Local keypad interface 15
Occupied setpoints adjustments 16
Unoccupied and stand-by setpoints adjustments 16
Mode button menu sequence 16
System mode function 16
Installer Configuration Parameter Menu 16
Configuration interface 17
Specifications 28
Drawing & Dimensions 29
1 | PIR Ready VT7200 Series-Installation Guide
Page 2
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom side
of Terminal Equipment Controller (fig.
1).
Remove wiring terminals from sticker.
Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any direct
heat source.
3. Should not be installed near an air
discharge grill.
4. Should not be affected by direct sun
radiation.
5. Nothing should restrict vertical air
circulation to the Terminal
Equipment Controller.
Installation
1. Swing open the Terminal Equipment
Controller PCB to the left by
pressing the PCB locking tabs (fig.
2).
2. Pull out cables 6” out from the wall.
3. Wall surface must be flat and clean.
4. Insert cable in the central hole of the
base.
5. Align the base and mark the location
of the two mounting holes on the
wall. Install proper side of base up.
6. Install anchors in the wall.
7. Insert screws in mounting holes on
each side of the base (fig. 2).
8. Gently swing back the circuit board
on the base and push on it until the
tabs lock it.
9. Strip each wire 1/4 inch from end.
10. Insert each wire according to wiring
diagram.
11. Gently push excess wiring back into
hole (fig. 3).
12. Re-Install wiring terminals in their
correct locations (fig. 3).
2 | PIR Ready VT7200 Series-Installation Guide
Page 3
13. Re-install the cover (top side first) and gently push extra wire length back into the
If replacing an existing Terminal Equipment Controller, label the wires
before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure
proper and reliable operation in the field. Whenever a control failure
could lead to personal injury and/or loss of property, it becomes the
responsibility of the user / installer / electrical system designer to
incorporate safety devices (such as relays, flow switch, thermal
protections, etc…) and/or an alarm system to protect the entire system
against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.
hole in the wall.
14. Install security screw.
CONFIGURABLE BI/UI INPUTS OVERVIEW
Binary input #1 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Rem NSB): remote NSB timer clock input. The scheduling will now be set as
per the binary input. It provides low cost setback operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
3. (Motion NO) and (Motion NC): Advanced PIR occupancy functions using a
Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Occupancy mode is now set as per applied PIR function and configuration.
Application information and examples are available on document: APP-PIR-Guide-Exx. This document will provide the installers and system designers with
detailed examples on applications, parameter configuration information,
3 | PIR Ready VT7200 Series-Installation Guide
sequence of operation, troubleshooting and diagnostic help required for the
proper usage of the PIR accessory covers
4. (Window) EMS: Forces the system to disable any current heating or cooling
action by the Terminal Equipment Controller. The mode stays the same and the
current setpoints are the same occupied setpoints. Only the outputs are disabled.
There is a Door/Window alarm displayed on the Terminal Equipment Controller
to indicate to the local tenant that the door/window needs to be closed for
cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm
Contact closed = System enabled
Page 4
Binary input #2 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector: This configuration is only
functional if binary input #1 is set to Motion NO or Motion NC or a PIR accessory cover is used. With this sequence enabled, the occupancy is now
dictated through those 2 inputs. Any motion detected will set the zone to
occupied status. The zone will remain permanently in occupied mode until the
door contact switch opens momentarily. The Terminal Equipment Controller will
then go in stand-by mode. If more movements are detected, the occupied mode
will resume. While the door is opened, any movements detected by the remote
PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed
contact switching device.
Contact opened = Door opened
Contact closed = Door closed
3. (RemOVR): temporary occupancy remote override contact. This function
disables the central button override function on the Terminal Equipment
Controller. The override function is now controlled by a manual remote
momentarily closed contact. When configured in this mode, the input operates in
a toggle mode. It is now possible to toggle between unoccupied & occupied
setpoints for the amount of time set by parameter (TOccTime) temporary
occupancy time.
4. (Filter): a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitor filters
Contact opened = No alarm
Contact closed = Alarm displayed
5. (Service): a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold air /
water change over switching in 2 pipe systems.
Contact closed = Cold air / water present
Contact opened = Hot air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold air /
water change over switching in 2 pipe systems.
Contact closed = Hot air / water present
Contact opened = Cold air / water present
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
4 | PIR Ready VT7200 Series-Installation Guide
Page 5
4. (COS) Change over analog sensor: Used for hot / cold air / water change over
switching in 2 pipe systems.
Only used and valid if system is setup as 2.0. Parameter ( Out1Conf ) set as 2.0.
If temperature is > 77 °F = Hot air / water present
If temperature is < 75 °F = Cold air / water present
5. (SS) Supply air sensor monitoring: Used for supply air temperature
monitoring.
Only used for network reporting of the supply air temperature. Has no internal
function in the Terminal Equipment Controller.
MODEL CHART
5 | PIR Ready VT7200 Series-Installation Guide
Page 6
Network ready
Viconics Part NumbersVT7200C5x00(x)Viconics numberVT7200F5x00(x)
Description / Application1 or 2 Floating outputsDescription / application1 or 2 Analog outputs
1 or 2 On/Off outputs
4- 24 V~ Hot24 V~ Hot4- 24 V~ Hot24 V~ Hot
5- 0 V~ Com24 V~ Com5- 0 V~ Com24 V~ Com
6- Aux BO 5BO 5-Aux6- Aux BO 5BO 5-Aux
7- Aux BO 5BO 5-Aux7- Aux BO 5BO 5-Aux
8- BO 3 Open HeatBO 3
9- BO 4 Close HeatBO 49- AO 2 HeatAO 2
10- BO 1 Open CoolBO 1 10- AO 1 CoolAO 1
11- BO 2 Close CoolBO 2Not used BlankBlank
12- BI 1BI 112- BI 1BI 1
13- RSRS13- RSRS
14- ScomScom14- ScomScom
15- BI 2BI 215- BI 2BI 2
16- UI 3 COS / COC /SSUI 316- UI 3 COS / COC /SSUI 3
All Viconics VT7200 series Terminal Equipment Controllers are designed for
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7300V5000B, Terminal Equipment Controller BACnet™ MS-TP
communication adapter
o VCM7300V5000E, Terminal Equipment Controller Echelon™Lontalk™
communication adapter
o VCM7000V5000W Terminal Equipment Controller wireless
Out1Conf = 2.0
CntrltTyp = Floating
FL time = as per
actuator
If heat / cool autochangeover with a local
water temperature
sensor set:
SeqOpera = 0
Cooling only
UI3 = COS
UI3 COS
0 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
Supply water
temperature sensor
UI3 COS
0 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
Modulating Floating
Valve Cooling or Heating
Room Temperature
Control Thermostat
Analog Valve
Cooling or Heating
Room Temperature
Control Thermostat
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Modulating Floating Valve
Heating and/or Cooling
Optional Water
Supply Sensor
Room Temperature
Control Thermostat
11 | PIR Ready VT7200 Series-Installation Guide
Page 12
Cooling / heating with changeover hydronic valve control: VT7200F5x00(x)
Analog actuator
Mandatory
Out1Conf = 2.0
RA/DA = as per
actuator
If heat / cool auto-changeover with a local
water temperature
sensor set:
SeqOpera = 0
Cooling only
UI3 = COS
Model no.
Description
S3010W1000
Wall mounted temperature sensor
S3020W1000
Wall mounted temperature sensor with override key and occupancy
status LED
S2060A1000
Averaging temperature sensor
S2000D1000
Duct mounted temperature sensor
Wiring example of single remote room sensor:
Dip switch
settingfor:
1sensor
S2-1= ONS2-2= ON
S3020W1000
Remote wiring 1 sensor
S2=On,
S3=On
VT7200 Series
BO 5
BI 2
RS
Scom
Scom
RS
Scom
RS
C
DI
Aux
Scom
RS
Scom
RS
OR
S3010W1000
Remote wiring 1 sensor
S2=On,
S3=On
24 Vac
Com
1
2
ON
Dip switch
setting for:
1 sensor
S2-1 = ON
S2-2 = ON
Analog Valve
Heating and/or Cooling
Optional Water
Supply Sensor
Room Temperature
Control Thermostat
Supply water
temperature sensor
0 to 10
VDC
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Remote sensor accessories
Remote mount temperature sensors use 10K NTC thermistor.
This sensor can be used for:
Each sensor can be configured for various averaging combinations
Optional occupancy led
Optional override key
S3020W1000
Wall mounted sensor
12 | PIR Ready VT7200 Series-Installation Guide
Page 13
Wiring examples of 2 remote room sensors for averaging applications:
Wiring examples of 3 remote room sensors for averaging applications:
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
ºC
ºF
Kohm
-40
-40
324.3197
-20
-4
94.5149 0
32
32.1910
20
68
12.4601
40
104
5.3467
-35
-31
234.4009
-15 5 71.2430 5
41
25.1119
25
77
10.0000
45
113
4.3881
-30
-22
171.3474
-10
14
54.1988
10
50
19.7390
30
86
8.0694
50
122
3.6202
-25
-13
126.6109
-5
23
41.5956
15
59
15.6286
35
95
6.5499
55
131
3.0016
Notes for averaging applications:
S3010W1000 and S3020W1000 can
be mixed matched.
S3010W1000 and S3020W1000 are
to be wired in parallel.
Respect the dip switch setting in
each remote sensor.
Dip switch
settingfor:
2sensors
S2-1= OFFS2-2= ON
Dip switch
settingfor:
3sensors
S2-1= OFFS2-2= OFF
1 x S3010W1000 and 1 x
S3020W1000
Remote wiring 2 sensors
S1=On,
S2=Off
Scom
RS
Scom
RS
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS C DI
Aux
2 x
S3020W1000
Remote wiring 2 sensors
S2=On,
S3=Off
Scom
RS
Scom
RS
C
DI
Aux
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS
C
DI
Aux
2 x S3010W1000
Remote wiring 2 sensors
S2=On,
S3=Off
Scom
RS
Scom
RS
VT7200 Series
RS
Scom
Scom
RS
Scom
RS
2x S3010W1000 and 1 x
S3020W1000
Remote wiring 3 sensors
S2=Off,
S3=Off
Scom
RS
Scom
RS
Scom
RS
Scom
RS
VT7200 Series
BO 5
BI 2
RS
Scom
24 Vac
Com
Scom
RS
Scom
RS C DI
Aux
3x S3010W1000
Remote wiring 3 sensors
S2=Off,
S3=Off
Scom
RS
Scom
RS
Scom
RS
Scom
RS
VT7200 Series
RS
Scom
Scom
RS
Scom
RS
1
2
ON
Dip switch
setting for:
2 sensors
S2-1 = OFF
S2-2 = ON
1
2
ON
Dip switch
setting for:
3 sensors
S2-1 = OFF
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R
10K±3%, B
= 3975K±1.5%)
25/85°C
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the actual status of the system. There is an option in the configuration menu to
lockout the scrolling display and to only present the room temperature and conditional
outdoor temperature to the user. With this option enabled, no local status is given of mode,
occupancy and relative humidity.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any
key will cause the back light to come on to high level. When left unattended for 10
13 | PIR Ready VT7200 Series-Installation Guide
25°C
=
Page 14
seconds after changes are made, the display will resume automatic status display
ROOM &
HUMIDITY
SYSTEM MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C or °F
XX % RH
Sys mode
Occupied
Outdoor
Service
Auto x.x °C or°F
Filter
Sys mode
Cool
Stand-By
Window
Sys mode
heat
Unoccup
Service
Indicates that there is a service alarm as per one of the configured binary
inputs ( BI2 )
Filter
Indicates that the filters are dirty as per one of the configured binary
inputs ( BI2 )
Window
Indicates that the outside window or door is opened and that the Terminal
Equipment Controller has cancelled any cooling or heating action ( BI1 )
scrolling.
To turn on the back light to high level, press any key on the front panel. The back lit
display will return to low level when the Terminal Equipment Controller is left unattended
for 45 seconds
Sequence of auto-scroll status display:
Outdoor air temperature
Display is only enabled when outdoor air temperature network variable is received.
Occupancy Status
Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling
display.
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time. The priority for the alarms is as
follows:
Two status LED’s on the Terminal Equipment Control cover are used to indicate a call for
heat or a call for cooling.
14 | PIR Ready VT7200 Series-Installation Guide
Page 15
Zoning Models
When heating & reheat is ON, the HEAT LEDwill illuminate
When cooling is ON, the COOL LED will illuminate
An Override can be made during an unoccupied period. If the Override
option is enabled in the lockout configuration pressing the override key
will resume occupied setpoints for a time specified by parameter
ToccTime
In cooling mode only the cooling setpoint is displayed,
In heating mode only the heating setpoint is displayed
In auto mode, (See below)
In cooling mode only the cooling setpoint is displayed,
In heating mode only the heating setpoint is displayed
In auto mode, (See below)
USER INTERFACE
Unoccupied mode override
An Override can be made during an unoccupied period. If the Override option is enabled
in the lockout configuration pressing the Override button will resume occupied setpoints
for a time specified by parameter ToccTime
Local keypad interface
Any setpoint change can be permanent or temporary based on configuration
parameter (Setpoint Type)
Any setpoint written through the network, will be permanent and cancel any
active temporary setpoints
Lockouts of access to certain functions is made with configuration parameter
the last action taken by the Terminal
Equipment Controller or the one currently in
use.
Both heating and cooling setpoints are
changed simultaneously while respecting the
minimum configured deadband
Cool XX.X
°F or °C
Heat
XX.X
°F or °C
No access
to setpoint
Cool XX.X °F or °C and Heat XX.X °F or °C
Both heating & cooling setpoints change
simultaneously
Unoccupied and stand-by setpoints adjustments
Setting of the stand-by and unoccupied setpoints is done through the network or through
configuration setup only.
Mode button menu sequence
Modes presented to the user are dependent on the sequence of operation selected.
Default mode is shown in bold when sequence of operation parameter is changed.
System mode function
PLEASE NOTE THAT: Default system mode of operation is dependent on sequence of
operation selected
Default mode is in bold when sequence of operation parameter is changed
The available mode can only be changed through the network since there is no local
mode access
INSTALLER CONFIGURATION PARAMETER MENU
Configuration can be done through the network or locally at the Terminal Equipment
Controller.
To enter configuration, press and hold the middle button (°C/°F or Override) for
8 seconds.
If a password lockout is active, “Password” is prompted. Enter password value
16 | PIR Ready VT7200 Series-Installation Guide
using the “up” and “down” arrows and press the middle button again to gain
Page 17
access to all configuration properties of the Terminal Equipment Controller.
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value = 0
Range is: 0 to 1000
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Com Addr
Terminal Equipment
Terminal Equipment Controller
networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet™ MS-TP models
VT7200X5x00B
Conditional parameter to Wireless models
VT7200X5x00W
For BACnet™ MS-TP models, the valid range is
from 1 to 127. Default value of 254 disables
BACnet™ communication for the Terminal
Equipment Controller.
For wireless models, the valid range is 0 to 254
with a maximum of 30 Terminal Equipment
Controller per VWG
Pressing repetitively will individually scroll all the available parameters
Adjust / rotate parameter value down
Adjust / rotate parameter value up
Entering a wrong password will prevent local access to the configuration menu.
Press the same middle button repetitively to scroll between all the available
parameters.
Use the up and down key to change the parameter to the desired value.
To acknowledge and save the new value, press the middle button again.
The next parameter will now be displayed.
Configuration interface
17 | PIR Ready VT7200 Series-Installation Guide
Page 18
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models
VT7200X5x00W
This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone (Network
Ready) unit or with a BACnet™ or Echelon™ adapter,
this parameter will not be used or displayed.
This parameter (Personal Area Network Identification)
is used to link specific Terminal Equipment
Controllers to a single specific Viconics wireless
gateway ( VWG ). For every Terminal Equipment
Controller reporting to a gateway ( maximum of 30
Terminal Equipment Controllers per gateway ), be
sure you set the SAME PAN ID value both on the
gateway and the Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.
The valid range of available PAN ID is from 1 to 500.
Range 1 to 250 for centralized networked applications
using a VWG or a Jace with the wireless stat driver
Range 251 to 500 is for stand-alone (Network Ready)
applications where no VWG or Jace with the wireless
stat driver is used.
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models
VT7200X5x00W
This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone (Network
Ready) unit or with a BACnet™ or Echelon™ adapter,
this parameter will not be used or displayed.
This parameter (Channel) is used to link specific
Terminal Equipment Controllers to specific Viconics
wireless gateway(s) (VWG). For every Terminal
Equipment Controller reporting to a gateway
(maximum of 30 Terminal Equipment Controllers per
gateway ), be sure you set the SAME channel value
both on the gateway and the Terminal Equipment
Controller(s).
Viconics recommends using only the usage of
channels 15 and 25 only.
The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26
18 | PIR Ready VT7200 Series-Installation Guide
Page 19
Get From
Terminal Equipment
Controller Get From
another device
configuration utility
Default value = 0
Range is: 0 to 254
Conditional parameter to Wireless models
(VT7200X5x00W)
Entering a MAC address enables an automatic routine that
automatically fetches all the required configuration properties
of the current device from another already configured device
and copies the same required configured property values.
If a value other than the default value of 255 is entered, user
will then be prompted to exit the Configuration Menu thus
leaving all other parameter configuration to be copied from the
referenced Terminal Equipment Controller MAC address.
Ex.: If you are currently configuring MAC12 and the settings
matches exactly the settings of ZN MAC5, then enter 5 as the
current parameter value.
If the process is successful and all required configuration
properties have been copied, the value will revert back to
255
If the process is NOT successful and all required
configuration properties have NOT been copied ( either
the reference device is NOT the same model number or is
offline or does not exists ) the value will revert back to 254
to indicate the failure of the process
Leaving the Get From parameter to 255 means that every
configuration parameters will be set manually.
19 | PIR Ready VT7200 Series-Installation Guide
Page 20
BI 1
Binary input no.1
configuration
Default value =None
(None): No function will be associated with the input. Input can
be used for remote network monitoring.
(Rem NSB): remote NSB timer clock input. The scheduling will
now be set as per the binary input. It provides low cost setback
operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy
functions using a Normally Open (NO) or Normally Closed
(NC) remote PIR motion sensor. Occupancy mode is now set
as per applied PIR function and configuration. Application
information and examples are available in document: APP-PIR-Guide-Exx. This document will provide the installers and
system designers with detailed examples on applications,
parameter configuration information, sequence of operation,
troubleshooting and diagnostic help required for the proper
usage of the PIR accessory covers
(Window) EMS: Forces the system to disable any current
heating or cooling action by the Terminal Equipment
Controller. The mode stays the same and the current setpoints
are the same Occupied setpoints. Only the outputs are
disabled. There is a Door/Window alarm displayed on the
Terminal Equipment Controller to indicate to the local tenant
that the door/window needs to be closed for cooling or heating
to resume.
* These settings will disable the local override function on the
Terminal Equipment Controller.
BI 2
Binary input no.2
configuration
Default value = None
(None): No function will be associated with the input
(Door Dry) Door contact & Motion detector: This configuration
is only functional if binary input #1 is set to Motion NO or
Motion NC or a PIR accessory cover is used.
With this sequence enabled, the occupancy is now dictated
through those 2 inputs. Any motion detected will set the zone
to occupied status. The zone will remain permanently in
occupied mode until the door contact switch opens
momentarily. The Terminal Equipment Controller will then go
in stand-by mode. If more movements are detected, the
occupied mode will resume. While the door is opened, any
movements detected by the remote PIR sensor or the PIR
accessory cover will be ignored. Use a Normally Closed
contact switching device.
Contact opened = Door opened
Contact closed = Door closed
(RemOVR): temporary occupancy remote override contact.
This function disables the central button override function on
the Terminal Equipment Controller. The override function is
now controlled by a manual remote momentarily closed
contact. When configured in this mode, the input operates in
a toggle mode.
It is now possible to toggle between unoccupied & occupied
setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
20 | PIR Ready VT7200 Series-Installation Guide
Page 21
(Filter): a backlit flashing Filter alarm will be displayed on the
Terminal Equipment Controller LCD screen when the input is
energized. It can be tied to a differential pressure switch that
monitor filters
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): a backlit flashing Service alarm will be displayed on
the Terminal Equipment Controller LCD screen when the
input is energized. It can be tied in to the AC unit control card,
which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
UI3
Universal input no.3
configuration
Default value = None
(None): No function will be associated with the input
(COC/NH) Change over dry contact. Normally Heat: Used for hot /
cold water or air change over switching in 2 pipe systems.
Contact closed = Cold water or air present
Contact opened = Hot water or air present
Only used and valid if system is setup as 2 pipes. Parameter (Pipe
No) set as 2 pipes.
(COC/NC) Change over dry contact. Normally Cool: Used for hot /
cold water or air change over switching in 2 pipe systems.
Contact closed = Hot water present
Contact opened = Cold water present
Only used and valid if system is setup as 2 pipes. Parameter (Pipe
No) set as 2 pipes.
(COS) Change over analog sensor: Used for hot / cold water or air
change over switching in 2 pipe systems.
Only used and valid if system is setup as 2 pipes. Parameter (Pipe
No) set as 2 pipes.
If water temperature is > 78 °F = Hot water present
If water temperature is < 75 °F = Cold water present
(SS) Supply air sensor monitoring: Used for supply air
temperature monitoring.
Only used for network reporting of the supply air temperature. Has
no internal function in the Terminal Equipment Controller.
MenuScro
Menu scroll
Default value = On =
Scroll active
Removes the scrolling display and displays the room
temperature/humidity to the user. With this option enabled, no
mode, schedule and outdoor temperature status is given.
On = Scroll active
Off = Scroll not active
C or F
Sets scale of the Terminal
Equipment Controller
Default value = °F
°F for Fahrenheit scale
°C for Celsius scale
21 | PIR Ready VT7200 Series-Installation Guide
Page 22
Lockout
Keypad lockout levels
Default value = 0 No lock
USER KEY FUNCTIONS
LEVEL
0
1
2
NOT USED
3
4
5
Out1Conf
Output # 1 configuration
Default is: 4.0 (2 control
outputs, no changeover)
Defines the type of operation needed for Output #1 (BO1
& BO2)
2.0, will limit the number of sequences of operation
available from 0 to 3
Will enable heat/cool operation from the same output
( refer to wiring diagram )
4.0, can access all the sequences of operation from 0 to 5
Will enable heat/cool operation from different output
( refer to wiring diagram )
CntrlTyp
Control type for Triac models
Default is: Floating
Defines the type of control output for the type of valves
installed VT7200C10xx only On/Off is for normally opened or normally closed 24 VAC 2
position valves
Floating is for modulating 3 wires control of 24 VAC
floating valves
SeqOpera Sequence of
operation
Default is: Sequence #1
Single output application
(Out1Conf) = 2.0
Dual output application
(Out1Conf) = 4.0
0 = Cooling Only
Yes access
Yes access
1 = Heating only
Yes access
Yes access
2 = Cooling with Reheat
Yes access
Yes access
3 = Heating with Reheat
Yes access
Yes access
4 = Cool and Heat, 2 outputs
No access
Yes access
5 = Cool and Heat, 2 outputs
with Reheat
No access
Yes access
For single output applications, the system access is also limited if UI3 is configured for
local changeover COS, COC/NC or COC/NC.
22 | PIR Ready VT7200 Series-Installation Guide
Page 23
St-By TM
Stand-by Timer value
Default 0.5 hours
Time delay between the moment where the PIR cover
detected the last movement in the area and the time which
the Terminal Equipment Controller stand-by mode and
setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5hr increments
Unocc TM
Unoccupied Timer value
Default 0.0 hours
Time delay between the moment where the Terminal
Equipment Controller toggles to stand-by mode and the time
which the Terminal Equipment Controller unoccupied mode
and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its
default value of 0.0 hours disables the unoccupied timer.
This prevents the Terminal Equipment Controller to drift from
stand-by mode to unoccupied mode when PIR functions are
used
Range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT
Stand-by heating setpoint
Default value = 69 °F
The value of this parameter should reside between the
occupied and unoccupied heating setpoints and make sure
that the difference between the stand-by and occupied value
can be recovered in a timely fashion when movement is
detected in the zone.
Stand-by heating setpoint range is: 40 to 90 °F ( 4.5 to 32.0
°C )
St-By CL
Stand-by cooling setpoint limit
Default value = 78 °F
The value of this parameter should reside between the
occupied and unoccupied cooling setpoints and make sure
that the difference between the stand-by and occupied value
can be recovered in a timely fashion when movement is
detected in the zone.
Stand-by cooling setpoint range is: 54 to 100 °F ( 12.0 to
37.5 °C )
Unocc HT
Unoccupied heating setpoint
Default value = 62 °F
Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CL
Unoccupied cooling setpoint
limit
Default value = 80 °F
Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
heat max
Maximum heating setpoint
limit
Default value = 90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
23 | PIR Ready VT7200 Series-Installation Guide
Page 24
Pband
Proportional band setting
Default is : 3
Adjust the proportional band used by the Terminal Equipment
Controller PI control loop.
Note that the default value of 3.0 °F (1.2 °C) gives
satisfactory operation in most normal installation cases. The
use of a proportional band different than the factory one is
normally warranted in applications where the Terminal
Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall
mounted unit where the Terminal Equipment Controller is
installed between the return and supply air feeds and is
directly influenced by the supply air stream of the unit.
VALUE
°F SCALE PBAND
°C SCALE
PBAND
3
3 F
1.2 C
4
4 F
1.7 C
5
5 F
2.2 C 6 6 F
2.8 C
7
7 F
3.3 C
8
8 F
3.9 C 9 9 F
5.0 C
10
10 F
5.6 C
24 | PIR Ready VT7200 Series-Installation Guide
Page 25
Set Type
Temporary setpoint
enable
Default is : Permnent
Enables temporary
setpoints feature to any
change of occupied or
unoccupied setpoint.
Temporar: (temporary) Local changes to the heating or cooling
setpoints by the user are temporary. They will remain effective
for the duration specified by “ToccTime”. Setpoints will then
revert back to their default value after internal timer “ToccTime”
expires.
To change setpoints permanently, revert this variable to No or
write setpoints through the network. Any setpoints written
through the network will be permanent and saved to EEPROM.
Permnent: (permanent) Any change of occupied or unoccupied
setpoints through the keypad by the user are permanent and
saved to & EEPROM
TOccTime
Temporary occupancy
time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints when
override function is enabled.
When the Terminal Equipment Controller is in unoccupied
mode, function is enabled with either the menu or UI2
configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Deadband
Minimum deadband
Default value = 2.0 °F
( 1.0 °C )
The minimum deadband value between the heating and cooling
setpoints. When modified, it will take effect only when any of
the setpoints are modified again.
Range is: 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5
°C increments )
Cal RS
Room temperature
sensor calibration
Default value =
0.0 °F or °C
Offset that can be added/subtracted to the actual displayed
room temperature
Range is: ± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C
increments )
25 | PIR Ready VT7200 Series-Installation Guide
Page 26
aux cont
Auxiliary contact function
& configuration
Default value = 0 Not
Used
0 Aux contact function used for reheat
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK
OR LOCAL, Ignore this parameter
The output will directly follow the occupancy of the
Terminal Equipment Controller
1 Auxiliary NO, Occ or St-By = Contact Closed / Unoccupied =
Contact Opened
2Auxiliary NC, Occ or St-By = Contact Opened / Unoccupied
= Contact Closed
Output to follow directly main occupancy and Fan on
command
Typically used for 2 position fresh air damper applications.
3Auxiliary NO, Occ or St-By & Fan On = Contact Closed /
Unoccupied & Fan On or Off = Contact Opened
4Auxiliary NC, Occ or St-By & Fan On = Contact Opened /
Unoccupied & Fan On or Off = Contact Closed
Output to follow secondary network occupancy command
5 Auxiliary On/Off Control through auxiliary network
command. The output can be commanded through the network
for any required auxiliary functions through a separate &
dedicated network variable.
FL time
Floating actuator timing
VT7200C5x00(x) models
only
Default value: 1.5
minutes
Maximum stroke time of floating valve actuator.
0.5 to 9.0 in 0.5 minutes increment
cph
On/Off devices cycles per
hour
VT7200C5x00(x) models
only
Default value = 4 C.P.H.
Will set the maximum number cycles per hour under normal
control operation. It represents the maximum number of cycles
that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of
control at the expense of wearing mechanical components
faster. 3, 4, 5, 6,7 & 8 C.P.H.
26 | PIR Ready VT7200 Series-Installation Guide
Page 27
RA/DA
Reverse acting or Direct
acting signal for Analog
output signals
VT72xxF5x00(x) models
only
Default value: DA signal
Changes the action of the analog outputs on the analog
models.
DA = Direct acting
0 to 100 % = 0 to 10 VDC
RA = Reverse acting
0 to 10 % - 10 to 0 VDC
Reheat
Sets the time base for the
reheat output if used
Default value: 0 = 15 minute
Sets the reheat output time base
Valid only if reheat sequences are enabled
0 = 15 minutes
1 = 10 seconds for Solid state relays
UI3 dis
Display supply or
changeover temperature
Used as diagnostic / service help to troubleshoot and diagnose
sensor operation
Only when UI 3 is configured as an analog input ( SS or COS )
27 | PIR Ready VT7200 Series-Installation Guide
Page 28
SPECIFICATIONS
Terminal Equipment Controller power
requirements:
Operating conditions:
Storage conditions:
Temperature sensor:
Temperate sensor resolution:
Temperature control accuracy:
Contact output rating
Occ, Stand-By and Unocc cooling setpoint range:
Occ, Stand-By and Unocc heating setpoint range:
Room and outdoor air temperature display range:
Proportional band for room temperature control:
Binary inputs:
Wire gauge:
Approximate shipping weight:
Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
19-30 VAC 50 or 60 Hz; 2 VA Class 2
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Local 10 K NTC thermistor
± 0.1 °C ( ± 0.2 °F )
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F )
typical calibrated
Triac output: 30 VAC, 1 Amp.
Maximum, 3 Amp. In-rush.
Analog: 0 to10VDC into 2KΩ
resistance min.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F )
Cooling & Heating: Default: 1.8°C
( 3.2°F )
Dry contact across terminal BI1,
BI2 & UI3 to Scom
18 gauge maximum, 22 gauge
0.75 lb ( 0.34 kg )
UL: UL 873 (US) and CSA C22.2 No.
24 (Canada), File E27734 with CCN
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
FCC: Compliant to CFR 47, Part 15,
Subpart B, Class A (US)
CE : EMC Directive 89/336/EEC
(Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant
(Australia / New Zealand) Supplier
Code Number N10696
FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS
SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT
CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE
UNDESIRED OPERATION.
Please check with your local government for instruction on disposal of this product.
28 | PIR Ready VT7200 Series-Installation Guide
Page 29
DRAWING &DIMENSIONS
Viconics Technologies Inc.
Tel.:Fax:Toll free:
www.viconics.com
29 | PIR Ready VT7200 Series-Installation Guide
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.