Viconics C1013 User Manual

C1013
Electronic Thermostat
APPLICATIONS
VAV and by-pass units control floating output
Heating/Cooling change over with supply temp. sensor
Single stage of auxiliary reheat
with modulating tri-state
ADVANCED DESIGN AND PI CONTROL
Advanced PI control thermostats provides precise temperature control and eliminates wasted energy caused by the typical On / Off cycling in conventional thermostats. Thus the room occupant is able to reduce the thermostat setpoint to the lowest comfortable setting. The result is energy savings ranging from 5% to 10%.
DIMENSIONS
Specifications and equipment are subject to change without prior notice.
BASE
WIRING
FROM BACK
SECURITY SCREW
3.275"
( 83 mm )
COVER TOP
80
70
60
2.8"
( 71 mm )
2.8"
( 71 mm )
90
F
50
4.5"
114 mm
1.275" 32 mm
COVER INSIDE
5432176
SCREW TERMINALS
2.8"
( 71 mm )
COVERS
Factory standard scale is 10°C to 32°C for horizontal mounting. °F & °C scales are available on special order for horizontal or vertical mounting. The thermostat and the terminals are an integral part of the cover. The cover hooks onto the base for easy service and is locked in place using a security screw.
MODULATING TRI-STATE FLOATING OUTPUT
For use with tri-state floating actuator (CW/Off/CCW) having a 1 to 2 minutes timing per 90° of rotation. This is a true multi positions modulating output. It gives performances which is equivalent to more expensive 0 to 10 Vdc type output.
HEATING / COOLING CHANGE OVER
The output is normally cooling but can be reversed to heating mode with 2 different methods:
Auto change over to heating mode with the supplied sensor.
1 change over sensor is used for each thermostat. Supply temperature < 75°F (24°C) = cooling mode Supply temperature > 78°F (26°C) = heating mode Hysterisys is 3°F (2°C) Auto change over to heating mode with a dry contact. A closed contact on the change over input will change operation of the tri-state output to heating mode. Open contact = cooling mode Closed contact = heating mode
Characteristics of change over sensor 47 K
140.0 °F 60.0 °C 11.700 Kohm 1.047 Volts
130.0 °F 54.4 °C 14.342 Kohm 1.225 Volts
120.0 °F 48.9 °C 17.682 Kohm 1.429 Volts
110.0 °F 43.3 °C 21.940 Kohm 1.659 Volts
100.0 °F 37.8 °C 27.412 Kohm 1.914 Volts
90.0 °F 32.2 °C 34.483 Kohm 2.191 Volts
80.0 °F 26.7 °C 43.704 Kohm 2.486 Volts
70.0 °F 21.1 °C 55.834 Kohm 2.791 Volts
60.0 °F 15.6 °C 71.866 Kohm 3.096 Volts
50.0 °F 10.0 °C 93.340 Kohm 3.393 Volts
40.0 °F 4.4 °C 122.298 Kohm 3.673 Volts
SINGLE STAGE OF AUXILIARY REHEAT
To be used with On/Off 2 position 24 Vac devices like:
On/Off N.C. electric valves
Electric duct heater relays
Electric base board relays
See and study wiring diagrams carefully to wire reheat devices using a separate power source.
SPECIFICATIONS
Operating
Conditions:
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy
(calibrated):
Ranges: 50 °F to 90 °F Standard
Outputs: Isolated Triac: 30 Vac at ½ A max.
Power: 24 VAC -15%, +10% 50/60 Hz; 2 VA
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
± 0.2 ° C ( ± 0.4 °F )
( 10 °C to 32 °C ) Optional
HOW TO ORDER
Thermostat C1010-02 C1011-02 ** C1012-02 C1013-02 **
Tri-state output in cooling mode
Tri-state output reverses to heating
mode with change over sensor
Auxiliary reheat 1 stage 1 stage
zzzz
zz
C1013-02 WIRING
a
C1013-02
Reheat
Open
Close
24 Vac
Common
Change over
Field wired by installer
Change over is automatic ( non adjustable )
If supply temperature is lower than 24 C: Cooling mode
If supply temperature is higher than 25.5 C: Heating mode
R
24 Vac
Single stage reheat
24 Vac relay or
24 Vac N.C. valve
Open
Close
Common
Transformer
Actuator
1 to 2 minutes
timing
120 Vac
8
7
6
5
4
3
2 2
Change over sensor
Optional wiring schematic for applications where
transformer is an integral part of reheat system
Transformer ( by others )
120 Vac
Single stage reheat
24 Vac relay or
24 Vac N.C. valve
Open
Close
Common
Transformer
Change over sensor
Actuator
1 to 2 minutes
120 Vac
timing
Reheat
Open
Close
24 Vac
Common
Change over
24 Vac
8
7
R
6
5
4
24 Vac
3
C1013-02 SEQUENCE
100%
on
50 %
0%
Damper in cooling mode
Device
TRUE
HEATING
SETPOINT
Device
off
Temperature increase
COOLING
SETPOINT
DIAL SETPOINT
CENTERED
IN DEAD BAND
Device
closed
DEAD BAND 2.0 F
TRUE
PROPORTIONNAL BAND
TRUE
HEATING
SETPOINT
DIAL SETPOINT
CENTERED
Device opened
Device
on
Device opened
Device
off
PROPORTIONNAL BAND
3.2 F
3.2 F
Damper in heating mode
changeover input active
IN DEAD BAND
Device closed
DEAD BAND 2.0 F
Temperature increase
TRUE
COOLING
SETPOINT
100%
50 %
0%
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.com