Viconics T186 User Manual

T186 Electronic Wall Sensor With Setpoint Adjustment
For Use With R842 Baseboard Relay
DESCRIPTION
The T186 series remote wall sensor with setpoint adjustment capability is specifically designed to be used with Viconics’ R842 electric baseboard relays. The unique design of the R842 permits solid state proportional and integral (PI) temperature control via the T186, resulting in exceptional temperature control accuracy (± 0.5 ºF).
The T186 can replace conventional electro-mechanical thermostats when used with the R842. Advantages include increased comfort and energy savings. Typical savings of 3-7% is possible and is attributed to the elimination of wasted energy inherent in less accurate electromechanical thermostats. Its solid state design permits the elimination of bimetal elements and mercury bulbs, which simplifies the installation since there is no anticipator and no levelling required. In addition, it is an environmentally friendly product.
A pleasing aesthetic design ensures a harmonious blend in most room decors. The T186 can be directly mounted to any flush vertical surface or to a standard 2” x 4” electrical mounting box via two mounting screws. Celsius and Fahrenheit models are available.
Using the T186 with the R842 relay will provide unmatched performance and give years of trouble-free installation.
Fig.1 - T186 wall sensor with setpoint adjustment
Fig.2 - R842 baseboard relay for electric heaters
Features Benefits
Electronic PI performance Increased comfort , accuracy, and energy savings
Solid state design Increased reliability
No bimetal elements No need to worry about anticipator settings
No mercury bulbs No levelling required; environmentally friendly
Fahrenheit or Celsius temperature scale Can be sold world-wide
Elegant aesthetic design Blends well in all environments
Mounts on any surface or standard electrical box Increased flexibility
TABLE 1: ORDER CODE
Scale Range Sensor model Replacement cover
5 °C to 30 °C T186C-01 C186C-01
40 °F to 90 °F T186F-01 C186F-01
WIRING DIAGRAM APPLICATION & WIRING
sensor
RED
BLACK
BLUE
Internal circuit
ON
2
1
T186
2 wire non polarized
3
2
1
Use proper dip switch setting on R842 relay
Refer to each wiring caution
Viconics T186 PI Wall Sensor
Refer to Fig.3 for wiring diagram of T186 with one R842 relay.
1 High voltage blue wire is always connected. R842
units are powered devices.
Load side
L1
L2 / N
Junction box
Fig.3 – Wiring diagram of T186 sensor with R842 relay
Set both switch on relay to
position
OFF
Note: refer to R842 manual for multiple relay application.
2 Provide overload protection and disconnect as
required.
3 Do not use 24 Vac terminal #1 as power supply to an
electronic thermostat. Use a separate transformer.
1
THERMOSTAT INSTALLATION
Important: All wiring must conform to local and national electrical code regulations. To avoid problems,
carefully follow the procedures below.
A) Location:
1- Should not be installed on an outside wall. 2- Must be installed away from any heat source. 3- Should not be installed near an air discharge grill. 4- Should not be affected by direct sun radiation. 5- Nothing must restrain vertical air circulation to
the thermostat.
Wiring terminal
Security screw
Fig. 4 - T186 wall sensor cover removal and wiring terminal location
TABLE 2: SPECIFICATIONS
Wall Anchor
Pull on plastic tab to releas e the printed circuit board
Flip printed circuit board to access mounting hole
Fig.5 - T186 wall sensor installation
Security Screw
B) Installation:
1- Remove security screw on the bottom of thermostat cover. 2- Open up by pulling on the bottom side of thermostat. 3- Pull out cables 6” out of the wall. 4- Wall surface must be flat and clean. 6- Insert cable in the central hole of the base. 7- Flip printed circuit board to access mounting hole 7- Align the base and mark the location of the two mounting
holes on the wall. Install proper side of base up. 8- Install anchors in the wall. 9- Insert screws in mounting holes on each side of the base.
DO NOT OVERTIGHTEN
10- Strip each wire 1/4 inch. 11- Insert each wire according to wiring diagram. 12- Gently push back into hole excess wring back into the wall. 13- Press back printed circuit board into place 14- Install the cover, top side 15- Install security screw.
Operating
Conditions:
Storage
Conditions:
-20°C to 50°C ( -4°F to 122°F ) 0 % to 95 % R.H. non-condensing
-40°C to 80°C ( -40°F to 176°F ) 0 % to 95 % R.H. non-condensing
Sensor: Local 10 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control
accuracy:
± 0.2 ° C ( ± 0.5 °F ) ( calibrated )
Ranges: 5 °C to 30 °C or 40 °F to 90 °F
DIMENSIONS
4.94" 125. 5 mm.
4.72" 119. 9 mm.
4.08" 103. 5 mm.
Fig.6 - T186 wall sensor dimensions
3.36" 85.8 mm.
3.20" 81.5 mm.
2.57" 65.2 mm.
All T186 series contr ols are for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and ver ific ations prior to shipment to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical panel designer to incorporate safety devic es ( such as relays, flow switch, thermal protections, etc… ) and/or alarm s ystems to protect the entire system against such catastr ophic failures. Any abusive use of the product will void the warranty.
NOTE: VICONICS RESERVES T HE RIGHT TO MAKE MODIFICATIONS WIT HOUT PRIOR NOTICE.
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, C anada H1P 3K9 www.viconics.com
LIT-T186X-E01