Vertiv LIEBERT EXS Quick Installation Manual

LIEBERT® EXS™ UPS 208/220 ‑V 15 – 20 KVA
Quick Installation Guide
Removing Packaging and Moving the UPS
Ramp in
shipping position
I M P O RTANT: Before installing, connecting to supply or operating your Liebert EXS UPS, please review the Safety and Regulatory Statements sheet. For detailed installation, operating, maintenance and troubleshooting information visit the EXS product page for the EXS User Guide available at www.VertivCo.com.
INSTALLATIO N Inspecting the UPS
Inspect the UPS for any signs of obvious damage. If damage is visible, do not proceed. File a damage claim with the carrier immediately and send a copy to:
Vertiv Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus OH 43085 Attn. Traic Department
Packaging
Choosing a location
Install the UPS in a clean, well­ventilated environment with the ambient temperature range of 32°F to 104°F (0°C to 40°C). For installation and maintenance, 3ft (914mm) clearance is required in the front and rear of the unit. For proper ventilation during normal operation, leave 8in. (203mm) clearance on the rear. No side clearance is required for installation or operation of the UPS.
Handling and unpacking the unit
The UPS ships on a pallet and is equipped with casters that permit two or more people to roll it o the pallet for installation. Use a forklift or pallet jack to move the palleted UPS as close as possible to the installation location before removing packing material or loosening shipping brackets.
Repositioned ramp placed
for unit transfer to
installation location
1. Remove the protective packaging, shown in the illustration at the top-right.
2. Locate the accessories package on top of the UPS and set aside.
3. Use a 16-mm (5/8 -in.) wrench or socket to un-bolt the shipping brackets from the pallet.
4. Un-bolt the shipping brackets from the front and rear of the UPS. Remove the front lower panel from the UPS to remove the front bracket.
5. Make sure the leveling feet are raised so they do not interfere when rolling the unit on the casters.
6. Roll the unit down the ramp to the installation location, see the illustration above, and lower the leveling feet to fix the UPS in the install location.
590-1912-501B/SL-26156_REV 1 1
LIEBERT® EXS™ UPS 208/220 ‑V 15 – 20 KVA
Quick Installation Guide
Table 1 Currents and Wire Size — UPS rectifier input
Unit Rating
15 kVA /k W 53 70 3 AWG 4 AWG 6 AWG
20 kVA /k W 71 90 2 AWG 6 AWG 6 AWG
Table 2 AC Currents and Wire Size — UPS bypass input* and output
Unit Rating
15 kVA /k W
20 kVA /k W
*Bypass input for dual-input configurations only.
Table 3 Recommended lug sizes
Part
Number
Maximum Input
Current (A)
Maximum Input
Current (A)
42 60 4AWG 4 AWG 6 AWG
56 70 3 AWG 3 AWG 6 AWG
6AWG (13.3mm2) 4AWG (21.2mm2) 3AWG (26.7mm2) 2AWG (33.6mm2)
McMaster-Carr: 7113K366 McMaster-Carr: 7113K441 McMaster-Carr: 6926K54 McMaster-Carr: 6926K54
Thomas & Betts: RE6-14 Thomas & Betts: 54138NT02 Thomas & Betts: 54107NT Thomas & Betts: 54107NT
Recommended OPD,
AmpTrip
Recommended OPD,
AmpTrip
75°C THW Copper Wire (phase)
Number of C ables per phase:1
75°C THW Copper Wire (phase)
Number of C ables per phase:1
Thomas & Betts: 54106NT Tyco Electronics: 132331-1
75°C THW Copper Wire
neutral)
Number of C ables:1
75°C THW Copper Wire
(neutral)
Number of C ables:1
75°C THW Copper Wire
(ground)
Number of C ables: 1
75°C THW Copper Wire
(ground)
Number of C ables: 1
POWER WIRING AND CONDUIT
When connecting wiring, follow the local wiring regulations, and take the environment situation into account.
NOTE : The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70.
The maximum current for operating modes, the recommended wire sizes, and the recommended power cables and plugs are listed in Tables 1 to 3, above, and are based upon
an
86°F (30°C) ambient temperature.
Lock-out and tag before you begin
Ensure that the feeder breakers are open and locked, and tagged to prevent inadvertent operation by unauthorized personnel.
2 590-1912-501B/SL-26156_RE V1
LIEBERT® EXS™ UPS 208/220 ‑V 15 – 20 KVA
Quick Installation Guide
Terminal Block Connections—Compression Type
Conduit-entry
panel
HARDWIRE INPUT/OUTPUT CONNECTIONS
Connecting a single-input configuration with compression-type terminal blocks
1. On the rear panel of the UPS, remove the cover plate to access the terminal blocks, shown in the “Compression­type” illustration above.
2. Remove the conduit-entry panel, punch holes for the conduit, connect the conduit to the panel, and re-install the conduit-entry panel.
3. Referring to the “compression­type” illustration, make the following input connections from the upstream feeder panel to the input terminal:
• Phase A to rA
• Phase B to rB
• Phase C to rC
• Neutral to N
• Ground cable to ground bus
4. Make the following output connections from the UPS output terminal to the downstream distribution-panel main lug breaker:
5. Torque phase conductor
6. Reinstall the terminal-block
Connecting a dual-input configuration with compression-type terminal blocks
1. On the rear panel of the UPS,
2. Remove the conduit-entry
3. Referring to the “Compression-
Single or
rectifier input
Input neutral
Output neutral
BATTERY TERMINALS
Ground busbar
dual input
Main lug
breaker
• Terminal A to Phase A
• Terminal B to Phase B
• Terminal C to Phase C
• Terminal N to neutral bus
• Ground (PE) to ground bus
connections to 110 lb-in, and neutral and ground conductor connections to 126 lb-in.
cover plate.
remove the cover plate to access the terminal blocks, shown in the “Compression­type” illustration above.
panel, punch holes for the conduit, connect the conduit to the panel, and re-install the conduit-entry panel.
type” illustration, relocate and re-torqe the wires from the factory-connections side of the input terminal block to the factory-side bypass terminal
INPUT
TERMINALS
Factory connections
Bypass
OUTPUT
TERMINALS
Factory connections
block, and re-torque to 50lb-in. as follows:
• wire BP-R to bA
• wire BP-S to bB
• wire BP-T to bC
4. Make the following rectifier­input connections from the upstream feeder panel to the input terminal:
• Phase A to rA
• Phase B to rB
• Phase C to rC
• Neutral to N
• Ground cable to ground bus
5. Make the following bypass­input connections from the upstream feeder panel to the input terminal:
• Phase A to bA
• Phase B to bB
• Phase C to bC
• Neutral to N
• Ground cable to ground bus
6. Make the following output connections from the UPS output terminal to the downstream distribution-panel main lug breaker:
• Terminal A to Phase A
• Terminal B to Phase B
590-1912-501B/SL-26156_REV 1 3
Loading...
+ 5 hidden pages