Vertiv Liebert MBX User Manual

Liebert® MBX Busway System
Optional Busway System Monitoring
Installer/User Guide
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
Vertiv™ | Liebert® MBX MonitoringInstaller/UserGuide
TABLE OF CONTENTS
1 Installation 1
1.1 End Feed Box Monitoring Setup 1
1.2 End Feed Box Ethernet Configuration 1
1.3 End Feed Box USB Configuration 2
2 Tap-Off Box Monitoring 5
3 Web Portal Configuration 7
4 Firmware Update 9
i
This page intentionally left blank
ii
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide

1 INSTALLATION

Vertiv™ offers optional monitoring packages for the Liebert® MBX Busway System End Feed Box and Tap­Off Box using Socomec DIRIS Digiware.
• End Feed Box Only Package: Includes DIRIS Digiware G-30, I-45 and U-30
• End Feed Box and Tap-Off Box Package: Includes DIRIS Digiware G-30, I-45, U-30, I-30 and C-31 interface module.

1.1 End Feed Box Monitoring Setup

NOTE: Before beginning to test or program any Digiware components in the Tap-Off Box, ensure that your G-30 and U-30 Modules are configured.
For the G-30 Module ensure:
• All settings are set to default unless otherwise required by the client.
• Set the address to 1.
For the U-30 Module ensure:
• All settings are set to default unless otherwise required by the client.
• Set the address to 2.
NOTE: The addresses for the G-30 Module and the U-30 Module must not conflict.
NOTE: The G-30 must be programmed first, followed by the U-30, then any I-modules. The U-30 Module governs all I-modules’ baud rate and parity. Always check when testing I-modules that the baud rate programmed into the U-30 carried over to the I-module.

1.2 End Feed Box Ethernet Configuration

1. Power ON the
2. Connect the
3. Browse to
4. Click the
5. Log in to the
6. Click
7. Enter a Name for the End Feed Box.
8. Select
9. Enter the IP address. The default address is
10. Click
11. Click
12. Check the following settings:
Add
DIRIS G-30/G-40/G-50/G60
Save
Connect To Device
a. Verify that the latest firmware is installed on the device. You can check the latest firmware
version on the "Socomec" website. If firmware needs updated, see Firmware Update on page 9 for instructions.
b. Set the IP address and set the address (Slave ID) to 1.
End Feed Box
G-30 Module
www.Socomec.us,
.
to your laptop using a standard straight through CAT5 ethernet cable.
download and install the latest Easy Config software.
Change Profile Button
Super User
a Device.
.
profile using password "sOcOmec".
.
in the upper right corner of Easy Config.
from the Type drop down menu.
192.168.0.2.
1 Installation
1
c. Set the Baud rate, Stop bits and Parity. The default settings are 38400/1/N. On the U-30
Modules, click the
Network Tab
. Confirm the power system settings are correct for the customer
site:
Network Type
Nominal Voltage
Frequency
Phase Rotation
NOTE: Record the serial number of each G-30 Module for future reference.
13. G-30 Only: Click the
14. G-30 Only: Click the
Device Detection Tab
New Discovery Button
.
and wait till discovery is complete, approximately 3
minutes.
15. After checking all the settings, click
16. Select the
17. Click
G-30orU-30 Module
Select All
, then click
OK.
Final Action
, then click
Send to Device
being programmed, then click
.
Connect to Device
.
18. Wait for the configuration to be sent to the device. When the successful operation message pops up, clickOK.
19. Return to the home screen in Easy Config. Click
20. Select the
U-30 Module
and Repeat Step 11 through Step 17, changing the address (Slave ID) to 2
Get From Device
.
for the U-30 Device.

1.3 End Feed Box USB Configuration

NOTE: Micro-USB cable must be a data and power cable. Power-only cables will not function.
To configure the End Feed Box monitoring device:
1. Power On the End Feed Box and ensure that the G-30 and U-30 Modules are On.
2. Connect the G-30 Module to your laptop using USB – micro USB lead.
3. Browse to
www.Socomec.us,
download and install the latest Easy Config software.
4. Click the
Change Profile
Button in the upper right corner of Easy Config.
5. Log in to the Super User profile using password "sOcOmec".
6. Open the
7. Click the device to configure, then click
Easy Config
software and select
Get Configuration from Device.
Connect to Device
. If no device is visible, verify that the G-30
Module is powered On and that the USB – Micro USB lead is connected correctly.
8. Check these settings:
a. Verify that the latest firmware is installed on the device. You can check the latest firmware
version on the "Socomec" website. If firmware needs updated, see Firmware Update on page 9 for instructions.
b. Set the IP address and set the address (Slave ID) to 1.
c. Set the baud rate, stop bits and parity. The default settings are 38400/1/N. On U-30 Modules,
click the
Network Tab
. Confirm the power system settings are correct for the customer
site:
2
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide
Network Type
Nominal Voltage
Frequency
Phase Rotation
NOTE: Record the serial number of each G30 Module for future reference.
9. G-30 Only: Click the
10. G-30 Only: Click the
Device Detection Tab
New Discovery Button
.
and wait till the discovery is complete, approximately 3
minutes.
11. After checking all settings, click
12. Select the G-30 or U-30 Module being programmed, then click
13. Click
Select All
, then clickOK.
Final Action
, then click
Send to Device
Connect to Devic
.
e.
14. Wait for the configuration to be sent to the device. When the successful operation message pops up, clickOK.
15. Remove the micro USB from the G-30 Module and insert it into the U-30 Module to configure the U­30 Module.
16. Repeat Step 6 through Step 14, changing the address (Slave ID) to 2 for the U-30 Device.
NOTE: Record the serial number of each U-30 Module for future reference. The C-31 interface module provides RS-485 Modbus and Digiware Bus communication support to an external network.
Figure 3.1 Optional Ethernet Connection
1 Installation
3
This page intentionally left blank
4
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide

2 TAP-OFF BOX MONITORING

If your Tap-Off Box is equipped with a monitoring option, there will be two RJ-45 jacks on the side of the enclosure. The Tap-Off Box RJ-45 connections must be daisy-chained from Tap-Off Box to Tap-Off Box with the final connection made at the End Feed Box that houses the gateway device. The last Tap-Off Box in the daisy-chain must have a "Socomec" termination plug installed in the final RJ-45 jack.
NOTE: You can daisy-chain a maximum of 26 Tap-Off Boxes to the network gateway device, located in the End Feed Box. If you need to daisy chain more than 26, a repeater Tap-Off Box is required. Consult your sales representative for information on repeater Tap-Off Boxes.
NOTE: Before beginning to test or program any Digiware components in the Tap-Off Boxes, ensure that your G-30 Module and U-30 Module are configured. The U-30 Module governs the baud rate and parity for all I-modules. Alwayas check when testing I-modules that the baud rate programmed into the U-30 carried over to the I-module.
To configure Tap-Off Boxes:
1. Power On the I-30 or I-60 using a Socomec RJ-45 cable, which is looped out from the U-30 Module. A green light appears on the I-30 or I-60 Module to indicate it is powered On.
2. Connect the I-module to your laptop via USB – micro USB lead.
3. Click the
4. Log in to the Super User profile using password "sOcOmec".
5. Click
change profile button
Get from Device.
in the upper right corner of Easy Config.
6. Click the
7. Select the
Identification – I-30 OR I-60 Serial Number
Type – Device Connected
Firmware Version – Latest firmware installed. You can check the latest firmware version on the
The ‘Communication Configuration’ shown is :
8. Select
Load Enabled – If CTs are connected, option to change settings.
Load Type – Select number of phases and amount of CTs.
Nominal Current – circuit rating associated with each CT.
Device
"Socomec" website. If firmware needs updated, see Firmware Update on page 9 for instructions.
Type – RS485.
Address – Set a unique Modbus address. The G-30 is 1, U-30 is 2, I-45 (if present) is 5. Continue numbering I-modules starting at 10.
Baud Rate – Confirm match to U-30 settings.
Stop Bits – Confirm match to U-30 settings.
Parity – Confirm match to U-30 settings.
Load
to configure, then click
Product
and confirm the following information:
Tab and verify the following information:
Connect to Device
.
CT Direction – If the CTs are reading an incoming or outgoing supply.
9. After the settings are updated, click
2 Tap-Off Box Monitoring
Final Action,
then click
Send to Device
.
5
10. Select the
I-module
being programmed, then click
Connect to Device
.
11. Click Select All, then clickOK.
12. Wait for the configuration to be sent to the device. When the successful operation message pops up, clickOK.
NOTE: After completing all the I-module configurations or after adding new Tap-Off Box Modules to a busway run, you must log into the G-30 module and re-perform device discovery.
1. Connect to the G-30 via Ethernet or USB.
2. Click
Device Detection
Tab.
3. Click
4. Click
5. Click
6. Select the G-30 Module and click
New Discovery
Final Action
.
Send to Device
. All newly configured I-modules should appear.
.
Connect To Device
7. Click Select All then ClickOk.
8. Wait for the configuration to be sent. ClickOk.
.
6
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide

3 WEB PORTAL CONFIGURATION

After completing all the I-module configurations or after adding a new Tap-Off Box Module to a busway run, you must log in into the Socomec web portal and update the configuration.
1. Click the
2. Select
3. Click the
4. Click
5. Click
6. Confirm all modules appear.
7. Click
Change Profile
Admin
and enter password
Settings Gear
Devices.
Read Configuration.
Save Configuration
Button in the upper right corner.
Icon on the top left.
.
Admin
.
3 Web Portal Configuration
7
This page intentionally left blank
8
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide

4 FIRMWARE UPDATE

If the firmware for each device is not the latest available on the Socomec website, download the firmware ZIP file for the module(s) to be updated. Firmware versions may be checked on the Socomec website:
https://www.socomec.com/product-upgrade-tool-software_en.html
To update a Socomec Digiware module firmware, perform the following steps:
1. Download the latest version of Socomec’s Product Upgrade Tool and firmware version from the page above.
2. Install the Product Upgrade Tool on your laptop.
3. Connect the module to your laptop via USB – micro USB lead.
4. Open the Product Upgrade Tool program.
5. Verify the module to be upgraded is displayed in the Master field.
6. Click the
Browse
button and select the firmware ZIP file for the module.
.
7. Click
8. Configure the module per the instructions in section 1 or 2.
Figure 6.1 Product Upgrade Tool
Update
and wait for the firmware upgrade to complete.
4 Firmware Update
9
This page intentionally left blank
10
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide
Vertiv™ | Liebert® MBX MonitoringInstaller/User Guide
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 VertivGroup Corp. Allrights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group Corp. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for anyerrors or omissions. Specifications are subject to change without notice..
SL-70526_REV02_05-20
Loading...