Vertiv LIEBERT EXS 208/220-V 30 KVA Quick Installation Manual

LIEBERT® EXS™ UPS
208/220‑V30KVA
Quick Installation Guide
I M P O RTANT: Before installing, connecting to supply or operating your Liebert EXS UPS, please review the Safety and Regulatory Statements sheet. For detailed installation, operating, maintenance and troubleshooting information visit the EXS product page for the EXS Installer/User Guide available at www.Vertiv.com or use the QR code below.
INSTALLATIO N Inspecting the UPS
Inspect the UPS for any signs of obvious damage. If damage is visible, do not proceed. File a damage claim with the carrier immediately and send a copy to:
Vertiv Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH 43085
Attn. Traic Department
Choosing a location
The UPS measures 23.6 x 33.5 x 63 in. (600 x 850 x 1600 mm). Install the UPS in a clean, well­ventilated environment with the ambient temperature range of 32°F to 104°F (0°C to 40°C). For installation and maintenance, 3 ft (914 mm) clearance is required in the front and rear of the unit. For proper ventilation during normal operation, leave 8 in. (203 mm) clearance on the rear. No side clearance is required for installation or operation of the UPS.
Removing Packaging and Moving the UPS
Packaging
Ramp in
shipping position
Handling and unpacking the unit
The unit weighs up to 1,650 lb (748 kg), depending on the number of batteries included. The UPS ships on a pallet and is equipped with casters that permit two or
more people to roll it o the pallet
for installation. Use a forklift or pallet jack to move the palleted UPS as close as possible to the installation location before removing packing material or loosening shipping brackets.
1. Remove the protective packaging, shown in the illustration at the top-right.
2. Locate the accessories package on top of the UPS and set aside.
3. Use a 16-mm (5/8 -in.) wrench or socket to un-bolt the shipping brackets from the pallet.
Repositioned ramp
placed for unit
transfer to
installation location
4. Un-bolt the shipping brackets from the front and rear of the UPS. Remove the front lower panel from the UPS to remove the front bracket.
5. Make sure the leveling feet are raised so they do not interfere when rolling the unit on the casters.
6. Roll the unit down the ramp to the installation location, see the illustration above, then
lower the leveling feet to x the
UPS in the install location.
590-1971-501A/SL-70330_REV0 1
LIEBERT® EXS™ UPS 208/220 ‑V 30 KVA
Quick Installation Guide
Table 1 Currents and Wire Size — UPS rectier input
Unit Rating
30 kVA /kW 105 150 2/0 2/0 6 AWG
Table 2 AC Currents and Wire Size — UPS bypass input* and output
Unit Rating
30 kVA /kW 83 125 1/0 1/0 6 AWG
*Bypass input for dual-input congurations only.
Table 3 Recommended lug sizes for phase, neutral and ground conductors
Recommended Torque 50 lb-in. / 4.2 lb-ft . / 5.6 Nm
Table 3 Recommended lug sizes for external battery conductors
Recommended Torque 126 lb-in. / 10.5 lb-ft . / 14.2 Nm
Maximum Input
Current (A)
Maximum Input
Current (A)
Part Number
Part Number
Recommended OPD,
Amp Tri p
Recommended OPD,
Amp Tri p
6 AWG (13.3 mm2) 1/0 AWG (53.5 mm2) 2/0 (67.4 mm2)
McMaster-Carr: 7113K366 Thomas & Betts: 54152NT Thomas & Betts: 54157NT
Thomas & Betts: RE6-14
6 AWG (13.3 mm2) 1/0 AWG (53.5 mm2) 2/0 (67.4 mm2)
Thomas & Betts: RE6-516 Thomas & Betts: 54153NT Thomas & Betts: 54158NT
Thomas & Betts: CTL6-516
75°C THW Copper Wire (phase)
Number of Cables per phase:1
75°C THW Copper Wire (phase)
Number of Cables per phase:1
75°C THW Copper Wire
neutral)
Number of Cables:1
75°C THW Copper Wire
(neutral)
Number of Cables:1
75°C THW Copper Wire
(ground)
Number of Cables: 1
75°C THW Copper Wire
(ground)
Number of Cables: 1
POWER WIRING AND CONDUIT
When connecting wiring, follow the local wiring regulations, and take the environment situation into account.
NOTE : The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70.
The maximum current for operating modes, the recommended wire sizes, and the recommended power cables and plugs are listed in Tables 1 to 3, above, and are based upon
an
86°F (30°C) ambient temperature.
Lock-out and tag before you begin
Ensure that the feeder breakers are open and locked, and tagged to prevent inadvertent operation by unauthorized personnel.
HARDWIRE INPUT/OUTPUT
CONNECTIONS Connecting a
single-input conguration
1. On the rear panel of the UPS, remove the upper conduit­entry panel, punch holes for the conduit, connect the conduit to the panel, and re-install the conduit-entry panel.
2. Remove the lower cover plate to access the terminal blocks, shown in the “Terminal-block Connections” illustration on the next page.
3. Leave the factory-installed single-input jumpers on the input terminal blocks and make the following input connections from the upstream feeder panel to the input terminal:
• Phase A to rA
• Phase B to rB
• Phase C to rC
• Neutral to inN
• Ground cable to PE
4. Make the following output connections from the UPS output terminal to the downstream distribution-panel main lug breaker:
• oA to Phase A
• oB to Phase B
• oC to Phase C
• oN to neutral bus
• PE to ground bus
5. Torque phase conductor connections to 50 lb-in, and neutral and ground conductor connections to 126 lb-in.
6. Reinstall the terminal-block cover plate.
Connecting a
dual-input conguration
2 590-1971-501A/SL-70330_REV0
Loading...
+ 2 hidden pages