Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 |iii
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 |iv
1.0INTRODUCTION
Speakers (not used)
Touchscreen LCD
EPO Switch
UPS Status LED
UPS Status LED
The Touchscreen Control Panel’s integrated interface simplifies monitoring and managing single or multiple
Liebert UPS modules. The control collects a profusion of information about the health of the modules and
presents it in a standardized format. This simple, dynamic display speeds operator response to changing power
input and demand.
Many of the settings will depend on the UPS type and features. Many settings will be made by Vertiv personnel
when setting up the UPS.
The Touchscreen Control Panel’s interface will display data either graphically or in text. The Status Scroll Bar at
the top of the touchscreen display summarizes system conditions. The bar changes color to indicate status and
includes an icon matched to the status. The Status Gauge displays such details as power demand from the
connected load, input power quality, output and bypass on each phase and battery capacity.
The Touchscreen Control Panel’s mimic display shows the comprehensive system information that the operator
needs:
• Is input power connected?
• Are there any alarms?
• Which breakers are open and which are closed?
• Is the UPS on battery?
• How much battery run time is available?
Checking a particular component is as simple as touching it on the mimic display—Detailed data appears,
allowing the operator to respond.
Visual and audible alarms alert personnel to faults and alarms requiring immediate attention.
Passcodes for each level of access—Operator, Administrator and Service—secure the UPS against unauthorized
changes. Personnel without a passcode can view UPS status, but cannot change any functions or the
appearance of the interface.
Figure 1Touchscreen Control Panel components
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 1
2.0 NAVIGATING THROUGH THE TOUCHSCREEN
CONTROL PANEL
The Touchscreen Control Panel is active whenever the UPS has input power. The touchscreen LCD on the front
of the UPS permits:
• Logging in to the system—3.1 - Log In to the Touchscreen Control Panel
• Customizing the user interface—2.4 - Customizing the Display
• Checking the status of the UPS and its external batteries, including all measured parameters, events and alarms—4.0 - VIEWING UPS STATUS and 5.0 - VIEWING UPS COMPONENT STATUS
• Determining when users logged in and out—4.3 - Logs—Events and Log-In Times
• Silencing alarms—3.3.1 - OPERATE Menu—Silence an Alarm
•Turning the UPS On —3.3.2 - OPERATE Menu—Inverter On
• Turning the UPS Off—3.3.3 - OPERATE Menu—Inverter Off
The Touchscreen Control Panel’s display default view is two panes: One-line animated mimic and UNIT STATUS.
The appearance can be changed to multiple panes that show other data. Customizing the appearance is detailed
in 2.4 - Customizing the Display.
2.1Restrict Physical Access with Barriers or Set Log-In Codes
NOTICE
Risk of unauthorized changes to UPS operational settings. Can cause equipment damage.
Because a UPS such as the Liebert EXL S1 is usually installed in areas that restrict physical access, the Touchscreen
Control Panel does not, by default, require a PIN to change UPS settings and operations.
If physical access cannot be restricted with barriers and identity cards, PIN codes may be set in the Touchscreen Control
Panel to prevent unwanted changes to the Liebert EXL S1.
The Touchscreen Control Panel has four possible access levels—Observer, Operator, Administrator and
Service—each with different levels of authority. The Service level, which permits configuration changes, is the
only level that, by default, requires a PIN.
The default access level for the Touchscreen Control Panel is Administrator. When a PIN is set for the
Administrator, the control panel opens at the Operator level.
To set or change a PIN, refer to 3.1 - Log In to the Touchscreen Control Panel.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 2
Figure 2Opening screens
Default opening
screen; no PIN
required;
Administrator
level access for
all with physical
access to UPS.
Default opening screen; PIN required; Note that
the SETUP Function Menu is absent. Operator
level access for all with physical access to UPS.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 3
2.2Touchscreen Control Panel Components
UPS Status Bar
(Scrolls through
status information)
Log In/Out
Icon
Parameter Icons
(Maximum of four visible if
the Status Gauge is showing)
Edit
Interface
Icon
Graphic or
Text View
Interface
Switch
Function Menu
Icons (Varies by
access level)
Context
Menu Icon
Status Gauge
Animated Mimic Display
(Unit 1 mimic displayed.)
Legend Drawer
(See Figure 6)
SERVICE ACCESS LEVEL SCREEN SHOWN
Other access levels will show different function menu icons, but
the rest of the screen will be the same.
Status Bar
Icon
Function Menu Icon
(Service is visible
only when Service
log-in is entered.)
LIFE Services
Menu Icon
System link
(When active,
output shows
system values)
Observer LevelOperator Level
Administrator Level
Service Level
The main areas of the Touchscreen Control Panel are shown in Figure 3. The display arrangement and the
information displayed can be changed.
At log-in for all access levels, the Touchscreen Control Panel opens to the STATUS screen in graphic display. The
status of Unit 0 will be shown if the system is a single-unit configuration. In a parallel setup, the STATUS screen shows
the unit where the HMI is installed or the system view. The STATUS screen will show the animated mimic and system
status readings at each log-in level. The appearance will differ only in the function menus displayed (see Figure 4).
Figure 4Control display by access level—if PIN’s are required
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 4
Each Function Menu offers different information and control choices.
STATUS
OPERATE
SETUP
SERVICE
LIFE
Services
Function Menu icons are orange and white when selected, except the LIFE
Services icon; it remains dark gray with green text, if LIVE Services is activated.
If PIN’s are not required, the user will see the STATUS, OPERATE, SETUP and LIFE Services Function Menus.
If PIN’s are required, the user’s access level determines which Function Menu icons are displayed. For example,
logging in as Operator will show the STATUS, OPERATE and LIFE Services Function Menus; logging in as
Administrator will show those menus as well as the SETUP Function Menu (see Figure 4).
• STATUS: Condition of the UPS modules and components and data affecting operation and performance; visible at all access
levels.
• OPERATE: UPS operation controls, such as Inverter On, Inverter Off and Energy Saving Status; visible to Operator,
Administrator and Service
• SETUP: Manage permissions through PIN’s; visible to Administrator and Service
• SERVICE: Input wiring and breaker configuration, parallel status, protocol used and battery charging method; visible only to
Service
• LIFE Services: Information for assistance to enable LIFE customer care. LIFE Services requires a maintenance contract. The
service must be activated with assistance by calling the listed telephone number; visible to all, including Observers.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 5
2.2.1Context Menus
Menu Icon
STATUS Function Menu Selected
OPERATE Function Menu Selected
SETUP Function Menu Selected
(Not shown to Observer or Operator
if PIN’s are required)
The Context Menus, available by touching the Menu icon at the top left corner of the interface,
display information about the UPS and permit changing various settings. The functions possible
through the Context Menus are determined by the user’s access level and on the Function Menu
that is active (see Figure 5).
The items under Display Options on the STATUS Context Menu, for example, differ for each access
level.
Some information available through the Context Menu, such as alarms and run hours, are available through other
areas of the Touchscreen Control Panel.
NOTE
The LIFE Services Function Menu icon has no associated Context Menu. Commands and operations related
to LIFE Services are found on the OPERATE Context Menu.
Figure 5Context Menus
Context Menu—STATUS
Selecting the STATUS icon and touching the Menu icon reveals a Context Menu that permits performing several
actions or accessing additional information (see Figure 5). Touching a Context Menu item will reveal data or
expand the menu to show additional options.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 6
The Context Menu for the STATUS icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events can be sorted by
type, event ID, component, description. The touchscreen also permits filtering events by severity (Status, Alarm or Fault); or
by component (bypass, monitoring process or the module where the event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component affected and
description; same options for all access levels. The Event Log can be exported as a CSV file for record-keeping,
analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system. The Audit log can
be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Run Time: Battery Cycle Monitor with duration and count
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and user is logged off;
touching the screen reactivates the interface.
• Total Run Hours: Component and hours it has operated; touching a component displays details in the right panel.
• Components: Component status, name and details
• Display Options (changes affect the view for all viewers)
• Customize Layout: Change panel content and layout (see 2.4 - Customizing the Display)
• Display Properties: Language, back-light timer, alarm timeout, auto-log-out timer, display brightness, status indicator
brightness and touchscreen calibration (see 2.4 - Customizing the Display)
• Date & Time: Drop-down lists for time zone, date, local time and UTC time (Coordinated Universal Time) (see 2.4 - Customizing the Display)
• Formats: Drop-down lists for date and time format and measurement system (metric or imperial) (see 2.4 - Customizing the Display)
• Custom Labels: Rename settings, serial ports and network interfaces to ease troubleshooting and refine data. (The
default name of COM1 may be adequate, but renaming it with the connected device may ease determining the cause
of an alarm).
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity, model number and
serial number.
Context Menu—OPERATE
Selecting the OPERATE icon and touching the Menu icon reveals a Context Menu that permits performing
several actions or accessing additional information (see Figure 5). Touching a Context Menu item will reveal
data or expand the menu to show additional options.
The Context Menu for the OPERATE icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events can be sorted by
type, event ID, component, description. The touchscreen also permits filtering events by severity (Status, Alarm or Fault); or
by component (bypass, monitoring process or the module where the event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component affected and
description; same options for all access levels. The Event Log can be exported as a CSV file for record-keeping,
analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system. The Audit log can
be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Battery Operations: Battery testing and charging; automatic, manual and calibration battery testing and battery equalize
charging.
• LIFE Services: Customer care assistance contact and reporting center; must be activated with assistance by calling the
listed telephone number;
• Screen Saver: Display Sleep Mode notification (immediate entry into screen saver); screen goes dark and user is logged off;
interface reactivated by touching the screen; same options for all access levels
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity, model number and
serial number
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 7
Context Menu—SETUP
Selecting the SETUP icon and touching the Menu icon reveals a Context Menu that permits
performing several actions or accessing additional information (see Figure 5). Touching a Context
Menu item will reveal data or expand the menu to show additional options.
The Context Menu for the SETUP icon shows these items:
• Events: Date and time of occurrence, type of event, Event ID, component affected and description. Events
can be sorted by type, event ID, component, description. The touchscreen also permits filtering events by
severity (Status, Alarm or Fault); or by component (bypass, monitoring process or the module where the event occurred).
• Logs: UPS Event Log and Audit Log
• UPS Event Log shows date and time of event occurrence, type of event, Event ID, status. component affected and
description; same options for all access levels. The Event Log can be exported as a CSV file for record-keeping,
analysis and similar uses.
• Audit Log shows date and time that users with UPS control access logged into and out of the system. The Audit log can
be exported as an XML or CS‘V file for record-keeping, analysis and similar uses.
• Manage Permissions: Change or require PIN for users of Administrators or Operators.
• Network: Modify communication settings.
• Configure Status Gauge: Modify information shown on Status Gauge.
• UPS Settings: Enable or disable audible alarm and modify energy saving configuration (Eco Mode or Intelligent Parallel).
• Display Options (Changes affect view for all access levels)
• Customize Layout: Change panel content and layout (see 2.4 - Customizing the Display).
• Display Properties: Language, back-light timer, alarm timeout, auto-log-out timer, display brightness, status indicator
brightness and touchscreen calibration (see 2.4 - Customizing the Display).
• Date & Time: Drop-down lists for time zone, date, local time and UTC time (Coordinated Universal Time) (see 2.4 - Customizing the Display).
• Formats: Drop-down lists for date and time format and measurement system (metric or imperial) (see 2.4 - Customizing the Display).
• Custom Labels: Rename settings, serial ports and network interfaces to ease troubleshooting and refine data. (The
default name of COM1 may be adequate, but renaming it with the connected device may ease determining the cause
of an alarm).
• Technical Support: Manufacturer’s support: Web site, e-mail address and telephone numbers.
• About: Information about the UPS and its software and firmware; UPS model, rating, configured capacity, model number and
serial number.
2.3SYSTEM PANE—Mimic Display Components
The animated mimic display, the default view for the control, shows each configured major component of the
UPS system, for both single-module and multi-module systems. The mimic display is the same for all access
levels. The power path is shown by animated lines; moving dashes show the active power path. Touching a
component (except a breaker) brings up details about the component’s status. Breakers are shown as open or
closed (see Figure 6), but they are not interactive.
Components in the mimic display signify their operational status by their color, green, amber or red. Tables 9
through 11 describe the various states of the indicators.
The animated mimic display can be changed to any of five other views: Status, Alarms, Run Hours, Event Log and
Battery Cycle Monitor Summary (see 2.4 - Customizing the Display).
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 8
Figure 6Mimic display, normal operation, default view/unit view
Output Power
(interactive)
Input Power
(interactive)
Internal Static Bypass
(interactive)
DC Source
(Batteries)
(interactive)
Rectifier Feed
Breaker
Touching the arrowhead reveals the legend.
Maintenance
Bypass Breaker
Breakers in a system are determined
during setup and can be installed or
removed by Service.
Breakers shown are:
Remote Back-Feed
Breaker; may be
replaced with optional
Back-Feed Disconnect
Maintenance Isolation Breaker
Module Output Breaker
Rectifier
(interactive)
Maintenance
Bypass Path
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 9
Figure 7Mimic display, normal operation, system view
Touching the arrowhead reveals the legend.
Green outline indicates
communication is active
and operating normally.
White outline indicates no
communication occurring.
Yellow indicates the unit is
communicating but in a
warning state.
Red indicates the unit is
communicating but in a
fault state.
System view is obtained
by touching SYSTEM in
the default mimic view.
To return to default view,
touch Unit 1 or Close
(bottom right).
2.3.1UNIT STATUS Pane Components
The UNIT STATUS pane is identical for all PIN access levels (see Figure 8), if PIN’s are required. Observers will
not have the edit icon (pencil). In the default graphic view, the UNIT STATUS pane shows:
• Status Gauge—Connected load shown in kW and as a percentage of capacity; input, output and bypass voltage for each
phase (default data may be changed; see 4.1 - Viewing UPS Data with the Status Gauge).
• Load Detail Icon
• Input Detail Icon
• Bypass Detail Icon
• Battery Detail Icon
The detail icon for Environmental may be added to the UNIT STATUS pane if there is space.
Touching any of the detail icons reveals additional data about that selection in the opposite pane. The data pane
may be closed by touching the Close button or by touching any detail icon. The read-only information is
available to all access levels (see Figures 9 through 13).
NOTE
If the Status Gauge is showing, no more than four detail icons will be visible. Removing the Status Gauge permits
showing all five detail icons. The view may be customized to show fewer than four.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 10
Figure 8UNIT STATUS pane components—Graphic display
Status Gauge
Detail Icons for Input,
Battery, Bypass and
Load (Touch an icon
to see details about
the linked
component [see
Figure 9].)
No more than four
detail icons will be
visible when the
Status Gauge is
shown.
Edit icon
Touch this icon to switch
to Text Display.
Touch Close or the
Load icon to close
the Load detail pane
and return to the
animated mimic.
Load icon touched
to show data in
the left pane.
Figure 9UNIT STATUS pane—Load details; graphic display
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 11
Figure 10UNIT STATUS pane—Input details; graphic display
Input detail icon
touched to show
data in the left pane.
Touch Close or the
Input icon to close
the Input detail pane
and return to the
animated mimic.
Bypass detail
icon touched to
show data in the
left pane.
Touch Close or the
Bypass icon to close
the Bypass detail
pane and return to
the animated mimic.
Figure 11UNIT STATUS pane—Bypass details; graphic display
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 12
Figure 12UNIT STATUS pane—Battery and cabinet details; graphic display
Battery detail icon
touched to show
data in the left pane.
Touch Close or the
Battery icon to close
the Battery detail
pane and return to
the animated mimic.
Environmental detail
icon touched to show
data in the left pane.
Touch Close or the
Environmental icon to
close the
Environmental detail
pane and return to the
animated mimic.
Figure 13UNIT STATUS pane—Environmental details; graphic display
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 13
2.4Customizing the Display
STATUS
Context Menu
STATUS Icon
Edit Icon
The Touchscreen Control Panel’s default appearance will be adequate for most installations, but the Status
panels can be altered to show additional or different data. The layout selected will be applied to all users. If PIN’s
have been activated, layouts may be created or altered with Operator, Administrator or Service Access.
NOTE
The original configuration, Default View 1, cannot be deleted, though it can be changed. Editing it will create a
modified view with the new settings. The Default View 1 can be altered with the edit icon (pencil) in the display
(see 2.4.2 - Using the Edit Icon to Customize Layout).
To customize the display’s appearance:
1.Log in to the Touchscreen Control Panel, if a PIN is required.
2.From the STATUS view, touch the Context Menu icon in the top left
corner.
3.Select Display Options > Customize Layout. (The right pane details how
to edit or create a view; see Figure 14.)
Edit a View
4.Touch a view to highlight it.
5.Touch Edit to change that view.
6.Alter the layout—Add or remove a panel or associate different options with a panel.
7.Touch the
Create a View
8.Touch the New button to create a view.
Save button to keep your changes or touch Cancel to exit without saving.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 14
Figure 14Customize the display
Edit Button
Remove View
Button
Panel shows
view name,
layout and
content.
Enter Key
9.Either accept the generated name (New View) or touch the view’s name to rename it using
the on-screen keyboard (maximum length is 15 characters including spaces). Touch the
Enter key on the on-screen keyboard after entering the new name.
10. Select the number of panels in the new or edited view from the drop-down list under the
Layout heading. The maximum is four.
11. Choose the data to be displayed in each pane by touching a choice in the PANEL OPTIONS
pane and then touching the appropriate panel. Repeat for each panel.
12. Touch the
Save button to keep the changes or touch the Cancel button to exit the screen
without saving.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 15
Figure 15Set number of panes and choose data
Choose the
number of
panels from
the drop-down
list.
Follow the instructions in PANEL OPTIONS
(see Figure 15) to choose the data to be
displayed. The Save button is inactive until
the setup requirements are complete.
To choose an existing layout, navigate to the PANEL CONTENT screen and touch the radio button beside the
layout, then touch the STATUS Function Menu.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 16
13. Touch the Save button.
14. When the window returns to two screens—PANEL CONTENT and PANEL OPTIONS—touch the radio button beside the
new view to activate it (this puts a dot in the circle).
15. Touch
Save.
16. Touch the STATUS Menu icon to see the new appearance.
2.4.1Remove a Layout
Context
Menu Icon
Edit Icon
Touch the X on a parameter
or the X on the Status Gauge
to remove it from the view.
To delete a layout:
1.Log in with Administrator or Service access, if a PIN is required.
2.From the STATUS view, touch the Context Menu icon in the top left corner.
3.Select Display Options > Customize Layout. (The right pane details how to edit or create a view; see
Figure 14.)
4.Touch a view to highlight it.
Edit a View
5.Touch Edit to change the highlighted view.
6.Make the changes.
7.To uch Save to keep the changes
Remove a View
8.Touch
Remove to delete the highlighted view.
2.4.2Using the Edit Icon to Customize Layout
The Touchscreen Control Panel layout can also be changed with the Edit icons on the screen. The
Edit icon can be used to add or remove panels, resize panels, rearrange panels and change
monitored parameters.
To use the Edit icon:
1.Touch the Edit icon on the panel to be edited and hold it until a Change content button appears on the panel
(about 1 second).
Change Panel
2.Touch an icon to choose the data to be displayed in the panel (see Figure 17); choices are:
One-LineEvent Log
StatusBattery Cycle Monitor
EventsEnergy Log
Run HoursBattery Log
Service HistoryBattery Time Remaining
Change UNIT STATUS Panel Content (see Figure 16)
3.To change the UNIT STATUS panel’s content:
a.Touch the Edit icon on the UNIT STATUS panel and hold it until the Change
parameters.
b.Touch the X on the parameter to be removed from the panel.
Figure 16Edit UNIT STATUS panel
content button and X’s appear on the
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 17
The Add Parameter icon (+) will appear in the panel if another parameter can be added. The number
+
Add Parameter
Icon
Touch the Change content
button to display the choices.
of parameters that may be shown is based on whether the Status Gauge is showing.
c.Touching the Add Parameter icon brings up a window to add parameters not already shown on
the UNIT STATUS panel.
d.Touch a parameter’s icon to add it to the UNIT STATUS panel.
Resize or Remove a Panel (see Figure 18)
4.Touch and hold the Edit icon again while the
5.Release the icon. Resize handles will appear around the panel and a large
right corner.
6.Pull on a handle to resize the panel, or
7.Touch the large
Rearrange Panels (see Figure 18)
8.With the resize handles and
Exit Edit Mode
9.Edit Mode will deactivate after some changes. If all changes have been made and Edit Mode is active, touch the panel’s
header area to exit Edit Mode.
Figure 17Change panel content
X to delete the panel.
X’s visible, touch the circle in the center of the panel and drag the panel to its new position.
Change content button is displayed.
X will appear at the top
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 18
Figure 18Resize, remove or rearrange a panel
Pull a handle to
resize the
panel.
Touch the X to remove
the panel from the view.
Use this large circle to drag
the panel to a new position
in the view.
+
Add Parameter
Icon
2.4.3Edit the UNIT STATUS Panel with the Edit Icon
The UNIT STATUS panel may be changed to add or remove data. The panel has four default parameters. Any or
all can be deleted or replaced using the Edit icon.
Possible parameters for the UNIT STATUS panel are:
•Input
•Bypass
• Battery
• Environmental
•Load
NOTE
Changes made to the UNIT STATUS panel will be applied to all views using the panel for all viewers.
NOTE
If the Status Gauge is showing, no more than four detail icons will be visible. Removing the Status Gauge permits
showing all five detail icons. The view may be customized to show fewer than four.
To edit the UNIT STATUS panel:
1.Activate Edit Mode by touching and holding the Edit icon on the UNIT STATUS panel.
2.Touch the large X beside a parameter icon or the X on the Status Gauge to delete the feature or touch
3.Touch the header area or a non-interactive area of the panel to deactivate edit mode.
the + icon at the right side of the panel to add a parameter icon.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 19
Figure 19Edit UNIT STATUS panel
Touch an X to remove the associated
parameter from the panel.
Touch the + icon to add a parameter to
the panel; a maximum of four icons are
possible if the Status Gauge is showing.
The Add Parameter box opens showing
parameters that may be added.
2.4.4Setting DISPLAY PROPERTIES
The Context Menu for either OPERATE or SETUP permits determining how data is displayed. The DISPLAY
PROPERTIES menu is available to any user, including Observers. However, the items that may be altered differs
with each access level, if PIN’s are required.
Table 1Available display properties by access level if PIN’s are required
Display Property
Language✔✔ ✔ ✔
Theme✔✔ ✔ ✔
Backlight Off TimerX✔✔✔
Alarm Window TimeoutX✔✔✔
Auto-Logout TimerXX✔✔
Display Brightness✔✔ ✔ ✔
Status Indicator BrightnessXX✔✔
Calibrate Touch ScreenXX✔✔
ObserverOperatorAdministratorService
Access Level
Language: The default setting is English; other choices are Chinese, Spanish and Canadian French.
Theme: The default setting is Dark_Gray_9; other choices are Blue_9 and Light_Gray_9. Themes change not only
the background, but also the color of some menus.
Backlight Off Timer: The default setting is Off After 5 Minutes; other choices are Off After 10 Minutes, 20
minutes, 30 minutes, 45 minutes, 60 minutes and Never.
Alarm Window Timeout: The default setting is Never. It may be changed in one-day increments from one day to
14 days.
Auto-Logout Timer: The default setting is Logout After 5 Minutes. It may be changed in one-minute increments
from one minute to 5 minutes.
Display Brightness: The default setting is 80 percent, but the brightness may be changed in increments of 20
percent from the low of 20 percent to 100 percent.
Status Indicator Brightness: The default setting is 80 percent; brightness may be changed in increments of 20
percent from the low of 20 percent to 100 percent.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 20
Calibrate Touch Screen: No default value; instructions must be followed to calibrate the touchscreen. A
These values are entered when the
Touchscreen Control Panel is
configured. Changing them requires
Administrator or Service access.
UTC is a world standard and cannot
be changed.
notification warns that performing a calibration on a properly functioning touchscreen could cause the
touchscreen to fail. The notification offers a choice of going ahead with the calibration or canceling it.
2.4.5Setting Date, Time and Time Zone
The date, time and time zone are set when the Touchscreen Control Panel is configured.
Changing the date, the time and the time zone may be done through the Context Menu on either the STATUS or
SETUP page (STATUS>Display Options>Date & Time or SETUP>Display Options>Date & Time). If PIN’s are
required, changing the date, time or time zone requires Administrator or Service access. These settings can be
viewed, but cannot be changed, by Observers and Operators.
The format of the date or time may be changed through the Context Menu on either the STATUS or SETUP
page (STATUS>Display Options>Date & Time or SETUP>Display Options>Date & Time) (refer to 2.5 - Changing
Date, Time and Measurement Formats).
NOTE
The UTC Time is a world standard that the Touchscreen Control Panel displays. It cannot be changed.
NOTE
If LIFE Services is enabled, neither the date nor the time can be changed.
Figure 20Date and time settings
Changing the Time Zone
The time zone is set when the Touchscreen Control Panel is configured (the default is America/New York). The drop-
down menu permits selecting any time zone on the globe, as well choosing one-hour increments before and
after UTC. To change the time zone:
1.Log in with either Administrator or Service access.
2.Navigate to STATUS>Display Options>Date & Time or to SETUP>Display Options>Date & Time.
3.Touch the
4.Scroll to the appropriate time zone and touch it.
5.Make any other changes on the DATE & TIME page.
6.Touch the
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 21
Time Zone box or either arrow on the drop-down menu.
Save button to make the changes or touch Cancel to exit without saving the changes.
Figure 21Time Zone drop-down menu
Touch the Time Zone box ...
... or either arrow to
display the choices.
Scroll through the list
and choose the
appropriate time zone.
Graphic
Date
Display
Touching
this icon ...
reveals the
text display
of the date.
Changing the Date
The date is set when the Touchscreen Control Panel is configured. The default format is month/day/year with
single numerals for months from January through September and for days 1 through 9. Changing how the date is
shown requires using the Formats page found on the Context Menu on either the STATUS or SETUP menu
(refer to 2.5 - Changing Date, Time and Measurement Formats).
To change the date:
1.Log in with either Administrator or Service access, if passwords are required.
2.Navigate to STATUS>Display Options>Date & Time or to SETUP>Display Options>Date & Time.
3.Touch either the
4.Scroll to the correct month and touch the correct day.
5.Make any other changes on the DATE & TIME page.
6.Touch the
Date box or the grid beside it. Either will display a calendar for the month.
Save button to make the changes or touch Cancel to exit without saving the changes.
Figure 22Change the date
NOTE
Touching the Graphic/Display icon permits changing the date by scrolling though months, days and years.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 22
Changing the Time
Touching a numeral or an arrow and
releasing it will increase or decrease the
associated numeral by one. Holding a
numeral or an arrow will scroll continuously.
The AM/PM choice
will not be shown if
the 24-hour clock
format is active.
The time is set when the Touchscreen Control Panel is configured The default format is h:mm AP (hour:minute
AM/PM) with one numeral for hours less than 10 (for example, 1:09 for nine minutes after 1 a.m. and 13:09 for nine
minutes after 1 p.m.). Changing how the time is displayed requires using the Formats page found on the Context
Menu of either the STATUS or the SETUP menu (refer to 2.5 - Changing Date, Time and Measurement Formats).
To change the time:
1.Log in with either Administrator or Service access.
2.Navigate to STATUS>Display Options>Date & Time or to SETUP>Display Options>Date & Time.
3.Touch the
4.Touch the hours, minutes or seconds to be changed or touch the associated Up or Down arrow.
Local Time box or the clock icon beside it. Either will display a digital version of the time.
NOTE
Touching a numeral or the Up arrow and releasing it will increase the numeral by one. Touching the Down arrow
and releasing it decreases the number by one.
Holding a numeral or arrow will scroll continuously. Holding a numeral will scroll Up, increasing the numeral.
Holding an arrow will scroll in the direction the arrow points.
5.When the correct time is shown, touch OK to save the change or touch Cancel to exit without saving.
NOTE
An AM/PM choice will be shown if that format is active. The AM/PM choice will not be shown for the 24-hour
clock format.
6.Make any other changes on the DATE & TIME page.
7.To uch
OK to save the changes or touch Cancel to exit without saving.
Figure 23Change the time
2.5Changing Date, Time and Measurement Formats
The Touchscreen Control Panel has these default settings:
• Date: M/d/yyyy
• Time: h/mm (either AM/PM or am/pm)
•Measurement System: Metric
These formats may be changed by any user, including an Observer, by going to Status>Display Options>Formats;
choose the format or measurement system and touch Save.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 23
2.5.1Change the Date Format
Date Format Choices
(scrolling reveals
additional formats)
Time Format Choices
Measurement
Format Choices
Touch inside this box to change the format.
Enter Key
To change the way the date is displayed, touch inside the box containing the date format and choose the format
from the choices shown in Figure 24.
2.5.2Change the Time Format
To change the way the time is displayed, touch inside the box containing the time format and choose the format
from the choices shown in Figure 24.
2.5.3Change the Measurement System
To change the way measured values, such as heat, kW and voltage, are displayed, touch inside the box
containing the Measurement System and choose either Imperial or Metric as shown in Figure 24.
Figure 24Date/Time format and Measurement System choices
2.6Create or Modify Custom Labels
The CUSTOM LABELS page permits renaming settings, serial ports and network interfaces. New names may be
entered for these to suit local preferences and to ease troubleshooting and refine data. (The default name of
COM1 may be adequate, but renaming it with the connected device may ease determining the cause of an
alarm).
Custom labels may be created or modified by any user, including Observers. The labels are universal and will be
displayed for all users.
To create or modify a custom label:
1.Go to STATUS>Display Options>Custom Labels.
2.Choose the label group to change.
NOTE
Changing a particular Setting may require scrolling (see Figure 25 and Table 2.
3.Touch inside the Custom Label box beside the setting to be labeled.
4.Use the on-screen keyboard to enter the label name.
5.Touch the Enter key.
6.Touch Save to make the change or touch
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 24
Cancel to exit without saving.
Figure 25CUSTOM LABELS page
Touch any of
these headings
to create or
modify a label
Table 2Additional custom label choices for Settings
SW1-Static switch disconnect switchScreen ResolutionSerial Number
Serial ProtocolService PINSingle Input
Status Indicator BrightnessSystem IdentificationTag Number
Test CycleTest Day of WeekTest Duration Time
Test Duration TypeTest Time of DayTest To Remaining Capacity
ThemeTime FormatTime Zone
UIB - UPS input breakerUOB - UPS system output breakerUTC Time
Unit NameUnit VersionWarning Temperature Limit
Warning TypeWebSite Contact—
Figure 26Custom Labels for Network Interfaces
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 26
3.0 OPERATION
SETUP
SETUP Icon
Enter Icon
Choose the Role
to receive a PIN.
The Service role
will be visible only
to a user with
Service access.
PIN Box
Enter Icon
3.1Log In to the Touchscreen Control Panel
The Touchscreen Control Panel is On whenever the UPS has control power. It
may be inactive and appear dark, depending on its settings. If it is inactive,
touch the LCD to activate it.
The Touchscreen Control Panel’s controls are available to anyone who has
physical access to the Liebert EXL S1. However, control panel access may be
restricted by adding PIN’s for Operator and Administrator access. The
Service level requires a PIN by default.
NOTE
Vertiv recommends recording any PIN’s set and storing the numbers where they are accessible if they are
forgotten. A user with authority to change a PIN will be able to see PIN’s of those with equal or lesser access.
To set a PIN:
1.Touch the SETUP icon at the top of the screen.
2.Touch the Role whose PIN will be set or changed.
3.Enter a PIN using the on-screen keypad, shown below (the PIN may be up to 9 digits).
4.Press the Enter icon.
5.Press the Save button.
Figure 27Set a PIN
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 27
To log in with a PIN to the Touchscreen Control Panel:
Choose a
Role to
designate its
PIN.
Touch dialog box to
bring up keypad.
Incorrect PIN Entered
1.Touch the LOG OUT icon at the top right of the screen.
The lock will close and will be named LOG IN.
2.Touch the LOG IN icon.
The background will change color and open a screen, with a keypad.
3.Enter a PIN at the screen below.
4.Touch Enter.
NOTE
Entering an impermissible PIN will generate a screen saying the number is invalid.
Figure 28Log in screen
3.2Operator Controls
The Operator Function Menu confers control of UPS functions:
• Silence (Alarm)
•Inverter On
•Inverter Off
• Reset Fault
• Energy Saving Mode Activation
• Battery Operations
Each command is available under the OPERATE menu, which is accessible by all in the default control panel
setup. If PIN’s are required, the OPERATE menu may be used by logging in with Operator, Administrator or
Service access.
NOTICE
Risk of improper operation. Can cause load drop, resulting in equipment damage.
The Inverter On, Inverter Off, Reset Fault and Energy Saving Mode Activation commands will be available whenever the
UPS is operating. Before executing any command, verify that the UPS status and the connected load status are suitable for
the command to be performed.
3.2.1LIFE™ Services
The OPERATE Context Menu also permits configure LIFE Services. Enabling LIFE Services requires a contract
with Vertiv and on-site activation by Vertiv Services. The LIFE Support group is reachable by the telephone
number on the dialog that opens at STATUS>LIFE Services>Support or by touching the LIFE Services icon (see
3.5 - LIFE™ Services—Context Menu and LIFE Services Function Menu.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 28
3.3OPERATE Menu Commands
Commands in the
OPERATE Function
Menu are the same
for all access levels
that can view it.
Animated mimic is not linked
to data in this view.
Reset
Fault
Button
All Operator commands are available from the OPERATE Function Menu whenever the UPS has control power. If
a PIN is required, it may be accessed by logging in with Operator, Administrator or Service access. The UPS need
not be supplying power to the load for the menu to be available.
The Touchscreen Control Panel shows the screen in Figure 29 when the OPERATE Function Menu is active. The
animated mimic moves to the right side of the screen; it is not linked to data in this view, so touching a
component will not cause it to display data. The animated mimic will display the power path in this view.
Figure 29OPERATE Function Menu screen
3.3.1OPERATE Menu—Silence an Alarm
To silence an alarm, touch the Silence button at the top of the panel. The time the alarm will remain silenced
depend on the UPS model, type of alarm and system configuration.
This command is also available at STATUS>Alarms. That screen permits silencing one or more alarms,
acknowledging an alarm and viewing either all alarms or just active alarms.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 29
3.3.2OPERATE Menu—Inverter On
Press the On button to start
the inverter.
Press either the System or Single button to
start the desired number of inverters.
The Inverter On menu item is available whenever the UPS has control power. Before executing the command,
verify that the UPS is prepared for the inverter to start. Performing this function requires Operator or higher
access, if PIN’s are required.
Figure 30Inverter On command, single UPS configuration
Figure 31Inverter On command, parallel UPS configuration
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 30
3.3.3OPERATE Menu—Inverter Off
Press the Off button to
shut Off the inverter.
Press the System or Single button to
shut Off the desired number of inverters.
The Inverter Off menu item is available whenever the UPS has control power. Performing this function requires
Operator or higher access. Before executing the command, verify that the UPS and connected load are prepared
for the inverter to be shut down (see Figure 32).
Figure 32Inverter Off command, single UPS configuration
Figure 33Inverter Off command, parallel UPS configuration
3.3.4OPERATE Menu—Reset Fault
Faults may be reset with the Reset button (see Figure 29 for the button’s location). Performing this function
requires Operator or higher access, if PIN’s are required.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 31
Figure 34Reset fault command
3.3.5OPERATE Menu—Suspended Time Remaining
The Suspended Time Remaining is not configurable. The reading shows the time required for the UPS to return
to Energy Saving Mode after input power has degraded, causing the UPS to exit Energy Saving Mode. It
becomes active when Energy Saving Mode has alternated between active and inactive too frequently and the
system has suspended Energy Saving Mode activation for a period. The UPS will enter Energy Saving Mode
when the feature is enabled and input power meets qualifications. If input power degrades, the UPS will exit
Energy Saving Mode.
The Suspended Time Remaining increases when the activation and deactivation of Energy Saving Mode
becomes more frequent.
3.3.6OPERATE Menu—Energy Saving Mode Activation
NOTE
Refer to the UPS manual before activating Energy Saving Mode. If a PIN is required, an Operator can only enable
or disable Energy Saving Mode. The modes available vary according to the UPS type and system configuration.
The types available must be set up by someone with either Administrator or Service access.
Energy Saving Mode
Either of two energy saving modes—Eco Mode and Intelligent Parallel Mode—may be activated or deactivated
through the OPERATE menu screen. Energy savings must be enabled through the SETUP Context Menu.
Eco Mode
Eco Mode permits the UPS to reduce power consumption by powering the load through bypass power when
utility-supplied power is within acceptable ranges. The inverter will remain in a state that will permit it to resume
supplying power if the utility power goes outside acceptable ranges.
Intelligent Parallel Mode
Intelligent Parallel puts units in Sleep Mode until required to support the load or until the unit is rotated into
operation. Intelligent Parallel rotates units into and out of service, equalizing run time, so that each unit’s service
life will be the same.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 32
To activate or deactivate Energy Saving Mode:
Choose an energy
saving setting
from the
drop-down list.
Touch Setup and use the drop-down
list to enable, disable or force start the
energy saving mode chosen.
YESNO
YESNO
1.Touch the SETUP Function Menu.
2.Touch the Context Menu and select UPS Settings.
3.Choose ECO Mode. Intelligent Parallel or Disabled from the drop-down menu.
•Choosing Disabled will remove the choices from the OPERATE Context Menu.
4.Touch Save. The Save button is inactive until the activation state is changed.
5.Set up the energy saving mode chosen by touching the OPERATE Function Menu, then touching Setup.
6.Choose from the drop-down menu to enable, disable or force start the selected energy saving mode.
•Choosing Disabled will deactivate Energy Saving Mode.
7.To uch Save.
Figure 35Activating Energy Savings Mode
3.4Audible Alarm Enabled or Disabled
The Touchscreen Control Panel permits enabling an audible alarm to alert personnel to problems with the power
supply to the connected load. Enabling or disabling the audible alarm requires Administrator or Service access.
To enable or disable the audible alarm:
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 33
1.Log in with Administrator or Service access.
2.Touch the SETUP Function Menu, touch the Context Menu and select UPS Settings.
3.Enable or disable the Audible Alarm by touching the lighter associated box.
3.5LIFE™ Services—Context Menu and LIFE Services Function Menu
The Context Menu on the OPERATE Function Menu permits initializing LIFE Services. Enabling LIFE Services
requires a maintenance contract, and the service must be enabled and configured by Vertiv Services.
LIFE Services provides increased up-time and operational efficiency through continuous monitoring, expert
analysis and proactive response. Detailed parametric data is continuously captured with advanced technology
embedded in select critical systems. The data is transmitted to an authorized remote service center staffed with
system engineers. Should an operating anomaly or alarm condition arise, the engineer analyzes the information
and initiates an appropriate response to have the critical system quickly, safely, and accurately restored to its
proper operating condition.
To initialize LIFE Services:
1.Log in with Operator, Administrator or Service access.
2.Touch the LIFE Services Function Menu.
3.Telephone the number on the screen and follow the instructions given.
Figure 36LIFE Services contact
To configure LIFE Services:
1.Log in with Operator, Administrator or Service access.
2.Touch the OPERATE Context Menu and select
3.Select the appropriate menu item: Status, Support or Actions.
• Status shows whether LIFE Services is enabled and gives details about calls and connections.
• Support shows telephone numbers to contact LIFE Support.
• Actions permits configuring LIFE Services.
Figure 37LIFE Services—Menus
LIFE Services.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 34
4.0 VIEWING UPS STATUS
Load as a percentage of
UPS capacity and in
output supplied (also
shown in green graph line)
Battery charge level
(also shown in green
graph line)
Voltage status for
each phase, input,
output and bypass
The Touchscreen Control Panel interface reports UPS status in multiple ways. The graphic views and text views
will show the same information, but display it differently.
Alarms and certain events will trigger audible alarms and the LED on the bezel, the light bar and the status
header will change color. (Audible alarms will not sound unless enabled.) The scrolling information bar at the top
of the interface summarizes information about the UPS status. The Status Gauge on the UNIT STATUS pane
gives additional details about the UPS status.
4.1Viewing UPS Data with the Status Gauge
The Status Gauge offers a quick summary of the UPS’s status in a single-unit configuration. In a parallel system,
the gauge shows the status of the unit the touchscreen is installed on. The information shown depends on the
type of UPS and its configuration as well as the choices made in the gauge’s setup. The Status Gauge’s data
options can be chosen by someone with Administrator or Service access.
The additional data will not replace the information shown in the center of the Status Gauge. Touching the
center of the Status Gauge multiple times will cycle through the data.
Figure 38Default Status Gauge view
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 35
To change the values shown on the Status Gauge:
1.If a PIN is required, log in with either Administrator or Service access.
2.Touch the SETUP Function Menu icon.
3.Touch the Context Menu icon.
4.Touch Configure Status Gauge. This opens the DIAL CONTROL SETUP panel, which holds settings for the readings in the
center of the gauge and for the upper and lower metering.
To change the data shown in the center of the gauge:
a.Expand the Center Readings menu by touching the arrow beside it.
b.Highlight or put a check mark (✔) in the check box beside each value to be displayed (see Figures 39 and 40).
NOTE
All possible values may be checked. Touching the center of the gauge multiple times will cycle through the
values.
To change the data shown in the gauge’s upper or lower section:
a.Expand the Upper Meter or Lower Meter menu by touching the arrow beside it.
b.Use the drop-down menu to choose whether the Upper Meter or Lower Meter shows data for the Battery or Load.
(Either the upper or lower part of the Status Gauge may be used to show Load or Battery readings.)
c.Use the sliders to change the Warning Threshold or Critical Threshold (see Figures 39 and 40).
5.Touch the
Save button to keep the changes or touch Cancel to exit without saving the changes.
NOTE
The DIAL CONTROL SETUP pane may be also be accessed by touching the Status Gauge and holding it for
about 2 seconds. This requires Administrator or Service access.
Figure 39Access Status Gauge settings
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 36
Figure 40Status Gauge settings options
Use the sliders to
change the warning
thresholds
Highlight or put a
check mark (✔) in
the box for each
value desired.
UPPER METER
READINGS
CENTER METER
READINGS
LOWER METER
READINGS
This drop-down menu permits putting the
Load or Battery readings in the upper or lower
portion of the meter.
4.2Viewing UPS Data with the Status Panel
More-detailed information about the UPS’s status is readily available through the UNIT STATUS pane. Touching
a component in the animated mimic display brings up data about that component on another pane. Touching a
parameter icon on the UNIT STATUS pane brings up further details about that parameter.
The same data can be viewed by switching to the text view. The length of the lists and order of the details may
require scrolling to see the desired data.
NOTE
A parameter must be visible on the UNIT STATUS screen for details to be viewed. For instance, if the UNIT
STATUS pane does not show the Environmental icon, details about Environmental cannot be viewed.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 37
Figure 41UNIT STATUS—Load details
GRAPHIC VIEW
TEXT VIEW
Some data in the
columns at left is
summarized in the
Status Gauge.
Touch the Load icon
to reveal the
information at left.
Data in the columns
in the graphic view is
visible in the text
view by expanding
the parameter. Here,
Load has been
expanded.
Table 3Load menus
Voltage (L-L)CurrentReal (Active) Power, kWApparent Power, kVAPower Factor
Voltage (A-B)Current AReal (Active) Power AApparent Power APower Factor A
Voltage (B-C)Current BReal (Active) Power BApparent Power BPower Factor B
Voltage (C-A)Current CReal (Active) Power CApparent Power CPower Factor C
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 38
Figure 42UNIT STATUS—Input details
GRAPHIC VIEW
Data in the columns in the graphic view
is visible in the text view by expanding
the parameter. Here, INPUT has been
expanded, showing the details.
TEXT VIEW
Some data in the
columns at left is
summarized in the
Status Gauge.
Touch the Input
icon to reveal the
information at left.
Table 4Input menus
Voltage (L-L)CurrentReal PowerApparent PowerFrequency
Voltage (A-B)Current AReal Power AApparent Power AFrequency
Voltage (B-C)Current BReal Power BApparent Power B
Voltage (C-A)Current CReal Power CApparent Power C
——Real Power TotalApparent Power Total
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 39
Figure 43UNIT STATUS—Bypass details
GRAPHIC VIEW
Some data in the columns at left is
summarized in the Status Gauge.
Touch the STATUS
icon to reveal the
information at left.
Data in the columns in the graphic view is visible
in the text view by expanding the parameter.
Here, BYPASS has been expanded.
TEXT VIEW
Table 5Bypass menus
Voltage (L-L)CurrentFrequency
Voltage (A-B)Current AFrequency Total
Voltage (B-C)Current BFrequency Total
Voltage (C-A)Current CFrequency Total
Real PowerApparent PowerPower Factor
Real Power AApparent Power APF A
Real Power BApparent Power BPF B
Real Power CApparent Power CPF C
Real PowerApparent PowerPF
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 40
Figure 44UNIT STATUS—Battery details
GRAPHIC VIEW
TEXT VIEW
Some data in the pane at left is
summarized in the Status Gauge.
Touch the Battery
icon to reveal the
information at left.
Data in the columns in the graphic view is
visible in the text view by expanding the
parameter. Here, BATTERY has been
expanded to show overall data and
information for Cabinet 1.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 41
Figure 45UNIT STATUS—Environmental details
GRAPHIC VIEW
Touch the
Environmental icon
to reveal the
information at left.
TEXT VIEW
Data in the columns in the graphic view is visible
in the text view by expanding the parameter.
Here, ENVIRONMENTAL has been expanded.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 |42
4.3Logs—Events and Log-In Times
STATUS
Touch
Events or
Logs
The Context Menu, when opened from the STATUS pane, permits viewing a log of alarms and events that have
occurred on the UPS. The log includes the date and time of occurrence, type (alarm or event), an Event ID,
component affected and a description of the alarm or event. The information is available to all users, including
Observers, those without a log-in passcode.
Events can be sorted by any of the associated information or filtered by severity (Status, Alarm and Fault) or by
component affected (bypass, monitoring or module); see 4.3.1 - Logs—Filtering and Sorting Events).
The Context Menu, when opened from the STATUS pane also permits seeing when various users logged in and
logged out—available by touching Audit Log.
To view the alarms or events:
1.Navigate to the STATUS pane.
2.Touch the Context Menu icon.
3.Touch the log to view: Events or Logs, which includes the Audit Log and UPS Event Log; see Figure 46.
Touching Events opens the list of events and alarms; touching Logs permits viewing the Audit Log or
the UPS Event Log.
Figure 46View alarms, events, log-out times
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 43
4.3.1Logs—Filtering and Sorting Events
Touch the Filter button to filter
events by any of the parameters
in the drop-down list.
Arrow shows events
sorted by Type.
The Events Log permits sorting Events and Filtering Events to ease understanding how the UPS is operating.
To sort events, touch on or just to the right of any of the headings—Type, Event ID, Component or Description. A
small arrow will appear beside the heading, indicating that the Events have been sorted (see Figure 47).
Figure 47Sorting and filtering events
Sorting a list follows this logic:
•If sorting by Component, the list then sorts by Severity, then by Date/Time
• If sorting by Date/Time, the list then sorts by Component, then by Severity
• If sorting by Type, the list then sorts by Component, then by Date/Time
• If sorting by Description, the list then sorts by Date/Time
• If sorting by Event ID, the list then sorts by Date/Time.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 44
4.4Logs—Exporting Event and Audit Logs
Touch the
Export button.
Name the file.
Choose the file’s
destination; here
it is an SD card
on the Customer
Connections.
Choose the file’s
format, XML or
comma-separated.
Touch Save.
The Touchscreen Control Panel records and retains information about alarms, events and user log-in and log out.
Users of any access level can export these logs as either XML or CSV files for analysis or record keeping. XML
files may be opened with most text editing programs; CSV files may be opened with a spreadsheet program, such
as Microsoft® Excel™.
To export an Event Log or Audit Log:
1.Navigate to STATUS>Logs, then choose the log to be exported, either the Event Log or Audit Log.
2.Touch the Export button at the top right of the screen.
3.In the EXPORT FILE screen that opens:
a.Name the file in the Save As box (an on-screen keyboard will appear).
b.Choose the destination (this may be a memory stick inserted into the Touchscreen Control Panel).
c.Choose CSV or XML in the Format box.
d.Touch Save.
Figure 48Exporting logs
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 45
5.0 VIEWING UPS COMPONENT STATUS
Main Input is
selected, so the
COMPONENT
DETAILS pane
shows data about
the Main Input.
The animated mimic screen permits viewing details about the main components installed in the UPS and
configured in the Touchscreen Control Panel. The data list opens on the opposite side of the screen and, for
most parameters, expands to show all details for the component selected. The information is available to anyone,
including Observers, who have no PIN number, if PIN’s are required.
Component information may also be viewed by going to STATUS Menu and touching COMPONENTS. Touching
the component name in the COMPONENTS pane brings details of the selected component in the right pane
(see Figure 49).
Figure 49Component status—STATUS Menu
Figure 50UNIT STATUS—Main Input details
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 46
Touching any major component on the animated mimic brings up similar details about that component of the
Bypass Details
Rectifier Details
Inverter Details
Charger/Booster Details
Battery Details
Load Details
Bypass Input Details
Liebert EXL S1. Scrolling is required to see all faults on some screens.
Figure 51UNIT STATUS details
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 47
6.0 STATUS BAR COMPOSITION
NormalWarningCritical
The status bar indicates UPS status by:
• scrolling messages to inform viewers; see Tables 9 through 11.
• changing color; green for normal, yellow for warning and red for alarm
• showing an icon inside the bar; shown at right
6.1Status Bar Messages
Up to three messages may scroll through the status bar to the right of
the status icon. Each message will have a duration of four seconds,
except they change immediately if the system’s status changes.
Table 6Normal messages—Green status bar
Message 1Message 2Message 3Definition
LOAD ON IN VERT ER
LOAD ON INVERTERX MODE ENABLED—
LOAD ON INVERTERX MODE ACTIVE—
LOAD ON INVERTEROPERATION NORMAL—
LOAD ON BYPASSX MODE ACTIVE—
LOAD ON BATTERY
LOAD OFFX MODE ACTIVE—
LOAD ON INVERTERSERVICE MODE ACTIVE—
LOAD ON INVERTERTEST MODE ACTIVE—
LOAD ON OTHER MODULE——
LOAD ON BATTERYX MINUTES REMAINING—
FREQUENCY CONVERTER
MODEACTIVE
BATTERY TEST
IN PROGRESS
OUTPUT
FREQUENCY X HZ
—
The system is in normal operating mode, supplied by the
inverter, and operating as a frequency converter.
The system is in normal operating mode, supplied by the
inverter, and has the specified energy saving modes
configured and enabled.
The system is in normal operating mode, supplied by the
inverter, and has the specified energy saving modes
active.
The system is in normal operating mode, supplied by the
inverter, and has no special configurations.
The system is in normal operating mode, supplied by the
bypass, and has the specified energy saving modes
active.
The system is in normal operating mode, supplied by the
inverter via the battery, and a battery test is running.
The system is in normal operating mode; the load is not
supplied by this unit, and has the specified energy saving
modes active.
The system is in normal operating condition on the
inverter with the service mode activated.
The system is in normal operating mode for the current
test mode that is activated.
The system is in normal operating mode, but the load is
supplied by another UPS module.
The system is operating in warning mode, supplied by the
inverter via the battery. There are X minutes of calculated
run time remaining. The precedes the battery low voltage
warning.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 48
Table 7Warning messages—Yellow status bar
Message 1Message 2Message 3Definition
The system is operating in warning mode, supplied by the
LOAD ON INVERTEROUTPUT OVERLOAD—
LOAD ON IN VERT ER
LOAD ON IN VERT ER
LOAD ON BYPASS
LOAD ON BATTERY
LOAD ON BYPASS
LOAD ON INVERTERX MODE ENABLED
LOAD ON INVERTERX MODE ACTIVE
LOAD ON BYPASSX MODE ACTIVE
LOAD OFFX MODE ACTIVE
LOAD ON INVERTERTEST MODE ACTIVE
LOAD ON IN VERT ER
LOAD ON BYPASSTEST MODE ACTIVE
LOAD ON BYPASS
LOAD ON BATTERYTEST MODE ACTIVE
LOAD ON BATTERY
LOAD ON IN VERT ER
LOAD ON MA INT BYPASS
LOAD ON OTHER MODULE
LOAD OFF
OVER
TEMPERATURE
ALARM ACTIVE –
WARNING
LOAD MANUALLY
TRANSFERRED TO
BYPASS
X MINUTES
REMAINING
ALARM ACTIVE –
WARNING
SERVICE MODE
ACTIVE
SERVICE MODE
ACTIVE
SERVICE MODE
ACTIVE
FREQUENCY
CONVERTER MODE
ACTIVE
ALARM ACTIVE WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
VIEW EVENT LOG
FOR DETAILS
LOAD
UNPROTECTED
VIEW EVENT LOG
FOR DETAILS
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
ALARM ACTIVE –
WARNING
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
—
—
inverter, and the system is in overload. The system will go off
inverter at some point.
The system is operating in warning mode, supplied by the
inverter, and at least one part of the system is incurring an
overtemperature alarm. This means if the temperature does not
recover, the system will go off inverter at some point.
The system is operating in warning mode, supplied by the
inverter, and has an active alarm.
The system is operating in warning mode, supplied by the
bypass. The user transferred the load to the bypass so the
system cannot protect itself from source variations.
The system is operating in warning mode, supplied by the
inverter via the battery. There are X minutes of calculated run
time remaining. This precedes the battery low voltage warnings.
The system is operating in warning mode, supplied by the
bypass, and has an active alarm.
The system is operating in warning mode, supplied by the
inverter, the specified energy saving modes is configured and
enabled, and has an active alarm.
The system is operating in warning mode, supplied by the
inverter, the specified energy saving modes is active, and has an
active alarm.
The system is operating in warning mode, supplied by the
bypass, the specified energy saving modes is active, and has an
active alarm.
The system is operating in warning mode, load off, the specified
energy saving modes is active, and has an active alarm.
The system is operating in warning mode, supplied by the
inverter, running in a system test mode, and has an active alarm.
The system is operating in warning mode, supplied by the
inverter, running in a service mode, and has an active alarm.
The system is operating in warning mode, supplied by the
bypass, running in a system test mode, and has an active alarm.
The system is operating in warning mode, supplied by the
bypass, running in a service mode, and has an active alarm.
The system is operating in warning mode, supplied by the
battery, running in a system test mode, and has an active alarm.
The system is operating in warning mode, supplied by the
battery, running in a service mode, and has an active alarm.
The system is operating in warning mode, supplied by the
inverter, operating as a frequency converter, and has an active
alarm.
The system is operating in warning mode, supplied by the
maintenance bypass, and has an active alarm.
The module is operating in warning mode. The load is supplied
by other UPS modules, and has an active warning.
The module is operating in warning mode. The load is not
supplied, and has an active warning.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 49
Table 8Critical messages—Red status bar
Message 1Message 2Message 3Definition
LOAD ON INVERTEROUTPUT OVERLOAD
LOAD ON INVERTERFAULT ACTIVE - CRITICAL
LOAD ON BYPASS
LOAD ON BYPASSFAULT ACTIVE - CRITICAL
LOAD ON BATTERYX MINUTES REMAINING
LOAD OFFFAULT ACTIVE - CRITICAL
LOAD OFF——
LOAD ON BATTERYFAULT ACTIVE - CRITICAL
LOAD ON INVERTERX MODE ENABLED
LOAD ON INVERTERX MODE ACTIVE
LOAD ON BYPASSX MODE ACTIVE
LOAD OFFX MODE ACTIVE
LOAD OFFTEST MODE ACTIVE—The system is Off with TEST MODE active.
LOAD OFFSERVICE MODE ACTIVE—The system is Off with SERVICE MODE active.
LOAD ON INVERTERTEST MODE ACTIVE
LOAD ON INVERTERSERVICE MODE ACTIVE
LOAD ON BYPASSTEST MODE ACTIVE
LOAD ON BYPASSSERVICE MODE ACTIVE
LOAD AUTOMATICALLY
TRANSFERRED TO BYPASS
TRANSFER TO
BYPASS PENDING
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
LOAD SHUTDOWN
IMMINENT
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
The system is in critical operating mode, supplied by the
inverter, and the load is about to be transferred to the
bypass due to overload timeouts.
The system is in critical operating mode, supplied by the
inverter. There is a critical fault raised in the system that
the user needs to check.
The system is in critical operating mode, supplied by the
bypass. The system moved the load to the bypass due to
a critical fault in the system.
The system is in critical operating mode, supplied by the
bypass. The system is running on bypass not due to autotransfer, and a critical fault is active in the system.
The system is in critical operating mode, supplied by the
inverter via the battery. The battery is extremely low and
the load will turn Off or transfer to bypass soon.
The system is in critical operating mode, the load is not
supplied by this unit and a critical fault is active.
The system is in critical operating mode, the load is not
supplied and no active fault is present.
The system is in critical operating mode, the system is
running on inverter via the battery, shutdown is not
imminent and a critical fault is active in the system.
The system is in critical operating mode, the system is
running on inverter, with the specified energy saving
mode configured and enabled, and a critical fault is active
in the system.
The system is in critical operating mode, supplied by the
inverter. The system is running on inverter, with the
specified energy saving mode active, and a critical fault is
active in the system.
The system is in critical operating mode, the system is
running on bypass, with the specified energy saving
mode active, and a critical fault is active in the system.
The system is in critical operating mode. The system is
NOT running, with the specified energy saving mode
active, and a critical fault is active in the system.
The system is in critical operating mode, supplied by the
inverter, running in a system test mode, and has an active
fault.
The system is in critical operating mode, supplied by the
inverter, running in a system service mode, and has an
active fault.
The system is in critical operating mode, supplied by the
bypass, running in a system test mode, and has an active
fault.
The system is in critical operating mode, supplied by the
bypass, running in a system service mode, and has an
active fault.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 50
Table 8Critical messages—Red status bar (continued)
Message 1Message 2Message 3Definition
The system is in critical operating mode, supplied by the
inverter via the battery, running in a system test mode,
and has an active fault.
The system is in critical operating mode, supplied by the
inverter via the battery, running in a system service mode,
and has an active fault.
The system is in critical operating mode, with LOAD OFF,
running in a system test mode, and has an active fault.
The system is in critical operating mode, with LOAD OFF,
running in a system service mode, and has an active fault.
The system is in critical operating mode, supplied by the
inverter, operating as a frequency converter, and has an
active fault.
The system is in critical operating mode, operating as a
frequency converter, has an active fault and the load is
not supplied.
The system is in critical operating mode, supplied by the
maintenance bypass. There is a critical fault raised in the
system that the user needs to check.
The module is in critical operating mode. The load is
supplied by other UPS modules. There is a critical fault in
the system that the user needs to check.
LOAD ON BATTERYTEST MODE ACTIVE
LOAD ON BATTERYSERVICE MODE ACTIVE
LOAD OFFTEST MODE ACTIVE
LOAD OFFSERVICE MODE ACTIVE
LOAD ON INVERTER
LOAD OFF
LOAD ON MAINT BYPASSFAULT ACTIVE – CRITICAL
LOAD ON OTHER MODULEFAULT ACTIVE – CRITICAL
FREQUENCY CONVERTER
MODE ACTIVE
FREQUENCY CONVERTER
MODE ACTIVE
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
FAULT ACTIVE CRITICAL
VIEW EVENT LOG
FOR DETAILS
VIEW EVENT LOG
FOR DETAILS
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 51
7.0 LIEBERT EXL S1 EVENTS, WARNINGS AND ALARMS
Table 9Liebert EXL S1 Status Events
ComponentTypeText DisplayIDDescription
BatteryStatusBattery warning04-000A warning is pending.
BatteryStatusBattery fault04-001A fault is pending.
BatteryStatusBattery idle04-002The battery is idle; energy is flowing neither in nor out.
BatteryStatusBattery is discharging04-004The battery is discharging.
BatteryStatusAutomatic Battery Test Started04-032An automatic battery test has been started.
BatteryStatusBattery Test Requested04-033(Not supported) see BAW1 bit 4
BatteryStatusBattery Test Failed04-035
BatteryStatusBattery Test Idle04-048The battery test function is not being performed.
BatteryStatusBattery Test Start Pending04-052
BatteryStatusBattery Test Stop Pending04-053
BatteryStatusBattery Non-Blocking Fault04-054Set when a non-blocking fault is active in the stage.
BatteryStatusBattery Not Connected04-065
BatteryStatusBattery is charging14-003The battery is being charged.
BatteryStatusBattery Test Running14-034Battery test is running.
BatteryStatusBattery Test Not Allowed14-036Conditions preclude performing a battery test.
BatteryStatusBattery Test Finished OK14-037
BatteryStatusBattery Test Canceled14-038(Not supported)
BatteryStatusBattery Test Interrupted14-050(Not supported)
BatteryStatusBattery Test Stopped by User14-051
BypassStatusBypass is not present01-000—
BypassStatusBypass Is On01-001—
BypassStatusBypass Is Off01-002—
BypassStatusBypass is stopped due to a fault01-003—
BypassStatusBypass not prepared01-004
BypassStatusBypass fault01-005Set when a blocking fault is active in the stage.
BypassStatusBypass warning01-007Set when at least one warning is active.
BypassStatusBypass available with delay01-008Set when the bypass and inverter are not synchronized.
BypassStatusParallel bypass OK01-029All bypass inputs are OK.
BypassStatusParallel bypass one fault01-030One bypass input fault exists.
BypassStatusParallel bypass at least one OK01-031At least one bypass input is OK.
BypassStatusParallel bypass fault01-032All bypass inputs are in fault.
BypassStatusUndelayed Bypass Ref. Failure01-040Bypass reference failure notification without any delay.
BypassStatusBypass is Centralized 01-041
A battery test has failed. Permanent state: a manual reset
is required.
In a parallel system with a common battery, the Start
command is present on some but not all the units.
In a parallel system with a common battery, the Stop
command is present on some but not all the units.
Set when V_BATT1 < 100V (fix threshold). Control always
active independently to battery breaker status.
Battery test finished; active for 5 seconds, then switches
to Battery Test Idle.
User has stopped the battery test; active for 5 seconds,
then switches to Battery Test Idle. Valid only for a manual
battery test.
Static switch board is not installed or the bypass voltage
is over the threshold (P 106.i04).
The internal bypass is disabled; the UPS is using the
centralized / common (MSS) bypass.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 52
Table 9Liebert EXL S1 Status Events (continued)
ComponentTypeText DisplayIDDescription
BypassStatusBypass Non-Blocking Fault01-042Set when a non-blocking fault is active in the stage.
BypassStatusBypass Global On Request01-078
BypassStatusBypass Global On01-079
BypassStatusBypass Global Off01-080
BypassStatusBypass mains is out of tolerance11-006Bypass failure notification without any delay.
BypassAlarmBypass Input Switch Open21-012Bypass input switch is open.
Charger/BoosterStatusCharger in Standby - (not charging)03-000—
Charger/BoosterStatusCharger is on03-001—
Charger/BoosterStatusCharger is off03-002—
Charger/BoosterStatusCharger Forced On03-003—
Charger/BoosterStatusCharger Stopped due to a Fault03-038—
Charger/BoosterStatusCharger in Current Limitation03-039
Charger/BoosterStatusCharging Status OFF03-040—
Charger/BoosterStatusCharging Status INIT03-041—
Charger/BoosterStatusCharging Status FLOAT 103-042—
Charger/BoosterStatusCharging Status FLOAT 203-043—
Charger/BoosterStatusCharging Status POST03-044—
Charger/BoosterStatusCharging Status PAUSE03-045—
Charger/BoosterStatusCharging Status MANUAL03-046—
Charger/BoosterStatusCharging Status FAULT03-047—
Charger/BoosterStatusBuck-Booster Fault03-048At least one fault is active.
Charger/BoosterStatusBuck-Booster Warning03-049Set when at least one warning is active.
Charger/BoosterStatusBooster Off03-050—
Charger/BoosterStatusBooster Turning On03-051—
Charger/BoosterStatusBooster On03-052—
Charger/BoosterStatusBooster Stopped Due To Fault03-053—
Charger/BoosterStatusBooster Runs From Battery03-054Status set after a fixed delay equivalent to P1110.
Charger/BoosterStatusBuck-Booster Non-Blocking Fault03-055At least one non-blocking fault is active.
Charger/BoosterStatusDC Bus Too Low To Charge03-061—
GeneralStatusWarning pending00-000Set when at least one stage in the core is in warning.
GeneralStatusFault pending00-001Set when at least one stage in the core is in fault.
GeneralStatusGeneral Fault00-002Set when a fault is active in general stage.
GeneralStatusParallel Unit00-003Set when P129 = 1.
GeneralStatusExternal Synch enabled00-005Set when P700 = 1.
GeneralStatusInverter/Rectifier OFF Command Issued00-006
GeneralStatusInverter on rectifier00-009Inverter is supplied by the rectifier.
GeneralStatusInverter on battery00-010Inverter is supplied by the battery.
Bypass Static Switch On command request on the shared
bus
Bypass Static Switch on global status read from the
shared bus.
Bypass Static Switch Off Global status read from the
shared bus.
Displayed as long as the voltage reference is lower than
the nominal.
Set when command UPS Off is received; resets when
command is not present.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 53
Table 9Liebert EXL S1 Status Events (continued)
ComponentTypeText DisplayIDDescription
GeneralStatusParameter reset active00-011
GeneralStatusIntelligent Parallel Not Allowed00-014
GeneralStatusCore Running00-016Core running.
GeneralStatusOperating Request for VFI00-102—
GeneralStatusSKRU: Inverter start inhibited00-131
GeneralStatusGeneral Warning00-146Set when a warning is active in the general stage.
GeneralStatusGeneral Non-Blocking Fault00-147Set when a non-blocking fault is active in general stage.
GeneralStatusNon-Blocking Fault pending00-148
GeneralStatusGeneral Fault00-171Set when a fault is active in general stage.
GeneralStatusGeneral Warning00-172Set when a warning is active in general stage.
GeneralStatusGeneral Non-Blocking Fault00-173Set when a non-blocking fault is active in general stage.
MUNStatusLife modem not detected08-035Set when MUN does not receive replies from modem
MUNStatusParameter read failed08-054
MUNStatusParameter set failed08-055
MUNStatusLife Service Mode08-060
MUNStatusNtp is Disconnected from Touchscreen08-061to be filled in
MUNStatusLife interface Init in Progress08-079Set at mund application startup; reset after one second
MUNStatusLife Events Sampling started08-095
MUNStatusMUN/DSP are not Sync with SYNW08-097—
MUNStatusLife Measures Sampling Started08-098
MUNStatusSystem Time Moved Ahead08-110
MUNStatusSystem Time Moved Back08-111
RectifierStatusRectifier is off02-000—
RectifierStatusRectifier is turning on02-001—
RectifierStatusRectifier is on02-002—
RectifierStatusRectifier fault02-004Set either blocking or non blocking
RectifierStatusRectifier Warning02-009Set when at least 1 warning is active
RectifierStatusNo precharge in progress02-010
RectifierStatusPrecharge in progress02-011Hold off delay and resistor pre-charge
RectifierStatusWalk-in in progress02-012Rectifier current limit ramp.
RectifierStatusPrecharge finished02-013Pre-charge finished. Active while mains is OK
RectifierStatusRectifier Power Limitation Active02-048
RectifierStatusRectifier Current Limit02-049
Set at mund Application startup; never reset. (mund is
the application name for Managed Ups Network,)
Parameter can not be read from DSP.
• Set when Parameter Reading returns with an
exception
• Reset when Parameter Reading returns with an OK.
Parameter can not be written to DSP.
• Set when Parameter Writing returns with an
exception.
• Reset when Parameter Writing returns with an OK.
Life is in Service mode, so emergency calls are not sent
to station (used when an SE is operating on the device in
field).
Ignore events history and restart sampling from current
time.
Ignore measures history and restart sampling from
current time.
Set when device time is moved ahead after time
adjustment from Life Station.
Set when device time is moved back after time
adjustment from Life Station.
No pre-charge active. Active while mains is out of
tolerance
Set when the input current is limited by standard or
customer limit.
Set when input current reaches the limit defined by
P 1740.11 and lasts more 3 ms but less 10 ms.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 56
Table 9Liebert EXL S1 Status Events (continued)
ComponentTypeText DisplayIDDescription
RectifierStatusRectifier Non-Blocking Fault02-050Set when a non-blocking fault in rectifier stage is set.
RectifierStatusRectifier fault02-070
RectifierStatusRectifier Warning02-071
RectifierStatusRectifier Non-Blocking Fault02-072
RectifierStatusRectifier Stopped - Fault02-092—
RectifierStatusRectifier Inhibited02-093
RectifierStatusRectifier mains is out of tolerance12-005Mains failure notification without any delay.
Set when CUSTOMER blocking fault flag is present. (Not
yet defined)
Set when at least one customer warning is active (not yet
defined).
Set when a customer non-blocking fault in stage is set
(not yet defined).
Set when the rectifier pulse is inhibited due to DC
overvoltage.
Table 10All EXL S1 Events - Alarms
ComponentTypeText DisplayIDDescription
The battery voltage is under the shutdown voltage
defined by 5 points of P1513 Shutdown Voltage Table.
BatteryAlarmBattery under voltage24-012
BatteryAlarmHigh battery temperature24-015
BatteryAlarmBattery temperature out of range24-016
BatteryAlarmTemperature Probe Broken24-017
BatteryAlarmBattery Switch Wiring Fault24-056
BatteryAlarmCubicle Battery Switch Open24-063
BatteryAlarmBattery Is Not Connected24-064Battery is not connected - warning.
BatteryAlarmImminent End Of Autonomy - Volt24-066
BatteryAlarmImminent End Of Autonomy - Time24-067
BatteryAlarmBCB Breaker Open24-068
BatteryAlarmBattery Breaker Open24-072One or more BIB boards report an open breaker.
BypassAlarmBypass Input Switch Open21-012Bypass input switch is open.
BypassAlarmBypass mains failure21-013Warning set after delay defined by P 110
BypassAlarmBypass in Overload Condition21-014—
BypassAlarmBypass disabled21-016
BypassAlarmBypass overtemperature21-017Set when inverter temp. P 151.01 < T < P 151.02.
This warning causes the inverter to stop. This warning will
be kept as long as the battery voltage is lower than the
Inverter Restart Threshold.
Remote Battery Monitoring battery temperature user
alarm (Temp. P1533.1 < T < P1533.2).
RBM battery temperature is out of range
-10°C < T < P 1533.1 or 1533.2 < T < 40°.
RBM temperature probe is not responding
(Temp. T < 10°C or T > 50°C or RBM Sensor Status
[bit 3-2] = 11.
Core only: Set when the RBM option is installed with Form
C wiring and related cubicle breaker wiring fails.
Core and Monolithic.
• CORE: set when an RBM option is installed.
• Monolithic: set when IO Function 18 is enabled.
Set if P1590 = 2 or 3.The battery voltage is lower than the
threshold defined by 5 points of P1513 Shutdown Voltage Tab le + P 1591 Delta shutdown imminent.
Set if P1590 = 1 or 3. The autonomy is below the defined
threshold P1117 Battery stored energy time limit.
Enabled by Input Function 21 BCB. Battery Circuit Breaker
(BCB) is open.
Bypass ON command disabled (SW bypass inhibition to
avoid DC capacitor overcurrent. Detected on DIC Inv.
when DC link higher than ([SQRT2 * Phase voltage RMS] 30V), delay 0.4 seconds).
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 57
Table 10All EXL S1 Events - Alarms (continued)
ComponentTypeText DisplayIDDescription
BypassAlarmBypass mode not auto21-018
BypassAlarmParallel Bypass Failure21-038Set when the input Bypass OK is set.
Charger/BoosterFaultBooster and Charger Desaturation33-060Charger and booster desaturation.
Charger/BoosterFaultCharger Temperature High33-070—
Charger/BoosterFaultCharger Temperature High33-071—
Charger/BoosterFaultTemp Probe Module B Broken33-072—
Charger/BoosterFaultCharger Desaturation33-073—
Charger/BoosterFaultBooster B Desaturation33-074—
Charger/BoosterFaultBooster and Charger B Desaturation33-075—
Charger/BoosterFaultFuse Blown Pos Pole33-076Positive line buck booster fuse is blown.
Charger/BoosterFaultFuse Blown Neg Pole33-077Negative line buck booster fuse is blown.
Charger/BoosterFaultFuse Blown Module B Pos Pole33-078Positive B line buck booster fuse blown.
BCB Control algorithm has detected an overcurrent condition.
BCB Open command issued.
Enabled by Input Function 22 BCB GND Fault. Battery ground
fault detector is tripped.
Output voltage is out of tolerance and the bypass input is
within tolerance (SW detected fault monitoring output
signals).
Set when the bypass static switch board is not installed
(i.e., bypass voltage < 170 V).
Set when temperature is greater then P 1152 value (see
Overload specification)
Buck booster temperature sensor fault SW detected; based
on M.I. value outside sensor limit interval -15°C < T< +150°C for
60 seconds (P 1780.6).
If the absolute value of the difference between primary and
secondary battery voltage acquisition is greater than a
predefined threshold, a fault is issued and the
Booster/charger is turned Off because the voltage
measurement is corrupted.
Set when DC voltage +/- is greater than the P753.i15
threshold.
The charger is switched Off due to an overvoltage on the
battery. The time until switch Off depends on the overvoltage
value.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 62
Table 11All EXL S1 Events - Faults (continued)
ComponentTypeText DisplayIDDescription
Charger/BoosterFaultFuse Blown Module B Neg Pole33-079Negative B line buck booster fuse is blown.
GeneralFaultIncorrect power class30-036—
GeneralFaultDSP Signal Hardware Failure30-049—
GeneralFaultDSP Signal Hardware Failure30-049—
GeneralFaultDSP Signal Hardware Failure30-049—
GeneralFaultDSAVE active30-053 —
GeneralFaultAmbient Sensor Broken30-059—
GeneralFaultParallel cable missing30-071—
GeneralFaultParallel timeout30-078—
GeneralFaultParallel Identification Error30-079—
GeneralFaultParallel impossible30-080—
GeneralFaultE.P.O.30-145—
GeneralFaultDSP ADC Serial Comm Failure30-163—
GeneralFaultDSP Signal Software Failure30-164—
GeneralFaultFast Desaturation30-178—
GeneralFaultHigh Ambient Temperature30-202—
GeneralFaultInput Contact Wiring Error30-203—
GeneralFaultSMPS DC Supply Failure30-216—
GeneralFaultSMPS Single AC Supply Failure30-217—
GeneralFaultSMPS Double AC Supply Failure30-218—
InverterFaultE.P.O.36-034—
InverterFaultOvertemperature36-035
InverterFaultOvertemperature36-036
InverterFaultOvertemperature36-038
InverterFaultOverload36-044
InverterFaultOverload36-045
InverterFaultOverload36-046Set when the RMS overload counter reaches the end.
InverterFaultDC Overvoltage36-047Set when DC voltage +/- is greater than P753.i15 threshold
InverterFaultOutput out of tolerance36-048
Set when the Phase U temperature is greater than the value
specified by P 152.
Set when the Phase V temperature is greater than the value
specified by P 152.
Set when the Phase W temperature is greater than the value
specified by P 152
Set if the inverter stops for DC bus undervoltage four times in
5 minutes.
Set when:
1. Current limit condition occurs at inverter start while the
output voltage is ramping up.
2. Current limit condition lasts more then 200 ms
3. Current limit condition set again after 2nd Dynamic line
Support
Set when
• output voltage filtered is above V Nominal + (P106.1 +
P107.1 + P118.0 + P105.0)
OR
• output voltage fast is above V Nominal + (P106.2 +
P118.8 + P105.0)
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 63
Table 11All EXL S1 Events - Faults (continued)
ComponentTypeText DisplayIDDescription
Set when
• output voltage filtered is below V Nominal - (P106.1 +
InverterFaultOutput out of tolerance36-049
InverterFaultOutput out of tolerance36-050—
InverterFaultOutput out of tolerance36-051—
InverterFaultOutput out of tolerance36-052—
InverterFaultOutput out of tolerance36-053—
InverterFaultOutput out of tolerance36-054—
InverterFaultInverter DC/AC desaturation36-055Desaturation Phase U (Group A)
InverterFaultInverter DC/AC desaturation36-056Desaturation Phase V (Group A)
InverterFaultInverter DC/AC desaturation36-057Desaturation Phase W (Group A)
InverterFaultDC Bus undervoltage36-059
InverterFaultFuse Blown Phase U-A36-080
InverterFaultFuse Blown Phase V-B36-081
InverterFaultFuse Blown Phase W-C36-082
InverterFaultTemp Probe Broken Phase U-A36-104
InverterFaultTemp Probe Broken Phase V-B36-105
InverterFaultTemp Probe Broken Phase W-C36-106
InverterFaultOvertemperature Choke Ph. U-A36-107
InverterFaultOvertemperature Choke Ph. V-B36-108
InverterFaultOvertemperature Choke Ph. W-C36-109
InverterFaultFuse Blown B Phase U-A36-122
InverterFaultFuse Blown B Phase V-B36-123
InverterFaultFuse Blown B Phase W-C36-124
InverterFaultOvertemperature36-125Inverter B overtemperature fault Phase U-A
InverterFaultOvertemperature36-126Inverter B overtemperature fault Phase V-B
P107.1)
OR
• output voltage fast is below V Nominal - (P106.2)
if (Udc < P135.i04) AND
• (rectifier mains within tolerance) AND
• (rectifier input breaker closed) AND
• (NO Test Mode) AND
• (NO HW-Init) AND
• (60-second delay expired)
Udc is DC Bus Voltage.
Set by M.I. Phase U XP21 pin 7 -8. Indicates output fuse
Phase U open.
Set by M.I. Phase V XP21 pin 7 -8. Indicates output fuse
Phase V open.
Set by M.I. Phase W XP21 pin 7 -8. Indicates output fuse
Phase W open.
Inverter temperature sensor fault SW detected; based on M.I.
value outside sensor limit interval -15°C < T< +150°C for
60 seconds (P 780.23).
Inverter temperature sensor fault SW detected; based on M.I.
value outside sensor limit interval -15°C < T< +150°C for
60 seconds (P 780.23).
Inverter temperature sensor fault SW detected; based on M.I.
value outside sensor limit interval -15°C < T< +150°C for
60 seconds (P 780.23).
Inverter filter overtemperature. Any of Thermal Switch “ALA”
(M.I. XP31 Pin 4-9) active.
Inverter filter overtemperature. Any of Thermal Switch “ALA”
(M.I. XP31 Pin 4-9) active
Inverter filter over-temperature. Any of Thermal Switch “ALA”
(M.I. XP31 Pin 4-9) active
Set by M.I. Phase U-B XP21 pin 7 -8. Indicates output fuse
Phase U is open.
Set by M.I. Phase V-B XP21 pin 7 -8. Indicates output fuse
Phase V is open.
Set by M.I. Phase W-B XP21 pin 7 -8. Indicates output fuse
Phase W is open.
Vertiv™|Liebert® EXL™ S1 Touchscreen Control User Manual | Rev. 1 | 12/2017 | 64
Table 11All EXL S1 Events - Faults (continued)
ComponentTypeText DisplayIDDescription
InverterFaultOvertemperature36-127Inverter B overtemperature fault Phase W-C
InverterFaultInverter DC/AC desaturation36-128Desaturation Phase U group B
InverterFaultInverter DC/AC desaturation36-129Desaturation Phase V group B
InverterFaultInverter DC/AC desaturation36-130Desaturation Phase W group B
Inverter temperature sensor fault SW detected; based on M.I.
InverterFaultTemp Probe B Broken Phase U-A36-131
InverterFaultTemp Probe B Broken Phase V-B36-132
InverterFaultTemp Probe B Broken Phase W-C36-133
InverterFaultOvertemperature Choke B Ph. U-A36-134
InverterFaultOvertemperature Choke B Ph. V-B36-135
InverterFaultOvertemperature Choke B Ph. W-C36-136
RectifierFaultE.P.O.32-024Depending on application: A02 stops rectifier
RectifierFaultRectifier precharge failure32-025DC bus under threshold P135.101
RectifierFaultRectifier precharge failure32-026DC bus under threshold P135.102
RectifierFaultRectifier precharge failure32-027KM1 feedback not OK.
RectifierFaultRectifier Temperature fault32-028
RectifierFaultRectifier Temperature fault32-029
RectifierFaultRectifier Temperature fault32-030
RectifierFaultRectifier DC Overvoltage32-031DC overvoltage.
RectifierFaultRectifier desaturation failure32-032Desaturation Phase U (group A)
RectifierFaultRectifier desaturation failure32-033Desaturation Phase V (group A)
RectifierFaultRectifier desaturation failure32-034Desaturation Phase W (group A)
Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners.
While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
This document may contain confidential and/or proprietary information of Liebert Corporation, and its receipt or possession does not convey
any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without
specific authorization from Liebert Corporation is strictly prohibited.
SL-26094_REV1_12-17
, 1050 Dearborn Drive, Columbus, OH, 43085, USA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.