Viconics BACnet Zoning System Engineering Guide Spec
1.01 System Description – The Viconics BACnet Zoning System (VBZS) shall provide a simple and
efficient demand based system for the operation of changeover bypass or pressure dependent type
zoning systems utilizing standard 2 heat / 2 cool configurations, 2 heat / 2 cool with economizer and IAQ,
analog heat/2 cool, or heat pump 3 heat/ 2cool. The system shall consist of two primary components as
manufactured by Viconics: A communicating rooftop unit controller / heat pump controller (model
VZ7656x1000B) and one/several communicating zone controllers (model VZ7260x5x00B). A local
BACnet MS_TP communication bus between all devices shall ensure proper communication and data
exchange of all required information between the zone controllers and the rooftop unit controller for
proper system operation. The system shall seamlessly integrate into any 3rd party BACnet supervision
system adding greater functionality without being limited to a single vendor. Controls that can only be
integrated into a proprietary non-open protocol network shall not be acceptable. All system configuration
tools shall be embedded within the local devices via real text configuration interface. Systems requiring
external tools for commissioning or configuration shall not be acceptable.
1.02 Quality Assurance - The control system shall be manufactured within a systems certified ISO-9001
and ISO-14001. Please see the Equipment section for industry approvals and specifications.
Part 2 – Equipment
2.01 General - The VZ7656x1000B Rooftop controller shall be designed for equipment control based on heating and cooling demands from the zone controller(s) (VZ7260). The packaged rooftop or heat
pump system controller VZ7656 shall also provide logic and required inputs/outputs to control system
specific static pressure. The VZ7260F5x00B zone controllers shall be designed for local pressure
dependent VAV control.
Communication Protocol – The control system shall communicate using the open-protocol BACnet
MS_TP over RS485. Zone controls shall be configured directly from the local keypad to communicate with
a specific Rooftop Unit controller. All zone and Rooftop Unit controllers must reside on the same network.
All controllers in the network shall communicate at the same baud rate in order to properly exchange
information. Baud rate for system shall be set at Rooftop/system controller (VZ7656). Zoning control
controller shall feature “Auto-baud capability” allowing system baud rate configuration from Rooftop
controller to be matched by zoning controller(s) thereby facilitating system configuration and
commissioning.
Scalability – The system shall be fully scalable in terms of number of zone controllers and Rooftop Unit
controllers used on the same BACnet MS_TP communication trunk. A segment shall be a shielded
network loop run between all communicating device connections. The segment shall be no longer than
1200 meters (4000 feet). A single network segment shall be capable of installing up to 64 nodes (of either
type of controller). To install more than 64 nodes or if the network wire loop is longer than 1200 meters
(4000 feet), repeaters shall be used to ensure proper communication. With repeaters and a BACnet
MS_TP supervisory system, the maximum number of nodes on a single BACnet MS_TP trunk can be
extended to 128 nodes (of either type of controller).
Overall system architecture shall be open-standard based upon Building Automation Control network
(BACnet) standard facilitating the future replacement or addition of other system components, quickly and
easily. System functionality shall be scalable to suit current and future building automation needs with
simple addition of other BACnet based building controllers. System shall support supervisory functionality
(supplied by others) which will support centralized scheduling, alarming and trending found commonplace
amongst today’s advanced automation systems.
Systems not capable of supporting supervisory BACnet workstations shall not be acceptable.
Communication Wiring and Layout – The wire shall be a balanced 22-24 AWG twisted pair with a
characteristic impedance of 100-130ohms, capacitance of 17 pF/ft or lower, with a braided shield. The
RS485 network requires a daisy chain configuration. A BACnet MS_TP network must be properly
terminated at each end of the daisy chain with an EOL (End of line) resistor. The polarity of the network
connections must be respected.
Functionality – The VBZS shall be capable of operating without external input from a supervisory
system. The control system however, shall be capable of communicating with any 3rd party BACnet
MS_TP compatible supervisory system, graphic user interface, charts and log software, advanced energy
management software, automatic response to alarms etc.
VZ7656x1000B BACnet Rooftop or Heat Pump Controller
The Rooftop unit Controller shall be:
VZ7656R1000B: Up to two heating and two cool stages, single fan speed output, 0-10Vdc output for
bypass damper or variable-frequency drive (VFD).
VZ7656F1000B: Modulating 0-10Vdc heating / 2 cooling stages, single fan speed output, 0-10Vdc output
for bypass damper or variable-frequency drive (VFD).
VZ7656E1000B: Up to two heating and two cooling stages, single fan speed output, 0-10Vdc output for
economizer actuator, 0-10Vdc output for bypass damper or variable frequency drive (VFD), indoor air
quality sequence (IAQ)
The Heat Pump Controller shall be:
VZ7656H1000B: 2 stage compressor with reversing valve and auxiliary heat, single fan speed output, 0-
10Vdc output for bypass damper or variable-frequency drive (VFD)
General VZ7656 Specifications:
VZ7656 controller shall be capable of controlling single or multistage HVAC units with automatic
changeover based on zone demands using the BACnet MS_TP communication protocol on
RS485.
The controller shall have the option of analyzing the PI heating or PI cooling demands from the
zones the following ways depending on the application:
1. Highest: The highest PI heating or PI cooling demand from the selected
voting zones shall dictate heating or cooling operation of the Rooftop Unit
controller.
2. Average of the three (3) highest demands: The average of the three (3)
highest PI heating or PI cooling demands from the selected voting zones will
dictate heating or cooling operation of the Rooftop Unit controller.
3. Average of the five (5) highest demands: The average of the five (5)
highest PI heating or PI cooling demands from the selected voting zones will
dictate heating or cooling operation of the Rooftop Unit controller.
The controller shall be capable of maintaining the system static pressure set point using
integrated proportional static pressure logic to modulate a bypass damper. A pressure transducer
with a 0-5Vdc output shall be wired directly to the VZ7656 controller. The controller shall have an
adjustable static pressure sensor range from 0-5” W.C. The control will output an analog signal
from 0-10Vdc to the bypass damper. A control system requiring a separate bypass damper
controller or separate sensors to display the bypass damper position is not acceptable.
The controller shall have EEPROM memory to prevent a loss of programming due to power
outage as well as a minimum of 6-hour reserve time for the internal clock.
Global Unocc
Override
System mode
setting
Schedule setting
Clock setting
Levels
Override **
….Y/N
Sys mode
set Y/N
Schedule
set Y/N
Clock
set Y/N
0
Yes access
Yes access
Yes access
Yes access
1
Yes access
No access
No access
Yes access
2
No access
No access
No access
Yes access
The controller shall be capable of operating the packaged unit even if there is a loss of
communication with the zone controllers. The packaged unit will run in heating or cooling based
on the return air temperature. If there is no return air sensor installed, the controller shall
automatically revert to the internal temperature sensor. Control systems that cannot operate the
packaged during a loss of communication with the zones are not acceptable.
The VZ7656 controller shall be 7 day programmable with a choice of 2 or 4 events per day.
Control systems that require an external time clock are not acceptable.
The controller shall have an adjustable (from 0 to 5 minutes) minimum On/Off operation time of
cooling & heating stages to prevent cycling.
The controller shall have a connection for an outdoor air temperature sensor. The outdoor air
temperature readings shall be used to lockout the system heating or cooling modes to prevent
equipment cycling as well as to lockout zone auxiliary heating (duct furnace and/or perimeter
heater).
The controller shall have a connection for a remote discharge air temperature sensor. The
discharge air temperature readings shall be used for monitoring purposes and can be
viewed directly on the LCD screen. The controller must have an adjustable discharge air
heating high-limit range of 70°F to 150°F (21°C to 65°C) as well as a discharge air cooling
low-limit range of 35 to 65°F (2.0°C to 19.0°C).
The controller shall have a connection for a remote return air temperature sensor. The
return air temperature readings shall be used for monitoring purposes as well as a backup
to controlling the RTU in case of a loss of communication with the zone controllers. The
return air temperature can be viewed directly on the LCD screen. The controller must have
an adjustable return air heating high limit and return air cooling low limit.
The controller shall have a lockable keypad with the following three lockout levels to prevent
changes to the settings from the keypad:
The controller shall have the ability to set the programmed occupied schedule time as the time at
which the desired occupied temperature setpoints will be attained at the zones. The controller
shall automatically optimize the equipment start. This progressive recovery feature can be
enabled or disabled.
The controller must have a programmable digital input that can be setup for the following
functions:
1. Service:a backlit flashing “SERVICE” alarm will be displayed on the
controller LCD screen when the input is energized.
2. Filter:a backlit flashing “FILTER” alarm will be displayed on the controller
LCD screen when the input is energized. The input can be tied to a
differential pressure switch to monitor filter status.
3. Remote NSB: Timer clock input for remote night-setback. This function shall
automatically disable the internal scheduling.
4. Remote OVR: Temporary occupancy remote contact. This function shall
disable all override menu functions.
The controller shall have “Smart Fan” operation to reduce energy consumption during unoccupied
periods.
The controller shall a fan delay that extends fan operation by 60 seconds after calls for heating or
cooling stage operation ends (can be enabled or disabled by the local keypad).
The controller shall have a configurable SPST output relay that can be used for lighting, exhaust
fan or fresh air control.
Packaged unit controller model dependent specifications:
VZ7656R1000B: Up to two heating and two cool stages, single fan speed output, 0-10Vdc output for
bypass damper or variable-frequency drive (VFD).
VZ7656F1000B: Modulating 0-10Vdc heating / 2 cooling stages, single fan speed output, 0-10Vdc output
for bypass damper or variable-frequency drive (VFD).
Specifications
The VZ7656F1000B shall have a configurable minimum supply temperature between 50 °F to 72
°F (10 °C to 22 °C) to be maintained during occupied mode. This parameter shall only be active
when the controller is in occupied mode, in heating mode and if the outdoor temperature is low
enough to prevent heating stage lockout.
VZ7656E1000B: Up to two heating and two cooling stages, single fan speed output, 0-10Vdc output for
economizer actuator, 0-10Vdc output for bypass damper or variable frequency drive (VFD), indoor air
quality sequence (IAQ).
Specifications
The VZ7656E1000B shall have capable of controlling the economizer for free cooling depending
on the outside air temperature.
If a fresh air station is used to measure CFM, the VZ7656E1000B shall have a 0-5 Vdc analog
input for a fresh air station transmitter to enable the Min/Max CFM control logic.
If CO2 levels must be maintained, the VZ7656E1000B can receive CO2 demands from the
VZ7260x5x00B controls and control the economizer to maintain a minimum and maximum C02
range. The default minimum and maximum CO2 set points shall be 800ppm and 1200ppm
respectively.
The Heat Pump Controller shall be:
VZ7656H1000B: 2 stage compressor with reversing valve and auxiliary heat, single fan speed output, 0-
10Vdc output for bypass damper or variable-frequency drive (VFD)
Lockout
Keypad lockout levels. Default: 0 = No Lockout
Levels
Occupied temperature setpoints
Local Override Only
Global Override Access
0
Yes access
Yes access
Yes access
1
Yes access
Yes access
No access
2
Yes access
No access
No access
3
No access
No access
No access
BACnet Zone Controller
VZ7260 Zone Controller –
The zone controller shall be capable of controlling a local VAV analog damper actuator as well as
a local duct furnace and on/off or PWM perimeter heater (if necessary). The zone controller shall
also be capable of auto-changeover based on the central VZ7656 controller signal.
The zone controller shall be capable of modulating the local VAV damper using integrated
damper control logic. The output signal shall be 0-10Vdc to modulate any standard analog
damper actuator. The minimum damper position and maximum damper position shall be
programmed directly on the controller keypad. Control systems that are mounted next to the
damper or require mechanical damper stops are not acceptable.
The zone controller shall have an output to control a duct furnace. The zone controller shall also
have an output for an on/off or PWM (SSR) perimeter heater.
The zone controller shall achieve accurate temperature control using a PI proportional-integral
algorithm. Traditional differential-based controllers are not acceptable.
The zone controller shall communicate with the Rooftop Unit controller VZ7656x1000B using the
BACnet MS_TP protocol on RS485. The zone controller shall have adjustable PI heating and PI
cooling weight from 0% to 100% in 25% increments to allow certain zones a higher priority versus
other zones.
The zone controller shall have a 0-10Vdc input for a CO2 transmitter for monitoring purposes or
to be used in conjunction with the VZ7656E1000B economizer model for CO2 level control.
The zone controller shall be compatible with the VI-PIR “passive infrared” occupancy sensor to
enable a “Stand-by” occupancy mode for additional energy savings.
The zone controller shall have a lockable keypad with the following three lockout levels to prevent
changes to the settings from the keypad:
BI1
Binary input no.1 configuration
Default: None
(None): No function will be associated with the input. Point
can still be monitored through the BACnet network.
(Motion NO): Used in Occupied Mode only to toggle from the
Occupied setpoints to the Stand-By setpoints when no motion
is detected for 60 minutes at the zone.
As soon as motion is detected at the zone, the Occupied
setpoints resumes.
Contact opened = No motion detected.
Contact closed = Motion detected
(Motion NC): Used in Occupied Mode only to toggle from the
Occupied setpoints to the Stand-By setpoints when no motion
is detected for 60 minutes at the zone.
As soon as motion is detected at the zone, the Occupied
setpoints resumes.
Contact opened = Motion detected.
Contact closed = No motion detected
The zone controller shall have a binary input that can be configured as follows:
The zone controller shall be capable of receiving the outdoor air temperature signal from the RTU
controller to lockout (if necessary) the zone’s analog reheat and/or the zone’s perimeter heating.
The zone controller shall have configurable temporary or permanent local override setpoints.
When the “temporary setpoints” mode is enabled, once the temporary occupancy timer expires,
the setpoints will revert back to their default values.
The zone controller shall have adjustable maximum heating and minimum cooling setpoints to
prevent locking conditions at the Rooftop Unit controller by having setpoints that are not
reachable.
Sequence of Operation –
The Viconics BACnet Zoning System shall operate in the following manner:
1. The VZ7656x1000B Rooftop Unit controller shall determine the mode of operation (heating /
cooling) by analyzing the PI heating and PI cooling demand sent by the weighted VZ7260x5x00B
zone controllers. The RTU controller shall supply heating or cooling based on the resulting
analysis (highest demand, average of three highest demands or average of five highest
demands). There is a mandatory two-minute delay between switchovers from heating to cooling
to prevent cycling.
2. The Rooftop Unit controller shall also monitor the static pressure sensor and modulate the bypass damper actuator accordingly to maintain the static pressure setpoint.
3. The Rooftop Unit controller shall monitor, return air temperature. If the high temperature limit or
low cooling temperature limit occurs, the Rooftop Unit controller will shut off heating or cooling to
prevent damage.
4. The Rooftop Unit controller shall monitor the outdoor air temperature and send the value to the
zone controllers to allow outside air lockout conditions at the zone level.
5. The VZ7260 zone controller(s) shall send the actual PI heating or PI cooling value multiplied by
the weight reduction factor (if necessary) to the Rooftop Unit controller.
6. The zone controllers shall modulate the local VAV damper to maintain the setpoint temperature.
Using the integrated PI algorithm, the controller will determine if heating or cooling is required. If
the particular zone has auxiliary reheat enabled, the auxiliary reheat (duct furnace and/or
perimeter heater) will be used if necessary. If the Rooftop Unit is in cooling mode and supplying
cold air and a particular zone requires cooling, the damper will modulate to supply the duct
furnace enough air to heat to try and attain the heating setpoint.
7. The zone controllers will cycle (on the LCD screen) between outdoor temperature, actual Rooftop
Unit occupancy and actual Rooftop Unit heating/cooling mode.
8. In case of a loss of network, the RTU unit will continue to control the Rooftop Unit based on the
return air temperature.
9. The VBZS can be integrated to any BACnet MS_TP DDC central workstation.
Sequence for economizer on VZ7656E1000B only:
The fresh air damper can be controlled through more than one sequence to achieve different control
strategies such as free cooling (economizer mode), minimum fresh air control and CO2 level control.
Note: For the sequences mentioned below, the following conditions must be met in order for the
sequences to be performed as stated:
- Max Pos parameter value must be greater than Min Pos Parameter value.
- Mac CO2 parameter value must be greater than Min CO2 Parameter value.
- Max FA parameter value must be greater than Min FA Parameter value.
Economizer Control Mode Only
If the fresh air damper is to be used only for free cooling purposes (economizer mode, without fresh air
measurement station or CO2 control), only the Min Pos parameter and the free cooling sequence will be
active.
- The FA Range parameter should be set to 0 CFM. (Default Value = 0 CFM)
- Set the Chngstpt parameter to desired value which free cooling is enabled. (Default Value =
55°F)
If the outside air temperature is greater than the changeover setpoint, then normal mechanical cooling will
be used. If the outside air temperature is less than or equal to the changeover setpoint, then free cooling
will be enabled and mechanical cooling stages will be locked out.
Economizer Mode and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and minimum fresh air volume control
(economizer mode and fresh air measurement station, but without CO2 level control), only the Min FA
parameter and the free cooling sequence will be active.
- The FA Range parameter should be set to a value higher than 0 CFM (0 CFM disables the fresh
air control).
- Min FA (minimum fresh air) parameter should be set to the desired level.
The FA Range parameter value should be set to the maximum capacity of the fresh air measurement
station. Therefore the relationship between air volumes and input signals can be established. For
example, if the fresh air station capacity is 10000 CFM, set FA Range to 10000.
This will set the relationship of 0 VDC = 0 CFM and 10VDC = 10000 CFM.
Min Pos
Max Pos
Min CO2
Max CO2
Current
Fresh Air
Setpoint
Current CO2 Level
Min FA
Setpoint
Max FA
Setpoint
Min CO2
Max CO2
Current
Current CO2 Level
Economizer Mode and CO2 Level Control
If the fresh air damper is to be used for both free cooling and CO2level control (economizer mode and
CO2 level control, but without fresh air measurement station), only the Min Pos, Max Pos, Min CO2and
Max CO2 parameters as well as the free cooling sequence will be active.
- The FA Range parameter should be set to 0 CFM.
- Set AI1 parameter to CO2 (0 VDC = 0ppm ; 10VDC = 2000ppm)
- Min Pos, Max Pos, Min CO2 and Max CO2 parameters should be set according to the required
setting.
The highest value between free cooling demand output and
interpolation output for the fresh air setpoint will be the output to
the fresh air damper.
Economizer Mode, CO2 Level Control and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and CO2 level control with a fresh air
measurement station, only the Min FA, Max FA, Min CO2 and Max CO2 parameters as well as the free
cooling sequence will be active.
- The FA Range parameter should be set to something other than 0 CFM.
- Use an air flow transmitter to read fresh air level with AI2 input (0-5 VDC input)
- Min FA, Max FA, Min CO2 and Max CO2 parameters should be set according to the required
setting.
The highest value between free cooling demand output and
interpolation output for the fresh air setpoint based on the CO2
level will be the output to the fresh air damper
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.