Viconics H100 User Manual

ELECTRONIC HUMIDITY
TRANSMITTER: H100
DESCRIPTION
The H100 series low voltage, microcomputer-based PI (proportional and integral) humidity transmitters are designed for accurate humidity and/or dehumidification control in non-corrosive commercial applications such as: hospitals, schools, office buildings, retail stores, museums, computer rooms, etc.
The H100 series is available with 0 to 5 Vdc or 10 Vdc output signal.
Each transmitter is computer calibrated and factory programmed with default parameters.
TABLE 1: ORDER CODE
H100 - AB - CD
AB Output Type
08 Analog 0 to 10 Vdc 0 to 10 Vdc
09 Analog 0 to 5 Vdc 0 to 5 Vdc
CD Main sensor location Sensor
01 Wall mounted transmitter H50
02 Duct mounted transmitter H71
Features Benefits
Microcomputer-based
design with PI algorithm
Integrated and remote
sensing
Ouput signal to digital
indicating devices
CE approved
Exceptional accuracy
Larger choice of
mounting options
Increases functionality
of product
Can be sold in
European markets
Example: H100 - 08 – 02 One 0-10 VDC transmitter, duct mounted.
Fig.1 Wall mounted transmitter
CALIBRATION OF TRANSMITTER
The transmitter is factory calibrated. However, it can be field recalibrated by using the ( -10%, 0%, +10% ) potentiometer inside the transmitter to adjust the zero (see page 2 for location). The transmitter is already factory calibrated to the center of the potentiometer. To recalibrate the transmitter to the factory preset, return the potentiometer to the 0% adjustment.
To calibrate, read the humidity with a precision hygrometer. If the reading is lower than the value you get from the sensor, remove transmitter from the base, turn the potentiometer by the amount of error in the negative scale. If the value is higher, turn the potentiometer in the positive scale. We recommend that you don’t try to adjust the two potentiometers on the sensor unless you have access to two points of calibration. If you really need to recalibrate the sensor, please return the transmitter to the factory.
1
TABLE 2: TRANSMITTER ACCESSORIES
H50 Internal humidity sensor for H100 transmitter and for H80 remote wall sensor.
H60 Duct humidity sensor to mount directly onto the back of any H100 transmitter.
H71 Duct humidity sensor to mount directly onto the supply or return of the ventilation duct.
H80 Wall humidity sensor to mount in any remote location.
008-0089 Replacement lexan (cover sticker) for H100 transmitter
024-0048 Transmitter replacement base with connector (H50 internal humidity sensor not included).
H50 INTERNAL SENSOR H60 DUCT SENSOR
This humidity sensor can be mounted directly on 024-0048 transmitter base.
H71 REMOTE DUCT SENSOR H80 REMOTE WALL SENSOR
This humidity sensor can be mounted directly onto the back of any H100 transmitter, with the supplied hardware. This transforms the transmitter into a duct-mounted transmitter.
WARNING:
Where failure or malfunction of H100 series transmitters could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of H100 transmitters must be incorporated into and maintained as part of the control system.
LOCATION OF CALIBRATION
POTENTIOMETER
This humidity sensor can be mounted directly onto the supply or return of the ventilation duct. The H100 may be located on the wall with humidity sensing from the remote H71 sensor location.
This humidity sensor can be wall mounted in any remote location. The transmitter may be located on the duct or other location, with humidity sensing from the H80 sensor location.