VES ecovent EVC Installation, Operation And Maintenance Manual

Page 1
1
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
VES Ref. ID.1120
June 2016
This manual must be read in full before Installation, Operation and Maintenance of the units supplied
Please ensure that this document is passed to the end user. This manual forms an integral part of the product and should be kept for the working life of the product. Additional copies of this and supporting documents are available by contacting VES or by visiting www.ves.co.uk and following the 'Download O & M's' link.
The following symbols used within this document refer to potential dangers, advice for safe operation or important points of reference
Indicates hazards associated with electric current and high voltages
Indicates hazards that require safety advice for personnel or potential unit/property damage
Indicates important information
page Introduction 1 Nomenclature 2 Receipt of Goods & Handling 3 Installation 3 Standard Wiring & Fan Installation 8 Maintenance 15
The Ecovent® EVC series is a range of Heat Recovery units, with duties up to 1.3 m³/s. Suitable for either plantroom, ceiling void or internal locations. As standard, each unit will have been supplied pre-wired to an isolator or fitted control panel, as specified at the time of order. The standard operating temperature of these units is -20 to +35 °C.
For further technical details regarding dimensions and weights, contact VES on 08448 15 60 60, quoting the sales order (SO) number and the unit type as found on the unit nameplate, or alternatively visit www.ves.co.uk.
Warning
Caution
Important
Important
Introduction
1 2 3 4 5 6
1
Contents
Page 2
2
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Nomenclature
Part Number Coding
Point Description Point Variants Details (as appropriate)
1 Product EV Ecovent® Acoustic Heat Recovery Units
2 Heat Recovery type C Counterflow plate heat exchanger
3 Unit Size 0...5 Sequential see unit outline for details
4 Fan Type 4...7 Centrifugal EC fan
5 Fan Size 2...7 Sequential
6 Phase -1 230V 50Hz Single Phase
-3 400V 50Hz Three Phase
7 Unit Configuration /FP Flat Plantroom
/SP Stacked Plantroom
8 Main Heating Null No Heating
-E Electric Heater Battery
-W LPHW Coil
9 Infill /DS 25mm double skinned
/EE 50mm double skinned
10 Handing /LT Left/Top Access
(denotes position of /RT Right/Top Access
supply airflow LIDSAF) /LB Left/Bottom Access
/RB Right/Bottom Access
/L Left (stacked)
/R Right (stacked)
11 Main Filter Null No filter
/G4 EU4 Pleated Filter
/F7 High efficiency pleated filter
12 Control Panel Section /CPSC Fitted control panel
/ISC Fitted isolator/speed controller
13 Colour Null Galvanised finish
/R7004 Powdercoated finish, RAL7004 etc...
14 Powder Coat Type Null As colour
/IT Internal powdercoated only
/BT Internal/External powdercoated
15 Special /S Special (non-standard) Unit
EVC152-1/FP-W/EE/RT/G4/CPSC/S
EV C 1 5 2 -1 /FP -W /EE /RT /G4 /CPSC /S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Typical Example
2
Page 3
3
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Immediately upon receipt of goods, check for possible damage in transit paying particular attention to fan impellers, coil connections and unit casing. Prior to installation please check to ensure alignment and smooth rotation of the impeller after transit. Also check to ensure that any ancillary items are included. These will normally be supplied fitted or, in the case of small items, taped to the unit. In the event of any damage having occurred or if any item is found to be missing, it is essential to inform VES Andover Ltd. within 7 days of delivery quoting sales order number and the unit type, as found on the unit nameplate. After this period, VES would be unable to accept any claim for damaged or missing goods.
The entire system must be considered for safety purposes and it is the responsibility of the installer to ensure that all of the equipment is installed in compliance with the manufacturer’s recommendations, with due regard to the current HEALTH AND SAFETY AT WORK ACT and con­forms to all relevant statutory regulations. Where a unit is installed so that a failure of components could result in injury to personnel, precautions should be taken to prevent such an injury. If the unit is installed where there is a reasonable possibility of persons or objects coming into contact with the impeller whilst operational, a guard should be fitted or steps taken to prevent this. It is the installer’s responsibility to ensure that access panels are not obstructed in any way and safe working access for maintenance must be provided in accordance with Health and Safety and Building Regulations. For confirmation of required access please see the appropriate unit outline drawing. Consideration must also be given by the installer for adequate illumination of the unit location in order for safe maintenance. Further consideration should be given to the unit’s position and secured into place as appropriate. This is especially important with external mounting as the wind and elements may effect the overall stability and safety of the unit.
Mounting hangers, door furniture, isolators etc. extend beyond the casework and so are vunerable to accidental damage. Take necessary precautions so as not to cause damage whilst handling the unit.
The weight of each unit/section is specified on the outline drawing and the total unit weight will be displayed on the unit inspection label. When lifting the unit using a fork lift truck ensure the whole unit is supported by the full length of the forks. It may be necessary to use fork extensions to fully support the unit properly. The centre of gravity may be offset from the centre of the unit; this needs to be taken into consideration when lifting the unit.
Handle with care. Failure to fully support the unit during lifting may result in damage to the unit casework Handles, lids, housings and coil connections must NOT be used as lifting points.
Units are to be rigged and lifted using spreaders, taking into account the weight of the unit, and lifting gear should be arranged so as not to bear on the casework see right.
Caution
Receipt of Goods
& Handling
Installation
3
Lifting Detail
Fig.
2
4
Fork Lifting Detail
Fig.
1
Caution
Page 4
4
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Continued
Ecovent® EVC units are supplied with feet suitable for floor or ceiling-void mounting, either by use of drop-rod mounting, in either top or bottom access orientation, with airflow in the horizontal plane. For alternative mounting please consult your outline drawing as supplied with the unit, or refer to VES Customer Services for further information.
Secure drop rods/unit with the appropriate fixings as shown below . Self-levelling feet are available for floor mounting, with fixings as per drop rods . The unit can be further secured to the floor via knockout fixings holes on the feet, fixings to be supplied by others .
When hanging units from drop-rods, ensure that the load is evenly spread and that ALL feet are used within the support, including those for fitted silencers if included. Ensure that the drop rod used is selected appropriatedly to accomodate the load of the unit.
Unit mounting detail
Fig.
345
Installation 4
Important
EVC units with fitted silencers are sectional and handed. It is important that all sections are
joined together securely prior to positioning and installation. Remove and retain the fixings from the joining bracket. Butt the correct silencer to the unit section ensuring the unit spigots enter the silencer section fully see fig.
6
. This joint should be assembled using self-adhesive rubber tape at the joints prior to assembly so as to prevent air leakage; replace with similar if damaged. Finish the assembly by installing the joint fixings through both parts of each joining bracket and tighten using a 6mm hex key, drawing the sections together evenly see fig.
7
.
Section joining detail
Fig.
6
7
Caution
Joining brackets are NOT structural and are included as part of the unit sealing only. When moving assembled units ensure that ALL sections are fully supported.
7634534
5
Page 5
5
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Continued
When accessing the unit ensure the access panels are handled/opened in a controlled manner so as to avoid damage to the unit or injury to personnel. This is particularly important with bottom access units. Ensure the AHU has been allowed to completely cool before attempting any work to the unit
Some units feature dual hinge/handles meaning access doors can be opened either way or removed completely.
Each handle assembly features a lockable handle, secured as standard by an M4 Hex key. In order to open the hinges correctly the locks must be in the open position. This is clearly
marked on the handle (see Fig.
9
) ; failure to do this may result in permanent damage to the
lock/handle mechanism.
When closing/replacing doors, ensure that all handles are fully closed and all locks are returned to the closed position.
Installation 4
Access
Caution
Locked
Unlocked
1
2
Dual Hinge handle
Fig.
8
Lock and release action
Fig.
9
10
Access opening/removal
options
Fig.
11
Caution
10
9
Page 6
6
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Continued
On EVC/ -E units, an electric heater battery (EHB) will be installed. Supply to the heater should be 1Phase or 3Phase with separate neutrals; confirmation of this can be found on the unit nameplate. Cables should be of silicone rubber, fibreglass or of a similar high temperature insulated type and be installed to current I.E.E. Regulations, ensuring a sufficient earth connection to the terminal provided. Care should be taken not to overstrain the terminal pillars as this may permanently damage the elements.
The heater is fitted with a manual-reset high temperature cutout with normally closed (NC) terminals and is set to break if the duct temperature rises above 130 °C. It is important that the cutout is connected to the safety circuit so the heater is isolated in the event of overheating caused by airflow failure.
The electrical supply must be isolated before attempting to reset the manual cut-out and should be given sufficient time to cool. For further information regarding electric heaters please see VES Ref. ID431.
If a speed controller is fitted to the system, it must not stop the fan independently of the control system, or allow airflow to fall below the stated volume on the electric heater battery. Suitable speed controllers without on/off switches are available from VES Andover.
Coils should be piped according to any relevant local codes of practice. Where threaded connections are supplied, the only approved method of jointing method is by use of Boss white and hemp. The thread fitted to the coil is to be supported at all times whilst making joints. All external piping is to be supported independently from the coil. Fluid filters are recommended.
It is important that water and steam coils are protected against damage from extreme weather conditions during the winter season. If the water is allowed to freeze in the coil system, damage may occur potentially bursting pipes and resulting in emergency problems. Fitting a frost thermostat at the unit inlet and ensuring that boilers run continuously in low ambient temperatures can help to prevent this.
Heating coils do not cool immediately when the hot water supply is cut off. The residual heat must be dissipated to avoid damage. The continuous running of the fan after shutdown resolves this, by operation of a run-on timer. The recommended length of run-on is 2 minutes minimum.
On Ecovent® EVC / -W units, a Low Pressure Hot Water (LPHW) coil will be installed. The coils are normally suitable for LPHW at 82 °C flow and 71 °C return temperature. LPHW coils are supplied as standard with an air vent and drain plug located on the pipe work immediately adjacent to the coil connections on the AHU. The air vent should be at the highest point, with the drain at the lowest. The coil should be regularly vented so as to avoid potential air locks, resulting in a fall off of duty.
Installation 4
Typical LPHW Coil
Fig.
12
Caution
Coils
Electric Heater
Batteries
Caution
LPHW Coils
Flow
Return
Caution
It is recommended that a check be made as to whether any treatment is required to the water supply for prevention of corrosion and scaling of the equipment. Information regarding the necessary action to be taken can be obtained from the relevant Local Water Supply Authority. The unit will have been supplied with connections either left or right-hand side looking in direction of airflow. Please see order acknowledgement for confirmation of this handing. Should you need to alter this please consult VES as unit adjustment may invalidate your warranty.
Airflow
Page 7
7
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Installation 4 Continued
A drain pan is fitted to all units and a peristaltic pump is fitted as standard for units size 0 to 4 and will require customer connection to an appropriate waste system from the pump outlet. It is important that the unit be mounted level. Failure to do so may mean the pump sensor is not level and so compromise its operation. The pump has been design for use with water only.
As standard the position for the primary pump output is next to the controls section. Should this position be inappropriate an alternate position is available on the opposite side of the unit (see below). The necessary pipework to use this secondary position is already in place but it will need to be connected to the outlet on the pump.
Doors and panels removed for clarity
Before the unit is fully operational it is recommended to perform an initial test to confirm the pump and sensor are operating correctly. Ensure that all debris is removed from the condensate drainpan. Manually add enough water to the drain to ensure the pump sensor float switch is activated. Turn the unit on and check that pump starts and then stops as the water level decreases.
The EVC Size 5 drain pan is fitted with an internal spigot suitable for connection with a Ø15 mm push-fit straight connector, to be supplied by others. Terminate through the case onsite as required, ensuring that any swarf is removed. Connect to an appropriate waste system ensuring the connection is trapped correctly.
Condensate Trapping
Typical
Pump connections
Fig.
14
Drain pan connection
(typical)
Fig.
13
Caution
Drain pan
Secondary Outlet
Pump
Sensor
Primary Outlet
IN
OUT IN
OUT
Page 8
8
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
The electrical supply must be fully isolated before attempting to affect any work on this unit. All electrical connections to any unit must be carried out in accordance with the current edition of the I.E.E Regulations, only competent Electricians should be allowed to affect any electrical work to our units.
It is recommended that the cable entry point should be at the end of the control section as shown below in figure 15. It is the responsibility of the installer to ensure that a suitable cable gland (giving adequate protection and strain relief) is fitted, and in doing so also ensure that no internal components are damaged during this installation. Take particular care to note the position of the drain outlet and associated pipework. Make certain all swarf is removed before use.
It is the customer’s responsibility to supply earth fault protection through the building installation device and a dedicated, isolated power supply with overload protection, to account for motor start up currents. See page 9 for specific fan details Fig.
16
.
Do not connect any unit to an electrical supply voltage outside of the specification.
The following wiring diagrams are a guide to installing the standard fan and actuator options found on Ecovent® EVC units. If in any doubt, for units with fitted VES controls or for special versions of the units, consult the wiring diagram in your document pack or contact VES Customer Services Department on 08448 15 60 60, quoting the sales order (SO) number and unit type as found on the unit name plate. For incorrect fan rotation, check with the VES Service Department for advice, on
08448 15 60 60.
Standard Wiring
& Fan Installation
5
Warning
Important
Warning
Recommended
cable entry points
Fig.
15
Recommended cable entry points
Page 9
9
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Standard Fan Details
Fig.
16
Standard Wiring
& Fan Installation
5 Continued
90
1
0
5
1
2
0
6
0
75
90
1
0
5
1
2
0
45
30
1
BK2RD3WH
+
T
L R
CM24-SR/NM24 Damper Actuator To isolate from the main power supply, the system must incorporate a device which disconnects all the phase conductors
Warning
Standard wiring
arrangement
Damper Motor Terminals
Fig.
17
AC 24 V 50Hz / DC 24 V
Size Phase
Motor
Size
Voltage
Fan
(rpm)Speed
Full Load
Current
Speed
Control
EVC152-1
EVC -1073
1 Phase 0.169 kW 230 VAC 4120 1.35 A EC
1 Phase
0.1 kW
230 VA C 0 A EC
00
141 0.83
EVC243-1 1 Phase 0.23 kW0 230 VAC 3290 1.65 A EC EVC262-1 1 Phase 0.50 kW0 230 VAC 3000 2.6 A0 EC EVC362-1 1 Phase 0.50 kW0 230 VAC 3000 2.6 A0 EC EVC445-1 1 Phase 0.40 kW0 230 VAC 2010 2.1 A0 EC EVC446-1 1 Phase 0.87 kW0 230 VAC 2200 4.5 A0 EC EVC547-3
3 Phase 400 VA C 2100 2.40 A EC
1.350 kW
Page 10
10
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
(Not fitted on EVC5)
Standard Wiring
& Fan Installation
5 Continued
16
16
Standard Isolator
arrangement
Fig.
18
Page 11
11
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Standard Wiring
& Fan Installation
5 Continued
Standard CPB Control Panel
Arrangement
Fig.
19
Continued over on page 12...
Energy Recovery
0-10V Output
24 VAC AUX SUPPLY
MAX 1A
24 VDC Fire Alarm
Shutdown Signal (SELV)
Supply Fan Enable
(24/230VAC 3A M AX)
Extract Fan Enable
(24/230VAC 3A M AX)
Op!onal V/F
BMS Common Trip
Fresh Air Sensor
(SELV)
Return Air Sensor
(SELV)
Supply Air Sensor
(SELV)
Customer
Connec!ons
400 V 3~50Hz
(For 1Ph Supply
Link L1, L2 & L3)
EPE L9041
Basic Room Unit
Op!onal
Fascia Mounted HMI Panel
Page 12
12
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Standard Wiring
& Fan Installation
5 Continued
Continued from page 11..
(Not fi" ed on EVC5)
16
16
Standard CPB Control Panel
Arrangement
Fig.
20
Page 13
13
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Standard wiring arrangement
Valve Actuator Terminals
Fig.
21
Standard Wiring
& Fan Installation
5 Continued
SGS65... Valve Actuator To isolate from the main power supply, the system must incorporate a device which disconnects all the phase conductors
Warning
Prior to starting the unit it is important to ensure that the fans are free running, and should any components have moved during transit take care to ensure they are realigned to allow correct operation/rotation. A trial spin by hand should indicate if the fan is rubbing. To align, losen either the fan plate fixings or the inlet ring, adjust and retighten, see figure above. The same should be applied to any wiring looms which may have become unfastened; ensure that loose wiring is securely stowed away from any moving components. The impellers on size zero units are not adjustable; any alignment issues should be reported to VES.
Fan alignment details
Fig.
22
Important
22
1
2
3 4 6
5 7
24 V
GND
Frost
Sensor
Valve N/A
Supply
Air
Sensor
0-10 V
Customer
Terminal Box
Page 14
14
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Continued
Unit sizes 2 to 5 in the Ecovent® EVC range feature tapped inlet rings it is possible to establish the volume flow rate by measuring the static pressure rise into the fan. The centrifugal fans have infinite speed adjustment, the benefits of real energy savings are apparent when the fan speed is reduced; this is best demonstrated when used in conjunction with additional sensors such as air quality or occupancy.
Using a micro manometer and adjusting the fan speed it is possible to commission each fan to the required air volume. Each fan section has a differential pressure tapping connection point; by connecting your micro manometer to the appropriate pitot a differential pressure reading can be taken. This measurement can then be applied to the calculation as below or by using the differential pressure curve. Simply read across from the pressure measurement to the fan curve and down to calculate the resultant air volume. If the unit features a fitted control panel this action can be undertaken within the programming available; see the accompanying controls documentation for further operational details.
Example: Measured differential pressure: 150 Pa
This measurement can then be expressed in the following calculation:
where qV is the air volume in m³/s
k is the fan nozzle coefficient (See Below Graph) pW is the measured differential pressure in Pa
Measured differential pressure: 150 Pa qV= (142 150) / 3600 qV= (142 x 12.247) / 3600 qV= 1739 / 3600
qV= air volume = 0.48 m³/s
Standard Wiring
& Fan Installation
5
Differential pressure
curve Fig.
24
Example: Measured differential pressure: 150 Pa
Air Volume: 0.48 m3/s
Differential pressure
calculation Fig.
23
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
Resistance - Pa
0
50
100
AirVolume - m³/s
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1.1 1.2
1.3
1.4
1.5
243-1 K=68
445-1 K=96
446-1 K=142
262-1 & 362-1 K=60
547-3 K=180
Page 15
15
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Maintainance 6
Before attempting to carry out any work on our units, all accompanying documentation including warning labels on the unit must be referenced. Should it be necessary to remove any component ensure that these are secured into position once reinstalled. It is critical that after any maintenance work has been conducted that all components removed/replaced be refitted correctly by a competent engineer.
Before attempting to carry out any maintenance work, investigative or repair work on our units, the unit MUST BE COMPLETELY ISOLATED from its electrical supply. Ensure a minimum of two minutes after electrical disconnection before removing access panels. This will allow any moving parts to come to a rest. Care should also be taken when accessing external units as the wind and elements may cause moving parts to ‘windmill’.
In general, this series of units require little maintenance. In the unlikely event of component failure, spares are available from stock at VES Andover Ltd.
When accessing the unit ensure the access panels are handled/opened in a controlled manner so as to avoid damage to the unit or injury to personnel. This is particularly important with bottom access units. Ensure the AHU has been allowed to completely cool before attempting any work to the unit For units featuring dual hinge/handle access, please see page 5 for further details
For bottom access units, should it be necessary to remove the heat exchanger from the unit casework take care to ensure that all components are correctly supported during their removal. Remove the lids and central mullion from the unit, exposing the bypass damper. As an additional safety measure some components are held into place using PK screws. Remove the required components with care and ensure all components are replaced correctly.
Ecovent® EVC units feature plug & socket connections to allow easy removal/replacement of key components. Separate the plug connection by hand (tools not required) by lifting the
locking lever
25
and pulling the plug/socket apart 26. DO NOT pull the cable to separate the
assembly.
Upon reconnection, the assembly features a locating lug to ensure correct orientation. Once rejoined, lock the connection together again using the locking lever as shown.
Plug & socket operation
Fig.
25
26
Important
Warning
Caution
26
25
Page 16
16
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Maintainance 6
Important
Continued
Ecovent® EVC units feature a bulkhead-mounted fan plate assembly.
Ensure that special care is taken when removing/replacing components/assemblies from bottom-access units. For larger components this may require the use of two or more persons. The mounting plate is slotted to aid plate alignment. It is important to keep the fan assembly supported at all times; the fan assembly should not be considered supported until all fixings are securely tightened.
To remove the fan assembly Fig.
26
, ensure the unit is fully isolated. Separate the supply plugs
to the fan as shown above
24. 1
Detach the measuring tube from the inlet ring and stow the tube clear. 2 Back-out the bottom screws but do not remove . 3 Remove the top fixings completely and retain . Carefully lift the fan assembly over the retained fixings and remove the fan assembly from the unit.
Fan assembly removal/
installation (1 - 5)
Fig.
26
1
2
3
Page 17
17
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
To replace the fan assembly, ensuring the pitot tapping on the fan inlet ring is accessible, locate the mounting plate over the fixings retained in the unit bulkhead.
2
3Secure the
loose fixings through the mounting plate and tighten all the mounting fixings.
1
Attach the measuring tube to the pitot tapping on the inlet ring ensuring that it is clear of all moving parts.
Reconnect the supply plugs as in Fig. 24; if more than one plug is used, ensure the
correct plugs are reconnected as marked.
Ensure that the fans are free running by following the fan alignment instructions on page 13, adjust as required.
EVC size Zero units feature a double inlet centrifugal fan mounted on an adapter plate. To remove, unplug as per Fig. undo the two screws and carefully remove the fan/adapter plate assembly, retaining all fixings.
To replace the fan assembly, secure one fixing leaving enough of a gap to allow the adapter plate to slide into place. Fit the remaining fixing and tighten both. Ensure the impellor is free running. Reconnect the supply plugs as in Fig. ; if more than one plug is used, ensure the
correct plugs are reconnected as marked. There is no pitot on this fan assembly.
Maintainance 6 Continued
Fan assembly removal/
installation (zero)
Fig.
27
24
27
Page 18
18
ORIGINAL INSTRUCTIONSVES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08448 156060 Fax: 02380 261204 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
Installation, Operation and Maintenance Manual
®
EVC Heat Recovery Unit
Three Monthly Checks
Six Monthly Checks
Twelve Monthly Checks
Spares & Repairs
Recommended Checks
Continued
In order to keep the unit in good order the following maintenance routine is recommended:
Filters should be inspected every three months. If they are found to be heavily soiled or damaged in any way they should be replaced. Spare filters can be ordered from VES Spares Department.
The fan impeller should be cleaned every 6 months. Failure to clean the fan on a regular basis could result in loss of fan performance, or cause it to fall out of balance. If a fan is stationary for long periods in a humid atmosphere, it should be switched ON for minimum of two hours every month to remove any moisture that may have condensed within the motor. The fan motors are maintenance free due to the use of ball bearings with ‘life-long lubrication’. At the end of the grease life it will be necessary to change the bearings or change the fan unit. The life expectancy of bearings for standard usage is approximately 30 - 40000 hours. Failure to keep dampers clean could result in the damper becoming inoperative. Clean damper blades and frames and lubricate with PTFE aerosol or equivalent. The heat exchanger matrix should be inspected for debris, dust or dirt build up. If found contaminated, foreign matter should be removed accordingly; superficial dust or debris can be removed from the surface of the heat exchange by gently brushing. Loosened debris can then be vacuumed from the surface of the matrix or flushed through with warm water. Stubborn deposits can be removed by using a low pressure washer with an approved detergent solution. The solution temperature should not exceed 50 °C. When using any pressure device care must be taken not to damage the heat exchanger matrix.
Under NO circumstances should the heat exchanger be steam cleaned.
Ensure the drain pan and the drain connection is free from debris ensuring any condensate produced can freely drain away. Where a pump is fitted check the sensor and float for contamination. Clean as required using a 95 / 5% Water/Chlorine solution. Check also all associated pipework. Any found to be damaged or blocked should be replaced, spare replacement pipes being available from VES. Should a full service be required it may be necessary to disassemble the unit casework to gain access to some components.
Ecovent® EVC units are supplied with unpainted galvanised steel cases as standard but have an option for powder coat paint finish. Check all painted items to ensure that they have not deteriorated, particularly where adverse environmental conditions prevail. Re-paint as necessary. Matching paint can be supplied upon request.
When enquiring after or ordering spares contact VES Spares Department, quoting the sales order (SO) number and unit type as found on the unit nameplate.
Tel: 08448 15 60 60 • Fax: 02380 26 12 04
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
PLEASE ENSURE THAT THIS DOCUMENT IS PASSED ON TO THE END USER
We reserve the right to alter the specifcation without notice ©VES Andover Ltd. 2016. No part of this publication may be photocopied or otherwise reproduced without the prior permission in writing of VES Andover Ltd.
Maintainance 6
Caution
WEEE Directive
Page 19
Declaraon of Conformity
Date:
Product: Ecovent EVC Heat Recovery Units
Type: EVC
Manufacturer: VES Andover Limited
The product above is produced in accordance with EC Council Direcves:
2004/108/EC (Electromagnec Compability Direcve)
2006/42/EC (Machinery Direcve)
The European Harmonised Standards applied are: BS EN ISO 12100:2010, BS EN ISO 13857:2008, EN61000, EN 60204-1, BS EN 60950-1:2006
Basis of Self aestaon: Quality Assurance to ISO 9001-2008, BSI Reg. Firm Cert. No. Q05375
Signature of Manufacturer:
Name: Signature Posion of Signatory:
R. Peters Deputy Managing Director
K. Feeney Engineering Associate Director
VES Andover Ltd.
Eagle Close, Cha ndlers Ford Ind. Est.
Eastleigh, Hamps hire SO53 4NF
Tel: 08448 156060 Fax: 02380 2612 04
E-mail: vesltd@ ves.co.uk Web: www.ves.co.uk
20th. May 2015
Loading...