Viconics T160 User Manual

T110 T160
THERMOSTAT WITH:
1 OUTPUT
POWER LIMIT INPUT
+ 1 HIGHER SIGNAL OUTPUT
DAY-NIGHT MODE ( T160 ONLY )
TO OPEN THERMOSTAT COVER
Open up by pulling on the left side of thermostat.
THERMOSTAT INSTALLATION
A) Location:
1- Shouldn’t be installed on outside wall. 2- Must be installed away from any heat source. 3- Shouldn’t be affected by direct sun radiation. 4- Nothing must restrain vertical air circulation to the thermostat.
B) Installation:
1- Pull out cables 6” out of the wall. 2- Wall surface must be flat and clean. 3- Separate the thermostat and the base by pulling cover on the left side (same
as the security screw.) 4- Insert cable in the central hole of the base. 5- Align the base and mark the location of the two mounting holes on the
wall. 6- Install shields in the wall. 7- Insert screws in mounting holes on each side of the base.
DO NOT OVERTIGHTEN!
8- Open the cable protection 1 1/4 inch more or less. 9- Strip each wire 1/4 inch. 10- Insert each wire according to wiring diagram. 11- Reinstall the cover ( right side first ). 12- Install security screw.
SETPOINT ADJUSTMENT KNOB LIMITATION
Note: To limit the rotation of setpoint knob, adjust setpoint to desired value, then insert stoppers in appropriate holes.
Horizontal model:
S1,S10 = No limitation S3 à S8 = Setpoint limitations
Vertical model:
S7,S10 = No limitation S1 to S7, or S12: Setpoint limitations
REMOTE SENSOR
It is possible to use a remote sensor ( for duct or room application) by connecting it to pins no. 6 and 7. Inside sensor must be disconnected by removing jumper J4 inside the thermostat.
Characteristics of remote sensor 47 KΩ.
180.0 °F 82.2 °C 5.494 Kohm 0.553 Volts
170.0 °F 76.7 °C 6.585 Kohm 0.648 Volts
160.0 °F 71.1 °C 7.933 Kohm 0.761 Volts
150.0 °F 65.6 °C 9.610 Kohm 0.893 Volts
140.0 °F 60.0 °C 11.700 Kohm 1.047 Volts
130.0 °F 54.4 °C 14.342 Kohm 1.225 Volts
120.0 °F 48.9 °C 17.682 Kohm 1.429 Volts
110.0 °F 43.3 °C 21.940 Kohm 1.659 Volts
100.0 °F 37.8 °C 27.412 Kohm 1.914 Volts
90.0 °F 32.2 °C 34.483 Kohm 2.191 Volts
80.0 °F 26.7 °C 43.704 Kohm 2.486 Volts
70.0 °F 21.1 °C 55.834 Kohm 2.791 Volts
60.0 °F 15.6 °C 71.866 Kohm 3.096 Volts
50.0 °F 10.0 °C 93.340 Kohm 3.393 Volts
40.0 °F 4.4 °C 122.298 Kohm 3.673 Volts
30.0 °F -1.1 °C 161.670 Kohm 3.927 Volts
20.0 °F -6.7 °C 215.805 Kohm 4.150 Volts
10.0 °F -12.2 °C 291.100 Kohm 4.341 Volts
0.0 °F -17.8 °C 396.830 Kohm 4.499 Volts
DAY-NIGHT MODE
An external contact closing between terminals 6 and 8 activates night mode. A LED on the thermostat flashes continuously indicating night mode. By pressing the button on the thermostat, day mode is reactivated. The thermostat returns to night mode when pressing again the button, or automatically after a 4 hours delay.
Note: Terminals 6 and 8 can be connected together between thermostats.
POWER LIMIT INPUT
An external DC voltage applied between terminals no. 9 (+) et 6 (-), limits the power permitted to output 1 only when this output is programmed as heating. The following table gives the relationship between input voltage and the allowed power for output 1.
DC VOLTAGE
AT TERMINALS
NO 6 AND 9
0 volt 100 %
1 volt 100 % 2 volts 100 % 3 volts 100 % 4 volts 100 % 5 volts 100 % 6 volts 98 % 7 volts 68 % 8 volts 40 % 9 volts 18 %
10 volts 0 %
Note: Terminals 6 and 9 can be connected together between thermostats.
HIGHER SIGNAL OUTPUT
Output no 3 (terminal no. 10) produces a DC voltage 0 to 10 volts . This signal can be connected with signals from all other thermostats. Resulting voltage corresponds to higher demand of heating or cooling, depending of programming at each thermostat. This signal can also be used to control a modulating 0 to 10 VDC actuator. Resistive load between 2 K and 100 K is recommended.
Note: Terminals 6 and 10 can be connected together between thermostats.
SPECIFICATIONS
MAXIMUM
POWER
OUTPUT 1
Operating Conditions: 0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy:
( calibrated )
Ranges:
± 0.2 ° C ( ± 0.4 °F ) for low ranges ± 0.9 ° C ( ± 1.8 °F ) for high ranges
10 °C to 32 °C ( 50 °F to 90 °F )
-18 °C to 82 °C ( 0 °F to 180 °F )
Outputs: Isolated Triac: 30 Vac at ½ A max.
0 to 10 Vdc into 2K resistance min. 0 / 5 Vdc at 20 mA max. for both outputs.
Power: 24 Vac -15%, +10% 50/60 Hz; 2 VA
Page: 1 Page: 2 Page: 3
ORDER CODE
T110 - AB - CD - EF ( without day-night mode )
T160 - AB - CD - EF ( with day-night mode )
A Output no. 1 ( controlled device ) Type
1 Relay, thermal relay, two position motor Isolated Triac
2 Normally open thermal valve Isolated Triac
3 Normally close thermal valve Isolated Triac
4 "SSR" with 24 Vac input Isolated Triac
5 "SSR" with 3-32 Vdc input Pulsed 0/5 Vdc
DIMENSIONS
1
2
3 4
5
6 7
8 9
10
3.275"
( 83 mm )
OR FROM BACK
BASE
VERTICAL
MODEL
90
45
0
135
180
F
4.5"
114 mm
WIRING FROM TOP
SECURITY SCREW
HORIZONTAL MODEL
OUTPUT #1 USING RELAY WITH ISOLATED TRANSFORMER
RELAY OR THERMAL
OUTPUT
CONTACT
3
4
VALVE 24 VAC
R
24VAC
Output #1 code A= 1, 2, 3 & 4 Triacs
OUTPUT #1 USING SAME TRANSFORMER TO OUTPUT
OUTPUT
CONTACT
24 VAC
COMMON
3
4
5
24VAC
6
RELAY OR
THERMAL VALVE
24 VAC
B Output no. 2
0 Not available
C Output no. 1 and 2 control mode
1 Heating, reverse acting, ( RA )
2 Cooling, direct acting, ( DA )
D Main control sensor location
1 Room, inside thermostat, or ( duct return air**)
2 Duct supply air**
** Order with: S60 or S70 sensor
E Setpoint adjustment
1 User adjustable
2 Blind cover
F Scale
1
10 °C to 32 °C Standard
2
50 °F to 90 °F
3
-18 °C to 82 °C
4
0 °F to 180 °F
Example: T160 - 50 - 31 - 12 One "SSR" 3-32 Volts heating output . Main sensor located inside the room Adjustable setpoint. Scale 50 °F to 90 °F. The output no. 3 is a higher demand cooling signal.
Note: These models have a vertical cover.
NOTE: ORDER REMOTE SENSORS SEPARATELY
Standard
Standard
Standard
2.8"
( 71 mm )
COVER
2.8"
( 71 mm )
1.275" 32 mm
WIRING
VICONICS
4.5"
( 114 mm )
NOTE: WITH THE PROPER CODES, TERMINALS 5, 6, 8, 9 AND 10 CAN BE
WIRED TOGETHER BETWEEN EACH THERMOSTAT IF POLARITY IS RESPECTED
Power supply 24 Vac -15% +10%
50/60 HZ 2 VA
POWER SUPPLY 24 Vac.
24 VAC
COMMON
5
6
IMPORTANT: IF USING A COMMON TRANSFORMER
24VAC
RESPECT POLARITY (COMMON AND 24 VAC) BETWEEN EACH THERMOSTAT
Day night mode T160 only
DAY NIGHT MODE
INPUT
DAY / NIGHT
8
6
COMMON
CLOSE = NIGHT SET BACK
1 CONTACT USED FOR ALL THERMOSTAT USING THE SAME TRANSFORMER
Output #1 code A= 1, 2, 3 & 4 Triacs
Output #1 code A= 5 Pulsed 0/5 Vdc
OUTPUT #1 USING PULSED 0/5 Vdc
0/5 V
COMMON
4
6
Output #3 Analog 0 to 10 Vdc
OUTPUT #3 USING 0 TO 10 Vdc
0 TO 10 Vdc
COMMON
0 TO 10 VDC
10
6
Remote main temperature control sensor
Room or return control code D= 1,
Supply control code D=2
REMOTE MAIN CONTROL SENSOR
COMMON
EXTERNAL SENSOR
NOTE: REMOVE INTERNAL J4 JUMPER
6
7
Power limit input Analog 0 to 10 Vdc
POWER LIMIT INPUT USING 0 TO 10 Vdc
0 TO 10 Vdc LIMIT INPUT
COMMON
0 TO 10 Vdc
9
6
SOLID STATE
RELAY
3-32 VDC TRIGGER
LOAD
ELECTRONIC ACTUATOR, SCR, OR VOLTAGE RELAY
DUCT S60 OR S70
IMMERSION S90
ENERGY
MANAGEMENT
SYSTEM
VICONICS
ROOM S80
Page: 4 Page: 5 Page: 6
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.com
028-2002 \\NTS40PDC02\BINDERS\1_BINDER\01_MICROSTAT T100-T200-T500\01_English\07_Manual\T160ME04.DOC 9/28/04
Loading...