T216
T266
THERMOSTAT WITH:
•
DAMPER MOTOR VOLTAGE OUTPUT, 0 TO 10 Vdc
•
DAMPER POSITION MIN/MAX ADJUSTMENTS
•
2 MORE OUTPUTS
•
REVERSING OF DAMPER
•
DAY-NIGHT MODE ( T266 ONLY )
TO OPEN THERMOSTAT COVER
•
Remove security screw on left side of thermostat cover.
•
Open up by pulling on the left side of thermostat.
THERMOSTAT INSTALLATION
A) Location:
1- Shouldn’t be installed on outside wall.
2- Must be installed away from any heat source.
3- Shouldn’t be affected by direct sun radiation.
4- Nothing must restrain vertical air circulation to the thermostat.
B) Installation:
1- Pull out cables 6” out of the wall.
2- Wall surface must be flat and clean.
3- Separate the thermostat and the base by pulling cover on the left side (same
as the security screw.)
4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two mounting holes on the
wall.
6- Install shields in the wall.
7- Insert screws in mounting holes on each side of the base.
DO NOT OVERTIGHTEN!
8- Open the cable protection 1 1/4 inch more or less.
9- Strip each wire 1/4 inch.
10- Insert each wire according to wiring diagram.
11- Reinstall the cover ( right side first ).
12- Install security screw.
SETPOINT ADJUSTMENT KNOB LIMITATION
Note: To limit the rotation of setpoint knob, adjust setpoint to desired value, then
insert stoppers in appropriate holes.
Horizontal model:
S1,S10 = No limitation
S3 à S8 = Setpoint limitations
Vertical model:
S7,S10 = No limitation
S1 TO S7, OR S12: SETPOINT LIMITATIONS
REMOTE SENSOR
It is possible to use a remote sensor ( for duct or room application) by connecting it to
pins no. 6 and 7. Inside sensor must be disconnected by removing jumper J4 inside the
thermostat.
Characteristics of remote sensor 47 KΩ.
180.0 °F 82.2 °C 5.494 Kohm 0.553 Volts
170.0 °F 76.7 °C 6.585 Kohm 0.648 Volts
160.0 °F 71.1 °C 7.933 Kohm 0.761 Volts
150.0 °F 65.6 °C 9.610 Kohm 0.893 Volts
140.0 °F 60.0 °C 11.700 Kohm 1.047 Volts
130.0 °F 54.4 °C 14.342 Kohm 1.225 Volts
120.0 °F 48.9 °C 17.682 Kohm 1.429 Volts
110.0 °F 43.3 °C 21.940 Kohm 1.659 Volts
100.0 °F 37.8 °C 27.412 Kohm 1.914 Volts
90.0 °F 32.2 °C 34.483 Kohm 2.191 Volts
80.0 °F 26.7 °C 43.704 Kohm 2.486 Volts
70.0 °F 21.1 °C 55.834 Kohm 2.791 Volts
60.0 °F 15.6 °C 71.866 Kohm 3.096 Volts
50.0 °F 10.0 °C 93.340 Kohm 3.393 Volts
40.0 °F 4.4 °C 122.298 Kohm 3.673 Volts
30.0 °F -1.1 °C 161.670 Kohm 3.927 Volts
20.0 °F -6.7 °C 215.805 Kohm 4.150 Volts
10.0 °F -12.2 °C 291.100 Kohm 4.341 Volts
0.0 °F -17.8 °C 396.830 Kohm 4.499 Volts
NIGHT MODE
An external contact closing between terminals 6 and 8 activates night mode. A LED
on the thermostat flashes continuously indicating night mode. By pressing the button
on the thermostat, day mode is reactivated. The thermostat returns to night mode when
pressing again the button, or automatically after a 4 hours delay.
Note: Terminals 6 and 8 can be connected together between thermostats.
DAMPER CHANGEOVER INPUT
A) MANUAL CHANGEOVER (Code G = 1 or 2): Output 3 operates generally as
per selected mode on the order code (example: cooling, G = 1). When a contact closes
between terminals 6 and 9, output 3 changes its action (Example: heating). Terminals
6 and 9 can be connected together between thermostats.
Use a diode (Example: 1N4001) as indicated on the wiring diagram. Only one diode is
needed for all thermostats connected together.
Note: Terminals 6 and 9 can be connected together between thermostats.
B) AUTOMATIC CHANGEOVER (Code G = 3): Use a remote sensor (S60 or
S70) for each thermostat, upstream of the damper. T his sensor can be calibrated ( ±
2.0 °C )at the thermostat if needed, using a small screwdriver on the right side of the
thermostat. Indicated temperature increases when rotating the potentiometer
clockwise.
When the supply temperature is below the setpoint, output 3 operates in cooling mode.
When the supply temperature is above the cooling setpoint (setpoint + co), output 3
operates in heating mode.
C) AUTOMATIC CHANGEOVER WITH RECIRCULATION (Code G = 4):
Damper operates as described above in B (automatic reversing), except that, when
supply air temperature is between heating and cooling setpoint for a period more than
25 seconds, damper opens 100 %.
DAMPER 0 TO 10 VDC OUTPUT
Output no 3 (terminal no. 10) produces a DC voltage 0 to 10 volts generally used for
damper control. Minimum value of damper or flow can be adjusted using the C263
programmer from 0 to 100 %. Adjust LL parameter to desired minimum position and
HL to maximum desired position. LL and HL are preprogrammed at 0 (0 volt) and
100% (10 volts) at the factory. Adjusting LL and HL does not affect the effective
proportional band. Example: LL=20%, HL=80%, Pb=0 .9 °C. damper will modulate
from 20 to 80 % on a 0.9 °C proportional band.
Parameter HF is used to adjust the maximum value of damper or flow. This
parameter is active when damper is in cooling mode only. If adjusted to 0, the damper
position will remain at minimum (LL) on a heating demand. If adjusted at a value
higher than the LL value, the damper position will raise proportionally with the
heating demand, up to this maximum value.
SPECIFICATIONS
Operating Conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy:
( calibrated )
Ranges:
± 0.2 ° C ( ± 0.4 °F ) for low ranges
± 0.9 ° C ( ± 1.8 °F ) for high ranges
10 °C to 32 °C ( 50 °F to 90 °F )
-18 °C to 82 °C ( 0 °F to 180 °F )
Outputs: Isolated Triac: 30 Vac at ½ A max.
0 to 10 Vdc into 2KΩ resistance min.
0 / 5 Vdc at 20 mA max. for both outputs.
Power: 24 Vac -15%, +10% 50/60 Hz; 2 VA
DIMENSIONS
WIRING
FROM TOP
SECURITY SCREW
1
2
3
4
5
6
7
8
9
10
3.275"
( 83 mm )
OR FROM BACK
BASE
VERTICAL
MODEL
90
45
0
2.8"
( 71 mm )
135
180
4.5"
F
114 mm
HORIZONTAL MODEL
VICONICS
COVER
( 114 mm )
2.8"
( 71 mm )
4.5"
1.275"
32 mm
ORDER CODE
T216 - AB - CD - EF - GH ( without day-night mode )
T266 - AB - CD - EF - GH ( with day-night mode )
Example: T266 - 52 - 11 - 12 - 30
One "SSR" 3-32 volts heating output
and one normally open thermal valve heating output.
Main sensor located inside the room. Setpoint adjustable by user.
Scale 50 °F to 90 °F. T he output no. 3 is for a 0-10 volts dc damper motor.
The damper changeover is automatic according to supply sensor temperature. Night
setback is available.
Note: Order remote/changeover sensors separately.
028-2006 M:\1_BINDER\01_MICROSTAT\01_English\07_Manual\T266ME03.DOC 3/21/03
Page: 1 Page: 2 Page: 3

A Output no. 1 ( controlled device ) Type
0 Not installed
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
6 0 to 10 Vdc actuator, voltage relay or "SCR" * 0 to 10 Vdc
* If output #1 is ordered A=6, the change over input is not available
B Output no. 2 ( controlled device ) Type
0 Not installed
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
C Output no. 1 and 2 control mode
1 Heating, reverse acting, ( RA )
2 Cooling, direct acting, ( DA )
3 Heating, RA ( no. 1 ) and cooling, DA ( no. 2 )
4 Cooling, DA ( no. 1 ) and heating, RA ( no. 2 )
D Main control sensor location
1 Room, inside thermostat, or ( duct return air**)
2 Duct supply air **
** Order with S60 or S70 sensor
E Setpoint adjustment
1 User adjustable
2 Blind cover
F Scale
1
10 °C to 32 °C ∗ Standard
2
50 °F to 90 °F
G Output no. 3 Damper changeover input
1 Normally cooling, ( DA ) Common dry contact for all thermostats
2 Normally heating, ( RA ) Comm on dry contact for all thermostats
3 Automatic Duct supply sensor **
4 Automatic
with recirculation
** Order with S60 or S70 sensor
H Future option
0 Unused
Duct supply sensor **
∗ Standard
∗ Standard
∗ Standard
∗ Standard
WIRING
NOTE: WITH THE PROPER CODES, TERMINALS 5, 6, 8 AND 9 CAN BE
WIRED TOGETHER BETWEEN EACH THERMOSTAT IF POLARITY IS RESPECTED
Power supply 24 Vac -15% +10%
50/60 HZ 2 VA
POWER SUPPLY 24 Vac.
24 VAC
COMMON
5
6
IMPORTANT: IF USING A COMMON TRANSFORMER
24VAC
RESPECT POLARITY (COMMON AND 24 VAC)
BETWEEN EACH THERMOSTAT
Day night mode T266 only
DAY NIGHT MODE
INPUT
DAY / NIGHT
8
6
COMMON
CLOSE =
NIGHT
SET BACK
1 CONTACT USED FOR ALL
THERMOSTAT USING THE
SAME TRANSFORMER
Output #1 code A= 1, 2, 3 & 4 Triacs
Output #2 code B= 1, 2, 3 & 4 Triacs
OUTPUT #1 AND/OR #2 USING RELAY WITH ISOLATED TRANSFORMER
RELAY OR THERMAL
VALVE 24 VAC
R
24VAC
OUTPUT
CONTACT
AND / OR
1
2
3
4
USE TERMINALS 3 & 4 FOR OUTPUT #1
USE TERMINALS 1 & 2 FOR OUTPUT #2
Output #1 code A= 1, 2, 3 & 4 Triacs
Output #2 code B= 1, 2, 3 & 4 Triacs
OUTPUT #1 AND/OR #2 USING SAME TRANSFORMER TO OUTPUT
OUTPUT
CONTACT
24 VAC
COMMON
AND / OR
3
1
4
2
5
24VAC
6
USE TERMINALS 3 & 4 FOR OUTPUT #1
USE TERMINALS 1 & 2 FOR OUTPUT #2
RELAY OR
THERMAL VALVE
24 VAC
Output #1 code A= 5 Pulsed 0/5 Vdc
Output #2 code B= 5 Pulsed 0/5 Vdc
OUTPUT #1 AND/OR #2 USING PULSED 0/5 Vdc
AND / OR
0/5 V
COMMON
24
6
USE TERMINALS 4 & 6 FOR OUTPUT #1
USE TERMINALS 2 & 6 FOR OUTPUT #2
SOLID STATE
RELAY
3-32 VDC
TRIGGER
LOAD
Output #1 code A=6 Analog 0 to 10 Vdc
OUTPUT #1 USING 0 TO 10 Vdc
0 TO 10 Vdc
COMMON
0 TO 10 VDC
4
6
NOTE: IF OUTPUT #1 IS 0 TO 10 Vdc (CODE A=6)
CHANGE OVER IS NOT AVAILABLE
ELECTRONIC ACTUATOR, SCR,
OR VOLTAGE RELAY
Output #3 Analog 0 to 10 Vdc
OUTPUT #3 USING 0 TO 10 Vdc
0 TO 10 Vdc
COMMON
0 TO 10 VDC
10
6
ELECTRONIC ACTUATOR, SCR,
OR VOLTAGE RELAY
Remote main temperature control sensor
Room or return control code D= 1,
Supply control code D=2
REMOTE MAIN CONTROL SENSOR
COMMON
EXTERNAL
SENSOR
NOTE: REMOVE
INTERNAL J4 JUMPER
AUTO CHANGE OVER INPUT WIRING: SUPPLY SENSOR
INPUT
COMMON
CHANGE OVER INPUT WIRING: CHANGE OVER THERMOSTAT
INPUT
COMMON
6
7
DUCT S60 OR S70
IMMERSION S90
Auto change over input.
1 supply sensor per thermostat
Automatic code G= 3
Automatic with recirculation code G= 4
NOTE: 1 SUPPLY SENSOR PER THERMOSTAT
9
6
DUCT S60 OR S70
IMMERSION S90
Change over input. 1 dry contact for all
thermostat using the same transformer
Normally cooling code G= 1
Normally heating code G= 2
9
6
NOTE: IF 5 THERMOSTATS OR MORE ARE USED
ON THE SAME TRANSFOMER, INSTALL 1 DIODE
PER CHANGE OVER CONTACT
COMMON
DIODE 1N4001
OR EQUIVALENT
1 CONTACT FOR ALL THERMOSTAT
USING THE SAME TRANSFORMER
CLOSE = REVERSE
DAMPER OPERATION MODE