H263
Programming tool
for Humidistats
Use C263H insert and place it over the C263 programmer f or use of
programmer with Humidistats.
CORRESPONDING DISPLAYED VALUES WHEN
CALIBRATING HUMIDISTATS
LED INDICATORS
DEV:
Deviation (Humidity - Setpoint) (DEV)
HUM.:
Humidity reading in the room or in the duct (TEMP)
SETPOINT:
Humidity setpoint (Adjusted or programmed) SETPOINT)
HUM. LIMIT :
Supply high limit humidity reading (POWER LIMIT)
HUM. LIMIT wih Decimal point :
Fraction of supply humidity reading.
OUTPUTS #1,#2:
Output values (0 à 100%) (OUT #1, OUT #2)
OUT. TEMP.:
Outside temperature (OUT #3)
All other indicators are not used.
PROGRAMMING
Push “ORDER CODE” key to access order code AB, use “∧” and “∨” keys to adjust the value. Refer to product literature to
determine desired code. Push “ORDER CODE” key again to access CD, EF and GH. To download the new the order code into
the humidistat, push and hold “PROG.” key for 3 seconds, H263 will turn OFF then ON.
To access “SETUP” push “VIEW” and “∨” simultaneously. First parameter displayed is “Db”, use “∧” and “∨” keys to adjust the
value. Refer to TABLE 1 on the next page for setting options. Push “VIEW” again to go to next parameter. . To download the
new the parameters into the humidistat, push and hold “PROG.” key for 3 seconds, H263 will turn OFF then ON.
For “CALIBRATION” use the AUTOCAL PROCEDURE explained on next page.
H270 HUMIDITY SETPOINT RESET BY OUTSIDE TEMPERATURE
HUMIDITY SETPOINT RESET BY OUTSIDE TEMPERATURE
OUTSIDE AIR TEMPERATURE
Note:
32°F
14°F
-4°F
-20°F
-40°F
rE, HT , LT
20%
parameters can be changed with C263 programming tool
rE
= 20%
HT = 32°F
LT = -20°F
25%
30% 40%
35%
%RH
USER
SETPOINT
45%
The H270 humidistat has an optional outdoor
temperature sensor. This sensor is used to
reset the humidity setpoint during the cold
season to minimize condensation on windows
and building structures.
When the outdoor temperature falls below the
selected high temperature, parameter HT
(32°F in the example beside), the humidity
setpoint will start to decrease. The lowest
humidity setpoint will be reached at selected
low temperature, param eter LT (-20°F).
The setpoint decrease from original setpoint
down to the lowest setpoint determined by the
parameter rE. In the exam ple beside, rE was
set to 20%, therefore the humidity setpoint
dropped from 45% to 20%.
If you don’t use the outdoor reset feature, put
a jumper between terminals 6 and 9 (supplied
with the humidistat.)
1
TABLE 1: H263 HUMIDISTAT PROGRAMMING TOOL
CODE VALUES
Db 0 to 40 % R.H. 25% R.H. Dead Band between humidific ation and dehumidification.
SL 30 to 100 % R.H. 85% R.H. Supply Limitation: High humidity limit in the supply duct (H270 only)
d2
Pb
o1
o2
cc
t1
t2
rA
Ca
hA 0 à 127
it 1 to 99 = 1 TO 99 MINUTES 60 "Integral time" Error integration time.
Lt -40 à +40 °C (-40 à 105 °F) -20 °F
Ht -40 à +40 °C (-40 à 105 °F) 32 °F
rE 1 à 99 % R.H. 20 % R.H.
0 to 199 % (of pr oportional
band)
0 = 1.6 % R.H.
1 = 3.2 % R.H.
2 = 6.4 % R.H.
3 = 12.8 % R.H.
4 = 25.6 % R.H.
0 = Humidification
1 = Dehumidification
0 = Humidification
1 = Dehumidification
2 = Without integral
3 = With integral
0 = On/off
1 = 8 minutes
2 = 1 second
0 = On/off
1 = 8 minutes
2 = 1 second
0 = °C
1 = °F
± 13 %
DEFAULT
VALUE
100% Differential for output #2": S hift f or output 2 relative to output 1
2= 6.4%
R.H.
3 "Control Code"
1 DO NOT
CHANGE
DESCRIPTION
Proportional Band
"Output #1" Action for output no 1
"Output #2" Action for output no 2
"Time #1" Time period for out put no 1
"Time #2" Time period for out put no. 2
"Range" Temperature Scale
Calibration ( deviation mode: DO NOT MODIFY: USE AUTOCAL PROCEDURE;
FOR H100 TRANSMITTER, USE THE ZERO POTENTIOMETER ON THE
TRANSMITTER.
"Hardware ass embly" Code r elated to thermostat model and entered at initial setup
at the factory.
"Lower temper ature" minimum outside temperature for setpoint reset (model H270
only)
"Higher temper ature" maximum outside temperat ure for setpoint reset (model H270
only)
"Reset” Minimum humidity value ( % HR ) (model H270 only)
Example: rE = 20%. Humidity setpoint will be reset from select ed setpoint to 20%,
from Ht to Lt
AIR SUPPLY HIGH LIMIT HUMIDITY SENSOR
The H270 includes a high limit circuit. This allows the use of a second
humidity sensor to limit the humidity in the supply air. Input signal goes to
100%
terminals #8 on the humidistat. High limit setpoint is preprogrammed at 85%
(parameter SL). It can be readjusted using the H263 service tool.
50%
If you don’t use the high limit feature, connect a 4.7 Meg Ω, ¼ watt resistor
between terminals 8 and 10 (supplied with the humidistat.)
0%
Remember: this high limit function is not a safety device. For critical
situations, provide installation with normal protections required to ensure a
safe operation.
CONTROL OUTPUT LEVEL
SUPPLY HUMIDITY
85%
Proportional high limit override signal.
AUTOCAL PROCEDURE
The programmer is not needed to calibrate the humidistat. Follow instructions below:
1. Measure the room humidity near the Viconics humidistat with an accurate hygrometer.
2. Turn the humidistat set point dial to match the reading of the hygrometer.
Push and hold the Autocal button for more than 3 seconds or until the internal red light turns On and Off.
Be careful when recalibrating the H270. Since the outdoor temperature resets the setpoint, the displayed value on the programmer
may be different from the adjusted setpoint. To avoid confusion, put a jumper across the sensor (pins 6 and 9) before doing
calibration. Calibrate the humidistat; then remove the jumper.