Vertiv Liebert Mini-Mate MT048, Liebert Mini-Mate MT036, Liebert Mini-Mate MT060 Installer/user Manual

Liebert®
Mini-Mate™ VariableCapacity ThermalManagementSystems
Installer/User Guide
3, 4 and5 Ton(10.5, 14 and 17.5 kW) Capacity, Ceiling-mounted,60Hz
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions 5
1.1 Agency Listed 7
2 Nomenclature and Components 9
2.1 Mini-Mate Model-number Nomenclature 9
2.2 Component Location 10
3 Pre-installation Preparation andGuidelines 11
3.1 Planning Dimensions 11
3.2 Location Considerations 11
3.2.1 Location Considerations for Outdoor Condensing Unit 12
3.3 Connections and System Setup 12
3.4 Operating Conditions 12
3.4.1 Cooling, Humidification and Dehumidification 12
3.4.2 Heating 12
3.5 Mini-Mate Unit Weights 13
3.6 Equipment Inspection and Handling 13
4 Piping and Refrigerant Requirements 15
4.1 Refrigerant Piping and Charging 15
4.1.1 Refrigerant Piping Guidelines forAir-cooledSystems 16
4.2 Refrigerant-line Sizes and Equivalent Lengths 17
4.2.1 Refrigerant Charge Requirements 17
4.2.2 Additional Oil Requirements for Digital-scroll Compressors 18
4.3 Drain and Humidifier Piping 20
4.3.1 Water-supply line to the Humidifier 20
4.3.2 Drain Line Installation Requirements 20
4.3.3 Condensate-drain Pump Kit 22
5 Electrical Connection Requirements 23
5.1 Low-voltage Electrical Field Connections 24
6 Installation 27
6.1 Installing Ceiling-mounted Evaporators 27
6.1.1 Installing Suspension Rods andMounting Ceiling Units 27
6.2 Installing Air-distribution Components for Evaporators 28
6.2.1 Installing a Filter Box for 4-ton and 5-ton Models 28
6.2.2 Installing a Filter Box for 3-ton Models 28
6.2.3 Installing an Air-distribution Plenum for 3-ton Models 28
6.2.4 Installing a Bottom-discharge Grille for4-tonand5-tonModels 29
6.2.5 Guidelines for Ducted Systems 29
7 Checklist for Completed Installation 31
7.1 Moving and Placing Equipment 31
7.2 Electrical Installation Checks 31
7.3 Piping Installation Checks 31
7.4 Other Installation Checks 31
8 Initial Start-up Checks andCommissioning ProcedureforWarrantyInspection 33 9 Maintenance 35
9.1 Filters 35
9.1.1 Filter-replacement 36
9.2 Blower Drive System—EC Fans 37
9.2.1 Fan Impellers and Bearings Maintenance 37
Vertiv | Liebert® Mini-Mate™ Installer/User Guide | 3
9.2.2 Protective Features 37
9.2.3 Fan Assembly Troubleshooting 38
9.3 Direct-drive Blower System 41
9.3.1 Fan Impellers and Motor Bearings Maintenance 41
9.4 Steam-generating Humidifier Maintenance 41
9.4.1 Operating the Humidifier 42
9.4.2 Replacing the Canister 43
9.4.3 Circuit Board Adjustments 43
9.4.4 Humidifier Troubleshooting 44
9.5 Condensate-drain and Condensate-pump System Maintenance 44
9.5.1 Condensate Drain 44
9.5.2 Condensate Pump 45
9.6 Electric Reheat Maintenance 45
9.7 Thermostatic Expansion Valve (TXV) Maintenance 45
9.7.1 Determining Suction Superheat 45
9.7.2 Adjusting Superheat Setting with the TXV 45
10 Preventive Maintenance Checklist 47 Appendices 51
Appendix A: Technical Support and Contacts 51 Appendix B: Submittal Drawings 53
Vertiv | Liebert® Mini-Mate™ Installer/User Guide | 4

1 IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert®Mini-Mate. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all installation, operation and maintenance instructions and all applicable national and local building, electrical and plumbing codes.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supply disconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not isolate power from the unit, even in the “Unit Off” mode. Some internal components require and receive power even during the “Unit Off” mode of the controller. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local codes.
WARNING! Risk of over-pressurization of the refrigeration system. Can cause explosive discharge of high-pressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate. Local building or plumbing codes may require installing a pressure-relief device in the system. Do not close off any field-installed, refrigerant-line isolation valves for repairs unless a pressure-relief valve is field- installed in the line between the isolation valve and the check valve. The pressure-relief valve must be rated 5% to 10% higher than the system-design pressure. An increase in ambient temperature can cause the pressure of the isolated refrigerant to rise and exceed the system-design pressure rating (marked on the unit nameplate).
WARNING! Risk of contact with high-speed, rotating fan impeller blades. Can cause injury or death. Open all local and remote electric power-supply disconnect switches, verify with a voltmeter that power is off, and verify that allfan impellers have stopped rotating before working in the unit cabinet.
WARNING! Risk of electric shock. Can cause serious injury or death. The Liebert® iCOM microprocessor does not isolate power from the unit, even in the "Unit Off" mode. Some internal components require and receive power even during the "unit off" mode of the Liebert® iCOM control. Open all local and remote electric power disconnect switches and verify with a voltmeter that power is Off before working on any component of the system.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move, lift, remove packaging from or prepare the unit for installation.
1 Important Safety Instructions 5
NOTICE
NOTICE
CAUTION: Risk of contact with hot surfaces. Can cause injury. The compressor, refrigerant discharge lines, fan motor, and some electrical components are extremely hot during unit operation. Allow sufficient time for them to cool to a touch-safe temperature before working within the unit cabinet. Use extreme caution and wear appropriate, OSHA-approved PPE when working on or near hot components.
Risk of oil contamination with water. Can cause equipment damage.
Liebert®Mini-Mate systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant charge must be weighed into air-cooled compressorized systems before they are started. Starting digital scroll compressors without proper refrigerant charging can cause the compressors to operate at less than 5°F (–15°C) evaporator temperature and at less than 55psig (379kPa). Operation for extended periods at less than 55psig (379kPa) can cause premature compressor failure.
NOTICE
NOTICE
Risk of clogged or leaking drain lines and leaking water-supply lines. Can cause equipment and building damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and periodically, and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in catastrophic and expensive building and equipment damage and loss of critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid-detection system to immediately discover and report coolant-fluid system and condensate drain-line leaks.
Risk of leaking water. Can cause equipment and building damage.
Improper installation, application, and service practices can result in water leakage from the unit. Do not mount this unit over equipment and furniture that can be damaged by leaking water. Install a water-tight drain pan with a drain connection under the cooling unit. We recommend installing monitored leak detection equipment for the unit and supply lines. Check drain lines periodically for leaks, sediment buildup, obstructions, kinks and/or damage and verify that they are free running.
6
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
NOTICE
NOTICE
NOTICE
Risk of improper water supply. Can reduce humidifier efficiency or obstruct humidifier plumbing.
Do not use completely demineralized water with this unit. The water must contain minerals for the electrode principle to work.
Do not use a hot water source. It will cause deposits that will eventually block the fill-valve opening.
Risk of water backing up in the drain line. Leaking and overflowing water can cause equipment and building damage.
Do not install an external trap in the drain line. This line already has a factory-installed trap inside the cabinet. Installation of a second trap will prevent drain-water flow and will cause the water to overflow the drain pan.
This line may contain boiling water. Use copper or other material that is rated for handling boiling water for the drain line. Sagging condensate drain lines may inadvertently create an external trap.
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.

1.1 Agency Listed

Standard 60-Hz units are CSA Certified to the harmonized U.S. and Canadian product safety standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and are marked with the CSA c-us logo.
1 Important Safety Instructions 7
This page intentionally left blank
8
Vertiv | Liebert® Mini-Mate™ Installer/User Guide

2 NOMENCLATURE AND COMPONENTS

This section describes the model number for Liebert® Mini-Mate units and components.

2.1 Mini-Mate Model-number Nomenclature

The tables below describe each digit of the 25-digitconfigurationnumber. The 14-digit model number consists of the first 10 digits and last 4 digits of the configuration number.
Table 2.2 below describes each digit of the model number.
Table 2.1 Mini-Mate 25-digit Configuration Number
Model Number Digits 1 to 10 Model Details
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
M T 0 6 0 H E 1 A 0 S H 2 0 D 0 U 0 P 0 0 A # # #
Table 2.2 Model-number Digit Definitions
Digit and Description
Digits 1 and 2 = Unit Family
MT = Mini-Mate Ceiling System
Digits 3, 4, 5 = Nominal Cooling Capacity
036 = 36kBtuh
048 = 48kBtuh
060 = 60 kBtuh
Digit 6 = Air Direction and Discharge
H = Horizontal air flow
Digit 7 = System type
E = Split-system evaporator
Digit 8 = Fan type
1 = Direct-drive EC motor (variable-speed)
Digit 9 = Supplypower
A = 460V/ 3ph/ 60Hz
B = 575V/ 3ph/ 60Hz (048 and 060 models only)
C = 208V/ 3ph / 60Hz (048 and 060 models only)
D = 230V/ 3ph / 60Hz (048 and 060 models only)
P = 208-230/1ph/60Hz (036 model only)
Y = 208-230/3ph/60Hz (036 model only)
Digit 10 = Evaporator Type
0 =Split-system evaporator
Digit 11 = Humidifier
0 = No humidifier
S = Steam-gen canister humidifier
Digit 12 = Displaytype
H = 9-in. remote display, IntelliSlot-based monitoring (048 and 060 models only)
1 = 9-in. remote display, iCOM-based monitoring (036 model only)
ModelNumber Digits11to14
2 Nomenclature and Components 9
Table 2.2 Model-number Digit Definitions (continued)
Digit and Description
Digit 13 = Reheat
0 = No reheat
2 = Electric reheat
5 = SCR reheat (048 and 060 models only)
Digit 14 = Coil, Valve, Pressure
0 = Split-system evaporator
Digit 15 = High-voltage options
D = Non-locking disconnect, 5k SCCR (048 and 060 models only)
L = Locking disconnect, 5kA SCCR (036 model only)
M = Locking disconnec t, 65k SCCR (048 and 060 models only)
Digit 16 = Low-voltage options
0 = None
L = Low-voltage terminal package (LVTP)
Digit 17 = Monitoring Cards
0 = No card, IntelliSlot only(048 and 060 models only)
U = IS-UNITY-DP card, factory-installed (048 and060 models only)
B = BACnet, Modbus, SNMP usingiCOM board (036 model only)
Digit 18 = Sensors
0 = None
S = Smoke sensor
H = High-temperature sensor
F = Smoke andhigh-temperature sensor
Digit 19 = Packaging
P = Domestic
C = Wood crate export
Digits 20, 21 = Future use
Digit 22 = Factory Configuration c ode
A = No SFA’s (Any Alphaletter except S)
S = SFA
Digit 23-25 = Factory Configuration Number

2.2 Component Location

The unit component locations are described in the submittal documents included in the Submittal
Drawings on page53.
The following tables list the relevant documents by number and title.
Table 2.3 Component-location Drawings
Document Number Title
DPN004808 Evaporator Unit, 3-ton
DPN004179 Evaporator Unit, 4-ton and 5-ton
10
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
3 PRE-INSTALLATION PREPARATIONANDGUIDELINES
NOTE: Before installing unit, determine whether any building alterations are required to run piping, wiring and ductwork. Follow all unit dimensional drawings and refer to the submittal engineering dimensional drawings of individual units for proper clearances.
Refer to Model-number Digit Definitions on page9, and submittal drawings to determine the type of system being installed and anticipate building alterations, piping and ductwork needed.
The unit dimensions, pipe-connection locations, and piping schematics are described in the submittal documents included in the Submittal Drawings on page53.
Confirm that the room is properly insulated and has a sealed vapor barrier.
For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of total air circulated in the room).
Install the units as close as possible to the largest heat load.
Allow at least the minimum recommended clearances for maintenance and service. See the appropriate submittal drawings for dimensions.
We recommend installing a water detection system. Contact your Vertiv representative for information.

3.1 Planning Dimensions

The unit dimensions described in the submittal documents included in the Submittal Drawings on page53.
The following table lists the relevant documents by number and title.
Table 3.1 Dimension Planning Drawings
Document Number Title
DPN004800 Cabinet dimensions, 3-ton DX module
DPN004055 Cabinet dimensions, 4-ton and5-ton DX module
Filter andDucting Options
DPN004805 Dimensional data, Filter box and Duct Flange, 3-ton
DPN004807 Dimensionaldata, Air-distribution plenum 3-ton
DPN004166 Dimensional data, Filter box and Duct Flange, 4- and 5-ton
DPN004842 D imensionaldata, Bottom-discharge Grille, 4- and 5-ton

3.2 Location Considerations

The evaporator is usually mounted above the dropped ceiling and must be securely mounted to the roof structure. For ducted systems, the evaporator may be located in a different room. See Guidelines for
Ducted Systems on page29, for additional guidelines. For a split system with an air-cooled, outdoor
condensing unit, the condensing unit may be mounted on the roof or remotely in an outdoor area. See
Location Considerations for Outdoor Condensing Unit on the next page, for additional guidelines.
Refer to Refrigerant-line Sizes and Equivalent Lengths on page17 for maximum refrigerant line lengths.
The ceiling and ceiling supports of existing buildings may require reinforcement. See Mini-Mate Unit
Weights on page13. Be sure to follow all applicable national and local codes.
Install the ceiling-mounted unit over an unobstructed floor space if possible. This will allow easy access for routine maintenance or service. Do not attach additional devices (such as smoke detectors, etc.) to the housing, as they could interfere with the maintenance or service.
Do not install units in areas where normal unit operating sound may disturb the working environment.
3 Pre-installation PreparationandGuidelines 11

3.2.1 Location Considerations for Outdoor Condensing Unit

Observe the following when planning the installation of the outdoor unit:
To ensure a satisfactory air supply, locate air-cooled condensing units in an environment with clear air, away from loose dirt and foreign matter that may clog the coil.
Condensing units must not be located in the vicinity of steam, hot air or fume exhausts or closer than 18 inches from a wall, obstruction or adjacent unit.
Avoid areas where heavy snow will accumulate at air inlet and discharge locations.
The condensing unit should be located for maximum security and maintenance accessibility. Avoid ground-level sites with public access. Install a solid base, capable of supporting the weight of the condensing unit.
The base should be at least 2in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger than the dimensions of the condensing-unit base. For snowy areas, a base of sufficient height to clear snow accumulation must be installed.
Before beginning, refer to Piping and Refrigerant Requirements on page15 for unit placement, piping guidelines, and refrigerant-charge requirements for your system.

3.3 Connections and System Setup

The unit requires a drain, which must comply with all applicable codes. This drain line may contain boiling water. See Drain Line Installation Requirements on page20, for details.
Electrical service is required for all models. Electrical service must conform to national and local electrical codes. See equipment nameplate for details.
Plan the routing of wiring, piping and ductwork to the unit. Refer to the appropriate piping connection location drawings, piping schematics, and electrical-connection drawings for your system in .
NOTE: Seal openings around piping and electrical connection to prevent air leakage. Failure to do so could reduce the unit’s cooling performance.

3.4 Operating Conditions

The Liebert® Mini-Mate must be operated in a conditioned space within the operating envelope that ASHRAE recommends for data centers. Operating the Mini-Mate outside of this envelope can decrease equipment reliability. Refer to ASHRAE’s publication, “Thermal Guidelines for Data Processing Environments.”

3.4.1 Cooling, Humidification and Dehumidification

For operation in the Cooling, Humidification or Dehumidification modes, the Liebert® Mini-Mate unit’s return-air requirements for proper unit operation are:
Maximum dew point of 59°F (15°C)
Minimum 65°F (20°C)DB
Maximum 85°F (29.4°C) DB

3.4.2 Heating

For operation in the Heating mode, the Liebert® Mini-Mate unit’s return-air requirements for proper unit operation are:
Maximum humidity: less than 80% RH and less than 64°F (17.8°C) dew point.
Maximum dry bulb of 80°F (27°C)
12
Vertiv | Liebert® Mini-Mate™ Installer/User Guide

3.5 Mini-Mate Unit Weights

Table 3.2 Mini-Mate Unit weights
Model # Weight, lb (kg)
MT036 328 (149)
MT048 498 (22 6)
MT060 498 (226)

3.6 Equipment Inspection and Handling

SAFETY INFORMATION
WARNING! Risk of improper moving, lifting, or handling of the unit. Can cause equipment damage, injury or death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the weight of the unit before attempting to move, lift, remove packaging from or prepare the unit for installation. Unit weights are specified in section Table
3.2 above.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move, lift, remove packaging from or prepare the unit for installation.
NOTICE
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.
Upon arrival of the unit and before unpacking:
Verify that the labeled equipment matches the bill of lading.
Carefully inspect all items for visible or concealed damage.
Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales representative.
Equipment Recommended for Handling the Unit:
Forklift
Pallet jack
3 Pre-installation PreparationandGuidelines 13
This page intentionally left blank
14
Vertiv | Liebert® Mini-Mate™ Installer/User Guide

4 PIPING AND REFRIGERANT REQUIREMENTS

All fluid and refrigeration connections to the unit, with the exception of the condensate drain and humidifier supply line, are sweat copper. Factory-installed piping brackets must not be removed. Field­installed piping must be installed in accordance with local codes and must be properly assembled, supported, isolated and insulated. Avoid piping runs through noise-sensitive areas, such as office walls and conference rooms.
Refer to specific text and detailed diagrams in this manual for other unit-specific piping requirements.
The pipe connection locations, piping general arrangement and schematics are described in the submittal documents included in the Submittal Drawings on page53.
The following tables list the relevant documents by number and title.
Table 4.1 Piping General-arrangment Drawings
Document Number Title
Air-cooled System
DPN004060 Piping arrangement, 3-, 4- and 5-ton split-system
Table 4.2 Piping Connection Drawings
Document Number Title
DPN004801 Primary connection locations, 3-ton DX module
DPN004806 Condensate-pump connection locations, 3-ton
DPN004056 Primary connection locations, 4-ton and 5-ton D X module
DPN004077 Condensate-pump connection locations, 4-ton and 5-ton

4.1 Refrigerant Piping and Charging

WARNING! Risk of over-pressurization of the refrigeration system. Can cause explosive discharge of high-pressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate. Local building or plumbing codes may require installing a pressure-relief device in the system.
CAUTION: Risk of excessive refrigerant line pressure. Can cause tubing and component rupture resulting in equipment damage and personal injury. Do not close off any field-installed refrigerant-line isolation valves for repairs unless a pressure-relief valve is field- installed in the line between the isolation valve and the check valve. The pressure-relief valve must be rated 5% to 10% higher than the system-design pressure. An increase in ambient temperature can cause the pressure of the isolated refrigerant to rise and exceed the system-design pressure rating (marked on the unit nameplate).
Consult local building and plumbing codes for installation requirements of additional pressure-relief devices when isolation valves are field installed. Do not isolate any refrigerant circuits from over­pressurization protection.
4 Piping and Refrigerant Requirements 15
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
Liebert®Mini-Mate systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
NOTICE
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant charge must be weighed into air-cooled compressorized systems before they are started. Starting digital scroll compressors without proper refrigerant charging can cause the compressors to operate at less than 5°F (–15°C) evaporator temperature and at less than 55psig (379kPa). Operation for extended periods at less than 55psig (379kPa) can cause premature compressor failure.
4.1.1 Refrigerant Piping Guidelines forAir-cooledSystems
Evaporators and condensing units ship with an inert-gas holding charge. Do not vent the evaporator and condensing unit until all refrigerant piping is in place, ready for connection to the unit and condensing unit.
Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Avoid soft solders, such as 50/50 or 95/5.
Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide scale inside the piping. When copper is heated in the presence of air, copper oxide forms. POE oils will dissolve these oxides from inside the copper pipes and deposit them throughout the system, clogging filter driers and affecting other system components.
A pure dry nitrogen flow of 1-3 ft3/min (0.5-1.5 l/s) inside the pipe during brazing is sufficient to displace the air. Control the flow using a suitable measuring device.
Ensure that the tubing surfaces to be brazed are clean and that all burrs have been removed from the ends of the tubes.
Ensure that all loose material has been cleaned from inside the tubing before brazing.
Protect all refrigerant line components within 18in. (460mm) of the brazing site by wrapping them with a wet cloth or with a suitable heat-sink compound.
Isolate piping from building using vibration-isolating supports.
When sealing openings in walls and to reduce vibration transmission, use a soft, flexible material to pack around the tubes to prevent tube damage.
When installing remote condensing units above the evaporator, the suction gas lines should be trapped at the evaporator. These traps will retain refrigerant oil in the off cycle. When the unit starts, oil in the traps is carried up the vertical risers and returns to the compressors. For rises over 25ft (7.6m), trap every 20ft (6m)or evenly-divided.
Consult factory if piping run exceeds 150ft(46m) equivalent length.
Keep piping clean and dry, especially on units with R-410A refrigerant.
Avoid piping runs through noise-sensitive areas.
Do not run piping directly in front of discharge air stream.
Refrigerant oil – do not mix oil types.
Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
NOTE: All indoor and outdoor suction-line piping must have 1/2 in. minimum of insulation. All outdoor insulation must be UV and ozone resistant.
16
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
NOTE: Proper safety equipment and proper refrigeration tools are required when working with R-410A refrigerant. Check unit serial tag for correct refrigerant type before topping-off or recharging a system.
NOTE: Refrigerant R-410A uses a POE (polyolester) lubricant. The refrigerant must be introduced and charged from the cylinder only as a liquid.
NOTE: When installing field piping, you must take care to protect all refrigerant lines from the atmosphere especially when using refrigerants with POE oils. Do not allow the piping to stand open to air for more than 15minutes. Units designed for R-410A have a compressor that contains POEoil, which quickly absorbs water from the air. The longer that the refrigerant piping is left open to air, the harder it will be to fully evacuate the system. If left open too long, the POE oil may require replacement to achieve the required vacuum level.
Refer to Refrigerant-line Sizes and Equivalent Lengths below,for recommended refrigerant piping sizes based on equivalent pipe lengths.
Refer to the condensing unit's Installer/User Guide for the complete charging procedure of the system.

4.2 Refrigerant-line Sizes and Equivalent Lengths

The following tables list the information required to field-install the refrigerant piping for the system.
Table 4.3 Recommended refrigerant line sizes, O.D.cubyequivalentlength
Equivalent Length, ft (m)
System Models
50 (15) 75 (23) 100 (30) 125 (38) 150 (45)
MT036E/PFD037A-*L or PFD037A-*H
MT048HE/PFD054A-*L
MT060HE/PFD067A-*L
MT060HE/PFDZ67A-*L or PFD067A-*H
Consult factory for proper line sizing for runs longer than maximum equivalent length shown.
1.Use one line size smaller on suction lines for verticalrisers.
Suction line, in. 7/8 7/8 7/8 7/8 7/8
Liquid line, in. 1/2 1/2 1/2 1/2 1/2
Suction line, in. 7/8 1-1/8
Liquid line, in. 1/2 1/2 5/8 5/8 5/8
Suction line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid line, in. 1/2 5/8 5/8 5/8 5/8
Suction line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid line, in. 1/2 5/8 5/8 5/8 5/8
1

4.2.1 Refrigerant Charge Requirements

To calculate the charge requirements:
1. Determine the charge for your units by model number from the following tables.
2. Determine the charge for the piping by line size and length.
3. Add these all together to obtain the total refrigerant charge for your system.
Table 4.4 Indoor Evaporator Approximate R-410Arefrigerant charge
Model # Charge, lb (kg)
MT036HE 1 (0.45)
MT048HE 2.2 (1.0)
MT060HE 2.2 (1.0)
1-1/8
1
1-1/8
1
1-1/8
1
4 Piping and Refrigerant Requirements 17
Table 4.5 Interconnecting piping refrigerant charge for R-410A, lbper 100ft (kgper30m)
Line Size,
O.D., in.
3/8 3.2 (1.4)
1/2 5.9 (2.7) 0.2 (0.1)
5/8 9.6 (4.3) 0.4 (0.2)
3/4 14.3 (6.4) 0.6 (0.3)
7/8 19.8 (8.8) 0.8 (0.4)
1-1/8 33.8 (15.1) 1.4 (0.6)
1-3/8 51.5 (23.0) 2.1 (1.0)
Source:DPN003099 Rev. 1
Liquid Line,lb (kg) Suction Line, lb (kg)
Table 4.6 Liebert® PFD R-410A refrigerant charge
Model # Charge, lb (kg)
PFD037A-*L1 13.4 (6.1)
PFD037A-*H1 27 (12.2)
PFD054A-*L1 27 (12.2)
PFD067A-*L1 27 (12.2)
PFDZ67A-*L1 57 (25.8)
PFD067A-*H1 57 (25.8)

4.2.2 Additional Oil Requirements for Digital-scroll Compressors

NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage.
Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty.
Do not mix polyolester (POE) and mineral-based oils.
Do not mix oils of different viscosities.
Consult your Vertiv sales representative, visit https://www.vertivco.com/en-us/support/, or contact the compressor manufacturer if questions arise.
System charges may require additional oil charge to be added. See Table 4.7 on the facing page, for the amount required for various system charge levels.
After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system while the system is running.
On the tag marked “Oil Added Field Service Record,” attached to each compressor, record the date the oil was added and the amount of oil added.
18
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
Table 4.7 Additional oil required per refrigerant charge
Model
MT036HE/PFD037 MT048HE/PFD054 MT060HE, PFD067, PFDZ67
Refrigerant System
Charge per Circuit,
lb (kg) *
Additional Oil Required Per Circuit, oz (ml)
<40 (18.1) 0 0 0
40 (18.1) 4 (120) 4 (120) 6 (180)
50 (22.7) 6 (180) 6 (180) 9 (270)
60 (27.2) 8 (240) 8 (240) 12 (350)
70 (31.8) 10 (300) 10 (300) 15 (440)
80 (36.3) 12 (350) 12 (350) 18 (530)
* System Charge = indoor unit + condensing unit + refrigerant lines. For system charges over 80lb. (36.3 kg), consult your Vertivrepresentative.
Source: DPN003950 Rev5.
Table 4.8 Compressor oil types for R-410A Refrigerant
Compressor Type Oil Type
CopelandScroll and Digital Scroll POE Oil - ISO 32 Centistoke Viscosity
1. Use CopelandPOE OilULTRA 32-3MAF or other Copeland-approved oils.
Source: DPN003950. Rev. 5
1
4 Piping and Refrigerant Requirements 19

4.3 Drain and Humidifier Piping

The following pipe connections are required:
A drain line from the evaporator-unit drain connection.
A drain line from the secondary drain pan (if applicable).
A water-supply line to the optional humidifier (if applicable).
On air-cooled systems: refrigerant piping connections between the evaporator unit and the condensing unit. See Piping and Refrigerant Requirements on page15.
NOTICE
Risk of clogged or leaking drain lines and leaking water-supply lines. Can cause equipment and building damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and periodically, and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in catastrophic and expensive building and equipment damage and loss of critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid-detection system to immediately discover and report coolant-fluid system and condensate drain-line leaks.

4.3.1 Water-supply line to the Humidifier

The following is required for units with the optional steam-generating humidifier package:
1/4-in. (6.4mm) copper compression fitting connection for water inlet.
The supply pressure range is 10psig to 150psig (69to1034kPa) at 1gpm (3.8(lpm).
A shut-off valve in the supply line to isolate the humidifier for maintenance.
Do not supply steam-generating humidifier with softened water.
Do not use hot water source.
Water conductivity must be in the range of 330-750micro-siemens.
To install the water supply:
1. Cut the tube square and remove any burrs.
2. Slide nut, then the sleeve on tube. The threaded end of the nut faces the end of the tube.
3. Insert the tube into the fitting, seating it against the stop shoulder and tighten the nut hand­tight to the body.
4. Use a wrench to tighten the nut 1-1/4 to 2-1/4 turns.
NOTICE
Risk of improper tightening of the piping fittings. Can damage fittings and cause leaks.
Use caution not to over-tighten or under-tighten the piping fittings.
Do not route the humidifier supply line in front of the filter-box access panel.

4.3.2 Drain Line Installation Requirements

20
NOTICE
Risk of water backing up in the drain line. Leaking and overflowing water can cause equipment and building damage.
Vertiv | Liebert® Mini-Mate™ Installer/User Guide
Do not install an external trap in the drain line. This line already has a factory-installed trap inside the cabinet. Installation of a second trap will prevent drain-water flow and will cause the water to overflow the drain pan.
This line may contain boiling water. Use copper or other material that is rated for handling boiling water for the drain line. Sagging condensate drain lines may inadvertently create an external trap.
A 3/4 in. (19.1mm) NPT-female connection is provided for the evaporator-unit condensate drain. The evaporator drain pan includes a float switch to prevent operation if the drain line becomes blocked. This line also drains the humidifier, if applicable.
Observe the following requirements and refer to Figure 4.1 below, when installing and routing the drain line:
The drain line must be sized for 2gpm (7.6 l/m) flow.
The drain line must be located so it will not be exposed to freezing temperatures.
The drain should be the full size of the drain connection.
The drain line must slope continuously away from the unit.
Do not externally-trap the drain line.
The drain line must be rigid enough that it does not sag between supports, which unintentionally creates traps.
Use copper or other material suitable for draining water that can reach temperatures up to 212°F (100°C).
When the evaporator is installed below the level of the gravity-fed drain line, the optional condensate pump kit is required. See Condensate-drain Pump Kit on the next page.
NOTE: Remove the shipping band from the float switch in the evaporator pan before operating the unit.
Figure 4.1 Correct and Incorrect gravity drains
Table 4.9 Gravity-fed Drain Line Figure Descriptions
Item D escription
1 Correct drain installation.
2 Incorrect. Do not trap externally.
3 Incorrect. Sagging between supports and bowed line causes unintentionalexternal traps.
4 Continuous downward slope away from the unit.
5 Unit
6 External trap
7 Unintentional trapsfrom bowing of line. Lines must be rigid enough not to bow or sag between supports, creatinga trap.
4 Piping and Refrigerant Requirements 21

4.3.3 Condensate-drain Pump Kit

WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote electric power supply disconnect switches and verify with a voltmeter that power is off before working within any electric connection enclosures. Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations and manufacturers’ specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages within the unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.
The optional condensate pump kit is required when the evaporator is installed below the level of the gravity-fed drain line. The condensate pump is field-installed alongside the evaporator unit.
A 3/4-in. NPT-Female connection is provided for the evaporator-unit condensate drain.
The drain is trapped internally, do not trap external to unit.
Size the discharge piping based on the available condensate head.
The pumps are rated as follows:
460-V condensate pump rated for 7.5 GPM (28.4 l/m) at 10-ft head pressure. The 460-V pump is used on units with 575-V supply power.
208/230-V condensate pump rated for 5.1 GPM (19.3 l/m) at 10-ft head pressure.
The installation of the condensate-drain pump is described in the submittal documents included in the
Submittal Drawings on page53.
The following tables list the relevant documents by number and title.
Table 4.10 Condensate-drain Pump Drawings
Document Number Title
DPN004806 Condensate-pump connection locations, 3-ton models
DPN004077 Condensate-pump connection locations, 4- and5-ton models
22
Vertiv | Liebert® Mini-Mate™ Installer/User Guide

5 ELECTRICAL CONNECTION REQUIREMENTS

WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supply disconnect switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not isolate power from the unit, even in the “Unit Off” mode. Some internal components require and receive power even during the “Unit Off” mode of the controller. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local codes.
WARNING! Risk of improper wire sizing/rating and loose electrical connections. Can cause overheated wire and electrical connection terminals resulting in smoke, fire, equipment and building damage, injury or death. Use correctly sized copper wire only and verify that all electrical connections are tight before turning power On. Check all electrical connections periodically and tighten as necessary.
NOTE: Seal openings around piping and electrical connections to prevent air leakage. Failure to do so could reduce the unit's cooling performance.
NOTICE
Risk of improper electrical supply connection. Can cause equipment damage.
See transformer label for primary tap connections. Installer will need to change transformer primary taps if applied unit voltage is other than pre-wired tap voltage.
NOTE: For 208-VAC, 3-ton applications, the low-voltage transformer tap must be changed. Refer to the electrical schematic.
All power and control wiring and ground connections must be in accordance with the National Electrical Code and local codes. Refer to the equipment serial-tag data for electrical requirements.
A manual electrical disconnect switch should be installed in accordance with local codes and distribution system. Consult local codes for external disconnect requirements.
NOTE: Input-power requirements: For 3-phase units, only 3 power wires and an earth ground are required.
The electrical connections are described in the submittal documents included in the Submittal Drawings on page53.
The following table lists the relevant documents by number and title.
Table 5.1 Electrical Field-connection Drawings
Document Number Title
DPN004802 ElectricalField Connections, 3-ton DX Module
DPN004057 Electrical Field Connections, 4-ton and5-ton DX Module
DPN004238 4- and5-ton iCOM Wall-mount FieldConnection
DPN004803 3-ton iCOM Wall-mount Field Connection
5 Electrical ConnectionRequirements 23
Table 5.1 Electrical Field-connection Drawings (continued)
Document Number Title
Unit-to-Unit Networking
DPN004840 3-ton Model iCOM unit-to-unit field connection
DPN004841 4- and5-ton Models iCOM unit-to-unit field connection

5.1 Low-voltage Electrical Field Connections

Figure 5.1 on the facing page, shows an overview of the low-voltage wiring connections between the Mini-Mate module and the condensing unit (on DX systems only), and the wiring and cabling between the wall-mounted iCOM display for all system types. Detailed connection information is included in the submittal drawings listed in Table 5.1 on the previous page.
Connect field-supplied, shielded, Class 1 wiring from the condensing unit to the indicated terminal-strip locations.
For the wall-mounted iCOM-controller display:
Connect a field-supplied, CAT5 Crossover Ethernet cable between P64 on the iCOM-control board in the Mini-Mate module and ETH-1 on the wall-mount iCOM display.
Locate the wire harness inside the wall-mount display, and connect field-supplied, Class 1 wiring between the harness and landing on the terminal-strip 13, 14, and 15 in the Mini-Mate module to provide power for the display.
For the wall-mounted temperature/humidity sensor:
Plug the factory-supplied, CANbus cable into P66 on the iCOM-control board in the Mini-Mate module and into P66, Ethernet connection on the temperature/humidity sensor.
24
Vertiv | Liebert® Mini-Mate™ Installer/User Guide