Vertiv Liebert APS UPS User Manual

Liebert® APS UPS
5kVA - 20kVA N+1
Flexible, redundant scalable UPS for room or row-based applications
A Scalable Power Solution for Dynamic Demands
Pay as you grow design of the Liebert® APS simplifies the capacity planning process and provides budget flexibility. FlexPower™ assemblies and battery modules allow for rapid deployment of capacity and runtime upgrades.
Built-in Redundancy and Modular Design provide Maximum Availability
Provide mission-critical availability and reduce costs while maintaining future flexibility with the Liebert APS uninterruptible power supply (UPS), a modular power solution for 5-20kVA N+1 applications.
y High overload capabilities up to 200%
allow the unit to provide conditioned power during temporary overloads without transfers to/from bypass power
y Modular batteries, controls, and power
components help reduce maintenance costs with user replacement
y Scalability allows for the cost-eectively
addition of power capacity or battery modules as needed
y Module-level, built-in redundancy
eliminates the expense of purchasing and planning for additional cabinets
y Integral battery monitoring with
temperature-compensated charging prolongs battery life and helps reduce replacement costs
y Pre-installed IS-UNITY-DP card
provides remote management and environmental monitoring support
Ultimate Flexibility and Serviceability
Your business depends on digital continuity, and along with the following benefits, the Liebert® APS UPS ensures your critical IT applications are protected from power disruptions, fluctuations, and outages:
y Hot-swappable FlexPower™ assemblies and battery modules allow for quick
and easy capacity and runtime changes without powering down the UPS or connected equipment
y Ensured system integrity due to fault-tolerant design that enable the
power, battery, and control modules to take themselves oline in the event of a problem
y Improved availability and reliability with internal wrap-around
maintenance bypass
y Two-year hassle-free factory warranty program eliminates unexpected repair
or replacement costs for added peace of mind
FlexPower™ core hardware assemblies
Delivers quick and easy capacity changes in 5kVA/4.5kW
increments, without powering down.
Hot-swappable FlexPower™ assemblies
and battery modules
May be added without powering down connected equipment.
2
Reliability and Serviceability
Flexibility
Your business depends on the data center and the IT network to run. With the Liebert® APS UPS solution, you get peace of mind that your critical IT functions – and your business – will be available and running as expected through power disruptions, fluctuations and outages.
y Internal redundancy capability
enhances reliability and provides multiple layers of protection.
y No single point of failure - Full
redundant design allows the critical load to run on conditioned power if there is a failure of any component.
y Configurable design provides
your desired level of capacity and redundancy.
y Fault-tolerant design, enables the
power, battery and control modules to take themselves oline if there is a problem, without sacrificing overall system integrity.
y Superior overload capabilities,
able to provide conditioned power to temporary overloads without transfers to/from bypass power.
The Liebert APS UPS helps you enhance flexibility to stay ready for what’s next:
y Capacity on demand with FlexPower™ core modules delivers capacity changes in
5 kVA/4.5 kW increments - without powering down.
y More real kW - 0.9 power factor provides more real power to support the I.T. load
than many other solutions in this size range.
y Isolated and non-isolated models to provide the protection and eiciency
you need.
y Installation Flexibility – use on raised floors, non-raised or in rack.
y Large input voltage window, which minimizes transfer to battery and increases
battery life; low line transfer can range down to 110V.
y Power output distribution PODs create the right distribution options to meet
application requirements.
Manageability
y IS-UNITY-DP factory-installed in
each Liebert APS to provide LIFE™ Services, Web Interface, SNMP, Modbus IP / RTU, BACNet IP / MSTP, & Envrionmental Sensor support. (temperature, humidity, contact closure, leak detection and more).
y Power Management Software,
Free downloads are available for
Trellis™ Power Insight.
y Optional External Maintenance
Bypass in separate assembly provide higher reliability and availability.
y Trellis™ platform connectivity, so the
Liebert APS can easily be integrated with this robust, real-time data center optimization solution.
3
Standard Configurations
The Liebert® APS is a modular UPS System. Standard configurations shown here include the all the power and battery modules required, but the modules ship separately on most models. The Liebert APS is also a build-to-order product that can be fully-configured at the factory. For configure-to-order solutions, please contact your local Vertiv oice and a product expert will guide you through this process.
20 kVA, 16 Bay, Xfmr-free
17.3 W x 33.5 D x 38.2 H inches (440 W x 850 D x 970 H mm)
15 kVA, 10 Bay, Xfmr-free
17.3 W x 31.5 D x 27.4 H inches (440 W x 800 D x 695 H mm)
APS Series
AS3 208V, 3-Wire (L-L-G) 208/120V 15kVA N+1
AS4 208V, 3-Wire (L-L-G) 208/120V 20kVA N+1
AS5 208/120V
AS6 208/120V
Input Output
208/120V 15kVA N+1
4-Wire (L-L-N-G)
208/120V 20kVA N+1
4-Wire (L-L-N-G)
Max Capacity
AS3 & AS4 Series
15 kVA, 12 Bay, Xfmr-based
17.3 W x 31.5 D x 41.7 H inches
(440 W x 800 D x 1060 H mm)
20 kVA, 16 Bay, Xfmr-based
17.3 W x 33.5 D x 48.8 H inches (440 W x 850 D x 1240 H mm)
FlexPower™ Module Options
FlexPower™ Modules allow for quick and easy power capacity upgrades to Liebert APS systems, in 5kVA / 4.5kW increments. The modules are hot-swappable, and can be installed without taking the Liebert APS unit oline.
Model Number Description
APS5KPWRMOD1 5kVA/4.5kW Power Module for AS5 & AS6 series Liebert APS systems
APS5KPWRMOD2 5kVA/4.5kW Power Module for AS1, AS2, AS3, and AS4 series Liebert APS systems
Battery and Battery Charger Modules
What's Included
y UPS
AS5 & AS6 Series
y Power and Battery Modules
y Quick Start Guide
y UPS with quick start guide
y IS-UNITY-DP Networking Card
y Pre-installed casters and
leveling feet
y Removable LCD Display
4
Liebert® APS Battery Module
APSBATMODCU includes 2 battery modules, or 1 complete battery string. each complete string uses 2 bays in the Liebert APS.
Liebert® APS Charger Module
10A battery charger that operates in parallel with the chargers integrated in each Power module. To increase runtime in the Liebert APS, this 10A charger should be used when battery string to power module ratio is greater than 3:1.
Standard Configuration Selection Guide
Model Number Power Capacity
AS3A0NCUGNNXLKB* 5kVA / 4.5kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 14 AS3A0NCVGNNXLKB 5kVA / 4.5kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 15 38 AS3B0NCVGNNXLKB 10kVA / 9.0kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 15 AS3B0NCYGNNXLKB 10kVA / 9.0kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 21 51 AS3C0NCWGNNXLKB 15kVA / 13.5kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 15 AS3C0NCXGNNXLKB 15kVA / 13.5kW 15 / 13.5 N+1 Hardwire (L-L-G) Hardwire Optional PODs 8.0 22 AS4A0NCUGNNXLKB* 5kVA / 4.5kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 14 AS4A0NCVGNNXLKB 5kVA / 4.5kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 15 37 AS4B0NCVGNNXLKB 10kVA / 9.0kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 15 AS4B0NCYGNNXLKB 10kVA / 9.0kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 21 51 AS4C0NCWGNNXLKB 15kVA / 13.5kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 15 AS4C0NCJGNNXLKB 15kVA / 13.5kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 15 39 AS4D0NCXGNNXLKB 20kVA / 18.0kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 5.0 15 AS4D0NCJGNNXLKB 20kVA / 18.0kW 20 / 18.0 N+1 Hardwire (L-L-G) Hardwire Optional PODs 10 26 AS5A0NCUGNNXLKB* 5kVA / 4.5kW 15 / 13.5 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 15 AS5A0NCVGNNXLKB 5kVA / 4.5kW 15 / 13.5 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 15 40 AS5B0NCVGNNXLKB 10kVA / 9.0kW 15 / 13.5 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 15 AS5B0NCXGNNXLKB 10kVA / 9.0kW 15 / 13.5 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 16 41 AS5C0NCWGNNXLKB 15kVA / 13.5kW 15 / 13.5 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 16 AS6A0NCUGNNXLKB* 5kVA / 4.5kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 15 AS6A0NCVGNNXLKB 5kVA / 4.5kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 15 40 AS6B0NCVGNNXLKB 10kVA / 9.0kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 16 AS6B0NCWGNNXLKB 10kVA / 9.0kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 10 27 AS6B0NCYGNNXLKB 10kVA / 9.0kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 21 53 AS6C0NCWGNNXLKB 15kVA / 13.5kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 16 AS6C0NCJGNNXLKB 15kVA / 13.5kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 16 41 AS6D0NCXGNNXLKB 20kVA / 18.0kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 5.0 16 AS6D0NCJGNNXLKB 20kVA / 18.0kW 20 / 18.0 N+1 Hardwire (L-L-N-G) Hardwire Optional PODs 10 27
Scalable to
(kVA/kW)
Input
Connection
Output
Connection
Full-Load
Runtime (min)
Half-Load
Runtime (min)
Notes
1. Models denoted with * will ship with power and battery modules pre-installed. All other models will include one power and battery module pre-installed, with additional modules shipped separately.
2. Models 10kVA and up can be configured to N+1 redundancy with a 5kVA/4.5kW De-rate to unit capacity.
3. For applications requiring runtime exceeding the values within this table, please contact your local Vertiv office for a configure-to-order solution.
Power Output Distribution (POD) Options
Liebert® APS AS3 and AS5 Series can support 1 POD, Liebert® APS AS4 and AS6 Series can support up to 2 PODs. Each POD provides multiple output receptacles and is designed for easy installation.
POD Model Number Output Connections
PD2-101 (8) 5-15/20R T-slot, (2) L6-30R
PD2-102 (4) 5-15/20R T-slot, (4) L6-20R
PD2-103 (4) 5-15/20R T-slot, (4) L6-30R
PD2-104 (4) 5-15/20R T-slot, (2) L6-30R, (2) L6-20R
PD2-105 (4) 5-15/20R T-slot, (2) L5-30R, (2) L5-20R
PD2-106 (4) L5-20R, (4) L6-20R
PD2-107 (4) L5-20R, (4) 5-15/20R T-slot
PD2-108 (2) L6-30R, (2) L6-20R
PD2-109 (2) L14-30R
PD2-200 (4) IEC320-C19, (4) IEC320-C13
PD2-201 (2) IEC320-C19, (8) IEC320-C13
PD2-202 (12) IEC320-C13
PD2-204 (4) IEC320-C13, (2) IEC309-32A
5
Intellislot Card Options
Each Liebert® APS UPS comes with the IS-UNITY-DP card pre-installed, with 2 additional empty Intellislot ports, accepting any of the below networking cards.
Model Number Description
IS-UNITY-SNMP
IS-UNITY-DP Network communications and Environmental Sensor Support
IS-RELAY Provides relay signals for connection to customer’s hardwire terminal block
SNMP Network communications for interfacing to Network and Building Management Systems
Mounting Kit Options
Each Liebert APS UPS include factory-installed casters and levelling feet. They can also be rack mounted with the optional rack mounting kit. The rack mount kit comes with ramps to allow the Liebert APS to roll into the bottom of the rack.
Model Number Application Model(s) Supported Style Description
APSRACKKIT 4-Post Rack AS3, AS5, and, AS6 Series APS Shelf & Bracket
Includes all necessary hardware to mount the Liebert APS UPS in a 600mm wide 4-Post rack. Included with the kit is a shelf, two sets of ramps, rackmount brackets, and a bezel.
Power Startup Service - Power and Battery modules installation and Start-up Only
y Expands the Liebert APS warranty to
include on-site parts and labor for the full two-year warranty period
y Startup of new UPS performed by Vertiv
factory trained technician
y Services performed Monday thru Friday
8-5 pm or 7 X 24, excluding national holidays within the 48 contiguous states and Hawaii
y The site trip includes the following
services for each UPS system:
• UPS integration (frame + power module(s) + battery module(s))
• Non powered inspection
• UPS electrical and operational checkout
• Full parts and labor for any work required on the UPS
Installation and Startup Only Standard Plus
Equipment Model / Type M-F, 8-5 7x24 M-F, 8-5 7x24
All Liebert® APS UPS Models SUAPSXXMF SUAPSXX24 SUPAPSXXMF SUPAPSXX24
• Customer operation training at time of start-up
NOTE: UPS frame must be installed and hardwired by customer with a certified electrician.
y Start-up Plus: Adds 1 full Preventive
Maintenance (PM) visit during the standard warranty period
Power Assurance Package Summary — 5-year On-site Emergency Response
y Full-service five (5) year contract term
commencing upon the start-up date
y On Site Service Support
y Includes all above "Power Startup
Services" and 5-year On-site services
y Services performed 7 X 24,
excluding national holidays within the 48 contiguous states
y One Preventive Maintenance
visit after 3rd year scheduled by the customer (excluding national holidays)
y 100% parts coverage, including internal
batteries, POD and web card
y 100% labor and travel coverage
7 days/week, 24 hours/day
y 24-Hour Customer Resolution
Center via 1-800-LIEBERT
y Access to Customer Services
Network portal
Power Assurance Package Options
LIFE™ Services includes above plus:
y Continuous Monitoring, Expert
Analysis, and Proactive Response
6
Bundled Start-up Service AND 5-Year On-site Emergency Response
Equipment Model / Type Part Number Part Number
Liebert® APS AS3 & AS5 Series PAPAPS-15K PAPAPS-15KLF
Liebert® APS AS4 & AS6 Series PAPAPS-20K PAPAPS-20KLF
Standard With LIFE Services
Liebert® APS UPS Technical Specifications
AS3 Series AS4 Series AS5 Series AS6 Series
Description 12-Bay, w/ Xfmr 16-Bay, w/ Xfmr 10-Bay, Transformer-free 16-Bay, Transformer-free
Frame Rating 15 kVA / 13.5 kW 20 kVA / 18 kW 15 kVA / 13.5 kW 20 kVA / 18kW
Mechanical W x D X H
Dimension mm (in)
440 x 800 x 1060 (17 x 32 x 42)
Max Weight (frame fully populated)
Unit weight kg (lbs) 360.6 (795) 417.3 (920) 256.3 (565) 317.5 (700)
Shipping weight kg (lbs) 378.7 (835) 435.4 (960) 274.4 (605) 335.7 (740)
Environmental
Operating temperature 0°C - 40°C (32°F - 104°F)
Relative humidity 0 - 95%, non-condensing
Altitude 3,000m (10,000ft) @ 25°C (77°F)
Efficiency 88.5 AC - 89.9 AC 88.6 AC - 89.7 AC 90.4 AC - 91.0 AC 90.0 AC - 91.0 AC
Nominal heat dissipation 5528 BTU/Hr (max) 7965 BTU/Hr (max) 4904 BTU/Hr (max) 6768 BTU/Hr (max)
Input Data
Default Input Voltage 208 VAC 208 VAC 208/120 VAC 208/120 VAC
Configurable Input Voltage 200/208/220/230/240 VAC 200/208/220/230/240 VAC
Input Power Factor > 0.99 > 0.99 > 0.99 > 0.99
Input frequency range 40 Hz to 70 Hz auto-sensing
Output Data
Default Output Voltage 120/208VAC 120/208VAC 120/208VAC 120/208VAC
Configurable Output Voltage
Voltage regulation ±3% ±3% ±3% ±3%
Voltage stability (100% step load)
Voltage Recovery time
Output frequency 60Hz default; 50/60Hz user-configurable
Output overload capability < 104% continuous; 105% - 130% for 1 min; 131% - 150% for 10 sec; 151% - 200% for 1 sec; > 201% for 250 msec
100/100/173/200, 110/110/190/220, 115/115/199/230, 120/120/208/240 VAC
±7% ±7% ±7% ±7%
≤ 3%, linear load ≤ 7%, non-linear load
Compliance
Conducted and radiated EMC levels IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
Compliant safety standards IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22.2 No. 107.1 UL 1778 4th Ed and CSA 22.2 No. 107.1
Compliant immunity standards IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Environmental WEEE and ROHS2 (6 by 6), REACH Compliant
Battery Module
Battery capacity 36W @ 15min-rate to 1.67V per cell @ 25°C (77°F)
Backup time (full load) 5hrs (for non-redundant system which has equal number of battery strings and power modules)
Maximum charge current (full load) Power module internal charger: 1.8A / Charger module: 10A
Nominal voltage 144 VDC 144 VDC 144 VDC 144 VDC
Recharge time < 5 to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
440 x 850 x 1240 (17 x 34 x 49)
100/100/173/200, 110/110/190/220, 115/115/199/230, 120/120/208/240 VAC
≤ 3%, linear load ≤ 7%, non-linear load
440 x 800x 695 (17 x 32 x 27)
200/100, 208/120, 220/110, 230/115, 240/120 VAC
200/100, 208/120, 220/110, 230/115, 240/120 VAC
≤ 3%, linear load ≤ 5%, non-linear load
440 x 850 x 970 (17 x 34 x 38)
200/100, 208/120, 220/110, 230/115, 240/120 VAC
200/100, 208/120, 220/110, 230/115, 240/120 VAC
≤ 3%, linear load ≤ 5%, non-linear load
Build-to-order systems are available, please contact your local Vertiv office for details.
7
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv G roup Corp. All right s reserved. Vertiv ™ and the Vertiv logo are tr ademarks or regis tered trademarks of Ver tiv Group Corp. All o ther names and log os referred to are trade n ames, trademar ks or registered tra demarks of their res pective owners . While every precauti on has been taken to en sure accuracy and c ompleteness he re, Vertiv Group Cor p. assumes no resp onsibility, and dis claims all liabili ty, for damages resu lting from use of this inf ormation or for any erro rs or omissions . Specificatio ns, rebates and oth er promotional oers are su bject to change at Ver tiv’s sole discret ion upon notice.
SL-55000 (R06/20)