Viconics H270 User Manual

ELECTRONIC HUMIDISTAT: H270
ONE OR TWO STAGES
HUMIDITY SUPPLY HIGH LIMIT
OUTDOOR TEMPERATURE RESET
DESCRIPTION
The H270 series low voltage, microcomputer-based PI (proportional and integral) humidistats are designed for accurate humidification and/or dehumidification control in commercial applications such as: hospitals, schools, office buildings, retail stores, museums, computer rooms, etc.
The H270 series is available with one or two outputs for maximum flexibility. Outputs can be of the following type: proportional, on/off, and pulse width modulation (PWM). Two additional inputs are provided in order to perform unique functions: humidity setpoint reset based on outdoor air temperature and proportional high limit override. The former function minimizes condensation on window surfaces during cold outdoor temperatures by automatically lowering the humidity setpoint as the outdoor temperature drops. The latter function improves accuracy and safety by throttling back the humidifier control output if the humidity level reaches unacceptably high levels.
There are many different types of mounting configurations available. Sensing options include remote duct and room as well as integral room and duct. Setpoint adjustment can be either concealed or exposed, adding even more versatility to the product. Exposed models feature internally selectable minimum and maximum setpoint knob stops. In order to facilitate periodic recalibration, the H270 series contains a unique autocal key, which permits
instant recalibration (see dimension drawing on page 5 for location).
Each humidistat is computer calibrated and factory programmed with default parameters. All control parameters (such as proportional band, stage differential, etc.) may be changed in the field with the H263 programming tool without having to remove the thermostat cover. The H263 also doubles as a diagnostic tool and indicates the status of all the inputs and outputs, and will reduce troubleshooting time by quickly identifying the specific problem.
Fig.1 Wall mounted humidistat
Features Benefits
Microcomputer-based design with PI algorithm
One or two outputs
On/off and/or proportional outputs
Direct or reverse acting outputs
Integrated and remote sensing
Autocal button
Concealed or exposed set point
Ouput signal to digital indicating devices
Optional H263 diagnostic tool with digital display
Sensor failure protection
Humidity setpoint reset based on outdoor temp.
Proportional high limit override
CE approved
Exceptional accuracy
Controls humidification and dehumidification equipment
Greater flexibility
Controls humidification and dehumidification equipment
Larger choice of mounting options
Permits instant recalibration
Can be used in a large variety of environments
Increases functionality of product
Simplifies troubleshooting
Prevent water dammage
Prevents window condensation in colder climates
Prevents costly damage due to over-humidification
Can be sold in European markets
1
TABLE 1: ORDER CODE
WIRING
H270 - A-B - C-D - E-F G-H
A Output no. 1 ( controlled device )
1 ON/OFF (15 min. time based) 4 (PWM) 24 VAC 5 (PWM) 5 VDC 6 Analog 0-10 Volts DC
B Output no. 2 ( controlled device )
0 Not installed 1 ON/OFF (15 min. time based) 4 (PWM) 24 Volts AC 5 (PWM) 5 Volts DC 6 Analog 0-10 Volts DC 8 Signal transmitter (0-10 VDC)
(1V= 10% , 9V-90%)
9 Signal transmitter (0-5 VDC)
(0.5V= 10% ; 4.5 V=90%)
C Output no. 1 and 2 control mode
1Humidify 2 Dehumidify 3 Humidify ( no. 1 ) and dehumidify ( no. 2 ) 4 Dehumidify ( no. 1 ) and humidify ( no. 2 )
D Main sensor location Sensor
0 Not installed None 1 Inside humidistat ( Local ) H50 2 Duct mount ( stat on duct ) H60 3 Duct mount ( stat on wall ) H71 4 Remote wall mount H80
E Setpoint adjustment
1 User adjustable 2 Blind cover
F Future option
0 Unused
G Duct humidity supply high limit
0 Without sensor 3 With H71 duct mounted humidity sensor
H Outdoor temperature reset input
0 Without sensor 1 With S71 duct mounted outdoor temp.
sensor
Example: H270 - 61 - 32 – 10 - 31 One “SCR” 0 to 10 volts humidify output and one relay dehumidify output. Humidistat and sensor are duct mount. Setpoint is user adjustable. A remote duct mounted high limit is installed in the supply. An outdoor temperature sensor is installed to reset the humidity setpoint.
Resolution: 0.5 % for retransmit only
See sensor specications for dimensions of sensors
Note: the complete order code includes the sensor that will be shipped with the humidistat.
2 ON/OFF OUTPUTS
Single transformer
+
+
BLACK
WHITE
RED
BLACK
WHITE
RED
RELAY or 24 Vac VALVE
-
RELAY or 24 Vac VALVE
-
HUMIDITY SENSOR
FOR CONTROL
HUMIDITY SENSOR
HIGH LIMIT
S71
TEMPERATURE SENSOR
24 Vac
INPUT
SIGNAL
RESET
+10 Vdc
1 2
3 4
5 6
7
8
9
10
24 Vac
OUTPUT #2
ON / OFF
OUTPUT #1
ON / OFF
COMMON
MAIN SENSOR
HIGH LIMIT
HUMIDITY
OUTDOOR
Fig.2: Wiring diagram with single transformer
Multiple transformers
24 Vac
+
+
BLACK
WHITE
RED
BLACK
WHITE
RED
RELAY or 24 Vac VALVE
-
RELAY or 24 Vac VALVE
-
HUMIDITY SENSOR
FOR CONTROL
HUMIDITY SENSOR
HIGH LIMIT
S71
TEMPERATURE SENSOR
24 Vac
INPUT
SIGNAL
RESET
+10 Vdc
1 2
3 4
5 6
7
8
9
10
24 Vac
24 Vac
OUTPUT #2
ON / OFF
OUTPUT #1
ON / OFF
COMMON
MAIN SENSOR
HIGH LIMIT
HUMIDITY
OUTDOOR
Fig.3: Wiring diagram with multiple transformers
Note: both of the above wiring diagrams show how to wire output of type 1, 2, 3 and 4 (switched 24 vac). For outputs of type 5 and 6 (vdc out) refer to wiring diagrams 3 and 4 on next page.
2
2 PROPORTIONNAL OUTPUT
1 PROPORTIONNAL AND 1 TRANSMITTER OUTPUT
OUTPUT # 2
0 to 5 Vdc
0 to 10 Vdc
TRANSMITTER
OUTPUT # 1
0 to 10 Vdc
COMMON
MAIN SENSOR
HIGH LIMIT
SENSOR
OUTDOOR
TEMP. SENSOR
+10 Vdc
Fig.5: Wiring diagram with one analog and one transmitter output
24 Vac
INPUT
1 2
3 4
5 6
7
8
9
10
24 Vac
+
DDC SYSTEM or METER
-
ELECTRONI C MOTOR
+
or "SCR"
-
BLACK
WHITE
RED
HUMIDITY SENSOR
FOR CONTROL
24 Vac
INPUT
N/A
N/A
1 2
3 4
5 6
7
8 9
10
24 Vac
OUTPUT #2
0 to 10 Vdc
OUTPUT #1
0 to 10 Vdc
COMMON
MAIN SENSOR
+10 Vdc
Fig.4: Wiring diagram with two analog outputs
+
-
+
-
BLACK
WHITE
RED
ELECTRONIC MOTOR or "SCR"
ELECTRONIC MOTOR or "SCR"
HUMIDITY SENSOR
FOR CONTROL
APPLICATION EXAMPLE:
Steam humidification system controlled by a 0 to 10 Vdc valve wired to output #1. Remote humidity display using 0 to 5 Vdc signal is wired to output #2. The humidity s ensor is located in the return air duct. A proportional high limit humidity s ensor is installed in the supply duct. An outdoor temperature sensor is installed in the fresh air duct.
Humidistat model number: H270-69- 13-10-31
Fig.6: Application ex ample