The NetSure™ 5100 Series, a compact -48 volt 600 A DC power solution, features an
advanced control unit, up to (29) positions for 2000 W high-eiciency eSure™ rectifiers
or 1500 W -48 V to +24 V converters or 2000 W solar converters, a single, bulk or dual
row distribution cabinet, and hybrid and solar connectivity panels. The power system
supports 19" W and 23" W rack mounting and is available in a number of configurations,
designed to work with a wide range of applications.
The distribution cabinet supports up to (52) 1 A to 300 A circuit breakers or 1 A to 100 A
TPS/TLS fuses. Options for battery disconnect breaker positions and dual voltage (-48
V/+24 V) breaker positions are available. Multiple LVD levels are supported, allowing load
prioritization in up to two steps.
Remote monitoring and control is supported through multiple web browsers including IE,
Firefox, Chrome and Safari. Standard supported protocols include
ModBus and SNMP. Encrypted security is also available as an option. Local access is
provided through the controllers’ keypad and TFT display. NetSure DC Power systems
from Vertiv oer extremely low failure rates, as well as low total cost of ownership.
The 2000 W eSure™ rectifier delivers peak system eiciency above 96%. Maximum value
is achieved by an advanced energy optimization function known as ECO mode, enabling
significant energy savings even at low loads.
Table of Contents
Step 1. Choose Distribution Cabinet or Bulk Power Shelf ...........................................3
Step 2. Choose Distribution Panels .................................................................4
Step 3. Choose Distribution/Battery Devices for Selected Distribution Panels ......................6
Right angle adapter converts
(1) load position (1/4-20 on 5/8" centers) to
(1) load landing (1/4-20 on 5/8" centers).
Right angle load busbar and straight return busbar
for rear wiring egress converts
(2) load positions (1/4-20 on 5/8" centers) to
(1) landing (3/8-16 on 1" centers).
Right angle load busbar and straight return busbar
for rear wiring egress converts
(3) load positions (1/4-20 on 5/8" centers) to
(1) landing (3/8-16 on 1" centers).
Includes (1) busbar that mounts on the two lug landing
positions of a 125 A, 150 A, or 200 A bullet nose circuit
breaker, and provides a landing for one standard two-hole lug
having 3/8" bolt clearance holes on 1" centers. Also includes
(1) busbar that mounts on two landings of the associated
ground return bar (if furnished), and provides one landing for
a standard
two-hole lug having 3/8" bolt clearance holes on 1" centers.
All busbar and lug mounting hardware is included. Order (1)
part no. 534449 per 125 A, 150 A, and 200 A bullet nose
circuit breaker ordered.
Includes (1) busbar that mounts on the three lug landing
positions of a 225 A through 300 A bullet nose circuit
breaker, and provides one landing for a standard two-hole lug
having 3/8" bolt clearance holes on 1" centers. Also includes
(1) busbar that mounts on three landings of the associated
ground return bar (if furnished), and provides one landing for
a standard
two-hole lug having 3/8" bolt clearance holes on 1" centers.
All busbar and lug mounting hardware is included. Order (1)
part no. 514714 per 225 A through 300 A bullet nose circuit
breaker ordered.
(4) 1/4-20 nuts, lock washers, and flat washers.
Step 5. Optional – Choose Low Voltage Disconnect
Select either low-voltage battery disconnect (List LB) or load disconnect (List LL) for a single row panel. For a dual row panel, select
either List LB or List LL or select both.
List
Number
List LB582137100LB
List LL582137100LL
Vertiv
Part Number
DescriptionQ ty.Notes
Low voltage
battery disconnect
Low voltage
load disconnect
Maximum of one in a system.
Maximum of one in a system.
On dual row cabinet contactor only disconnects bottom row.
Step 6. Choose 19" W or 23" W Rectifier/Converter Module Shelves
Select one List 30 for each module shelf chosen except when 58870530036 is chosen. Select one shelf with a controller slot and then
select expansion shelves. For conduit input order a List 40, 45 or 46 and the hard-wired module shelves.
19" W NetSure 5100 Shelf23" W NetSure 5100 Shelf
List
Number
List 3058213710030Interface components for 1RU module, shelfn/a
List 405821371004019" W AC/Solar input termination paneln/a
List 455821371004523" W AC/Solar input termination paneln/a
List 465821371004623" W AC input termination paneln/a
Module Shelves e/w Controller
n/a58870530011
n/a58870530014
n/a58870530015
n/a58870530031
n/a58870530034
n/a58870530035
Bulk Output Shelf
n/a58870530036
Module Shelves for Expansion
n/a58870530021
n/a58870530024
n/a58870530025
n/a58870530041
n/a58870530044
n/a58870530045
n/a58870530001
n/a58870530004
n/a58870530005
*When using molex cords and solar converters only one solar converter can be powered per AC Cord.
Vertiv™
Part
Number
DescriptionQt y.
23" W shelf e/w controller slot.
Holds (5) rectifier or solar converter modules. Hard-wire AC.
23" W shelf e/w controller slot. Holds (5) rectifier or solar
converter modules. Hard-wire AC with cord clamp.
23" W shelf e/w controller slot. Holds (5) rectifier or solar
converter modules. Molex cord connectors.
19" W shelf e/w controller slot.
Holds (4) rectifier or solar converter modules. Hard-Wire AC.
19" W shelf e/w controller slot. Holds (4) rectifier or solar
converter modules. Hard-wire AC withcord clamp.
19" W shelf e/w controller slot. Holds (4) rectifier or solar
converter modules. Molex cord connectors.
19" bulk output stand-alone shelf e/w controller slot. Holds (4)
rectifier modules. AC input consists of molex cord connectors. Shelf
comes with output bus bar lug landing points for customer lugs.
23" W shelf. Holds (6) rectifiers or (3) rectifier and (3) solar
converter modules. Hard-wire AC.
23" W shelf. Holds (6) rectifiers or (3) rectifier and (3) solar
converter modules. Hard-wire AC with cord clamp.
23" W shelf. Holds (6) rectifiers or (3) rectifier and (3) solar
converter modules. Molex cord connectors.
19" W shelf. Holds (5) rectifiers or (2) rectifiers and (3) solar
converter modules. Hard-wire AC.
19" W shelf. Holds (5) rectifiers or (2) rectifiers and (3) solar
converter modules. Hard-wire AC with cord clamp.
19" Wshelf. Holds (5) rectifiers or (2) rectifiers and (3) solar
converter modules. Molex cord connectors.
23" W shelf with (6) positions for rectifiers, solar converters and
-48V to +24V converter modules. Hard-wire AC.
23" W shelf with (6) positions for rectifiers, solar converters and
-48V to +24V converter modules. Hard-Wire AC with cord clamp.
23" W shelf with (6) positions for rectifiers, solar converters and
-48V to +24V converter modules. Molex cord connectors.
Rack
Space
1 RU
1 RUFor use in Vertiv cabinets.
1 RUFor use with Molex AC cords.*
1 RU
1 RUFor use in Vertiv cabinets.
1 RUFor use with Molex AC cords.*
1 RU
1 RU
1 RU
1 RU
1 RU
1 RU
1 RU
1 RU
1 RU
1 RU
NotesPictorial
Order one for each module shelf that
is ordered other than when the
58870530036 shelf is chosen.
Order for individual solar or AC input
in conduit.
Order for individual solar or AC input
in conduit.
Order for AC input in conduit.
Each AC feed picks up two rectifiers.
For use with up to (3) shelves.
For use with AC input that will be in conduit.
Requires List 45 or 46.
For use with AC input that will be in conduit. Requires List
40.
For use with Molex AC cords*. No distribution required.
System requires, controller, rectifiers, AC cords.
For use with AC input that will be in conduit.
Three left most slots can hold solar converter modules.
Requires List 45 or 46.
For use in Vertiv cabinets.
Three left most slots can hold solar converter modules.
For use with Molex AC cords.
Three left most slots can hold solar converter modules.*
For use with AC input that will be in conduit.
Three left most slots can hold solar converter modules.
Requires List 40.
For use in Vertiv cabinets. Three left most slots can hold
solar converter modules.
For use with Molex AC cords.
Three left most slots can hold solar converter modules.*
For use with AC input that will be in conduit. Left three slots
set up for solar converters. Right three slots set up for -48V
to +24V converter modules. Requires List 45 or 46.
For use in Vertiv cabinets. Left three slots set up for solar
converters. Right three slots set up for -48V to +24V
converter modules.
For use with Molex AC cords. Left three slots set up for
solar converters. Right three slots set up for -48V to +24V
converter modules.*
Select AC cords for molex AC input module shelves.
List
Number
n/a535232
n/a547898
n/a553202
n/a540946
Vertiv™
Part Number
DescriptionQt y.Pictorial
30" long, 8 AWG,
input cable assembly
6' long, 8 AWG,
input cable assembly
12' long, 8 AWG,
AC input cable assembly
14' long, 8/3 AWG,
AC input line cord, L6-30P
n/a545252
n/a545616
14' long, 8/3 AWG,
AC input line cord, L5-30P
6' long, 8 AWG,
AC input line cord, L6-30P
Step 8. Choose Controller
Select one, quantity of one.
List
Number
n/a1M830BNANCU controller
Vertiv
Part
Number
DescriptionQt y.NotesPictorial
Standard or special firmware configuration
can be assigned. Distribution panel comes
equipped with IB2 interface board which provides
(8) programmable and mappable output relays,
(8) programmable binary inputs and (2)
temperature inputs.
Note: Items below cannot be used with 58870530036 bulk output shelf.
List
Number
List 7058213710070EIB, extended interface board
n/a547490
n/a556155
n/a552992
n/a04119122
n/a559741
Vertiv™
Part Number
DescriptionQty.NotesPictorial
SMTEMP, 8 input
temperature module
Temperature probe, 3.3m,
includes 0.3 m sensor
Temperature probe, 10.3m,
includes 0.3m sensor
10 m temperature
probe extension
NCU controller second Ethernet
port kit
Maximum quantity of one. Provides (5) relay outputs, (2)
temperature inputs, (8) battery mid-point monitoring inputs
and (3) shunt inputs. Mounts internal to the system.
Provides (8) temperature inputs. Maximum quantity of eight per
system. Mounts external to power system.
Provides temperature monitoring and alarming for battery
or ambient. Battery-assigned probes provide temperature
compensation and battery thermal runaway management.
Provides temperature monitoring and alarming for battery or
ambient. Battery-assigned probes provide temperature
compensation and battery thermal runaway management.
Provides 10 meter extension for temperature probe.
Provides dual Ethernet feature - one static and one dynamic
n/a555877Critical LED KitIlluminates for a critical alarm.
n/a431300200
n/a431300300
n/a535135
n/a424227900
n/a424228000
n/a424228100
1 amp in-line fuse pigtail kit with
3/8" ring lug
1 amp in-line fuse pigtail kit with
5/16" ring lug
In-line fuse pigtail kit with splice
connector, 3/8" ring lug, and 1/4"
ring lug
In-line 49.9 ohm resistor pig-tail
kit with 3/8" ring lug
In-line 49.9 ohm resistor pig-tail
kit with splice connector
In-line 49.9 ohm resistor pig-tail
kit with 5/16" ring lug
Used for connecting to battery or bus potentials for use with
digital inputs on IB2 Interface board and battery midpoint/block
voltage inputs on the EIB extended interface board.
Used for connecting to battery or bus potentials for use with
digital inputs on IB2 Interface board and battery midpoint/block
voltage inputs on the EIB extended interface board.
Used for connecting to battery or bus potentials for use with
digital inputs on IB2 Interface board and battery midpoint/block
voltage inputs on the EIB extended interface board.
Used for connecting to shunts for use with the EIB extended
interface board and SMDU+ shunt interface board.
Used for connecting to shunts for use with the EIB extended
interface board and SMDU+ shunt interface board.
Used for connecting to shunts for use with the EIB extended
interface board and SMDU+ shunt interface board.
Step 10. Optional – Choose 20 Position GMT Fuse Module
Note: Not available with 58870530036 bulk output shelf.
List
Number
List KG582137100KG(20) position GMT fuse panelMounts below last rectifier shelf