Engineering Guide Specs Viconics Electronics Inc
VH7200 Series Digital PI Humidity Controller June 2008
Viconics VH7200 Digital PI Humidity Controller
General – The VH7200 family is specifically designed for control of humidification and dehumidification
equipment such as steam header direct injection, desiccant wheel, or stand alone humidification /
dehumidification equipment. The VH7200 features a complete embedded humidity control solution with a backlit
LCD display. Non-communicating stand-alone as well as communicating BACnet, Echelon and Zigbee wireless
models are available depending on the application.
Quality Assurance - The humidistat shall be manufactured within a certified ISO-9001 and ISO-14001 facility
and must have the following industry approvals:
All models:
• UL 873 (US)
• CSA C22.2 No.24 (CANADA)
• File E27734 with CCN XAPX (US) and XAPX7 (CANADA)
• Industry Canada : ICES-003 (Canada)
Stand-Alone, BACnet & LON models:
• FCC Compliant to CFR 47, Part 15, Subpart B, Class A (US)
• CE EMC Directive 89/336/EEC (Europe Union)
• C-Tick AS/NZS CISPR 22 Compliant (Australia / New Zealand)
Wireless models
• FCC: Compliant to: Part 15, Subpart C
VH72xX
General – The low-voltage humidistat shall be capable of on/off dehumidification as well as (on/off and/or
analog 0-10Vdc humidification). The humidistat shall be a (non-communicating stand-alone model, BACnet
MS_TP communicating model, Echelon Lontalk communicating model or Zigbee wireless communicating
model).
• Humidistat shall provide accuracy of +/-3% over control range.
• Humidistat shall be equipped with a large, 2 line, 16 character LCD dual intensity backlit display with
two status LEDs showing HUM (Humidification), DEHUM (Dehumidification).
• Humidistat shall achieve accurate relative humidity control using a unique PI proportional-integral
algorithm. Traditional differential-based humidistats are not acceptable.
• Humidistat shall have an embedded local “real text” configuration utility for simplified sequence
selection, start-up and configuration using an integrated three-button keypad. Humidistats requiring
external configuration tools or network interface for start-up and configuration are not acceptable.
• Humidistat shall have an internal relative-humidity sensor in addition to embedded humidification and
dehumidification sequences. The hum i di st at shall have a 0-10Vdc analog output and/or on/off out p ut to
control modulating humidifiers. The humidistat shall also have a discreet output (dry contact) to activate
. Dessicant type or mechanical dehumidification equipment.
• Humidistat shall have an input for a remote relative humidity sensor (0-10Vdc). Remote sensor shall be
auto-sensing and require no internal configuration. While connected the internal RH sensor shall be
disabled
• Humidistat shall have ability to display the actual relative humidity directly on the LCD display.
• Humidistat shall have adjustable relative humidity setpoints as well as adjustable maximum
humidification (from 10% to 90% relative humidity) and minimum dehumidification limits (from 15%
to 95% relative humidity).
• Humidistat shall be capable of humidity set point reset based upon outdoor temperature sensing for
added flexibility (outdoor temperature sensor or network signal required). When an outdoor air
temperature sensor is connected, the humidistat shall be capable of displaying the outdoor air
temperature on the local LCD display.
• Humidistat shall have integrated proportional high-limit logic and input (0-10Vdc humidity sensor
required) for discharge humidity sensor. This feat ure shall prevent excess condensation in the supply
duct.Humidistat shall be capable of displaying the high limit when a humidity sensor is connected.
Humidistat shall have an adjustable “reset humidity setpoint” from 10% RH to 90% RH. The humidistat
will override the user relative humidity setpoint and revert to this setpoint when the outside air
temperature reaches the low temperature setpoint (adjustable from –40°F to 15°F (-40°C to –9.5°C))
*Models VH7270K1000x and VH7270F1000x only
Document #028-8018-R00
Engineering Guide Specs Viconics Electronics Inc
VH7200 Series Digital PI Humidity Controller June 2008
• Humidistat shall have the following modes of operation that can be selected using the local keypad
(model dependant):
Off
Auto
Humidification
Dehumidification
System is disabled
System will satisfy both Humidification and Dehumidification setpoints
System will satisfy the Humidification setpoint only
System will satisfy Dehumidification setpoint only
• Humidistat shall have the ability to lockout the dehumidification sequence based on outside air
temperature from –40ºF up to 122ºF, -40ºC up to 50ºC (outdoor air temperature sensor required).
• Humidistat shall have the ability to lockout the humidification sequence based on outside air
temperature from –15ºF up to 120ºF, -26ºC up to 49ºC (outdoor air temperature sensor required).
• Humidistat shall have an adjustable maximum number of cycles per hour (under normal control
operation) for the output relay for dehumidification and humidification (for on/off models). The
adjustments range from 3 to 8 cycles per hour.
• Humidistat shall be supplied (without networking interface, BACnet MS_TP network interface, Echelon
Lontalk network interface, Zigbee wireless network interface). BACnet MS_TP versions shall be
provided with Protocol Implementation Conformance Statement or Lonmark approval disclosing all
object/SNVT properties and instance numbers to facilitate the integration process. Echelon-Lontalk
Communicating versions shall be provided with appropriate application files and LNS plug-in as
required free of charge from the manufacturer.
• Humidistat shall utilize EEPROM memory to back up local configuration parameters in the event of
power failure. Humidistats requirin g bat t eri es, or have no provisions for retention duri ng l oss of p ow er
shall not be acceptable.
• Thermostat shall have two (2) adjustable keypad lockout levels limiting access as follows:
Access Level System Mode Changes Setpoint Adjustment
0
1
Yes access Yes access
No access No Access
• Humidistat shall have a programmable binary input that can be used for the following local monitoring
capabilities:
DI-1
1. None: No function will be associated with the input
2. Service: A backlit flashing “Service” alarm shall be displayed on the local
humidistat LCD screen when input is energized.
3. Canister: A backlit flashing “Canister” alarm shall be displayed on the local
humidistat LCD screen when input is energized. This input can be tied to a dry
contact output supplied by others.
.
• Humidistat shall be pre-programmed, containing all required I/O to accomplish local humidity control.
• Humidistat shall be provided with intelligent HMI, to which will display services only as are available
as switched through local digital input or network layer such as:
Outdoor air temperature display only enabled when outdoor air temperature sensor is
connected
COM Address and various other parameters when a communication module is
integrated inside the unit.
Humidistat with outdoor reset and proportional high limit shall be Viconics, model
VH7270x1000x
Humidistat with outdoor reset only shall be Viconics, model VH7200A1000x
Document #028-8018-R00