Viconics C1010 User Manual

C1010
Electronic Thermostat
APPLICATIONS
VAV and by-pass units control state floating output
with modulating tri-
ADVANCED DESIGN AND PI CONTROL
Advanced PI control thermostats provides precise temperature control and eliminates wasted energy caused by the typical On / Off cycling in conventional thermostats. Thus the room occupant is able to reduce the thermostat setpoint to the lowest comfortable setting. The result is energy savings ranging from 5% to 10%.
DIMENSIONS
BASE
WIRING
FROM BACK
SECURITY SCREW
3.275"
( 83 mm )
COVER TOP
80
70
60
2.8"
( 71 mm )
2.8"
( 71 mm )
90
F
50
4.5"
114 mm
1.275" 32 mm
COVER INSIDE
5432176
SCREW TERMINALS
2.8"
( 71 mm )
MODULATING TRI-STATE FLOATING OUTPUT
For use with tri-state floating actuator (CW/Off/CCW) having a 1 to 2 minutes timing per 90° of rotation. This is a true multi positions modulating output. It gives performances which is equivalent to more expensive 0 to 10 Vdc type output.
COVERS
Factory standard scale is 10°C to 32°C for horizontal mounting.
F & °C scales are available on special order for horizontal
°
or vertical mounting. The thermostat and the terminals are an integral part of the cover. The cover hooks onto the base for easy service and is locked in place using a security screw
SPECIFICATIONS
Operating
Conditions:
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy
(calibrated):
Ranges: 50 °F to 90 °F Standard
Outputs: Isolated Triac: 30 Vac at ½ A max.
Power: 24 VAC -15%, +10% 50/60 Hz; 2 VA
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
± 0.2 ° C ( ± 0.4 °F )
( 10 °C to 32 °C ) Optional
Specifications and equipment are subject to change without prior notice.
HOW TO ORDER
Thermostat C1010-02 C1011-02 ** C1012-02 C1013-02 **
Tri-state output in cooling mode
Tri-state output reverses to heating mode
with change over sensor
Auxiliary reheat 1 stage 1 stage
zzzz
zz
C1010-02 WIRING
C1010-02
Open
Close
24 Vac
Common
C1010-02 SEQUENCE
6
5
4
3
Open
Close
Common
24 Vac
Actuator
1 to 2 minutes
timing
Transformer
120 Vac
SETPOINT
Opened
100%
50 %
Closed
0%
Cooling mode
PROPORTIONNAL BAND
3.2 F
Temperature increase
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.com
028-0016 LIT-C1010-E01