ELECTRONIC HUMIDISTAT: H270
• ONE OR TWO STAGES
• HUMIDITY SUPPLY HIGH LIMIT
• OUTDOOR TEMPERATURE RESET
DESCRIPTION
The H270 series low voltage, microcomputer-based PI
(proportional and integral) humidistats are designed for
accurate humidification and/or dehumidification control
in commercial applications such as: hospitals, schools,
office buildings, retail stores, museums, computer
rooms, etc.
The H270 series is available with one or two outputs
for maximum flexibility. Outputs can be of the following
type: proportional, on/off, and pulse width modulation
(PWM). Two additional inputs are provided in order to
perform unique functions: humidity setpoint reset
based on outdoor air temperature and proportional
high limit override. The former function minimizes
condensation on window surfaces during cold outdoor
temperatures by automatically lowering the humidity
setpoint as the outdoor temperature drops. The latter
function improves accuracy and safety by throttling
back the humidifier control output if the humidity level
reaches unacceptably high levels.
There are many different types of mounting
configurations available. Sensing options include
remote duct and room as well as integral room and
duct. Setpoint adjustment can be either concealed or
exposed, adding even more versatility to the product.
Exposed models feature internally selectable minimum
and maximum setpoint knob stops.
In order to facilitate periodic recalibration, the H270
series contains a unique autocal key, which permits
instant recalibration (see dimension drawing on page 5
for location).
Each humidistat is computer calibrated and factory
programmed with default parameters. All control
parameters (such as proportional band, stage
differential, etc.) may be changed in the field with the
H263 programming tool without having to remove the
thermostat cover. The H263 also doubles as a
diagnostic tool and indicates the status of all the inputs
and outputs, and will reduce troubleshooting time by
quickly identifying the specific problem.
Fig.1 Wall mounted humidistat
Features Benefits
• Microcomputer-based design with PI algorithm ⇒
• One or two outputs ⇒
• On/off and/or proportional outputs ⇒
• Direct or reverse acting outputs ⇒
• Integrated and remote sensing ⇒
• Autocal button ⇒
• Concealed or exposed set point ⇒
• Ouput signal to digital indicating devices ⇒
• Optional H263 diagnostic tool with digital display ⇒
• Sensor failure protection ⇒
• Humidity setpoint reset based on outdoor temp. ⇒
• Proportional high limit override ⇒
• CE approved ⇒
Exceptional accuracy
Controls humidification and dehumidification equipment
Greater flexibility
Controls humidification and dehumidification equipment
Larger choice of mounting options
Permits instant recalibration
Can be used in a large variety of environments
Increases functionality of product
Simplifies troubleshooting
Prevent water dammage
Prevents window condensation in colder climates
Prevents costly damage due to over-humidification
Can be sold in European markets
1
TABLE 1: ORDER CODE
WIRING
H270 - A-B - C-D - E-F G-H
A Output no. 1 ( controlled device )
1 ON/OFF (15 min. time based)
4 (PWM) 24 VAC
5 (PWM) 5 VDC
6 Analog 0-10 Volts DC
B Output no. 2 ( controlled device )
0 Not installed
1 ON/OFF (15 min. time based)
4 (PWM) 24 Volts AC
5 (PWM) 5 Volts DC
6 Analog 0-10 Volts DC
8 Signal transmitter (0-10 VDC)
♦
(1V= 10% , 9V-90%)
9 Signal transmitter (0-5 VDC)
♦
(0.5V= 10% ; 4.5 V=90%)
C Output no. 1 and 2 control mode
1Humidify
2 Dehumidify
3 Humidify ( no. 1 ) and dehumidify ( no. 2 )
4 Dehumidify ( no. 1 ) and humidify ( no. 2 )
D Main sensor location Sensor
0 Not installed None
1 Inside humidistat ( Local ) H50
2 Duct mount ( stat on duct ) H60
3 Duct mount ( stat on wall ) H71
4 Remote wall mount H80
E Setpoint adjustment
1 User adjustable
2 Blind cover
F Future option
0 Unused
G Duct humidity supply high limit
0 Without sensor
3 With H71 duct mounted humidity sensor
H Outdoor temperature reset input
0 Without sensor
1 With S71 duct mounted outdoor temp.
sensor
Example: H270 - 61 - 32 – 10 - 31
One “SCR” 0 to 10 volts humidify output and one relay
dehumidify output. Humidistat and sensor are duct mount.
Setpoint is user adjustable. A remote duct mounted high limit
is installed in the supply. An outdoor temperature sensor is
installed to reset the humidity setpoint.
♦ Resolution: 0.5 % for retransmit only
See sensor specications for dimensions of sensors
Note: the complete order code includes the sensor that will be
shipped with the humidistat.
2 ON/OFF OUTPUTS
Single transformer
+
+
BLACK
WHITE
RED
BLACK
WHITE
RED
RELAY
or 24 Vac VALVE
-
RELAY
or 24 Vac VALVE
-
HUMIDITY SENSOR
FOR CONTROL
HUMIDITY SENSOR
HIGH LIMIT
S71
TEMPERATURE SENSOR
24 Vac
INPUT
SIGNAL
RESET
+10 Vdc
1
2
3
4
5
6
7
8
9
10
24 Vac
OUTPUT #2
ON / OFF
OUTPUT #1
ON / OFF
COMMON
MAIN SENSOR
HIGH LIMIT
HUMIDITY
OUTDOOR
Fig.2: Wiring diagram with single transformer
Multiple transformers
24 Vac
+
+
BLACK
WHITE
RED
BLACK
WHITE
RED
RELAY
or 24 Vac VALVE
-
RELAY
or 24 Vac VALVE
-
HUMIDITY SENSOR
FOR CONTROL
HUMIDITY SENSOR
HIGH LIMIT
S71
TEMPERATURE SENSOR
24 Vac
INPUT
SIGNAL
RESET
+10 Vdc
1
2
3
4
5
6
7
8
9
10
24 Vac
24 Vac
OUTPUT #2
ON / OFF
OUTPUT #1
ON / OFF
COMMON
MAIN SENSOR
HIGH LIMIT
HUMIDITY
OUTDOOR
Fig.3: Wiring diagram with multiple transformers
Note: both of the above wiring diagrams show how to
wire output of type 1, 2, 3 and 4 (switched 24 vac).
For outputs of type 5 and 6 (vdc out) refer to wiring diagrams
3 and 4 on next page.
2
2 PROPORTIONNAL OUTPUT
1 PROPORTIONNAL AND 1 TRANSMITTER OUTPUT
OUTPUT # 2
0 to 5 Vdc
0 to 10 Vdc
TRANSMITTER
OUTPUT # 1
0 to 10 Vdc
COMMON
MAIN SENSOR
HIGH LIMIT
SENSOR
OUTDOOR
TEMP. SENSOR
+10 Vdc
Fig.5: Wiring diagram with one analog and one transmitter output
24 Vac
INPUT
1
2
3
4
5
6
7
8
9
10
24 Vac
+
DDC SYSTEM
or METER
-
ELECTRONI C MOTOR
+
or "SCR"
-
BLACK
WHITE
RED
HUMIDITY SENSOR
FOR CONTROL
24 Vac
INPUT
N/A
N/A
1
2
3
4
5
6
7
8
9
10
24 Vac
OUTPUT #2
0 to 10 Vdc
OUTPUT #1
0 to 10 Vdc
COMMON
MAIN SENSOR
+10 Vdc
Fig.4: Wiring diagram with two analog outputs
+
-
+
-
BLACK
WHITE
RED
ELECTRONIC MOTOR
or "SCR"
ELECTRONIC MOTOR
or "SCR"
HUMIDITY SENSOR
FOR CONTROL
APPLICATION EXAMPLE:
Steam humidification system controlled by a 0 to 10 Vdc valve wired to output #1. Remote humidity display using 0 to 5 Vdc signal is wired to
output #2. The humidity s ensor is located in the return air duct. A proportional high limit humidity s ensor is installed in the supply duct. An
outdoor temperature sensor is installed in the fresh air duct.
Humidistat model number: H270-69- 13-10-31
Fig.6: Application ex ample
3