Viconics R850 Installation Guide

Innovative Control Solutions For Your Needs
R850 SERIES
R850V STEP CONTROLLER
WITH INTEGRATED VERNIER STAGE
Pulsed or analog 0 to 10 Vdc vernier stage
4 or 8 step models
Up to 16 stage total with a slave unit
Test button
DESCRIPTION
An integrated vernier control output will give a precise and full modulation of the load from 0 to 100% of the total capacity.
FEATURES AND BENEFITS
Microcomputer-based design Accuracy and reliability Adjustable inter-stage delay Provides flexibility in
replacement applications
Adjustable Vernier ratio Simplifies design of
proportional stage Choice of pulsed or analog Vernier output
Permits use of SCR or lower
cost SSR Up to 16 stages One product family can handle
all applications Choice of LIFO or FIFO sequencing
Increased flexibility of FIFO
permits even use of contactors Test button Quick troubleshooting
MODELS AVAILABLE
The R850-V is available in 2 models
R850V-4 4 stage unit
R850V-8 8 stage unit
If more than 8 stage are required, the R850-V8 can be used as a master unit with another R850V as a slave unit. Adding another unit ( R850-V4 or R850-V8 ) can bring the total step number up to 12 or 16.
OVERRIDE TEST BUTTON
The override test button can be used to by-pass the interstage delay and bring on all stage at one time. This simplifies the verification of configured maximum number of stage.
A status LED per step will come on for each of the configured stage.
SPECIFICATIONS
Operating
Conditions:
0°C to 80°C ( 32°F to 176°F ) 0 % to 95 % R.H. non-condensing
Relay outputs: Isolated relay 30 Vac @ 1.0 amps. max. per
output, up to a maximum of 4.0 amps. total per R850 controller. See application note 02.
Vernier stage: Vdc pulsed: 6 Vdc, 30 mA max.
0 to 10 Vdc 5 mA max.
Input
0 to 10 Vdc into 10 KΩ minimum
impedance:
Power supply: 24 Vac -15%, +10% 50/60 Hz; 4 VA
Use a Class 1 ( properly fused ) or Class 2, CSA or UL recognized transformer for power supply & relay outputs.
Specifications and equipment are subject to change without prior notice.
INPUT SIGNAL
The R850V has four INPUT dip switch (S1 to S4) to select the control signal input: They are compatible with industry standard signals.
DIP SWITCH ADJUSTMENTS & WIRING CONTROL INPUT
ON
21 43
I
NPU
(1-4) Input
signal sele ction
0 to 10 Vdc
4 to 20 mA
0 to 135
ON
ON
ON
R850V-8
1 W
S
T
21 3 4
21 3 4
21 3 4
ON
421 3 56
CONTR
(3-6) Number of steps selection
(see next pages for details)
(2) Vernier stage selection
OFF = 0 to 10 Vdc (SCR) ON = Vdc pulsed signal (SSR)
(1) Sequence of operation (LIFO or FIFO)
OFF = L IFO (Last IN, First OUT) ON = FIF O (Fir st IN, First OUT)
2W
S
L
O
ON ON
(1-4) Input
signal sele ction
0 to 10 Vdc
4 to 20 mA
0 to 135
1 32 44
I
NPU
ON
1
ON
1 32 4
ON
1 234
R850V-4
W1 S
T
CONTR
32 4
2WS
3122 4
(3-4) Number of steps selection
(see next pages for details)
(2) Vernier stage selection
OFF = 0 to 10 Vdc (SCR) ON = Vdc pulsed signal (SSR)
(1) Sequence of operation (LIFO or FIFO)
OFF = L IFO (Last IN, First OUT) ON = FIF O (Fir st IN, First OUT)
L
O
Input Signal Switch Switch #1 Switch #2 Switch #3 Switch #4
0 to 10 Vdc control signal ( 2 to 10 Vdc control range ) Off Off Off On 4 to 20 mA control signal Off Off On Off 0 to 135 control signal
On On Off Off
If a slave unit is used, wire the control signal input to the master unit only
2 To 10 Vdc Or 0 To 10 Vdc Stand Alone Thermostat
y
y
y
2
y
( Power To The Thermostat Is Supplied By The R850V )
0 To 135 Stand Alone Thermostat
1
123ON4
123
I
P
U
N
2 Vdc = 0% capacity
10 Vdc = 100% capacit
Common
24 Vac
0 to 10 Vdc
output
2 To 10 Vdc Or 0 To 10 Vdc From D.D.C.
Building Automation System
1
123ON4
123
I
PUT
N
2 Vdc = 0% capacity
10 Vdc = 100% capacit
-
+
T
0 Ohms = 0% capacity
135 Ohms = 100% capacit
Building Automation System
4 mA = 0% capacity
0 mA = 100% capacit
1
123ON4
123
W
R
B
I
4 To 20 mA From D.D.C.
1
123ON4
123
­+
PUT
N
I
T
P
U
N
24 VAC POWER & RELAY OUTPUT WIRING
The wiring diagrams are for the R850V-8 models with 8 outputs. The wiring for the R850V-4 is the same except that the unit only has 4 outputs.
Terminals
Screw terminal & connector #1 Common Screw terminal & connector #2 24 Vac Screw terminal & connector #3 Control Signal input
It is not necessary to ground any leg of the transformer to earth with the controller card.
The controller uses internally a half wave rectifier bridge. On 0 to 10 Vdc control signal, the reference of the control signal is the
Common of the power supply of the SCR controller card.
Use a Class 1 ( properly fused ) or Class 2, CSA or UL recognized transformer.
4 STAGE APPLICATION R850V-4
24 Vac contactor coils
C1
C2 C3 C4
V
S
C8
C7
C6
C5
C4
C3
C2
C1
C
POWER
12 3
R850V-4
23ON4
1
I
123
P
N
120
90
123ON4
CONTROL
60
30
T
U
200
VR2
150
DELAY(s)
RATIO(%)
100
COM
JUNE 99
REV.1
001-0102
TEST
of stage
Switch #3 Switch #4
1 Off Off 2 On Off 3 Off On 4 On On
2
R850V-4 Control SwitchNumber
Loading...
+ 4 hidden pages