Vertiv|Liebert® PPC™ User Manual | Rev. 6 | 03/18 |ii
IMPORTANT SAFETY INSTRUCTIONS
Read this entire manual before installing or operating the system.
WARNING
Risk of cutting bands under tension. Can cause injury or death.
The shipping bands may be under tension. Use appropriate eye, face and hand protection to safeguard
against injury from band backlash.
WARNING
Risk of electric shock. Can cause injury or death.
Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and
locked out before installing cables or making connections, whether in the junction box or in the unit.
Equipment inspection and startup should be performed only by trained personnel. Lethal voltages are
present during startup procedures. Electrical safety precautions must be followed throughout inspection
and startup.
Only properly trained and qualified service personnel should perform maintenance on the Liebert PPC. All
voltage sources to the unit must be disconnected before inspecting or cleaning within the cabinet.
Lethal voltages exist within the equipment during operation. Observe all warnings and cautions in this
manual. Failure to comply may result in serious injury or death. Obtain qualified service for this equipment
as instructed.
The monitoring system contains a lithium battery for memory backup. Danger of explosion if battery is
incorrectly replaced. Replace only with same or equivalent type. Dispose of used batteries according to
manufacturer’s instructions.
WARNING
Risk of electric shock. Can cause injury or death.
All power and control wiring should be installed by licensed electricians and must comply with the NEC
and applicable codes.
WARNING
Risk of improper handling. Can cause equipment damage, injury or death.
The Liebert PPC is heavy; its weight ranges from 400lb. (182kg) to 2450lb. (1111kg) The unit should not
be loosened from the shipping pallet until after all handling by forklift or pallet jack is completed
ELECTROMAGNETIC COMPATIBILITY—The Liebert PPC complies with the limits for a Class A digital device,
pursuant to Part 15 of FCC rules.
Operation is subject to the following conditions:
•This device may not cause harmful interference.
•This device must accept any interference received, including interference that may cause undesired operation.
Operating this device in a residential area is likely to cause harmful interference that users must correct at their
own expense.
The Liebert PPC complies with the requirements of EMC Directive 2014/30/EU and the published technical
standards. Continued compliance requires installation in accordance with these instructions and use of
accessories approved by Vertiv.
Read the entire manual before installing and operating the system. Upon receipt of a Liebert PPC, the installer
should perform the following steps to ensure a high-quality installation.
1.1.1Unpacking and Preliminary Inspection
A high-quality installation begins on the receiving dock.
1.Inspect for damage or signs of mishandling before unpacking the unit(s). Check the Shock-Watch™ indicator.
2.If the Liebert PPC was shipped in an export crate, open the shipping crate carefully. (Use care to avoid puncturing the
container with sharp objects that would damage the contents.)
3.Remove the packing and vapor barrier and inspect the equipment for any obvious shipping damages.
NOTE
The units should not be loosened from the shipping pallet until after all handling by fork lift or pallet jack is
completed. Complete internal inspection should be accomplished only after equipment positioning and prior to
electrical hookup.
If any shipping damage is observed, immediately file a damage claim with the shipping agency and forward a
copy to:
The Liebert PPC is bolted to a wooden pallet to allow handling by fork lift equipment.
Moving—The Liebert PPC sits on casters that allow the unit to be rolled into place after it has been unbolted
from the pallet.
Check size and weight—Refer to the cabinet drawings furnished with the unit for size and weight information.
Typical cabinet dimensions and weights are shown in Figures 1 and 2.
Plan the route—The route that the unit will follow to its installation area should be planned to ensure that all
passages are large enough to accommodate the unit, and that the floors are adequate to support the weight.
(For example: Are the doorway, elevators, ramps, etc., adequate? Are there any non-negotiable corners or offsets
in the hallways?)
Move with care—To prevent panel damage, Vertiv recommends removing the exterior panels before moving the
unit. Reconnect all panel ground wires when replacing panels.
The Liebert PPC may be removed from the shipping pallet and installed by customer personnel. A typical
procedure is:
1.Set the palletized assembly in a level area, where there is enough room to roll the unit and entire cable assembly off the
pallet onto the floor.
2.Cut the shipping bands.
WARNING
Risk of cutting bands under tension. Can cause injury or death.
The shipping bands may be under tension. Use appropriate eye, face and hand protection to safeguard
against injury from band backlash.
3.Remove the factory-provided ramp from its shipping position—packed in front of the unit. Place the ramp adjacent to the
pallet to provide a smooth path from pallet to floor.
4.Remove side and rear panels from the module. An Allen wrench for the side panels is furnished in the installation packet.
(Carefully disconnect panel ground wires by pulling the easy-disconnect terminals at the unit frame.)
5.Remove the bolts holding the unit to the shipping pallet. (Located in each of the four bottom corners.)
6.Remove shipping blocks from under unit, then remove chocks from all casters.
7.Roll unit off pallet onto floor.
8.Roll unit to its installation location. For units located on a raised floor, use care when positioning unit over the floor cutout
to avoid casters falling through the cutout.
NOTE
Before maneuvering the unit into its final position, read and follow all advisories in the following paragraphs in
1.1.4 - Location Considerations.
1.1.4Location Considerations
The Liebert PPC should be located within the computer room, and/or close to the load(s) which it is supplying.
Equipment Location—Should employ the shortest output distribution cable runs consistent with logical
equipment arrangement and allowances for future additions.
Operating Environment—Ambient temperatures of 32°F to 104°F (0°C to 40°C) with a relative humidity of 0%
to 95% (non-condensing).
Bottom Clearance—Required for exit of cables/conduit and/or for cooling air flow. This clearance is
automatically provided by a raised floor (6 in. / 150 mm minimum height). Figures 1 and 2 show typical
raised-floor cutout dimensions.
When units are not located on a raised floor (or if the raised floor is not adequate to support the unit), optional
floor pedestals may be used. (Non-raised floor applications are not CSA approved.) Units with top cable exit
provisions and side vents do not require bottom clearance.
Recommended Minimum Service Clearances—Shown in Figure 4. The indicated clearances at the front and
one other side or rear of the unit are required for service access by the National Electrical Code (NEC)
(Article 110-26). Clearance above the unit is required for cooling air flow (exhaust).
Heat Output—As do all electrical devices, the Liebert PPC produces heat under normal operation. (See Table 1.)
This heat output should be included when calculating the environmental conditions of the room.
Floor pedestals are optional equipment intended to provide clearance for bottom cable entry without relying on
a raised floor to support the unit. The pedestals are adjustable over approximately 3-1/2 in. (89mm) to allow
leveling the unit and minor adjustments in the unit’s installed height.
NOTE
Floor pedestals may be reverse-assembled for shipping. Before installation, reassemble the pedestals as shown
in Figure 5. When the pedestal is properly assembled, the washer on top of the welded nut provides a bearing
surface for the unit’s weight.
1.Insert the pedestal threaded shaft into the inside corner tubing of the cabinet base as shown in Figures 1 and 2.
2.Adjust the pedestal height by turning the welded nut/shaft assembly into or out of the pedestal base as required.
3.Lock the height by tightening the jam nut against the pedestal base.
The pedestal may be secured to the floor by means of the four holes in the base. Locations of floor pedestals are
shown in Figures 1 and 2.
For Liebert PPC units with more than two panelboards, the additional panelboards are furnished in side-mounted
enclosures that are shipped separate from the main unit.
1.2.1Sidecar Mounting
The additional distribution sidecar is 18 in. x 30 in. (457x762mm) and can be mounted on either the left or right
side of the main unit, with left side mounting recommended.
1.Provide a floor cutout for exit of output cables, as shown in Figure 1.
2.Remove the side panel, the upper panel retainers and the lower panel hooks from the main unit.
3.Align the distribution sidecar with the main unit and bolt the two frames together using the four bolts and hardware
provided.
4.If floor pedestals are used for the main unit, two additional floor pedestals are required for the outside corners of the
sidecar. See Figure 1.
5.Install the upper panel retainers and lower panel hooks on the sidecar enclosure.
6.After electrical connections are completed, install the unit side panel on the sidecar.
1.2.2Sidecar Electrical Connections
Five conductors (3-phase conductors, neutral and ground) are furnished with the distribution sidecar for
connection to the main unit in the field, along with an intercabinet frame ground conductor.
For Liebert PPC’s with transformers, the sidecar phase conductors are connected directly to the transformer
terminals:
•Phase A (wire 412) to X1
•Phase B (wire 422) to X2
•Phase C (wire 432) to X3
The sidecar neutral (Wire 442) and ground (Wire 452) conductors are connected to the Liebert PPC main
ground busbar (see unit wiring diagram).
For Liebert PPC’s without transformers, the sidecar phase and neutral conductors are connected to the
corresponding output power distribution terminal blocks inside the main unit. The sidecar ground conductor is
connected to the main ground busbar.
For all Liebert PPC’s with VPMP monitoring, route each sidecar conductor through the appropriate current
transformer (CT) in the main unit.
NOTE
Sidecar conductors must pass through the current transformers in the same direction as the main unit
panelboard conductors. Use the existing main unit panelboard wiring for reference.
1.3Power and Control Wiring
Power and control wiring should be installed by licensed electricians. All power and control wiring must comply
with the NEC and applicable local codes.
If the unit is furnished with junction boxes, input power connections are made as detailed in 1.3.2 - Junction Box
Installation (If Used).
If junction boxes are not furnished, the input power feeder is connected to the input power lugs or blocks located
inside the unit. (See Figures 6, 8, and 10.)
WARNING
Risk of electric shock. Can cause injury or death.
Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and
locked out before installing cables or making connections, whether in the junction box or in the unit.
To minimize disturbances caused by other loads in the building, the 3-phase power input to the unit should be
supplied directly from the service entrance or other power source (a dedicated power feeder).
The input feeder circuit should be sized in accordance with the NEC and any local building codes to assure the
feeder’s ability to safely carry the system’s full load current, including losses.
Input feeder conductors should be sized for no more than 2% voltage drop. If operation at undervoltage
conditions for extended periods of time is desired, the input feeders must be oversized.
Typical conductor size data is shown in Ta bl e 2. All connections must comply with the NEC and all other
applicable codes.
For units with a transformer, the main input feeder should consist of 3-phase conductors and one (safety)
ground conductor (3W + G).
For units without a transformer, the main input feeder must consist of 3-phase conductors, one neutral and
one (safety) ground conductor (4W + G).
Figure 6Electrical connection locations, sidecar unit
Interconnection Wiring
provided by factory
Neutral Connections
Distribution Cables Neutral(s)
connected to distribution
panelboard neutral busbar
Panelboard Main Circuit Breaker
Factory-Wired
NOTES
1. The unit bolts to the main
Liebert Precision Power Center. See
installation manual for instructions.
2. Site panel is taken from the Liebert PPC
and installed to either the left or right side
of the unit.
FRONT VIEW WITH DOOR OPEN
AND PANEL REMOVED
Distribution Panelboard
Ground Connections
Distribution Cable Ground(s)
connected to distribution
panelboard ground busbar
Distribution Cable Conduit Connection
Cable Tray 1-3/32" (27.8mm) holes for
3/4" conduit fittings and 7/8" (22.2mm)
holes for 1/2" conduit fittings provided for
securing optional distribution cables