VWG
Pressing repetitively will individually scroll all the available parameters
Adjust / rotate parameter value down
Adjust / rotate parameter value up
Page 18
18 | PIR Ready VT7200 Series-Installation Guide
PAN ID
Personal Area Network Identification Default value = 0 Range is: 0 to 500
Conditional parameter to Wireless models VT7200X5x00W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit or with a BACnet™ or Echelon™ adapter, this parameter will not be used or displayed.
This parameter (Personal Area Network Identification) is used to link specific Terminal Equipment Controllers to a single specific Viconics wireless gateway ( VWG ). For every Terminal Equipment Controller reporting to a gateway ( maximum of 30 Terminal Equipment Controllers per gateway ), be sure you set the SAME PAN ID value both on the gateway and the Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from 1 to 500.
Range 1 to 250 for centralized networked applications using a VWG or a Jace with the wireless stat driver
Range 251 to 500 is for stand-alone (Network Ready) applications where no VWG or Jace with the wireless stat driver is used.
Channel
Channel selection Default value = 10 Range is: 10 to 26
Conditional parameter to Wireless models VT7200X5x00W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit or with a BACnet™ or Echelon™ adapter, this parameter will not be used or displayed.
This parameter (Channel) is used to link specific Terminal Equipment Controllers to specific Viconics wireless gateway(s) (VWG). For every Terminal Equipment Controller reporting to a gateway (maximum of 30 Terminal Equipment Controllers per gateway ), be sure you set the SAME channel value both on the gateway and the Terminal Equipment Controller(s).
Viconics recommends using only the usage of channels 15 and 25 only.
The default value of 10 is NOT a valid channel. The valid range of available channel is from 11 to 26
Page 19
19 | PIR Ready VT7200 Series-Installation Guide
Get From
Terminal Equipment Controller Get From another device configuration utility Default value = 0 Range is: 0 to 254
Conditional parameter to Wireless models (VT7200X5x00W)
Entering a MAC address enables an automatic routine that automatically fetches all the required configuration properties of the current device from another already configured device and copies the same required configured property values. If a value other than the default value of 255 is entered, user will then be prompted to exit the Configuration Menu thus leaving all other parameter configuration to be copied from the referenced Terminal Equipment Controller MAC address.
Ex.: If you are currently configuring MAC12 and the settings matches exactly the settings of ZN MAC5, then enter 5 as the current parameter value.
If the process is successful and all required configuration
properties have been copied, the value will revert back to 255
If the process is NOT successful and all required
configuration properties have NOT been copied ( either the reference device is NOT the same model number or is offline or does not exists ) the value will revert back to 254 to indicate the failure of the process
Leaving the Get From parameter to 255 means that every configuration parameters will be set manually.
Page 20
20 | PIR Ready VT7200 Series-Installation Guide
BI 1
Binary input no.1 configuration Default value = None
(None): No function will be associated with the input. Input can be used for remote network monitoring.
(Rem NSB): remote NSB timer clock input. The scheduling will now be set as per the binary input. It provides low cost setback operation via a dry contact
Contact opened = Occupied Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions using a Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor. Occupancy mode is now set as per applied PIR function and configuration. Application information and examples are available in document: APP- PIR-Guide-Exx. This document will provide the installers and system designers with detailed examples on applications, parameter configuration information, sequence of operation, troubleshooting and diagnostic help required for the proper usage of the PIR accessory covers
(Window) EMS: Forces the system to disable any current heating or cooling action by the Terminal Equipment Controller. The mode stays the same and the current setpoints are the same Occupied setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the Terminal Equipment Controller to indicate to the local tenant that the door/window needs to be closed for cooling or heating to resume.
* These settings will disable the local override function on the Terminal Equipment Controller.
BI 2
Binary input no.2 configuration Default value = None
(None): No function will be associated with the input  (Door Dry) Door contact & Motion detector: This configuration
is only functional if binary input #1 is set to Motion NO or Motion NC or a PIR accessory cover is used.
With this sequence enabled, the occupancy is now dictated
through those 2 inputs. Any motion detected will set the zone to occupied status. The zone will remain permanently in occupied mode until the door contact switch opens momentarily. The Terminal Equipment Controller will then go in stand-by mode. If more movements are detected, the occupied mode will resume. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed contact switching device.
Contact opened = Door opened  Contact closed = Door closed  (RemOVR): temporary occupancy remote override contact.
This function disables the central button override function on the Terminal Equipment Controller. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode.
It is now possible to toggle between unoccupied & occupied
setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time.
Page 21
21 | PIR Ready VT7200 Series-Installation Guide
(Filter): a backlit flashing Filter alarm will be displayed on the
Terminal Equipment Controller LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
Contact opened = No alarm  Contact closed = Alarm displayed  (Service): a backlit flashing Service alarm will be displayed on
the Terminal Equipment Controller LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
UI3
Universal input no.3 configuration Default value = None
(None): No function will be associated with the input
(COC/NH) Change over dry contact. Normally Heat: Used for hot /
cold water or air change over switching in 2 pipe systems. Contact closed = Cold water or air present Contact opened = Hot water or air present Only used and valid if system is setup as 2 pipes. Parameter (Pipe
No) set as 2 pipes.
(COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems. Contact closed = Hot water present Contact opened = Cold water present Only used and valid if system is setup as 2 pipes. Parameter (Pipe No) set as 2 pipes.
(COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems.
Only used and valid if system is setup as 2 pipes. Parameter (Pipe No) set as 2 pipes.
If water temperature is > 78 °F = Hot water present If water temperature is < 75 °F = Cold water present
(SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
Only used for network reporting of the supply air temperature. Has no internal function in the Terminal Equipment Controller.
MenuScro
Menu scroll Default value = On =
Scroll active
Removes the scrolling display and displays the room temperature/humidity to the user. With this option enabled, no mode, schedule and outdoor temperature status is given.
On = Scroll active Off = Scroll not active
C or F
Sets scale of the Terminal Equipment Controller Default value = °F
°F for Fahrenheit scale °C for Celsius scale
Page 22
22 | PIR Ready VT7200 Series-Installation Guide
Lockout
Keypad lockout levels Default value = 0 No lock
USER KEY FUNCTIONS
LEVEL
0
1
2
NOT USED
3
4
5
Out1Conf
Output # 1 configuration Default is: 4.0 (2 control outputs, no changeover)
Defines the type of operation needed for Output #1 (BO1 & BO2)
2.0, will limit the number of sequences of operation available from 0 to 3 Will enable heat/cool operation from the same output ( refer to wiring diagram )
4.0, can access all the sequences of operation from 0 to 5 Will enable heat/cool operation from different output ( refer to wiring diagram )
CntrlTyp
Control type for Triac models Default is: Floating
Defines the type of control output for the type of valves installed VT7200C10xx only On/Off is for normally opened or normally closed 24 VAC 2 position valves Floating is for modulating 3 wires control of 24 VAC floating valves
SeqOpera Sequence of operation Default is: Sequence #1
Single output application
(Out1Conf) = 2.0
Dual output application
(Out1Conf) = 4.0
0 = Cooling Only
Yes access
Yes access
1 = Heating only
Yes access
Yes access
2 = Cooling with Reheat
Yes access
Yes access
3 = Heating with Reheat
Yes access
Yes access
4 = Cool and Heat, 2 outputs
No access
Yes access
5 = Cool and Heat, 2 outputs with Reheat
No access
Yes access
For single output applications, the system access is also limited if UI3 is configured for local changeover COS, COC/NC or COC/NC.
Page 23
23 | PIR Ready VT7200 Series-Installation Guide
St-By TM
Stand-by Timer value Default 0.5 hours
Time delay between the moment where the PIR cover detected the last movement in the area and the time which the Terminal Equipment Controller stand-by mode and setpoints become active. Range is: 0.5 to 24.0 hours in 0.5hr increments
Unocc TM
Unoccupied Timer value Default 0.0 hours
Time delay between the moment where the Terminal Equipment Controller toggles to stand-by mode and the time which the Terminal Equipment Controller unoccupied mode and setpoints become active. The factory value or 0.0 hours: Setting this parameter to its default value of 0.0 hours disables the unoccupied timer. This prevents the Terminal Equipment Controller to drift from stand-by mode to unoccupied mode when PIR functions are used Range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT Stand-by heating setpoint Default value = 69 °F
The value of this parameter should reside between the occupied and unoccupied heating setpoints and make sure that the difference between the stand-by and occupied value can be recovered in a timely fashion when movement is detected in the zone. Stand-by heating setpoint range is: 40 to 90 °F ( 4.5 to 32.0
°C )
St-By CL
Stand-by cooling setpoint limit Default value = 78 °F
The value of this parameter should reside between the occupied and unoccupied cooling setpoints and make sure that the difference between the stand-by and occupied value can be recovered in a timely fashion when movement is detected in the zone. Stand-by cooling setpoint range is: 54 to 100 °F ( 12.0 to
37.5 °C )
Unocc HT
Unoccupied heating setpoint Default value = 62 °F
Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CL
Unoccupied cooling setpoint limit Default value = 80 °F
Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
heat max
Maximum heating setpoint limit Default value = 90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit Default value = 54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint adjustment. Cooling setpoint range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Page 24
24 | PIR Ready VT7200 Series-Installation Guide
Pband
Proportional band setting Default is : 3
Adjust the proportional band used by the Terminal Equipment
Controller PI control loop.
Note that the default value of 3.0 °F (1.2 °C) gives satisfactory operation in most normal installation cases. The use of a proportional band different than the factory one is normally warranted in applications where the Terminal Equipment Controller location is problematic and leads to unwanted cycling of the unit. A typical example is a wall mounted unit where the Terminal Equipment Controller is installed between the return and supply air feeds and is directly influenced by the supply air stream of the unit.
VALUE
°F SCALE PBAND
°C SCALE
PBAND
3
3 F
1.2 C
4
4 F
1.7 C
5
5 F
2.2 C 6 6 F
2.8 C
7
7 F
3.3 C
8
8 F
3.9 C 9 9 F
5.0 C
10
10 F
5.6 C
Page 25
25 | PIR Ready VT7200 Series-Installation Guide
Set Type
Temporary setpoint enable Default is : Permnent
Enables temporary setpoints feature to any change of occupied or unoccupied setpoint.
Temporar: (temporary) Local changes to the heating or cooling setpoints by the user are temporary. They will remain effective for the duration specified by ToccTime. Setpoints will then revert back to their default value after internal timer ToccTime expires.
To change setpoints permanently, revert this variable to No or write setpoints through the network. Any setpoints written through the network will be permanent and saved to EEPROM.
Permnent: (permanent) Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to & EEPROM
TOccTime
Temporary occupancy time Default value = 2 hours
Temporary occupancy time with occupied mode setpoints when override function is enabled.
When the Terminal Equipment Controller is in unoccupied mode, function is enabled with either the menu or UI2 configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Deadband
Minimum deadband Default value = 2.0 °F
( 1.0 °C )
The minimum deadband value between the heating and cooling setpoints. When modified, it will take effect only when any of the setpoints are modified again.
Range is: 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5
°C increments )
Cal RS
Room temperature sensor calibration Default value =
0.0 °F or °C
Offset that can be added/subtracted to the actual displayed room temperature
Range is: ± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C
increments )
Page 26
26 | PIR Ready VT7200 Series-Installation Guide
aux cont
Auxiliary contact function & configuration Default value = 0 Not
Used
0 Aux contact function used for reheat
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK OR LOCAL, Ignore this parameter
The output will directly follow the occupancy of the Terminal Equipment Controller 1 Auxiliary NO, Occ or St-By = Contact Closed / Unoccupied =
Contact Opened 2 Auxiliary NC, Occ or St-By = Contact Opened / Unoccupied = Contact Closed
Output to follow directly main occupancy and Fan on command
Typically used for 2 position fresh air damper applications. 3 Auxiliary NO, Occ or St-By & Fan On = Contact Closed / Unoccupied & Fan On or Off = Contact Opened 4 Auxiliary NC, Occ or St-By & Fan On = Contact Opened / Unoccupied & Fan On or Off = Contact Closed
Output to follow secondary network occupancy command 5 Auxiliary On/Off Control through auxiliary network
command. The output can be commanded through the network for any required auxiliary functions through a separate & dedicated network variable.
FL time Floating actuator timing
VT7200C5x00(x) models only Default value: 1.5 minutes
Maximum stroke time of floating valve actuator.
0.5 to 9.0 in 0.5 minutes increment
cph
On/Off devices cycles per hour
VT7200C5x00(x) models only
Default value = 4 C.P.H.
Will set the maximum number cycles per hour under normal control operation. It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour. Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing mechanical components faster. 3, 4, 5, 6,7 & 8 C.P.H.
Page 27
27 | PIR Ready VT7200 Series-Installation Guide
RA/DA Reverse acting or Direct acting signal for Analog output signals
VT72xxF5x00(x) models only
Default value: DA signal
Changes the action of the analog outputs on the analog models. DA = Direct acting 0 to 100 % = 0 to 10 VDC RA = Reverse acting 0 to 10 % - 10 to 0 VDC
Reheat Sets the time base for the reheat output if used Default value: 0 = 15 minute
Sets the reheat output time base Valid only if reheat sequences are enabled
0 = 15 minutes 1 = 10 seconds for Solid state relays
UI3 dis
Display supply or changeover temperature
Used as diagnostic / service help to troubleshoot and diagnose sensor operation Only when UI 3 is configured as an analog input ( SS or COS )
Page 28
28 | PIR Ready VT7200 Series-Installation Guide
SPECIFICATIONS
Terminal Equipment Controller power requirements: Operating conditions:
Storage conditions: Temperature sensor:
Temperate sensor resolution: Temperature control accuracy:
Contact output rating
Occ, Stand-By and Unocc cooling setpoint range: Occ, Stand-By and Unocc heating setpoint range: Room and outdoor air temperature display range: Proportional band for room temperature control:
Binary inputs: Wire gauge:
Approximate shipping weight: Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
19-30 VAC 50 or 60 Hz; 2 VA Class 2 0 °C to 50 °C ( 32 °F to 122 °F ) 0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F ) 0% to 95% R.H. non-condensing Local 10 K NTC thermistor ± 0.1 °C ( ± 0.2 °F ) ± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated Triac output: 30 VAC, 1 Amp. Maximum, 3 Amp. In-rush. Analog: 0 to10VDC into 2K resistance min.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F ) Cooling & Heating: Default: 1.8°C ( 3.2°F ) Dry contact across terminal BI1, BI2 & UI3 to Scom 18 gauge maximum, 22 gauge
0.75 lb ( 0.34 kg ) UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada) FCC: Compliant to CFR 47, Part 15,
Subpart B, Class A (US) CE : EMC Directive 89/336/EEC (Europe Union) C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand) Supplier Code Number N10696 FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Please check with your local government for instruction on disposal of this product.
Page 29
29 | PIR Ready VT7200 Series-Installation Guide
DRAWING & DIMENSIONS
Viconics Technologies Inc.
Tel.: Fax: Toll free:
www.viconics.com
Loading...