Viconics VH20 User Manual

Features
Benefits
Microcomputer-based
Exceptional accuracy and linearity
2% models 10 point calibration 3% models 3 point calibration
Increased accuracy and linearity across the required control range
Timed RH level status LED
Rapid trouble-shooting and commissioning. Humidity level is proportional to a 10 second duty cycle. Ex, using a time clock, if pulse duration is 6.5 seconds, sensed % RH by transmitter is 65% RH
Elegant aesthetic design
Blends well in all environments
Various additional temperature sensor options available
More functionality for DDC system installation by combining local temperature and humidity sensing in a single component
Model Output
Accuracy Temperature Sensor
Mounting
Extension
VH2
0 0-5 / 0-10 V
2 +/- 2%
0 None W Wall 1 4-20 mA
3 +/- 3%
1 3K Ohms thermistor
+/- 1%
D Duct 2 10K Ohms Type 2
+/- 1%
E Outdoor
3
10K Ohms Type 3
+/- 1%
4
100K Ohms thermistor
+/- 1% 5
1K Ohm NIFE
6
100 Ohms Platinum
7
1K Ohm Platinum
VH2
0 2 2 W 1000
Model:
Description:
Application:
Picture:
VH20 Wall
Room sensor
Remote room humidity sensing  Accessory temperature sensor available
VH20 Duct
Duct sensor with junction box
Remote return air humidity sensing with the
sensor mounted on the return air duct.
Outside air humidity sensing with the sensor
installed in the fresh air plenum.
Supply air humidity sensor  Accessory temperature sensor available
VH20
Exterior
Outside air sensor, NEMA 4 enclosure
Outside air humidity sensing with the sensor
installed directly exposed to the elements.
Sensor uses a water resistant NEMA 4 PVC
enclosure for outdoor applications
Accessory temperature sensor available
VH20 Electronic Humidity Transmitter Series
Description
The VH20 series, microcomputer-based humidity transmitters are designed for accurate humidity sensing in non-corrosive commercial applications such as: hospitals, schools, office buildings, retail stores, museums and computer rooms.
Available models
Example: Above model is VH2022W1000 for wall mount, 2% accuracy, 0-10 or 0-5 Vdc output with 10K Ohms Type 2 temperature sensor.
Models description
1
Fig. 2
Installation of room sensors (VH20 Wall) (Fig. 1 & 2)
VH20 Wall mounted
VH20 Duct mounted
VH20 Outdoor
Fig. 1
Fig.3
Probe tip, flat side facing airflow
Fig.4
Calibration +/- 5% RH
Sensing probe
PCV conduit Adapter by others
Wiring terminal
Mounting hole
Remove security screw on the bottom of sensor cover.  Open up by pulling on the bottom side of sensor. (Fig.1)
Location: 1- Should not be installed on an outside wall. 2- Must be installed away from any heat source. 3- Should not be installed near an air discharge grill. 4- Should not be affected by direct sun radiation. 5- Nothing must restrain vertical air circulation to the sensor.
Installation:
1. Remove security screw on the bottom of thermostat cover.
2. Open up by pulling on the bottom side of thermostat.
3. Pull out cables 6” out of the wall.
4. Wall surface must be flat and clean.
5. Insert cable in the central hole of the base.
6. Flip printed circuit board to access mounting hole
7. Align the base and mark the location of the two mounting holes on the wall.
8. Install proper side of base up.
9. Install anchors in the wall.
10. Insert screws in mounting holes on each side of the base. DO NOT OVERTIGHTEN
11. Strip each wire 1/4 inch.
12. Insert each wire according to wiring diagram.
13. Gently push back into hole excess wring back into the wall.
14. Press back printed circuit board into place
15. Install the cover, top side first
16. Install security screw.
Installation of duct sensors (VH20 Duct) – (Fig.3)
1. Drill 1” [25mm] hole mid height on the side of the duct to insert the probe.
2. Direct the probe so that the flat side of probe tip is facing the airflow.
3. Mark the position of the two holes to be drilled for mounting the sensor on the duct. Fasten the sensor to the duct with the two self-taping screws ( not­included ). Do not overtighten!
4. Junction box must be directed downwards or sideways.
5. For best results, locate sensor as far as you can from heating/cooling source.
Installation of outside air sensor (VH20 Outdoor) – (Fig.4)
1. Install sensor using mounting holes on each side.
2. Install on a vertical surface, respect mounting orientation
3. Remove the four screws and remove the cover.
4. Strip each wire 1/4 inch.
5. Insert each wire according to wiring diagram.
6. Install the cover with supplied screws.
7. In snowy area allow sufficient height for snow accumulation.
Maintenance of transmitter
Calibration: The transmitter is factory calibrated. However, it can be field recalibrated by using the ( -5%, 0%, 5% ) potentiometer
inside the transmitter to adjust the zero. The transmitter is already factory calibrated to the center of the potentiometer. To recalibrate the transmitter to the factory preset, turn the potentiometer to the 0% adjustment. (see pictures below)
Cleaning: The VH20 duct sensor probe needs inspection annually to be cleaned of any excess dirt on the sensing element tip.
The whole filter tip can be ordered and replaced if it cannot be cleaned properly. Part number: VH20DuctTip.
Loading...
+ 2 hidden pages