T200
T250
THERMOSTAT WITH:
•
2 OUTPUTS
•
DAY-NIGHT MODE ( T250 ONLY )
TO OPEN THERMOSTAT COVER
•
Remove security screw on left side of thermostat cover.
•
Open up by pulling on the left side of thermostat.
SETPOINT ADJUSTMENT KNOB LIMITATION
Note: To limit the rotation of setpoint knob, adjust setpoint to desired value, then
insert stoppers in appropriate holes.
Horizontal model:
S1,S10 = No limitation
S3 à S8 = Setpoint limitations
Vertical model:
S7,S10 = No limitation
S1 to S7, or S12: Setpoint limitations
REMOTE SENSOR
It is possible to use a remote sensor ( for duct or room application) by connecting it to
pins no. 6 and 7. Inside sensor must be disconnected by removing jumper J4 inside the
thermostat.
SPECIFICATIONS
Operating Conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy:
( calibrated )
Ranges:
± 0.2 ° C ( ± 0.4 °F ) for low ranges
± 0.9 ° C ( ± 1.8 °F ) for high ranges
10 °C to 32 °C ( 50 °F to 90 °F )
-18 °C to 82 °C ( 0 °F to 180 °F )
Outputs: Isolated Triac: 30 Vac at ½ A max.
0 to 10 Vdc into 2KΩ resistance min.
0 / 5 Vdc at 20 mA max. for both outputs.
Power: 24 Vac -15%, +10% 50/60 Hz; 2 VA
THERMOSTAT INSTALLATION
A) Location:
1- Shouldn’t be installed on outside wall.
2- Must be installed away from any heat source.
3- Shouldn’t be affected by direct sun radiation.
4- Nothing must restrain vertical air circulation to the thermostat.
B) Installation:
1- Pull out cables 6” out of the wall.
2- Wall surface must be flat and clean.
3- Separate the thermostat and the base by pulling cover on the left side (same
as the security screw.)
4- Insert cable in the central hole of the base.
5- Align the base and mark the location of the two mounting holes on the
wall.
6- Install shields in the wall.
7- Insert screws in mounting holes on each side of the base.
DO NOT OVERTIGHTEN!
8- Open the cable protection 1 1/4 inch more or less.
9- Strip each wire 1/4 inch.
10- Insert each wire according to wiring diagram.
11- Reinstall the cover ( right side first ).
12- Install security screw.
Characteristics of remote sensor 47 KΩ.
180.0 °F 82.2 °C 5.494 Kohm 0.553 Volts
170.0 °F 76.7 °C 6.585 Kohm 0.648 Volts
160.0 °F 71.1 °C 7.933 Kohm 0.761 Volts
150.0 °F 65.6 °C 9.610 Kohm 0.893 Volts
140.0 °F 60.0 °C 11.700 Kohm 1.047 Volts
130.0 °F 54.4 °C 14.342 Kohm 1.225 Volts
120.0 °F 48.9 °C 17.682 Kohm 1.429 Volts
110.0 °F 43.3 °C 21.940 Kohm 1.659 Volts
100.0 °F 37.8 °C 27.412 Kohm 1.914 Volts
90.0 °F 32.2 °C 34.483 Kohm 2.191 Volts
80.0 °F 26.7 °C 43.704 Kohm 2.486 Volts
70.0 °F 21.1 °C 55.834 Kohm 2.791 Volts
60.0 °F 15.6 °C 71.866 Kohm 3.096 Volts
50.0 °F 10.0 °C 93.340 Kohm 3.393 Volts
40.0 °F 4.4 °C 122.298 Kohm 3.673 Volts
30.0 °F -1.1 °C 161.670 Kohm 3.927 Volts
20.0 °F -6.7 °C 215.805 Kohm 4.150 Volts
10.0 °F -12.2 °C 291.100 Kohm 4.341 Volts
0.0 °F -17.8 °C 396.830 Kohm 4.499 Volts
DAY-NIGHT MODE
An external contact closing between terminals 6 and 8 activates night mode. A LED
on the thermostat flashes continuously indicating night mode. By pressing the button
on the thermostat, day mode is reactivated. The thermostat returns to night mode when
pressing again the button, or automatically after a 4 hours delay.
Note: Terminals 6 and 8 can be connected together between thermostats.
DIMENSIONS
1
2
3
4
5
6
7
8
9
10
3.275"
( 83 mm )
4.5"
( 114 mm )
OR FROM BACK
BASE
WIRING
FROM TOP
SECURITY SCREW
HORIZONTAL MODEL
VICONICS
VERTICAL
MODEL
90
45
0
2.8"
( 71 mm )
COVER
2.8"
71 mm
135
180
F
4.5"
114 mm
1.275"
32 mm
028-2003 M:\1_BINDER\01_MICROSTAT\01_English\07_Manual\T250ME02.DOC 3/21/03
Page: 1 Page: 2 Page: 3
ORDER CODE
T200 - AB - CD - EF ( without day-night mode )
T250 - AB - CD - EF ( with day-night mode )
A Output no. 1 ( controlled device ) Type
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
6 0 to 10 Vdc actuator, voltage relay or "SCR" 0 to 10 Vdc
B Output no. 2 ( controlled device ) Type
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
6 0 to 10 Vdc actuator, voltage relay or "SCR" 0 to 10 Vdc
C Output no. 1 and 2 control mode
1 Heating, reverse acting, ( RA )
2 Cooling, direct acting, ( DA )
3 Heating, RA ( no. 1 ) and cooling, DA ( no. 2 )
4 Cooling, DA ( no. 1 ) and heating, RA ( no. 2 )
∗ Standard
Example: T250 - 53 - 31 - 12
One "SSR" 3-32 Volts heating output
and one normally close thermal valve cooling output.
Main sensor located inside the room
Adjustable setpoint. Scale 50 °F to 90 ° F.
∆ Note: These models have a vertical cover.
Note: Order remote sensors separately
WIRING
NOTE: WITH THE PROPER CODES, TERMINALS 5, 6 AND 8 CAN BE
WIRED TOGETHER BETWEEN EACH THERMOSTAT IF POLARITY IS RESPECTED
Power supply 24 Vac -15% +10%
50/60 HZ 2 VA
POWER SUPPLY 24 Vac.
24 VAC
COMMON
5
6
IMPORTANT: IF USING A COMMON TRANSFORMER
24VAC
RESPECT POLARITY (COMMON AND 24 VAC)
BETWEEN EACH THERMOSTAT
Day night mode T250 only
DAY NIGHT MODE
INPUT
DAY / NIGHT
8
6
COMMON
CLOSE =
NIGHT
SET BACK
1 CONTACT USED FOR ALL
THERMOSTAT USING THE
SAME TRANSFORMER
Output #1 code A= 1, 2, 3 & 4 Triacs
Output #2 code B= 1, 2, 3 & 4 Triacs
OUTPUT #1 AND/OR #2 USING SAME TRANSFORMER TO OUTPUT
OUTPUT
CONTACT
24 VAC
COMMON
AND / OR
3
1
4
2
5
24VAC
6
USE TERMINALS 3 & 4 FOR OUTPUT #1
USE TERMINALS 1 & 2 FOR OUTPUT #2
RELAY OR
THERMAL VALVE
24 VAC
Output #1 code A= 5 Pulsed 0/5 Vdc
Output #2 code B= 5 Pulsed 0/5 Vdc
OUTPUT #1 AND/OR #2 USING PULSED 0/5 Vdc
AND / OR
0/5 V
COMMON
24
6
USE TERMINALS 4 & 6 FOR OUTPUT #1
USE TERMINALS 2 & 6 FOR OUTPUT #2
SOLID STATE
RELAY
3-32 VDC
TRIGGER
LOAD
Output #1 code A or B= 6 Analog 0 to 10 Vdc
Output #2 code A or B= 6 Analog 0 to 10 Vdc
OUTPUT #1 AND / OR #2 USING 0 TO 10 Vdc
0 TO 10 Vdc
COMMON
24
AND / OR
6
USE TERMINALS 4 & 6 FOR OUTPUT #1
USE TERMINALS 2 & 6 FOR OUTPUT #2
ELECTRONIC ACTUATOR, SCR,
OR VOLTAGE RELAY
D Main control sensor location
1 Room, inside thermostat, or ( duct return air**)
2 Duct supply air**
** Order with S60 or S70
E Setpoint adjustment
1 User adjustable
2 Blind cover
F Scale
1
10 °C to 32 °C ∗ Standard
2
50 °F to 90 °F
3
-18 °C to 82 °C ∆
4
0 °F to 180 °F ∆
∗ Standard
∗ Standard
Output #1 code A= 1, 2, 3 & 4 Triacs
Output #2 code B= 1, 2, 3 & 4 Triacs
OUTPUT #1 AND/OR #2 USING RELAY WITH ISOLATED TRANSFORMER
AND / OR
OUTPUT
CONTACT
1
3
2
4
USE TERMINALS 3 & 4 FOR OUTPUT #1
USE TERMINALS 1 & 2 FOR OUTPUT #2
Page: 4 Page: 5 Page: 6
RELAY OR THERMAL
VALVE 24 VAC
R
24VAC
COMMON
EXTERNAL
SENSOR
NOTE: REMOVE
INTERNAL J4 JUMPER
Room or return control code D= 1,
Supply control code D=2
REMOTE MAIN CONTROL SENSOR
6
7
DUCT S60 OR S70
IMMERSION S90
VICONICS
ROOM S80
Remote main temperature control sensor