The Highly Eicient Indirect
Evaporative Freecooling Unit
Liebert® EFC from 100 to 450 kW
Vertiv™ brings together hardware, software, analytics and ongoing services to ensure its
customers’ vital applications run continuously, perform optimally and grow with their
business needs.
Vertiv solves the most important challenges facing today’s data centers, communication networks and commercial and industrial
facilities with a portfolio of power, cooling and IT infrastructure solutions and services that extends from the cloud to the edge of
the network.
Headquartered in Columbus, Ohio, USA, Vertiv employs around 20,000 people and does business in more than 130 countries.
For more information, and for the latest news and content from Vertiv, visit Vertiv.com.
Liebert® EFC, the Highly Eicient Indirect Evaporative Freecooling Solution
The Liebert EFC is equipped with the most advanced industry technology. The system includes indirect air-to-air heat exchange
and evaporative cooling technology all in one footprint. The Liebert EFC is capable of reducing air temperatures by leveraging on
the evaporative cooling principle.
The process involves the evaporation of water which, as a consequence, cools the surrounding air. Through this technology, the
Liebert EFC can thus achieve pPUE levels of 1.03 ensuring top energy eiciency, as well as minimized operating costs.
Liebert EFC 300Liebert EFC 220Liebert EFC 320
Liebert EFC 400Liebert EFC 440
2
Optimized Water
Consumption
Data Center
Freefrom
Contaminations
1.03
Top Energy
Eiciency Levels
pPUE down to 1.03
<
Reduced Electrical
Infrastructure
$
Reduced
Capital Cost
Technical
Expertise
Supplying indirect freecooling for data center applications
via the evaporative technology.
3
Liebert® EFC from 100 to 450 kW
Liebert® EFC: Enhancing Data Center Eiciency
Evaporative Cooling
The highly eicient evaporative system
sprays water onto the heat exchanger to
enable cooling even at high ambient air
temperatures, without the need for
mechanical cooling.
Highly Eicient EC Fans
The new generation of fans installed in
the Liebert EFC dramatically reduce the
noise level and increase the overall
eiciency of the unit.
Reduced CO2 Emissions
At pPUE levels of 1.03, Liebert EFC
requires minimum power input
consequently reducing CO2 emissions.
Energy Eiciency
The evaporative cooling technology
enables Liebert EFC to reach pPUE
levels as low as 1.03.
Eurovent Certified Heat Exchanger
Eurovent certification guarantees that
Liebert EFC heat exchangers undergo
independent testing, thus delivering
rating accuracy and enhancing the unit's
reliability.
Freecooling
Evaporative cooling extends indirect
freecooling operation all year round.
Data Center Free from
Contaminations
The air-to-air heat exchanger separates
external and internal air, protecting the
data center air from bacterial
contamination, as well as other external
events such as fire and pollution.
Liebert® iCOM™
Liebert® iCOM™ Control ensures high level
management of the units to work together
as a single system, thus optimizing room
temperature and airflow.
Integrated Chilled Water Coil and
Direct Expansion System
These technologies ensure the unit's
operation even in climates characterized
by extreme humidity levels or severe
temperature peaks.
Partial Load Eiciency
New generation EC fans and integrated
digital scroll compressors contribute to
achieving the highest eiciency levels at
partial load.
4
The evaporative system has a dedicated internal pump that provides the water needed.
Water is sprayed through special nozzles onto the heat exchanger and evaporates, thus humidifying and cooling the air.
5
Liebert® EFC from 100 to 450 kW
Temperature (°C)
%
%
Absolute Humidity (g/kg)
3540455055
Ensuring Top Eiciency Levels through the Evaporative Principle
The Liebert® EFC combines the capabilities of freecooling and evaporative cooling principles in one single unit. It has been
specifically designed to select the most appropriate operating mode based on the external environment conditions,
leveraging both principles in order to deliver significant energy savings.
The use of the evaporative cooling,
hence using cold external air as a means
of cooling, allows freecooling operation
to be maximized and compressor-related
cooling to be reduced to a minimum,
thus optimizing operating costs.
30
25
The evaporative principle uses air to
absorb water that is sprayed through
special nozzles onto the heat exchanger.
Water evaporation, thus removes heat
from the air and cools the outside air
temperature.
30
Outside air consequently transitions
from Dry Bulb Temperature to Wet Bulb
Temperature (the graph below shows
the transition from 35°C to 20°C).
100% 90%80% 70%60%50%40%
30
20
15
10
25
20
15
10
5
5
-5
0
50-5-1010152025303540455055
( 35°C DB ; 20°C WB )
Psychrometric Chart for Sea-Level Elevation
20
10%
6
Where Indirect Evaporative Cooling Works
In order to optimize the overall system eiciency, the Liebert® EFC has been designed to change its operation mode
according to the external environment. When the external air is cold enough to allow freecooling, the unit works in dry
operation mode (winter operation mode).
When ambient temperatures are higher,
also external humidity determines unit
capacity and performances as the
evaporative eect is directly associated
to the external air capacity to absorb
water.
When the unit operates in environments
with higher temperature and lower
relative humidity (summer operation
mode), Liebert EFC works in evaporative
(wet) mode.
In climates featuring high levels of
humidity the unit may thus require the
integration of a Direct Expansion (DX)
system or the installation of a Chilled
Water (CW) coil (extreme operation
mo de).
DRY OPERATION
(Dry Bulb Temperature
<17°C -20°C)*
The unit can cool the data center
solely via the air-to-air heat
exchanger, thus using only cold
external air.
WET OPERATION
(Wet Bulb Temperature
<20°C - 22°C)*
The unit can leverage the
evaporative eect via humidification.
DX/CW
INTEGRATION
WET
DRY
OPERATION
Dry Bulb Temperature, °C
*Assumptions: data center 36°C 24° C - 100% of full load per unit (redundancy operation)
OPERATION
DX/CW
INTEGRATION
External humidity assumes a key role
in determining unit performances:
Moisture Content, kg/kg Dry Air
y At 24°C and 90% relative
humidity, the unit may require
DX/CW integration.
y At 35°C (higher temperature)
and 25% (lower relative
humidity), the unit can solely
operate with evaporative
cooling.
7
Liebert® EFC from 100 to 450 kW
DC HotReturn Air
DC Supply Air
Externel Air
ExhaustExternal Air
DC HotReturn Air
Externel Air
DC HotReturn Air
DC Supply Air
Externel Air
ExhaustExternal Air
Liebert® EFC Operation Modes In Detail
Winter
The use of the evaporative cooling,
hence using cold external air as a means
of cooling, allows freecooling operation
to be maximized and compressor-related
cooling to be reduced to a minimum,
thus optimizing operating costs.
DC Hot
Return Air
Externel Air
Exhaust
External Air
DC Supply Air
DRY OPERATION
Air-to-Air Heat Exchange
Without Spraying Water
Summer
During the warm season (summer
operation mode) the evaporative system
must run in order to saturate the air.
Thisenables the unit to cool the data
center air even with high external air
temperatures. By saturating the air, the
dry bulb temperature can be reduced.
Optional
In case of extreme external conditions,
a Direct Expansion (DX) system is
available to provide additional cooling.
As an alternative, the Chilled Water (CW)
coil can be installed. DX and CW
systems are sized to provide partial back
up for the overall cooling load and are
designed to provide maximum eiciency
with minimum energy consumption.
DC Hot
Return Air
Externel Air
DC Hot
Return Air
Externel Air
Exhaust
External Air
Exhaust
External Air
DC Supply Air
DC Supply Air
WET OPERATION
Air-to-Air Heat Exchange Via
the Spraying of Water to the
External Air Side
DX/CW INTEGRATION
External Air Is too Hot to
Achieve 100% Cooling with
Adiabatic, the DX Module Is
thus Integrated to Cover the
Missing Capacity
8
The State-of-the-Art Liebert® iCOM™ Control
50-5-1010152025303540455055
Temperature (°C) in the Data Center
100%90%80%70%60%50%40%
30%
20%
10%
5
10
15
20
25
30
Absolute Humidity (g/kg) in the Data Center
2004
ASHRAE
Recommended
2011
ASHRAE
Recommended
A1
A2
A3
A4
Precise, User-friendly Information at Unit Level
To guarantee ASHRAE
recommended guidelines even
at extreme conditions
y Extreme Winter Operation
(i.e.below-20°C) can cause the
unit's unrequired internal
dehumidification causing it to
exceed ASHRAE
recommended minimum
humidity. Liebert® EFC oers a
constant control of data center
air via its integrated Liebert®
iCOM™ control logic, ensuring
dew point temperature is lower
than heat exchanger surface
temperature, thus avoiding
unrequired dehumidification.
To provide precise temperature
and airflow control in front of
servers
yThe Vertiv SmartAisle™ control
logic embedded in the Liebert®
iCOM™ optimizes internal air
volumes and temperatures
according to specific server
needs. VertivSmartAisle logic
allows Liebert EFC to exactly
match the servers' airflow
needs, ensuring that not even
a single Watt is wasted in
moving or cooling unrequired
air.
To optimize water and
electricity costs with the Cost
Function software feature
yThe user friendly Liebert®
iCOM™ Control exploits the
management of energy and
water also at teamwork level.
The system collects
information from the dierent
units’ key parameters and
operating modes (dry, wet and
DX/CW) while taking into
account water and electricity
costs. The control predictively
calculates and then
implements the combination
which optimizes operating
costs.
Utmost Eiciency Even at the Data Center System Level
The Liebert® iCOM™ Control manages the operation of the Liebert EFC units, in order to ensure top reliability in all conditions.
Accessto the units installed in the data center, is granted through the Ethernet connection, that is capable of coordinating the
multiple on-site installations. The high-level supervision of multiple units allows these to work together as a single system, thus
optimizing overall system performance.
9
Liebert® EFC from 100 to 450 kW
High Flexibility Matching Customer Needs
The Liebert® EFC delivers substantial reductions and savings in terms of electrical infrastructure and equipment. With the
unit being installed externally, the available internal white space is maximized ensuring ease of system installation.
All of these features significantly reduce data center TCO.
Main Options AvailableBenefits
Water storage reduction
DX or CW coil for mechanical cooling integration
G4 or M5 data center air filterState-of-the-art filtration class
Low ambient kitTo avoid unrequired dehumidification at very low ambient temperatures
Automatic transfer switch with intelligent controllerDue to the communication with the unit control, all the electrical power data is monitored through the BMS
Dehumidification availability
Premium efficiency
Delivery temperature guaranteed also under the worst ambient conditions
UltraCapacitorControl always active even during a power failure
MonitoringIntegrated BMS interface (i.e. ModBus, Bacnet and SNMP)
Energy meter/water meterTo manage energy and water consumption, thus optimizing operating costs
Right and left versions available in both perimeter
and roof configurations
Perimeter ConfigurationRoof Configuration
To adapt to any data center layout
Multi-Storey Configuration
10
Annual Distribution of Operating Modes with Indirect Evaporative Freecooling
600
Hours per Year
Hours per Year
Hours per Year
Ambient Air Temperature
While respecting ASHRAE guidelines,
the Liebert® EFC unit can be installed
not only in cold climates, where the unit
can leverage on the dry operating mode,
but also in hotter ones (as shown in the
example below for Istanbul) where DX
operation is reduced to a minimum and
used only during extreme temperature
peaks that may be experienced
throughout the year. This results in
asignificant reduction in electrical
consumption possible even at full load
(reaching the highest possible savings at
partial loads).
The Liebert EFC Cost Function
optimizes running costs (water and
electricity), and according to the external
dry bulb and heat load, selects the most
convenient working mode (i.e. dry vs.
wet). With the same logic, the Cost
Function will also optimize the use of the
optional Direct Expansion (DX) mode.
550
500
450
400
350
300
250
200
150
100
50
0
-20-1001020304050
600
550
500
450
400
350
300
250
200
150
100
50
0
-20-1001020304050
600
550
500
450
400
350
300
250
200
150
100
50
0
-20-1001020304050
Ambient Air Temperature
Ambient Air Temperature
London
45% dry mode45% dry or wet mode
(cost function)
10% wet mode
Frankfurt
48% dry mode36% dry or wet mode
(cost function)
16% wet mode
Istanbul
31% dry mode33% dry or wet mode
(cost function)
34% wet mode
2% wet + DX mode
Technical Specifications
ModelEFC 220EFC 300EFC 320EFC 400EFC 440
Net Cooling Capacity 1kW203373385425418
FANSn°4+49+99+69+69+8
Maximum Airflow - Data Center Side
Max Wet Bulb - Adiabatic Effect Only
Max Wet Bulb - Adiabatic + DX Effect
Adiabaitic CapabilityHighHigh+MediumMediumHigh
DX Capability RatioHighMediumMediumHighHigh+
2
m3/h52.50097.000100.000110.000107.500
3
°C21,221,816,919,520,4
3
°C29,026,222,926,528,6
Dimensions
Lengthmm40004500365036504620
Depthmm23002900290034003400
Height mm40504700470047004600
1
Return air temperature: 36°C RH=25%; Supply air temperature: 24°C - considering maximum airflow condition below.
2
ESP = 0 Pa data center and process side.
3
Maximum wet bulb temperatures to provide the above net cooling capacities.
11
Liebert® EFC from 100 to 450 kW
Vertiv™ LIFE™ Services Remote Diagnostic and Preventive Monitoring
Vertiv's service program is designed to ensure that your critical power protection system is maintained in an optimum
state of readiness at all times.
The Vertiv™ LIFE™ Services Remote
Diagnostic and Preventive Monitoring
provides early warning of UPS conditions
and out of tolerances. This allows
eective proactive maintenance, fast
incident response and remote trouble
shooting, giving customers complete
security and peace of mind.
With Vertiv LIFE Services you will
benefit from:
Uptime Assurance
Constant monitoring of UPS parameters,
thus maximizing the system’s availability.
First Time Fix Rate
Pro-active monitoring and data
measuring ensure that when our
customer engineers are dispatched
on-site, they arrive prepared for first time
resolution.
Proactive Analysis
From Vertiv LIFE Services centers, our
experts proactively analyze the data and
trends of your equipment, to recommend
a ctions to ensure their best
performance.
Minimized Total Cost of Ownership
of Your Equipment
The continuous monitoring of all relevant
parameters in turn maximizes unit
performance, reduces on-site
maintenance and extends the life of
your equipment.
Fast Incident Response
Vertiv LIFE Services allows for
immediate definition of the best course
of action, as a result of the regular
communication between your Liebert® EFC unit and our Vertiv LIFE Services
centers.Reporting
You will receive a comprehensive report
detailing the working order of your
equipment and its operational
performance.
Reporting
You will receive a comprehensive report
detailing the working order of your
equipment and its operational
performance.
12
Customer Experience Center
Thermal Management
Vertiv’s Customer Experience Center
located in Tognana (Padova - Italy), is
specifically designed for customers to
interact with Thermal Management data
center technologies.
The center gives our customers the
unique opportunity to witness
pre-installation demonstrations, covering
technical performance, interoperability
and eiciency of Thermal Management
solutions under a broad range of real
field conditions.
Customers visiting the center may also
benefit from a comprehensive
consultation from our R&D, engineering
and application specialists.
Evaporative Cooling Validation Area
Our Thermal Management Customer
Experience Center features a dedicated
area to test the state-of-the-art Liebert®
EFC unit.
The scope of the Evaporative Cooling
Validation Area is to provide customers,
consultants and data center specialists
with the most complete testing area to
experience the capabilities of our
evaporative technology at peak
conditions.
Testing parameters include IT loads up
to450 kW and an airflow of up to
120,000 m3 per hour, replicating typical
peak conditions across the EMEA region,
and an exceptional performance
measurement accuracy within a +/- 5%
maximum tolerance and a +/- 2% airflow
tolerance. Airflow rate is also measured
at the outlet side using calibrated intake
nozzles in compliance with ANSI-AMCA
210/07 and ISO5801.
measurements are in line with the
metrological laboratories’ standards
(Accredia/EA/ILAC) and that our
equipment precision level is also
compliant with the European EN14511
standard.
Every customer visit is accompanied by
a complete final report which includes
each and every tested parameter.
Customers are guided through a firsthand experience with full transparency
and flexibility enabling them to achieve
the highest standards of technical
excellence.
All our measuring tools are also
periodically tested to adhere to the
current international quality procedure
ISO9001. This guarantees that all our
13
Liebert® EFC from 100 to 450 kW
Thermal Management Data Center Infrastructure for Small and Large Applications
Liebert® HPC
Wide range of high eiciency Freecooling Chillers
from 40 kW to 1600 kW
•Designed specifically for data center applications
and to work with Vertiv™ SmartAisle™
• Premium energy eiciency version
•Unique control capabilities with the Liebert® iCOM™
Control.
Liebert® HPM
Room cooling air
conditioners available
from 4 to 30 kW
Liebert® PDX
Liebert® PCW
Available from 5-220 kW
•Premium energy eiciency
•Eurovent certified
performance
•Unique control capabilities
with the Liebert® iCOM™
Control
• Liebert EconoPhase™
available for the direct
expansion system and inverter
driven compressors models.
Liebert® EFC
Indirect evaporative freecooling unit leveraging on
data center know-how. Available from 100 to 450 kW
• Unique control capabilities optimizing water and
energy costs
•Substantial reductions and savings in terms of
electrical infrastructure.
14
14
Liebert® AFC
The Adiabatic Freecooling Chiller available
from 500-1700 kW
•Integrated adiabatic pad system
•High freecooling capacity
• 100% compressor back up.
Service and Software
Solutions
Vertiv™ supports any application with
an extensive service oering
including installation, start-up,
commissioning, maintenance,
replacements, 24/7 remote
monitoring and diagnostics and
much more.
Our remote diagnostics and
preventive monitoring LIFE Service is
adding value providing actual
information to take decisions, as it
allows early detection of anomalies
and immediate reaction in case of
alarms.
Vertiv™ SmartAisle™
•Aisle containment
•Provides highest energy eiciency
•Works with any Liebert Thermal
•Management unit.
Liebert® HPW
High performance wall mount
outdoor package cooling system
from 5 to 5 kW.
Liebert® HPS
Split system from 5 to 4 kW
including an indoor evaporating
unit and an outdoor
compressorized condenser.
Liebert® HPF
Floor-mount package indoor
cooling system from 5 to 5 kW.