CRO-ST∆T
APPLICATIONS
VAV box control
•
Proportional room electric heating control
•
Proportional room hot water heating control
•
Air conditioning control
•
ADVANCED DESIGN AND PI CONTROL
Advanced microcomputer electronics and PI control algorithms
provides precise temperature control and eliminates wasted
heating energy caused by the typical On-Off cycling in
conventional thermostats. As a result the room occupant is able to
reduce the setpoint or desired temperature to the lowest
comfortable setting. The result is energy savings ranges from 5%
to 10%.
DAY-NIGHT MODE
A night mode, initiated by a remote timer or computer contact,
provides energy savings during unoccupied periods of up to 10 %,
without sacrificing comfort in occupied rooms. A flashing LED
indicator warns an person in an occupied room that the
thermostat is in Night mode. The occupant may override this
condition locally for 4 hours by pressing the switch on the
thermostat.
HIGH COOLING SIGNAL OUTPUT
A optional 0 to 10 Vdc cooling voltage output can be wired to
other thermostats and used as a signal to a voltage relay to
initiate cooling demand.
REPROGRAMMABLE
Each thermostat is computer calibrated and factory programmed
to the ordered specification. However, over 10 control parameters
( such as heating/cooling mode, stage differential, night set-back
etc. ) may be changed in the field with programming tool without
having to remove the thermostat cover. The C263 also doubles as
a diagnostic tool and indicates the status of all the inputs and
outputs to each stat, and will reduce troubleshooting time by
quickly identifying the specific problem.
COVERS
The thermostats are available with 4 covers options in either °C
and °F. Thermostat cover plugs in to base for easy wiring and
service. The base fits onto a standard electrical box. The User
adjustable front models feature internally selectable minimum
and maximum setpoint knob stops.
T500
T550
ELECTRONIC THERMOSTAT:
• TRI-STATE FLOATING
DAMPER MOTOR OUTPUT
• TWO MORE STAGES
• DAMPER CHANGEOVER INPUT
• DAY-NIGHT MODE ( T550 ONLY )
The model T500 and T550 are part of Viconics' Micro-Stat
Series low voltage RHVAC room temperature and
humidity controls line.
DAMPER CHANGEOVER INPUT
When the damper operation is selected for cooling mode, a closed
contact to the changeover input will reverse the operation of the
damper motor to heating mode. In the automatic mode a duct
sensor (S60 or S70) must be installed just before the VAV box.
When duct temperature is higher than room heating set point, the
damper operates in heating mode. When duct temperature is
lower than room cooling set point the damper operate in cooling
mode. With the recirculation mode selected, when the supply
temperature is in the dead zone between the heating and cooling
set point, the damper goes fully open to allow full ventilation.
This feature improves air quality and reduces temperature
variations across the room.
CONTROL OUTPUTS FOR ALL APPLICATIONS
The thermostats are available with various outputs to drive:
Relays
•
Contactors
•
Solenoids
•
Valves
•
SENSORS
Each thermostat can be either room or duct mounted with local or
remote sensors, and can be selected by an internal jumper.
SPECIFICATIONS
Operating Conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy:
( calibrated )
Ranges:
Outputs: Isolated Triac: 30 Vac at ½ A max.
Power: 24 Vac -15%, +10% 50/60 Hz; 2 VA
DIMENSIONS
1
2
3
4
5
6
7
8
9
10
3.275"
( 83 mm )
OR FROM BACK
BASE
WIRING
FROM TOP
SECURITY SCREW
Specifications and equipment are subject to change without prior notice.
Motors
•
SSR's
•
SCR Power Controllers
•
Three position motor
•
0% to 95% R.H. non-condensing
± 0.2 ° C ( ± 0.4 °F ) for low ranges
± 0.9 ° C ( ± 1.8 °F ) for high ranges
10 °C to 32 °C ( 50 °F to 90 °F )
-18 °C to 82 °C ( 0 °F to 180 °F )
0 to 10 Vdc into 2KΩ resistance min.
0 / 5 Vdc at 20 mA max. for both outputs.
VERTICAL
MODEL
45
0
2.8"
( 71 mm )
90
135
180
4.5"
F
114 mm
COVER
HORIZONTAL MODEL
VICONICS
4.5"
( 114 mm )
2.8"
( 71 mm )
1.275"
32 mm
ORDER CODE
COVERS ALL YOUR THERMOSTATS NEEDS
APPLICATION EXAMPLES
T500 - AB - CD - EF - GH ( without day-night mode )
T550 - AB - CD - EF - GH ( with day-night mode )
A Output no. 1 ( controlled device ) Type
0 Not installed
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
6 0 to 10 Vdc actuator, voltage relay or "SCR" * 0 to 10 Vdc
7 0 to 10 Vdc high cooling signal for Vdc relay Higher signal
B Output no. 2 ( controlled device ) Type
0 Not installed
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
C Output no. 1 and 2 control mode
1 Heating, reverse acting, ( RA )
2 Cooling, direct acting, ( DA )
3 Heating, RA ( no. 1 ) and cooling, DA ( no. 2 )
4 Cooling, DA ( no. 1 ) and heating, RA ( no. 2 )
D Main control sensor location
1 Room, inside thermostat, or ( duct return air**)
2 Duct supply air **
** Order with S60 or S70 sensor
E Setpoint adjustment
1 User adjustable
2 Blind cover
F Scale
1
10 °C to 32 °C ∗ Standard
2
50 °F to 90 °F
G Output no. 3 Damper changeover input
1 Normally cooling, ( DA ) Common dry contact for all thermostats
2 Normally heating, ( RA ) Com mon dry contact for all thermostats
3 Automatic Duct supply sensor **
4 Automatic
with recirculation
** Order with S60 or S70 sensor
H Maximum running time of tri-state floating actuator
1 1 minute
2 2 minutes
... etc.
9 9 minutes
Example: T550 - 75 - 41 - 12 - 12
One higher signal cooling output and one "SSR" 3-32 volts heating output.
Main sensor located inside the room. Setpoint adjustable by user.
Scale 50 °F to 90 °F. T he output no. 3 is a dam per with
a travel time of 2 minutes used in cooling mode.
Note: Order remote sensor separately.
Duct supply sensor **
∗ Standard
∗ Standard
∗ Standard
WIRING
For complete technical information on wiring, commissioning and
servicing, please refer to the T500 / T550 service manual.
From simple...
Pressure dependent VAV
Tri-state floating actuator
Day-night mode
TRI-STATE FLOATING ACTUATOR
2 MINUTES MAX. RUNNING TIME
DAY-NIGHT
24 VAC
T550-00-11-12-12
To more complicated...
Pressure dependent VAV c/w changeover
Tri-state floating actuator
Modulating duct heater, SCR 0 to 10 Vdc
Hydronic perimeter heating
TRI-STATE FLOATING ACTUATOR
5 MINUTES MAX. RUNNING TIME
ELECTRIC DUCT HEATER
WITH 0 TO 10 Vdc SCR
S60
SENSOR
24 VAC
T500-62-11-11-35
N.O. THERMAL VALVE
To sophisticated applications !
Hydronic heating and cooling
Tri-state floating actuator
1 stage on-off electric duct heater
Hydronic supply changeover sensor
Day-night mode
Blind cover
24 VAC
DAY-NIGHT
T550-01-11-22-32
Represented by:
1 STAGE ELECTRIC DUCT HEATER
S90
SENSOR
TRI-STATE FLOATING ACTUATOR
2 MINUTES MAX. RUNNING TIME
...
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.c om
T550SE15.DOC 6/7/02