![](/html/e9/e9d3/e9d3206e6c6ef921cb076b597e55796a27fd3d40bace92172ad79199bdbed243/bg1.png)
LIEBERT® EXS™ UPS
208/220‑V30KVA
Quick Installation Guide
I M P O RTANT: Before installing,
connecting to supply or operating
your Liebert EXS UPS, please
review the Safety and Regulatory
Statements sheet. For detailed
installation, operating, maintenance
and troubleshooting information
visit the EXS product page for the
EXS Installer/User Guide available
at www.Vertiv.com or use the QR
code below.
INSTALLATIO N
Inspecting the UPS
Inspect the UPS for any signs of
obvious damage. If damage is
visible, do not proceed. File a
damage claim with the carrier
immediately and send a copy to:
Vertiv Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus OH 43085
Attn. Traic Department
Choosing a location
The UPS measures 23.6 x 33.5 x
63 in. (600 x 850 x 1600 mm).
Install the UPS in a clean, wellventilated environment with the
ambient temperature range of 32°F
to 104°F (0°C to 40°C).
For installation and maintenance,
3 ft (914 mm) clearance is required
in the front and rear of the unit. For
proper ventilation during normal
operation, leave 8 in. (203 mm)
clearance on the rear. No side
clearance is required for installation
or operation of the UPS.
Removing Packaging and Moving the UPS
Packaging
Ramp in
shipping position
Handling and unpacking
the unit
The unit weighs up to 1,650 lb
(748 kg), depending on the number
of batteries included. The UPS
ships on a pallet and is equipped
with casters that permit two or
more people to roll it o the pallet
for installation. Use a forklift or
pallet jack to move the palleted
UPS as close as possible to the
installation location before
removing packing material or
loosening shipping brackets.
1. Remove the protective
packaging, shown in the
illustration at the top-right.
2. Locate the accessories
package on top of the UPS and
set aside.
3. Use a 16-mm (5/8 -in.) wrench
or socket to un-bolt the
shipping brackets from the
pallet.
Repositioned ramp
placed for unit
transfer to
installation location
4. Un-bolt the shipping brackets
from the front and rear of the
UPS. Remove the front lower
panel from the UPS to remove
the front bracket.
5. Make sure the leveling feet are
raised so they do not interfere
when rolling the unit on the
casters.
6. Roll the unit down the ramp to
the installation location, see
the illustration above, then
lower the leveling feet to x the
UPS in the install location.
590-1971-501A/SL-70330_REV0 1
![](/html/e9/e9d3/e9d3206e6c6ef921cb076b597e55796a27fd3d40bace92172ad79199bdbed243/bg2.png)
LIEBERT® EXS™ UPS 208/220 ‑V 30 KVA
Quick Installation Guide
Table 1 Currents and Wire Size — UPS rectier input
Unit Rating
30 kVA /kW 105 150 2/0 2/0 6 AWG
Table 2 AC Currents and Wire Size — UPS bypass input* and output
Unit Rating
30 kVA /kW 83 125 1/0 1/0 6 AWG
*Bypass input for dual-input congurations only.
Table 3 Recommended lug sizes for phase, neutral and ground conductors
Recommended Torque 50 lb-in. / 4.2 lb-ft . / 5.6 Nm
Table 3 Recommended lug sizes for external battery conductors
Recommended Torque 126 lb-in. / 10.5 lb-ft . / 14.2 Nm
Maximum Input
Current (A)
Maximum Input
Current (A)
Part Number
Part Number
Recommended OPD,
Amp Tri p
Recommended OPD,
Amp Tri p
6 AWG (13.3 mm2) 1/0 AWG (53.5 mm2) 2/0 (67.4 mm2)
McMaster-Carr: 7113K366 Thomas & Betts: 54152NT Thomas & Betts: 54157NT
Thomas & Betts: RE6-14
6 AWG (13.3 mm2) 1/0 AWG (53.5 mm2) 2/0 (67.4 mm2)
Thomas & Betts: RE6-516 Thomas & Betts: 54153NT Thomas & Betts: 54158NT
Thomas & Betts: CTL6-516
75°C THW Copper Wire (phase)
Number of Cables per phase:1
75°C THW Copper Wire (phase)
Number of Cables per phase:1
75°C THW Copper Wire
neutral)
Number of Cables:1
75°C THW Copper Wire
(neutral)
Number of Cables:1
75°C THW Copper Wire
(ground)
Number of Cables: 1
75°C THW Copper Wire
(ground)
Number of Cables: 1
POWER WIRING AND
CONDUIT
When connecting wiring, follow the
local wiring regulations, and take the
environment situation into account.
NOTE : The conduit size and wiring
method must be in accordance with
all local, regional and national codes
and regulations, including NEC
ANSI/NFPA 70.
The maximum current for operating
modes, the recommended wire
sizes, and the recommended power
cables and plugs are listed in Tables
1 to 3, above, and are based upon
an
86°F (30°C) ambient temperature.
Lock-out and tag before
you begin
Ensure that the feeder breakers are
open and locked, and tagged to
prevent inadvertent operation by
unauthorized personnel.
HARDWIRE INPUT/OUTPUT
CONNECTIONS
Connecting a
single-input conguration
1. On the rear panel of the UPS,
remove the upper conduitentry panel, punch holes for
the conduit, connect the
conduit to the panel, and
re-install the conduit-entry
panel.
2. Remove the lower cover plate
to access the terminal blocks,
shown in the “Terminal-block
Connections” illustration on the
next page.
3. Leave the factory-installed
single-input jumpers on the
input terminal blocks and make
the following input connections
from the upstream feeder
panel to the input terminal:
• Phase A to rA
• Phase B to rB
• Phase C to rC
• Neutral to inN
• Ground cable to PE
4. Make the following output
connections from the UPS
output terminal to the
downstream distribution-panel
main lug breaker:
• oA to Phase A
• oB to Phase B
• oC to Phase C
• oN to neutral bus
• PE to ground bus
5. Torque phase conductor
connections to 50 lb-in, and
neutral and ground conductor
connections to 126 lb-in.
6. Reinstall the terminal-block
cover plate.
Connecting a
dual-input conguration
2 590-1971-501A/SL-70330_REV0