Vertiv Liebert APS series Installer And User Manual

Liebert® APS™
5 – 20kVA Modular UPS
Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/
TABLE OF CONTENTS
2 Product Introduction 11
2.1 System Description 11
2.2 Features 16
2.3 Major Components 16
2.3.1 UPS Frame 17
2.3.2 User-Interface Module 17
2.3.3 System-Control Module and System-Monitor Module 18
2.3.4 Power Module 19
2.3.5 Battery Module 19
2.3.6 Charger Module 20
2.3.7 External Battery Cabinet (EBC) 20
2.4 Operating Principle 21
2.5 Operating Modes 22
2.5.1 Normal Mode 22
2.5.2 Backup Mode 22
2.5.3 Auto Restart Mode 22
2.5.4 Bypass Mode 22
3 Installation 23
3.1 Unpacking Inspection 23
3.2 Installation Environment 23
3.3 Installation Tools 23
3.3.1 Installation Site Considerations and Clearances 23
3.4 Removing the UPS from the Pallet 23
3.5 Installing the UPS 24
3.5.1 Tower Installation 25
3.5.2 Rack Installation 26
3.6 Installing Modules 29
3.6.1 Installing Power, Battery and Charger Modules 29
3.6.2 Installing System-Control andSystem-MonitorModules 31
3.7 Cable Connections 32
3.7.1 Connecting Cables on a Transformer-free UPS 32
3.7.2 Connecting Cables on a Transformer-Based UPS 36
3.7.3 Connecting Cables on a Transformer-free UPS with Dual Inverter Frames 41
3.8 Connecting an External Battery Cabinet 44
3.9 Connecting Integrated Power Output Distribution (POD) 47
3.10 Commissioning/Startup Procedures 48
3.10.1 Checks before Commissioning/Start-up 48
3.10.2 Commissioning/Start-up with AC Power Available (Normal-mode Operation) 48
3.10.3 Commissioning/Startup without AC Power Available (Battery-mode Operation) 49
Vertiv | Liebert® APS™ Installer/User Guide | 3
4 Communication 51
4.1 Liebert IntelliSlot Ports 51
4.1.1 Liebert IntelliSlot Unity Cards 51
4.1.2 Liebert IntelliSlot Dry-contact Card (IS-RELAY) 52
4.1.3 Liebert IntelliSlot MultiPort Card (IS-MULTIPORT) 52
4.1.4 Liebert IntelliSlot EBC Card 52
4.2 Dry-contact Ports 52
4.2.1 Battery-mode Dry Contact 52
4.2.2 Low Battery Dry Contact 53
4.2.3 Any Mode Shut Down 53
4.2.4 Battery Mode Shut Down 53
4.3 REPO (Remote Emergency Power Off) 53
4.4 Long-run-time (LRT) Battery-temperature-probe Terminals 54
4.5 USB Port 55
4.6 Liebert MultiLink® 55
4.7 LCD Port 55
5 Operation and Display Panel 57
5.1 Mimic LEDs 57
5.2 Audible Alarms 58
5.2.1 Control Buttons 58
5.3 LCD Screen and Menu Buttons 59
5.3.1 Start-up Screen 59
5.3.2 Main Screen 59
5.3.3 Default Screen/Screen Saver 65
5.3.4 Screen Views 65
5.3.5 Entering a Password to Edit Settings 67
5.3.6 Editing Parameter Settings 67
5.3.7 Prompt Window 67
6 Troubleshooting 69
6.1 Active Alarms 69
6.2 Module Troubleshooting 72
6.3 Module Replacement 72
6.3.1 Removing Power, Battery and Charger Modules 72
6.3.2 Removing System-Control andSystem-MonitorModules 73
6.3.3 Replacing the User Interface Module 75
7 Maintenance 77
7.1 Proper Care 77
7.2 Scheduled Maintenance 77
7.3 Cleaning Fan Filters 77
7.3.1 Accessing the Top Filter 77
7.3.2 Accessing the Bezel Filter 78
7.3.3 Accessing the Bottom Fan Filter 79
Vertiv | Liebert® APS™ Installer/User Guide | 4
8 Specifications 81
8.1 Estimated Battery Run Times: Model-number Digits 1-3 = AS1 or ASA 85
8.2 Estimated Battery Run Times: Model-number Digits 1to3 = AS2 or ASB 89
8.3 Estimated Battery Run Times: Model-number Digits 1to3 = AS3 or ASC 93
8.4 Estimated Battery Run Times: Model-number Digits 1to3 = AS4 or ASD 97
8.5 Estimated Battery Run Times: Model-number Digits 1-3 = AS5 or ASE 101
8.6 Estimated Battery Run Times: Model-number Digits 1-3 = AS6 or ASF 105
Vertiv | Liebert® APS™ Installer/User Guide | 5
Vertiv | Liebert® APS™ Installer/User Guide | 6

1 IMPORTANT SAFETY PRECAUTIONS

Save These Instructions
This manual contains important safety instructions. Read all safety, installation and operating instructions before operating the Liebert APS modular UPS system. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Individuals must fully understand this equipment to install and operate it.
The Liebert APS is designed for commercial/industrial use only. It is not intended for use with life-support or other designated critical devices. Maximum load must not exceed that shown on the rating label. Install and operate the unit only in a clean indoor environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances. The Liebert APS contains no user-serviceable parts. Refer all faults to your local dealer, local Vertiv™ representative or Vertiv™ Technical Support.
The Liebert APS UPS system is designed for use on a properly earthed (grounded) “TN” electrical supply. The system must be installed by qualified personnel. A qualified electrician must review and approve customer supplied wiring, circuit breakers, and intended loads and verify correct input, output, and earth connections to ensure compliance with the technical standards and local electrical codes of practice.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery can present a risk of electrical shock and high short-circuit current.
The following precautions must be observed before replacing the battery pack:
Wear rubber gloves and boots
Remove rings, watches and other metal objects.
Use tools with insulated handles.
Do not lay tools or other metal objects on the batteries.
If the battery kit is damaged in any way or shows signs of leakage, contact your local Vertiv™ representative immediately.
Do not dispose of batteries in a fire. The batteries may explode.
Handle, transport and recycle batteries in accordance with local regulations.
The Liebert APS is designed and manufactured to ensure personal safety, but improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:
Turn Off and unplug the Liebert APS before cleaning it.
Clean the unit with a dry cloth. Do not use liquid or aerosol cleaners.
Never block or insert any objects into the ventilation holes or other openings of the Liebert APS.
Do not place the Liebert APS power cord where it might be damaged.
This UPS contains no user-serviceable parts except for the user-replaceable module assemblies. The UPS On/Off push button does not electrically isolate internal parts.
All service and maintenance operations must be performed by properly trained and qualified personnel. Under no circumstances should unqualified or unauthorized personnel attempt to gain access to the internal portions of the Liebert APS.
Vertiv | Liebert® APS™ Installer/User Guide | 7
ELECTROMAGNETIC COMPATIBILITY—The Liebert APS complies with the limits of Category C2, pursuant to IEC/EN/AS 62040-2, and for a Class A digital device, pursuant to Part 15 of FCC rules. Operation is subject to the following conditions:
The output cables must be no longer than 10m (32ft).
This device may not cause harmful interference.
This device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
The Liebert APS complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Vertiv™.
Operate the unit in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
Do not continue to use the Liebert APS if the front panel indications are not in accordance with these operating instructions or the performance alters in use. Refer all faults to your Vertiv™ representative or Technical Support.
Servicing of batteries must be performed or supervised by properly-trained and qualified personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the Liebert APS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half-wave rectification.
Storing magnetic media on top of the Liebert APS may result in data loss or corruption.
Turn Off and isolate the Liebert APS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.
Vertiv | Liebert® APS™ Installer/User Guide | 8
Information for the Protection of the Environment
UPS SERVICING—This unit makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/CE.
The symbol at right is placed on this product to encourage recycling wherever possible. Recycle this product through a recycling facility at the end of its service life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).
For information regarding the disposing of this equipment, visit www.VertivCo.com or contact Vertiv™ technical support. Refer to the inside front cover of this manual for contact information.
For information regarding the scrapping of this equipment, please browse
h t t p s://www.vertiv co.com / e n -em e a / (“Products session” or “Contact us” session) or call our worldwide
technical support.
Toll Free: 00 80011554499
Toll Number Based in Italy: +39 0298250222
Table 1.1 Glossary of Symbols
SYMBOL  DESCRIPTION SYMBOL DESCRIPTION
Risk of electrical shock Recycle
Indicates caution f ollowed by important instruct ions Equipment grounding conductor
AC input Bonded to ground
AC output Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery DC voltage
Toggle between Onand Off Stand-by
Vertiv | Liebert® APS™ Installer/User Guide | 9
This page intentionally left blank.
Vertiv | Liebert® APS™ Installer/User Guide | 10

2 PRODUCT INTRODUCTION

To ensure proper installation and operation of this unit, please read this manual thoroughly.
The installation must be completed by trained professionals and follow all local codes. General operation of the units can be conducted without any specialized training.

2.1 System Description

The Liebert APS power system is a modular UPS that provides high reliability. It is intended for use with workstations, servers, networks, telecoms and other sensitive electronic equipment. It provides continuous, high-quality AC power to your equipment, protecting it from any power disturbance due to blackouts, brownouts, surges or noise interference.
The Liebert APS UPS is an easily adaptable UPS system. By installing additional power or battery modules, you can expand your current system capacity, extend your back-up runtime, or provide redundancy. The user interface lets you configure the operation according to application requirements. It also informs you of the status of the UPS and keeps a log of events.
The Liebert APS series UPS contains both transformer-free and transformer-based UPS frames. The use of the transformer-free or transformer-based frames depends on the specific application requirements. The appearance of the different frames is shown in Figure 2.1 on the next page through Figure 2.4 on page15.
Table 2.1 Frame designation
UPS MODEL NUMBER DIGITS 1- 3 FRAME TYPE FRAME RATING
AS1 or ASA or AS5 or ASE 10 Bay Transformer-free 15 kVA redundant
AS2 or ASB or AS6 or ASF 16 Bay Transformer-free 20 kVA redundant
AS3 or ASC 12 Bay Transformer-based 15 kVA redundant
AS4 or ASD 16 Bay Transformer-based 20 kVA redundant
Vertiv | Liebert® APS™ Installer/User Guide | 11
Figure 2.1 16-bay transformer-free UPS
ITEM DESCRIPTION ITEM DESCRIPTION
1 User-interface module 8 System-enable s witch
2 System-control module (under cover) 9 Power input andoutput terminals
3 Bays for batt ery modules 10 Output breaker
4 Bays for power, charger, or battery modules 11 External-batter-cabinet connector
5 Input breaker (under cover) 12 PODports
6 Manual bypass breaker (under cover) 13 USB port
7 Liebert IntelliSlot ports 14 Dry contacts and REPO connections
Vertiv | Liebert® APS™ Installer/User Guide | 12
Figure 2.2 10-bay transformer-free UPS
ITEM DESCRIPTION ITEM DESCRIPTION
1 Front view with bezels removed 9 Liebert IntelliSlot ports
2 Rear v iew 10 System-enable switch
3 User-interface module 11 Output breaker
4 System-control module (under cover) 12 External-batter-cabinet connector
5 Bays for batt ery modules 13 PODports
6 Bays for power, charger, or battery modules 14 USB port
7 Input breaker (under cover) 15 Dry contacts and REPO connections
8 Manual bypass breaker (under cover)
Vertiv | Liebert® APS™ Installer/User Guide | 13
Figure 2.3 12-bay transformer-based UPS
ITEM DESCRIPTION ITEM DESCRIPTION
1 Front view with bezels removed 10 System-enable s witch
2 Rear v iew 11 External-batter-cabinet connector
3 User-interface module 12 Input breaker
4 System-control module (under cover) 13 Power input andoutput terminals
5 Fans 14 Output breaker
6 Manual bypass breaker 15 PODports
7 Bays for batt ery modules 16 USB port
8 Bays for power, charger, or battery modules 17 Dry contacts and REPO connections
9 LiebertIntelliSlot ports
Vertiv | Liebert® APS™ Installer/User Guide | 14
Figure 2.4 16-bay transformer-based UPS
ITEM DESCRIPTION ITEM DESCRIPTION
1 Front view with bezels removed 10 System-enable s witch
2 Rear v iew 11 External-batter-cabinet connector
3 User-interface module 12 Input breaker
4 System-control module (under cover) 13 Power input andoutput terminals
5 Fans 14 Output breaker
6 Manual bypass breaker 15 PODports
7 Bays for batt ery modules 16 USB port
8 Bays for power, charger, or battery modules 17 Dry contacts and REPO connections
9 Liebert IntelliSlot ports
Vertiv | Liebert® APS™ Installer/User Guide | 15

2.2 Features

Flexible extension of capacity, up to 15 or 20kVA modular power, depending upon frame rating
N + 1 redundancy, improving availability
Modular design, modules hot-swappable by user
Intelligent battery management
External large batteries can be connected
Internal automatic and manual bypass
Transformer-based UPS frames provide output isolation transformer
Optional 10-A battery charger module
Continuous system monitoring
User-friendly interface with audible alarms and event logs
Supporting hot-pluggable and online update
Compatible with backup generators
Standard Components
UPS frame
User-interface module for comprehensive user indications and programmable controls
System-control modules and system-monitor module for system monitoring and communications
Power modules for power conditioning
Battery modules for back-up power
Charger module option for charging batteries and long run-time applications
External battery cabinet prolongs system run time
Communications
Dry contacts
Liebert IntelliSlot communication ports
USB port

2.3 Major Components

This section provides a general description of each component and its functions. Please review this section carefully, as it will give you a better understanding of how the UPS operates.

2.3.1 UPS Frame

All UPS components are located in the Liebert APS frame. The front of the UPS consists of a series of plastic bezels. Grasp the bezels from the sides and pull straight out to remove the bezel and reveal the battery/power-module bays. The standard-model frame provides cooling fans and a manual-bypass breaker on the top. The transformer-model frame provides a manual-bypass breaker on its bottom and fans on both top and bottom. The user-interface module is located above the power/battery-module bays for easy access, operation and for viewing UPS operating information. On the lower-right of the user­interface module are the system-control module bays.The UPS frames are shown in Figure 2.5 below.
NOTE: In the figure, the power module and battery module are extended for illustration purposes only. Extending more than one module at a time could cause the unit to tip over.
Vertiv | Liebert® APS™ Installer/User Guide | 16
Figure 2.5 Example UPS frames with bezels removed
ITEM DESCRIPTION ITEM DESC RIPTION
1 16-bay, transformer-free UPS 4 Manualbypass breaker
2 16-bay, transformer-based UPS 5 Fans
3 Fan, behind display bracket

2.3.2 User-Interface Module

The user-interface module, shown in Figure 2.6 on the next page,is the primary source of communication between the UPS and the user. The user interface module lets you:
View the UPS status
Configure the system
Review the event log
Silence the audible alarm
Refer to Operation and Display Panel on page 57 for details on operating the user interface module.
Vertiv | Liebert® APS™ Installer/User Guide | 17
Figure 2.6 User-interface module

2.3.3 System-Control Module and System-Monitor Module

The system-control module and the system-monitor module are the communication backbone of the UPS. They gather input from all modules and process the data to control system operation and monitor the condition of each module. Except for the silkscreen, the appearance of the system-control module and the system-monitor module appear as shown in Figure 2.7 below.
Under normal operation, the green status LED blinks and the yellow fault LED is Off. For any other condition, refer to Troubleshooting on page 69.
Figure 2.7 Example of system-control and system-monitor module
ITEM DESCRIPTION ITEM DESCRIPTION
1 Status LED (green) 4 Securing hole
2 Fault LED (yellow) 5 Locking lever
3 Handle

2.3.4 Power Module

Each power module, shown in Figure 2.8 below, is an independent 5-kVA unit, consisting of a power­factor-corrected rectifier, battery charger, and inverter with associated monitoring and control circuitry. The modules are connected in parallel for greater capacity and/or redundancy.
The power modules may be added or replaced on-line with no interruption or danger to the connected equipment or user.
Vertiv | Liebert® APS™ Installer/User Guide | 18
Figure 2.8 Power module
ITEM DESCRIPTION ITEM DESCRIPTION
1 Locking Lever 3 Status LED (green)
2 Fan 4 Fault LED(yellow)

2.3.5 Battery Module

When AC utility fails, the battery module supplies power to the load. Each battery module contains 6individual 12-V, valve-regulated lead-acid (VRLA) battery blocks. Two battery modules are connected in series to form a battery string.
Each battery module, shown in Figure 2.9 on the next page,has monitoring and controls that isolate the battery module in the event of a battery failure. The battery strings are connected in parallel to provide back-up time and/or redundancy.
NOTE: Two battery modules must be installed in the same row to make a complete battery string.
The battery modules may be added or replaced on-line with no interruption or danger to the connected equipment if the UPS is not operating on battery.
Under normal operation, the green status LED blinks continuously and the yellow fault LED is Off. For any other condition, refer to Troubleshooting on page 69.
Figure 2.9 Battery module
ITEM DESCRIPTION
1 Locking Lever
2 Status LED (green)
3 Fault LED (yellow)
Vertiv | Liebert® APS™ Installer/User Guide | 19

2.3.6 Charger Module

In AC mains mode, the charger module, shown in Figure 2.10 below, charges the system battery modules or external battery cabinet. Each charger module is rated to deliver 10-A charging current. The charger module has an independent control function and maintains real-time communication with the system and the battery modules to ensure stable charging and fault protection.
The charger module may be added or replaced on-line with no interruption or danger to the user, connected battery system or connected equipment.
Figure 2.10 Charger module
ITEM DESCRIPTION
1 Locking Lever
2 Status LED (green)
3 Fault LED (yellow)

2.3.7 External Battery Cabinet (EBC)

The external battery cabinet, shown in Figure 2.11 on the facing page, is divided into 9rows: the upper 7rows are used for the intelligent battery modules, and the lower 2 rows are used for overcurrent protection for each battery cabinet. For normal operation, 2battery modules must be inserted in the same row of the frame to create a complete string. The battery module strings work in parallel to provide longer back-up time for the UPS. The Liebert APS can be configured with up to 4external battery cabinets.
Vertiv | Liebert® APS™ Installer/User Guide | 20
Figure 2.11 External battery cabinet

2.4 Operating Principle

The operating principle of the Liebert APS UPS is shown in Figure 2.12 below.
The UPS is composed of AC input, EMI filter, power module(s), battery module(s), user interface, control interface, system control module, output and bypass contactor, manual bypass, output transformer (certain frames only) and AC output.
Figure 2.12 Operating principle diagram
Vertiv | Liebert® APS™ Installer/User Guide | 21

2.5 Operating Modes

The Liebert APS is a true online double-conversion system, with the following operating modes:
Normal Mode
Backup Mode
Auto Restart Mode
Bypass Mode

2.5.1 Normal Mode

The power-module rectifiers derive power from a utility AC source and supply regulated DC power to the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment. The battery charger is in the power module and maintains a float-charge on the batteries of the UPS. The optional charger module can also charge the batteries to maintain a quicker recharge time for long back­up time applications.

2.5.2 Backup Mode

When AC utility fails, the connected equipment is supplied power by the inverter, which obtains energy from the battery modules. The output power will not be interrupted during the failure or restoration of the AC utility/mains source.

2.5.3 Auto Restart Mode

After a power outage and complete battery discharge, and once AC utility is restored, the UPS automatically restarts and resumes supplying power to connected equipment. This feature is enabled at the factory, but can be disabled by you. You can also program two auto-restart delay settings from the LCD:
Battery capacity level (%)
Countdown timer

2.5.4 Bypass Mode

The bypass provides an alternate path for power to the connected equipment and operates as follows:
Automatic: In the event of an internal fault or the inverter overload capacity be exceeded, the UPS performs an automatic transfer of the connected equipment from the inverter to the bypass source.
Manual: If the UPS needs taken out of service for limited maintenance or repair, manual activation of the bypass causes an immediate transfer of the equipment from the inverter to the bypass source.
Vertiv | Liebert® APS™ Installer/User Guide | 22

3 INSTALLATION

3.1 Unpacking Inspection

Upon receipt, unpack the Liebert APS and conduct the following checks:
Inspect the unit for shipping damage. If any shipping damage is founded, report it to the carrier.
Check against the delivery list to verify that the types of the accessories are complete and correct. If there is any discrepancy, contact the carrier and your Vertiv™ representative immediately.

3.2 Installation Environment

NOTE: Operating the UPS in temperatures above 77°F (25°) will reduce battery life.
The environment must be free of conductive contaminants and excessive moisture (water and condensation), flammable vapors, chemical fumes, corrosive gases and liquids.

3.3 Installation Tools

The following tools are required to properly set up your UPS:
Pallet jack
17-mm (11/16-in.) wrench or socket
13-mm (1/2-in.) wrench or socket
10-mm wrench or socket
#1 and #3 Phillips-head screwdrivers
Torque wrench

3.3.1 Installation Site Considerations and Clearances

Consider the weight and size of the Liebert APS when deciding where to install the unit. Verify that the floor can support the weight of a fully-loaded unit, with any accessories and external cabinets.
The UPS is air-cooled by internal fans. Air is drawn into the front of the UPS and exhausted through ventilation grilles in the back. Verify that the UPS will be in a well-ventilated area with at least 6-in. (153-mm) clearance behind for ventilation and at least 39-in. (1-m) clearance in front for service and to meet local and national building codes.

3.4 Removing the UPS from the Pallet

The unit frame is bolted to the shipping pallet for safety during shipping. We recommend keeping the unit bolted to the pallet and using a pallet jack to transport the unit to the installation location.
NOTE: The UPS is very heavy. At least two people should unload it from the pallet.
To unload the UPS:
1. Move the UPS to its installation location and remove the package paper.
2. Use a 17-mm (11/16-in.) wrench, to remove the 4mounting bolts from the pallet brackets, see Figure 3.1 on the next page.
3. Remove the mounting brackets from the UPS with a 10mm wrench or socket or a #3 Phillips screwdriver.
Vertiv | Liebert® APS™ Installer/User Guide | 23
Figure 3.1 Remove the mounting brackets
ITEM DESCRIPTION
1 Mounting bracket (one on each side)
2 Mounting bolts (4 places, 2 each side)
4. Raise the 4leveling feet to provide clearance between the pallet and the UPS frame.
5. Connect the ramp to the UPS pallet as shown in Figure 3.2 below, and roll the UPS slowly down the ramp until it is on a level surface.
Figure 3.2 Connect the ramp and roll UPS off the pallet

3.5 Installing the UPS

The Liebert APS may be installed as a tower or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions. See Tower
Installation on page 25 or Rack Installation on page 26.
Vertiv | Liebert® APS™ Installer/User Guide | 24

3.5.1 Tower Installation

1. With the UPS in the installation location, adjust the leveling feet to secure its position, as shown in Figure 3.3 below.
a. Use an open end wrench to turn the lower nut to raise or lower the leveling foot.
b. After the unit is level, tighten the upper nut against the frame to prevent the height from
changing.
Figure 3.3 Adjust the leveling feet
ITEM DESCRIPTION
1 Upper nut
2 Lower nut
Vertiv | Liebert® APS™ Installer/User Guide | 25
2. For added stability or earthquake-resistant installations, the shipping brackets can be used to secure the unit to the floor.
a. Refering to Figure 3.4 below, drill 10.3-mm (13/32-in.) holes in the floor to accommodate
the mounting bolts removed from the pallet.
b. Use the mounting screws to install the mounting brackets on the front and rear of the
UPS (the brackets were removed from the sides of the unit when removing it from the pallet, see Remove the mounting brackets on page 24).
c. Secure the mounting brackets to the floor with the mounting bolts in the drilled holes. For
greater stability, use a higher-grade bolt.
Figure 3.4 Dimension-location of drilled holes for stationary mounting

3.5.2 Rack Installation

1. Install the cage nuts on the corresponding positions in the rack, see Figure 3.5 on the facing page.
a. Install cage nuts in the 2lower square holes of 1U space and in the 2upper square holes
of 2U space on all 4rack posts. These cage nuts secure the optional shelf that will support the weight of the Liebert APS.
b. Install a cage nut in the middle square hole of 4U, 6U, 10U, 12U spaces, respectively in all
4posts. These cage nuts help secure the UPS in the rack.
Vertiv | Liebert® APS™ Installer/User Guide | 26
2. Install the rack-mount shelf on the corresponding position between 1U space and 2U space on the bottom of the rack, as shown in Figure 3.5 below.
Figure 3.5 Install cage nuts and tray
3. Install the guide rails (ramp) in the mounting slot at the front of the tray, as shown in Figure 3.6 below.
ITEM DESCRIPTION
1 Cage nut
2 Screw (16 places)
3 Tray
Figure 3.6 Installthe guide rails
ITEM DESCRIPTION
1 Mounting slot
2 Guiderail
Vertiv | Liebert® APS™ Installer/User Guide | 27
4. Unscrew the 10 screws, 5 each side, on the front of the side panels of the UPS frame, and use the screws to attach the brackets to each side of the UPS frame, as shown in Figure 3.7 below.
Figure 3.7 Install the brackets
5. Push the Liebert APS frame slowly, up the guide rails into the enclosure from the front. The rear of the UPS goes into the rack first when installing through the front of the rack.
6. Using 8panel screws, 4in each bracket, secure the UPS frame to the rack posts.
ITEM DESCRIPTION
1 Brackets (1 each side)
2 Screws (8 places)
NOTE: You may need to adjust the leveling feet to align the holes.
7. Use 4screws to install the metal plate (accessory in the rack-mount kit) on the corresponding position on the lower-front part of the UPS frame as shown in Figure 3.8 below.
8. Insert the plastic bezel into the square holes of the metal plate, see Figure 3.8 below.
Figure 3.8 Metal plate and Square holes for bezel
ITEM DESCRIPTION
1 Square hole (4 places)
2 Metal plate
3 Screw (4places)
Vertiv | Liebert® APS™ Installer/User Guide | 28

3.6 Installing Modules

The Liebert APS ships configured from the factory (modules pre-populated) and tested as a system to your requirements. If you removed any modules to facilitate installation, refer to the following steps to re­insert them properly.

3.6.1 Installing Power, Battery and Charger Modules

1. With the plastic bezel removed, lift module to appropriate bay, resting end of module on bay shelf.
NOTE: Do not rest the module on any plastic bezels. It could damage the bezel.
NOTE: Two battery modules must be installed in the same row to complete the battery string.
2. Refering to Figure 3.9 below, slowly push the module until about 1/3 of the module is in the bay.
3. Lift the module up, then continue pushing until about 5cm (2in.) of the module remains outside the bay, then push it firmly and smoothly to insure that it is fully inserted.
Figure 3.9 Inserting power, battery and charger modules
ITEM DESCRIPTION
1 Push in slowly about 1/3 of the module.
2 Lift and push smoothly and f irmly until fully inserted.
4. Pull out the lock lever slightly, and press the lever down slightly, see Lock lever and module-
securing bracket on page 30.
NOTE: If the lever does not press down smoothly, remove and reinstall the module.
Vertiv | Liebert® APS™ Installer/User Guide | 29
5. Use a #2 Phillips screwdriver to install the module-securing bracket as shown in Lock lever and
module-securing bracket on page 30.
6. Replace the plastic bezels.
Figure 3.10 Lock lever and module-securing bracket
ITEM DESCRIPTION
1 Install module-securing bracket.
2 Pull out and down t o secure lock lever.
Vertiv | Liebert® APS™ Installer/User Guide | 30
Loading...
+ 80 hidden pages