60 Hz and 50 Hz, High Density Microchannel Condenser
The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
Vertiv | Lieb ert® MCV Installer/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions1
2 Nomenclature and Components5
2.1 Liebert® MCV Model Number Nomenclature5
2.2 Component Location6
2.3 Product Description and Features7
2.3.1 Control, Fan Types and Features7
3 Pre-installation PreparationandGuidelines9
3.1 Planning Dimensions10
3.2 Unit Weights10
4 Equipment Inspection and Handling11
4.1 Packaging Material11
4.2 Lift Points for Moving the Skid11
4.3 Removing Shipping Panels and Brackets12
5 Piping13
5.1 Refrigerant Piping and Charging13
5.1.1 Refrigerant Piping Guidelines for Air Cooled Systems14
5.1.2 Refrigerant Charge Requirements15
5.1.3 Additional Oil Requirements16
5.2 System Dehydration/Leak Test16
5.3 Charging for Condensers16
6 Electrical Connections17
6.1 Line Voltage Wiring18
6.2 Wye vs. Delta Connected Power Supply20
6.3 Low Voltage Control Wiring—CANbus Communication20
7 Checklist for Completed Installation21
7.1 Moving and Placing Equipment21
7.2 Electrical Installation Checks21
7.3 Piping Installation Checks21
7.4 Other Installation Checks21
8 Initial Start up Checks andCommissioningProcedure forWarrantyInspection23
10.3.3 Switch from Compressor Operation to Pump Operation33
i
10.3.4 Switch from Pump Operation to Compressor Operation33
10.4 Premium Efficiency Control Board and Interface34
10.4.1 Initial Display upon Power On35
10.4.2 Navigating the Controller Interface Main Menu35
10.4.3 Analog Signals Menu36
10.4.4 Active Alarms Menu39
10.4.5 History Alarms Menu39
11 Maintenance43
11.1 General Maintenance44
11.2 Condenser Cleaning44
11.2.1 When to Clean the Condenser Coil44
11.2.2 What to Use to Clean the Condenser Coil44
11.2.3 Cleaning the Condenser Coil45
11.3 Replacing the Condenser Fan45
11.3.1 Verifing the Fan Address51
11.4 Replacing the Premium Efficiency Control Board52
11.4.1 Preparing to Replace the Board52
11.4.2 Installing the Replacement Board53
12 Preventive Maintenance Checklist55
Appendices59
Appendix A: Technical Support and Contacts59
Appendix B: Submittal Drawings61
ii
Vertiv | Lieb ert® MCV Installer/User Guide
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the
Liebert®MCV. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual.
Follow all installation, operation and maintenance instructions and all applicable national and local building, electrical and
plumbing codes.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power
even during the Unit Off mode of the controller. The only way to ensure that there is NO voltage inside the
unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local
codes.
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturers’
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
WARNING! Risk of electric shock. Can cause serious injury or death. The Liebert® iCOM™ microprocessor
does not isolate power from the unit, even in the Unit Off mode. Some internal components require and
receive power even during the "unit off" mode of the Liebert® iCOM™ control. Open all local and remote
electric power disconnect switches and verify with a voltmeter that power is Off before working on any
component of the system.
WARNING! Risk of electric shock. Can cause serious injury or death. Open all local and remote electric power
supply disconnect switches and verify with a voltmeter that power is off before working within the fan motor
electric connection enclosures. Fan motor controls can maintain an electric charge for 10 minutes after power
is disconnected. Wait 10 minutes after power is verified as off before working within the fan electric
control/connection enclosures. Use only fully trained and qualified HVAC technicians to perform
maintenance on the fans.
1 Im portant Safety Instructions
1
WARNING! Risk of over pressurization of the refrigeration system. Can cause explosive discharge of high
pressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This
unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant
system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate.
WARNING! Risk of contact with high speed rotating fan blades. Can cause serious injury or death. Open all
local and remote electric power supply disconnect switches, verify with a voltmeter that power is off, and
verify that all fan blades have stopped rotating before working in the unit cabinet or on the fan assembly. If
control voltage is applied, the fan motor can restart without warning after a power failure. Do not operate the
unit with any or all cabinet panels removed.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury or death. Installation and service of this equipment should be done only by qualified personnel
who have been specially trained in the installation of air conditioning equipment and who are wearing
appropriate, OSHA-approved PPE.
WARNING! Risk of improper moving, lifting, or handling of the unit. Can cause equipment damage, injury or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from or prepare the unit for installation.
See Table 3.2 on page10, for weights.
WARNING! Risk of improper wire sizing/rating and loose electrical connections. Can cause overheated wire
and electrical connection terminals resulting in smoke, fire, equipment and building damage, injury or death.
Use correctly sized copper wire only and verify that all electrical connections are tight before turning power
On. Check all electrical connections periodically and tighten as necessary.
WARNING! Risk of electrical fire and short circuit. Can cause property damage, injury or death. Select and
install the line side electrical supply wire and overcurrent protection device(s) according to the specifications
on the unit nameplate(s), per the instructions in this manual and according to the applicable national, state
and local code requirements. Use copper conductors only. Verify that all electrical connections are tight. Unit
specific wiring diagrams are provided on each unit.
CAUTION: Risk of improper moving, lifting and handling. Can cause equipment damage or injury. Only
properly trained and qualified personnel should work on this equipment. Condenser fan modules weigh in
excess of 115lb(52.2kg). Use proper lifting techniques and wear appropriate, OSHA-approved PPE to avoid
injury and dropping the fan module during removal. Equipment used in handling/lifting, and/or installing the
fan assembly must meet OSHA requirements. Use handling/lifting equipment rated for the weight of the fan
assembly. Use ladders rated for the weight of the fan assembly and technicians if used during installation.
Refer to handling/lifting, and/or installation equipment operating manual for manufacturer's safety
requirements and operating procedures.
2
Vertiv | Lieb ert® MCV Installer/User Guide
NOTICE
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
CAUTION: Risk of contact with hot surfaces. Can cause injury. The electronics housing, humidifier
components, compressor, refrigerant discharge lines, fan motor, and some electrical components are
extremely hot during unit operation. Allow sufficient time for them to cool to a touch safe temperature before
working within the unit cabinet. Use extreme caution and wear appropriate, OSHA-approved PPE when
working on or near hot components.
CAUTION: Risk of exposure to harmful noise levels. Can cause hearing injury or loss. Depending on the
installation and operating conditions, a sound pressure level greater than 70dB(A) may arise. Take
appropriate technical safety measures. Operating personnel must wear appropriate, OSHA-approved PPE
and observe all appropriate hearing-protection safety requirements.
Risk of improper power supply connection. Can cause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a main or alternate power source (for example: backup generator
systems) for start up, commissioning, testing, or normal operation, ensure that these sources are correctly
adjusted to the nameplate voltage and frequency of all equipment to be connected. In general, power source
voltages should be stabilized and regulated to within ±10% of the load nameplate nominal voltage. Also, ensure
that no three phase sources are single phased at any time.
NOTICE
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
Liebert®MCV systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster rate
when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system,
extreme care must be used when opening systems during installation or service. If water is absorbed into the
POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil
is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a
refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring
any foreign matter back to the compressor.
Risk of control malfunction. Can cause improper unit operation.
Verify that all low voltage electrical wiring has been performed per the schematic diagram provided and that
all low voltage wiring connections are tight.
1 Im portant Safety Instructions
3
This page intentionally left blank
4
Vertiv | Lieb ert® MCV Installer/User Guide
2 NOMENCLATURE AND COMPONENTS
This section describes the model number for Liebert® MCV units and components.
2.1 Liebert® MCV Model Number Nomenclature
Table 2.2 below describes each digit of the 25 digitconfigurationnumber. The 14 digit model number consists of the first
10 digits and last four digits of the configuration number.
Table 2.1 Liebert® MCV 25 Digit Configuration Number Example
Model # Part 1Model DetailsModel # Part 2
1234567891 0111 2131415161 71819202122232425
MCV330E2AD0G00U020000****
Table 2.2 Liebert® MCV Model Number Digit Definitions
DigitDescription
Digits 1 and 2 = Unit Family
MC = Microchannel Condenser
Digit3 Platform Size
V = V-coil arrangement
Digits 4-6 - Nominal Capacity, kW
330 = 330kW
440 = 440kW
Digit7 - Control/Fan Type
E = Premium c ontrol and EC fan
Digit8 - Refrigerant Circuits/System Refrigerant Type
2 = Dual refrigerantcircuit, R-410A
Digit9 - Power Supply
A = 460V /3ph / 60Hz
2 = 380V / 3ph / 60Hz
M = 380-415V / 3ph /50Hz
Digit10 - Packaging
D = Domestic, non-stackable
E = Export crating, non-stackable
Digit11 - Coil Coating
0 = None
C = E-coat (epoxy withUV topcoat)
2 N omenclature an d Componen ts
5
Table 2.2 Liebert® MCV Model Number Digit Definitions (continued)
DigitDescription
Digit12 - Panel Material
G = Galvanizedsteel
Digit13 - Connection Pipe Unit of Measurement
0 = Inches (std. ACR copper)
Digit14 -Legs Included
0 = No legs (standard)
Digit15 - Agency Certification
U = CSA listed, marked with CSA c-uslogo
Digit16 -Undefined, Reserved for future use.
Digit17 - Receiver/Software Configuration
0 = Liebert® DSEsoftware, no receivers
2 = Liebert® DSEsoftware, withreceivers
Digits 1 8-21 - Undefined, Reserved for future use.
Digits 22-25 -Factory configuration number
2.2 Component Location
The unit component locations are described in the submittal documents included in Submittal Drawings on page61.
The following table lists the relevant documents by number and title.
The Liebert® MCV condenser is a direct drive EC fan type, air cooled heat rejection unit suitable for mounting outdoors. It
provides heat rejection for two separate refrigeration circuits, matches the heat rejection capacity corresponding with the
outdoor ambient temperature and with each corresponding compressor heat rejection requirements. Constructed with a
galvanized steel frame, galvanized steel panels, and aluminum microchannel coil, the unit is quiet and corrosion resistant.
The condenser is quickly and easily installed, because all internal wiring is completed at the factory with only electrical
connections to be made at the job site. All electrical connections and controls are enclosed in an integral, weatherproof
section of the condenser.
Figure 2.1 Liebert® MCV Heat Rejection Skid
2.3.1 Control, Fan Types and Features
Premium Efficiency Control/EC Fan
Premium Efficiency Controls and EC fans are matched to provide superior system energy efficiency. The premium control
board allows CANbus communication with the indoor unit’s Liebert®iCOM™ control. This communication feature provides
compressor run signals, condenser operating mode changes, condenser alarm monitoring, simplified system charging
procedures and outdoor temperature monitoring.
The Premium Efficiency Control board on a Liebert®MCV controls EC fans on the same circuit to the same speed to
maintain refrigerant head pressure in DX mode and refrigerant temperature in EconoPhase mode.
2 N omenclature an d Componen ts
7
Anti-Freezing Operation
The EC fans must be operated periodically in cold weather to reduce the possibility of lock up due to ice and snow
accumulation. During periods of fan inactivity and outdoor temperatures below 35°F (1.6°C), the EC fans will spin for at least
30 seconds every 15 minutes at 60% of the maximum fan speed.
Surge Protective Device
An optional Surge Protective Device (SPD) can be field wired to protect the condenser from power surges that threaten
sensitive equipment. The condenser’s electrical panel provides a terminal block to allow the SPD to be wired in parallel with
the high voltage power. An additional low voltage terminal block is provided on condensers to allow monitoring of the SPD
alarm circuit.
ASCO Series 420 surge protective device provides 50kA per mode of surge current protection. An illuminated green LED
indicates the SPD is on and operating properly. An illuminated red LED indicates that the device may require replacement.
When both LEDs are off, there is no power to the condenser, either from a power failure or because the condenser disconnect
is in the off position.
8
Vertiv | Lieb ert® MCV Installer/User Guide
3 PRE-INSTALLATION PREPARATIONANDGUIDELINES
The unit dimensions, pipe connection locations, and piping schematics are described in the submittal documents included
in the Submittal Drawings on page61.
•Install the condenser in a location offering maximum security and access for maintenance.
•Avoid ground level sites with public access and areas prone to heavy snow or ice accumulations.
•To ensure adequate air supply, we recommend that condensers be installed in an area with clean air, away from
loose dirt and foreign matter that might clog the coil. In addition, condensers should be located no closer than
3 ft. (1m) from a wall, obstruction or adjacent unit.
•For roof installation, mount the condenser on suitable curbs or other supports in accordance with local codes.
•Locations that require additional coil-corrosion protection, such as coastal regions, heavy industrial, or
agricultural air pollution, should specify coils with the optional epoxy e-coat.
•Condensers must not be installed in a pit.
•Condensers must be installed on a level surface to ensure proper refrigerant flow.
•The Liebert® MCV heat rejection skid cannot be installed below the evaporator.
•The DA125 through DA250 are used with a Liebert® MCV heat rejection skid with receiver tanks. For this
system, the outlet of the receivers on the outdoor Liebert® MCV heat rejection skid must be higher than the
elevation of the electronic (EEV) valves inside of the indoor unit. If the vertical height of the receiver outlet is
greater than 60 ft. (18.3m) above the EEV, consult the factory. Refer to DPN003965 in Submittal Drawings on
page61.
•The DA265 is used with a Liebert® MCV heat rejection skid without receiver tanks. For these systems, the
bottom of the condenser coil on the outdoor Liebert® MCV heat rejection skid must be higher than the
elevation of the EEVs inside of the indoor unit. If the vertical height between the condenser coil bottom and the
EEV is greater than 60 ft. (18.3m), consult the factory. Refer to DPN005207 in Submittal Drawings on page61.
•Condensers must be installed in vertical airflow orientation to maintain the NEMA 3R rating of the electrical
box.
3 Pre-install ation Preparationan dGuideli nes
9
3.1 Planning Dimensions
The condenser dimensions are described in the submittal documents included in the Submittal Drawings on page61.
Condensers mounted above and below the relative elevation of the indoor unit must follow the guidelines found in the
submittal drawings listed in the table below.
The following table lists the relevant documents by number and title.
Table 3.1 Dimension Planning Drawings
Docu ment NumberTitle
Heat Rejection Skid Dimensions
DPN003889Cabinet and Anchor Dimensional Data MCV330 +EconoPhase + Base Assembly
DPN003875Cabinet and Anchor Dimensional Data MCV330 (2) + EconoPhase (2) + Base Assembly
DPN004259Cabinet and Anchor Dimensional Data MCV440 + EconoPhase +Base Assembly
DPN004261Cabinet and Anchor Dimensional Data MCV440 (2)+ EconoPhase (2)+ Base Assembly
WARNING! Risk of improper moving, lifting, or handling of the unit. Can cause equipment damage, injury or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from or prepare the unit for installation.
See Table 3.2 on page10
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
NOTICE
Risk of improper lifting. Can cause equipment damage. Make sure that the spreader bars are wider than the
unit. If the spreader bars are too short, the slings may crush the unit.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures
and contact damage.
Upon arrival of the unit and before unpacking:
•Verify that the labeled equipment matches the bill of lading.
•Carefully inspect all items for visible or concealed damage.
•Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales
representative.
4.1 Packaging Material
All material used to package this unit is recyclable. Please save for future use or dispose of the material appropriately.
4.2 Lift Points for Moving the Skid
Refer to the appropriate submittal drawings to locate the lift points for your heat rejection skid located in the Submittal
Drawings on page61.
•Use the indicated lifting points to lift the unit.
•Use spreader bars and/or shimmed blocks to prevent external damage.
•Lift the unit level. Tilting or twisting can damage internal components.
•Use the proper rigging equipment and make sure that attachment and lifting at the designated points is
vertical.
4 Equipmen t Inspection and Hand ling
11
The following table lists the submittal documents by title and number.
Table 4.1 Heat Rejection Skid Drawings
Document NumberTitle
DPN003882Cabinet Lifting Points MCV330 + EconoPhase + Base Assembly
Shipping panels and securing brackets are located on each end of the unit. Before operating the unit, remove the panels and
brackets from both ends of the unit, Figure 4.1 below.
Figure 4.1 Shipping Panels and Securing Brackets to Remove
ItemDescription
14 panels on each end, 8 total.
23 brackets on each end, 6 total.
12
Vertiv | Lieb ert® MCV Installer/User Guide
5 PIPING
All refrigeration connections to the unit are sweat copper. Factory installed piping brackets must not be removed. Field
installed piping must be installed in accordance with local codes and must be properly assembled, supported, isolated and
insulated.
Refer to specific text and to the submittal documents included in Submittal Drawings on page61, for other unit specific
piping requirements.
The following tables list the relevant documents by number and title.
Table 5.1 Piping General Arrangement Drawings
Docu ment NumberTitle
DPN004476Piping Schematic DA125, DA150, and DA250 with Liebert®MCV
WARNING! Risk of over pressurization of the refrigeration system. Can cause explosive discharge of high
pressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This
unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant
system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate.
Consult local building and plumbing codes for installation requirements of additional pressure relief devices when isolation
valves are field installed. Do not isolate any refrigerant circuits from over pressurization protection.
5 Pip ing
13
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
Liebert®MCV systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster rate
when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system,
extreme care must be used when opening systems during installation or service. If water is absorbed into the
POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil
is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a
refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring
any foreign matter back to the compressor.
Table 5.4 System Refrigerant Pressures
Maximum Design Operating Pressure (High Side) 530 psig 3655 kPa N oted on the unit serial tag
5.1.1 Refrigerant Piping Guidelines for Air Cooled Systems
•Field installed interconnecting piping should be properly selected based on local codes and unit labeling.
•Air cooled units and condensers ship with an inert gas holding charge. Do not vent the charge until all
refrigerant piping is in place, ready for connection to the unit and condenser.
•Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Avoid
soft solders, such as 50/50 or 95/5.
•Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide scale inside
the piping. When copper is heated in the presence of air, copper oxide forms. POE oils will dissolve these
oxides from inside the copper pipes and deposit them throughout the system, clogging filter driers and
affecting other system components.
•A pure dry nitrogen flow of 1-3 ft3/min (0.5-1.5 l/s) inside the pipe during brazing is sufficient to displace the air.
Control the flow using a suitable measuring device.
•Ensure that the tubing surfaces to be brazed are clean and that all burrs have been removed from the ends of
the tubes.
•Ensure that all loose material has been cleaned from inside the tubing before brazing.
•Protect all refrigerant line components within 18in. (460mm) of the brazing site by wrapping them with a wet
cloth or with a suitable heat-sink compound.
•Isolate piping from building using vibration isolating supports.
•The Liebert® MCV heat rejection skid cannot be installed below the evaporator.
•The DA125 through DA250 are used with a Liebert® MCV heat rejection skid with receiver tanks. For these
systems, the outlet of the receivers on the outdoor Liebert® MCV heat rejection skid must be higher than the
elevation of the electronic expansion valves (EEV0 inside of the indoor unit. If the vertical height of the receiver
outlet is greater than 60 ft. (18.3m) above the EEV, consult the factory. Refer to DPN003965 in Submittal
Drawings on page61.
•The DA265 is used with a Liebert® MCV heat rejection skid without receiver tanks. For these systems, the
bottom of the condenser coil on the outdoor Liebert® MCV heat rejection skid must be higher than the
elevation of the EEVs inside of the indoor unit. If the vertical height between the condenser coil and the EEV is
greater than 60 ft (18.3m), consult the factory. Refer to DPN005207 in Submittal Drawings on page61.
•Install traps on hot gas (discharge) lines at the base of the vertical risers over 5 ft. (1.5m) and then for vertical
risers over 25 ft (7.6m). Install a trap in 20 ft. (6m) increments or evenly divided over the vertical rise. The
DA250 and DA265 each have piping out of the top of the unit with internally installed traps on the hot gas lines.
•Consult factory for piping lengths exceeding the lengths in Table 5.5 on the facing page.
14
Vertiv | Lieb ert® MCV Installer/User Guide
Table 5.5 Piping Lengths
Indoo r UnitMaximum Actual Leng th Maximum Equivalent Length
DA250, DA265200 ft. (61m)300 ft. (91m)
DA125, DA150, DA165300 ft. (91m)450(137.2m)
•Pitch horizontal hot gas piping down at a minimum rate of 1/2in.per 10ft (42mm per 10m) so that gravity will
aid in moving oil in the direction of refrigerant/oil flow.
•Keep piping clean and dry, especially on units with R-410A refrigerant.
•Avoid piping runs through noise sensitive areas.
•Do not run piping directly in front of discharge air stream.
•Refrigerant oil – do not mix oil types. Consult the indoor-unit installation/user guide for refrigerant type and oil
requirements.
Refer to ASHRAE Refrigeration Handbook for general, good practice refrigeration piping. The indoor cooling unit has a
factory installed high pressure safety switch in the high side refrigerant circuit. A fusible plug is installed in each Liebert®
DSE receiver.
NOTE: Liebert® DSE systems require all indoor and outdoor field refrigerant piping to be insulated 1/2 in. minimum.
All outdoor insulation must be UV and ozone resistant.
•Refer to the indoor unit's Installer/User Guide, for recommended refrigerant piping sizes based on equivalent
pipe lengths.
•Refer to the indoor unit's Installer/User Guide for the refrigerant-charge requirements of the system.
5.1.2 Refrigerant Charge Requirements
Table 5.6 Approximate R-410A Refrigerant Required per Circuit for MCV Heat Rejection Skid
Heat Rejection SkidSystem No .Circuit No.
1
MCV330 Single skid with (1) PRE unit1
2
1
MCV440 Single skid with (1) PRE unit1
2
with or witho ut Receivers lb (kg)
Charge per Circuit
52
(24.6)
62
(28.1)
5 Pip ing
15
Table 5.6 Approximate R-410A Refrigerant Required per Circuit for MCV Heat Rejection Skid (continued)
Heat Rejection SkidSystem No .Circuit No.
MCV330 Dual skid with (2) PRE units
MCV440 Dual skid with (2) PRE units
*The heat rejection skid contains:
•MCV condensers.
•DSE receivers, when used with a DA125 through DA250 system.
•EconoPhase (PRE)units, and all internal piping.
Liebert®DSE receivers are not used with a DA265 system.
1
2
1
2
1
2
1
2
1
262
1
2
Charge per Circuit
with or witho ut Receivers lb (kg)
52
(24.6)
(28.1)
5.1.3 Additional Oil Requirements
Refer to the indoor unit's Installer/User Guide to determine if additional oil is required for each circuit. The need for
additional oil is affected by compressor type, piping lengths, receiver, and total refrigerant charge.
5.2 System Dehydration/Leak Test
Refer to the indoor unit's Installer/User Guide for the leak check and evacuation procedures for the entire thermalmanagement system. Refer to the section that refers to the winter control system used on the condenser.
5.3 Charging for Condensers
Refer to the Liebert® DSE Installer/User Guide for the leak check and evacuation procedures for the entire thermalmanagement system.
16
Vertiv | Lieb ert® MCV Installer/User Guide
6 ELECTRICAL CONNECTIONS
Line voltage electrical service is required for all models. Electrical service must conform to national and local electrical
codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to electrical schematic
when making connections. Refer the appropriate submittal drawing, listed in Table 6.1 on the next page, for electrical
service entrances into unit.
A manual electrical disconnect switch should be installed in accordance with local codes and distribution system. Consult
local codes for external disconnect requirements.
All internal wiring is completed at the factory.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power
even during the Unit Off mode of the controller. The only way to ensure that there is NO voltage inside the
unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local
codes.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury or death. Installation and service of this equipment should be done only by qualified personnel
who have been specially trained in the installation of air conditioning equipment and who are wearing
appropriate, OSHA-approved PPE.
WARNING! Risk of improper wire sizing/rating and loose electrical connections. Can cause overheated wire
and electrical connection terminals resulting in smoke, fire, equipment and building damage, injury or death.
Use correctly sized copper wire only and verify that all electrical connections are tight before turning power
On. Check all electrical connections periodically and tighten as necessary.
NOTICE
Risk of improper power supply connection. Can cause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a main or alternate power source (for example: backup generator
systems) for start up, commissioning, testing, or normal operation, ensure that these sources are correctly
adjusted to the nameplate voltage and frequency of all equipment to be connected. In general, power source
voltages should be stabilized and regulated to within ±10% of the load nameplate nominal voltage. Also, ensure
that no three phase sources are single phased at any time.
NOTE: Use copper wiring only. Make sure that all connections are tightened to the proper torque mentioned on the
component.
The electrical connections are described in the submittal documents included in the Submittal Drawings on page61.
6 Electrical Connections
17
The following table lists the relevant documents by number and title.
DPN003886CANbus a nd Interlock ConnectionsLiebert®MCV + Liebert® EconoPhase + Base Assy.
6.1 Line Voltage Wiring
WARNING! Risk of electrical fire and short circuit. Can cause property damage, injury or death. Select and
install the line side electrical supply wire and overcurrent protection device(s) according to the specifications
on the unit nameplate(s), per the instructions in this manual and according to the applicable national, state
and local code requirements. Use copper conductors only. Verify that all electrical connections are tight. Unit
specific wiring diagrams are provided on each unit.
Risk of improper power supply connection. Can cause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a main or alternate power source (for example: backup generator
systems) for start up, commissioning, testing, or normal operation, ensure that these sources are correctly
adjusted to the nameplate voltage and frequency of all equipment to be connected. In general, power source
voltages should be stabilized and regulated to within ±10% of the load nameplate nominal voltage. Also, ensure
that no three phase sources are single phased at any time.
NOTE: For acceptable and unacceptable power supplies, see Wye vs. Delta Connected Power Supply on page20.
Condenser rated voltage should be verified with available power supply before installation. Refer to the unit’s electrical
schematic and serial tag for specific electrical requirements.
18
Vertiv | Lieb ert® MCV Installer/User Guide
Liebert® MCV condenser power connections are provided for three phase wires and one earth ground wire. Line voltage
electrical service is required for all condensers at the location of the condenser. The voltage supply to the condenser may
not be the same voltage supply as required by the indoor unit. Consider using a UPS on both indoor cooling units and MCV
condensers to maintain uninterrupted cooling capability. Refer to the unit’s serial tag for specific condenser electrical
requirements. A unit disconnect is standard. However, a site disconnect may be required by local code to isolate the unit for
maintenance. Route the supply power to the site disconnect switch and then to the unit. Route the conduit to the knockout
provided in the bottom right end of the electrical control enclosure. Connect the earth ground wire lead to the marked earth
ground connection terminal provided near the factory installed disconnect switch per the appropriate drawing in the
Submittal Drawings on page61.
NOTE: A separate neutral wire does not need to be run to the Liebert® MCV Condenser.
Table 6.2 Liebert® MCV Condenser Only Electrical Data, 3 Phase
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Ma ximum Ov ercurrent Protection Device.
Source: DPN005045 Rev . 1
6 Electrical Connections
B = 575V /60HzN/AN /AN /A
2 = 380V / 60Hz36.437.540
A = 460V /60Hz29.430.335
MCV440 + P RE
G = 415V / 50Hz35.436.340
B = 575V /60Hz23.524.235
19
NOTE: Heat rejection skids with 12 or 16 fans contain two 3 phase connection boxes, and each box requires a separate
supply input per Table 6.3 on the previous page.
6.2 Wye vs. Delta Connected Power Supply
Acceptable Power Supplies—380V to 460V Nominal Units
•380V wye with solidly grounded neutral and 220V line to ground
•480V wye with solidly grounded neutral and 277V line to ground
•Wye with high resistance (or impedance) ground
•Delta with corner ground
Unacceptable Power Supplies
•Delta without ground or with floating ground
•Delta with grounded center tap
6.3 Low Voltage Control Wiring—CANbus Communication
NOTICE
Risk of control malfunction. Can cause improper unit operation.
Verify that all low voltage electrical wiring has been performed per the schematic diagram provided and that
all low voltage wiring connections are tight.
CANbus communication and interlock wiring are required between the indoor and the outdoor units. CANbus cables are
supplied by others to connect the indoor unit to the outdoor condenser. No special considerations are required when the
total external cable connection between the indoor unit and outdoor unit is less than 450ft(137m). A CANbus isolator is
required for total external cable connections longer than 450ft(137m) but less than 800ft(243m).
The control wiring connections are described in the submittal documents included in the Submittal Drawings on page61.
The following tables list the relevant documents by number and title.
Table 6.4 CANbus Communication Connection Drawings
Docu ment NumberTitle
DPN003886CANbus and Interlock Connections between Unit and Condenser
20
Vertiv | Lieb ert® MCV Installer/User Guide
7 CHECKLIST FOR COMPLETED INSTALLATION
7.1 Moving and Placing Equipment
1.Unpack and check received material.
2. Proper clearance for service access has been maintained around the equipment.
3. Equipment is level and mounting fasteners are tight.
7.2 Electrical Installation Checks
1.Line voltage connected and matches equipment nameplate.
2. Power line circuit breakers or fuses have proper ratings for equipment installed.
3. CANbus communication and interlock wiring connections completed between indoor cooling unit and
condenser.
4. All internal and external high and low voltage wiring connections are tight.
5. Confirm that unit is properly grounded to an earth ground.
6. Control transformer setting matches incoming power.
7. Electrical service conforms to national and local codes.
8. Verify that the condenser is not connected to an unacceptable power supply, see Wye vs. Delta Connected
Power Supply on page20.
9. Verify that the CANbus wiring, CANbus END of Line jumper position, and the CANbus Device Address DIP
Switch setting are correct according to the application at the job site.
10. Verify that terminals 70, 71, (and 230 when applicable) are used and properly wired for interlock wiring,
particularly on systems that use two condensers for one indoor unit.
7.3 Piping Installation Checks
1.Piping completed to corresponding indoor cooling unit refrigeration circuit.
2. Piping is leak checked, evacuated and charged with specified refrigerant.
3. Additional refrigerant oil is added per circuit, if required.
4. Piping is properly sized, sloped, and trapped for proper oil return.
5. Check piping inside and outside of equipment for proper support and adequate spacing to prevent rub
through or chafing.
7.4 Other Installation Checks
1.Installation materials and tools have been removed from equipment (literature, shipping materials, construction
materials, tools, etc.).
2. Locate blank start up sheet, ready for completion by installer or startup technician.
7 Ch ecklist for Completed Installation
21
This page intentionally left blank
22
Vertiv | Lieb ert® MCV Installer/User Guide
8 INITIAL START UP CHECKS ANDCOMMISSIONINGPROCEDURE
FORWARRANTYINSPECTION
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power
even during the Unit Off mode of the controller. The only way to ensure that there is NO voltage inside the
unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local
codes.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury or death. Installation and service of this equipment should be done only by qualified personnel
who have been specially trained in the installation of air conditioning equipment and who are wearing
appropriate, OSHA-approved PPE.
WARNING! Risk of contact with high speed rotating fan blades. Can cause serious injury or death. Open all
local and remote electric power supply disconnect switches, verify with a voltmeter that power is off, and
verify that all fan blades have stopped rotating before working in the unit cabinet or on the fan assembly. If
control voltage is applied, the fan motor can restart without warning after a power failure. Do not operate the
unit with any or all cabinet panels removed.
CAUTION: Risk of exposure to harmful noise levels. Can cause hearing injury or loss. Depending on the
installation and operating conditions, a sound pressure level greater than 70dB(A) may arise. Take
appropriate technical safety measures. Operating personnel must wear appropriate, OSHA-approved PPE
and observe all appropriate hearing-protection safety requirements.
•Confirm that all items on Checklist for Completed Installation on page21 have been done.
•Locate the “Liebert® MCV Warranty Inspection Check Sheet” in the unit’s electric panel. (PSWI-8542-408CO).
•Complete the “Liebert® MCV Warranty Inspection Check Sheet” during start-up. (PSWI-8542-408CO).
•Forward the completed “Liebert® MCV Warranty Inspection Check Sheet” to your local sales office. This
information must be completed and forwarded to validate warranty.
•Contact your local sales representative or technical support if you have any questions or problems during unit
start-up and commissioning. Visit https://www.Vertiv.com/en-us/support/ or call 1-800-543-2778 for contacts.
8 Initial S tart up Checks and Commissi oning Procedure forWarrantyIns pection
23
This page intentionally left blank
24
Vertiv | Lieb ert® MCV Installer/User Guide
9 TROUBLESHOOTING
When an EconoPhase unit triggers an alarm, please refer to the Liebert® EconoPhase Installer/User Guide available on the
product page at www.Vertiv.com.
Table 9.1 Troubleshooting MCV Condenser Section
SymptomPossible causeCh eck or Remedy
No power to condenser.Check voltage at input terminal block.
Condenser will not
start
Low discharge
pressure
High discharge
pressure
SPD green and red
LEDs are extinguished
SPD red LED is
illuminated
Circuit breaker or fuse for low voltage
transformer in condenser is tripped.
No low voltage signal to/from indoor
unit.
Faulty head pressure control valve or
premium efficiency control board.
Dirty condenser f ins.Clean coil.
Condenser fans not operating.
High refrigerant chargeCheck refrigerant charge.
No voltage or improper phasing exists
at condenser.
Electrical connectionsto SPD are
faulty.
Condenser disconnect is turned O ff.Recheck lights with disconnect switch in the On position.
A surge exceeding the rating of the
SPD has occurred.
Connection to P24 is loose or
disconnected.
Locate problem in condenser electrical panel and repair.
Locate open circuit and repair.
Replace if defective.
Check for low voltage signal from indoor unit.
Check fan motors and fuses.
Check voltage at input terminal block.
Locate connection problem and repair.
Replace SPD and inspect other components for damage and replace them if
necessary.
Check the connection to P24 to verify that is connected securely.
Check the connector from the transformer for loose terminals.
9 Troubleshooting
Control Board LEDs
do not light.
Fan will not run
Fuse loca ted next to P24 has blown.Verify that the fuses next to P24 hav e not blown. Replace as needed.
24V transformer has failed.
Premium Efficiency Control Board has
failed.
Jumper not installed between 24V and
DIN1 (for Ziehl-Abegg fan motor).
With a voltmeter verify that the output from the transformer is 24Vac ±10%. If the
value exceeds ±1 0%, verify that the correct primary leads are being used.
If there is no output v oltage, verify that the primary connections are secure and
receiving the correct voltage. If they are, replace the transformer.
Install jumper between 24V and DIN1 (for Z iehl Abegg fan m otor).
25
This page intentionally left blank
26
Vertiv | Lieb ert® MCV Installer/User Guide
Loading...
+ 70 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.