Vertiv Liebert 10 User Manual

Liebert® 10 Fan Drycooler/Fluid Cooler™
Including Quiet-LineModels, 120to150Tons, 50&60Hz
User Manual
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
TABLE OF CONTENTS
1 Introduction 1
1.1 System Description and Standard Features 1
1.2 Optional Features 1
2 Product Performance Data & Selection 5
2.1 Standard Data 5
2.2 Typical Application 7
2.3 Engineering Data, Calculations and Selection Procedure 8
2.4 Selection Example 11
3 Installation 13
3.1 Location Considerations 13
3.2 Site Preparation 15
3.3 Equipment Inspection Upon Delivery 16
3.4 Lifting and Handling the Drycooler 16
3.4.1 Unit Weight 17
3.5 Piping Connections 17
3.5.1 Expansion Tanks, Fluid Relief Valves and Other Devices 18
3.6 Filling Instructions 22
3.6.1 Preparing the System for Filling 22
3.6.2 Glycol Solutions 22
3.6.3 Filling the System 23
3.7 Electrical Connections 24
3.7.1 Line Voltage 24
3.7.2 Low Voltage Control Wiring 25
3.8 Checklist for Completing Installation 26
4 Operation 29
4.1 Initial Startup Procedure 29
4.1.1 Control Setpoints 29
4.1.2 Current-Sensing Relays 30
4.1.3 Cold Weather Operation 31
5 System Maintenance 33
5.1 General Procedures 33
5.2 Special Procedures 34
5.2.1 Drycooler Cleaning 34
5.2.2 Maintenance Inspection Checklist 35
6 Troubleshooting 37
Vertiv | Liebert® 10-fan Drycooler User Manual | i
Vertiv | Liebert® 10-fan Drycooler User Manual | ii
Important Safety Instructions - Save These Instructions
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert®10 Fan Drycooler™. Read this manual thoroughly before attempting to install or operate this unit.
Only properly trained and qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
WARNING! Arc flash and electric shock hazard. Disconnect all electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
WARNING! Risk of high-speed moving parts. Can cause injury or death.
Disconnect all local and remote electric power supplies before working in the unit.
Do not operate this unit with any or all cabinet panels and/or blower guards removed.
CAUTION: Risk of contact with hot surfaces. Can cause injury.
The blower motors may become extremely hot during unit operation. Allow sufficient time for them to cool before working within the unit cabinet. Use extreme caution and wear protective gloves and arm protection when working on or near hot blower motors.
CAUTION: Risk of sharp edges, splinters and exposed fasteners. Can cause injury.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move the unit, lift it, remove packaging or prepare the unit for installation.
Vertiv | Liebert® 10-fan Drycooler User Manual | iii
NOTICE
NOTICE
NOTICE
Risk of clogged or leaking coolant fluid lines. Can cause equipment and building damage.
Improper installation, application and service practices can result in coolant fluid leakage from the unit that can result in severe property damage.
Vertiv™ recommends installing leak detection equipment for unit and supply lines.
Risk of a leaking coil due to freezing and/or corrosion. Can cause equipment and building damage.
Cooling coils and piping systems that are connected to open cooling towers or other open water/glycol systems are at high risk for freezing and premature corrosion. Fluids in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil corrosion. The water or water/glycol solution must be analyzed by a competent water treatment specialist before startup to establish the inhibitor requirement. The water or water/glycol solution must be analyzed every six months to determine the pattern of inhibitor depletion. The complexity of water-caused problems and their correction makes it important to obtain the advice of a water treatment specialist and follow a regularly scheduled maintenance program.
Risk of damage from forklift. Can cause unit damage.
NOTICE
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
Risk of improper storage. Can cause unit damage.
Keep the Liebert 10-Fan Drycooler upright and protected from freezing temperatures and contact damage.
Vertiv | Liebert® 10-fan Drycooler User Manual | iv

1 INTRODUCTION

1.1 System Description and Standard Features

The Liebert® 10 Fan Drycooler/Fluid Cooler™ is designed for maximum heat rejection with minimum footprint and to be used with glycol solutions for large-site installations. It has a nominal range of 150tons of heat rejection and is ideal for rejecting the heat of multiple evaporator units. Standard features include:
Three different coil circuits: 068 (half), 136 (full), 272 (double). Each coil circuit is designed for a range of specific flow rates based on the particular application.
Coil constructed of copper tubes in a staggered pattern expanded into continuous corrugated aluminum fins. The fins have full depth fin collars completely covering the copper tubes which are connected to heavy-wall type L headers. Inlet coil connector tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and vibration. Coil maximum operating pressure is 150 PSIG (1035 kPa).
Wire guards constructed of coated wire, in 1" x 4" pattern, mounted to protect the exposed vertical coil surface.
Current sensing relays are provided with customer connection to monitor change in motor current to detect possible motor/fan failure.
Choice of either 60 or 50Hz models as well as a Liebert Quiet-Line™ 60Hz; comes from the factory completely assembled and pre-wired. Units are available in 208, 230, 460 and 575V, 3­phase, 60Hz, and 380/415V, 3-phase, 50Hz.
Locking disconnect switch and fan cycling control.
Unit frame of heavy galvanized steel for strength and corrosion resistance, divided internally into individual fan sections by full-width baffles to prevent fan reverse windmilling when not energized.

1.2 Optional Features

Quiet-Line
The Liebert Quiet-Line 10 Fan Drycooler includes the same features as the standard Liebert10 Fan Drycooler, except that it has 8-pole motors in lieu of 6-pole motors for lower sound levels as well as reduced airflow and capacity. This option is not available on 50Hz units.
Aluminum Grilles
Aluminum grilles are used for unit aesthetic and general mechanical security purposes. The aluminum grilles extend from the base of the unit and protect the exposed coil sides.
Coil Fin Options
Pre-Coated Fin Stock provides pre-coated coil fins for added protection in corrosive environments.
Phenolic Coated Coil provides a baked phenolic coated coil for added protection in corrosive
environments.
Copper Fin/Copper Tube Coil provides coil constructed of copper fins and copper tubes.
Vertiv | Liebert® 10-fan Drycooler User Manual | 1
Enclosed Motor Option
TEAO motors are totally enclosed and are used in industrial applications. They are not available for Liebert Quiet-Line, or 575V models.
Ancillary Items
Tanks for fluid expansion, pumps, pump control panels, flow switches, shut off valves and relief valves should also be considered for the site/installation. Since these items are custom-sized per application, please consult with your sales representative for selection.
Vertiv | Liebert® 10-fan Drycooler User Manual | 2
Figure 1.1 Typical application
Vertiv | Liebert® 10-fan Drycooler User Manual | 3
Refer to Typical piping diagram on page19 for a detailed installation diagram.
Vertiv | Liebert® 10-fan Drycooler User Manual | 4

2 PRODUCT PERFORMANCE DATA & SELECTION

2.1 Standard Data

Vertiv | Liebert® 10-fan Drycooler User Manual | 5
6.....Liebert® 10-fan Drycooler User Manual
Shipping
Weight
Internal
Volume
Air Flow Sound
No.ofFans
No. &
Size of
Connec-
tions
(outlet)
No. &
Size of
Connec-
tions
(inlet)
No. of
Internal
Circuits
Pressure
Drop
Flow
Rate
Total Heat
Rejection* @25°F
(13.9°C) ITD
Btu/h kW gpm lps Ft of Water kPa cfm cmh dBA** Gal L Lbs Kg
1,172,000 343 136 8.6 27.2 81.2 68 2@2.625 2@2.625 10 74160 126000 65 92.8 351 5100 2313
1,447,000 424 272 17.2 15.8 47.1 136 2@4.125 2@4.125 10 74160 126000 65 92.8 351 5100 2313
1,579,000 463 544 34.3 15.1 45.1 272 2@4.125 2@4.125 10 74160 126000 65 92.8 351 5100 2313
1,287,000 377 136 8.6 27.3 81.5 68 2@2.625 2@2.625 10 99030 168250 72 92.8 351 5100 2313
1,703,000 499 272 17.2 1 5.8 4 7.1 136 2@4.125 2@4.125 10 99030 168250 72 92.8 351 5100 2313
1,924,000 564 544 34.3 15.1 45.1 272 2@4.125 2@4.125 10 99030 168250 72 92.8 351 5100 2313
1,218,000 357 136 8.6 27.3 81.5 68 2@2.625 2@2.625 10 82450 1 40080 68 92.8 351 5100 2313
1,541 ,000 452 272 17.2 15.8 47.1 136 2@4.125 2@4.125 10 82450 140080 68 92.8 351 5100 2313
1,703,000 499 544 34.3 15.1 45.1 272 2@4.125 2@4.125 10 82450 1 40080 68 92.8 351 5100 2313
Hz
Model
Table 2.1 Drycooler Performance Data
No.
120 60
150 60
150 50
* Ratings based on using 40% ethylene glycol @ 95°F (35°C) entering air, 120°F (48.9°C) enteringglycol; 2 gpm (.13 l/s) circ.
** Sounddata is for sound pres sure measured @ 5 ft. (1.5m) height, 30 ft.(9.1 m) from the unit.
Table 2.2 Drycooler Performance Data per Circuit
Model Hz
120 60
150 60
150 50
* Data is based on 4 0% ethylene glycol solutionat 1 15°F ( 46.1° C) average solution temperature expressed inBtu/h.
No. of Internal Circuits
68 68-136 29,507 39,991 46,972 8.2 16.1 27.3
136 136-34 0 45,829 53,713 57,917 5 9.2 23.7
272 272-544 56,201 60,785 63,153 4 8.7 15.1
68 68-136 30,144 42,440 51,621 8.2 16.1 27.3
136 136-34 0 50,346 61,660 68,219 5 9.2 23.7
272 272-544 65,785 73,11 8 77,019 4 8.7 15.1
68 68-136 29,791 41,011 4 8,823 8.2 16.1 27.3
136 136-34 0 47,617 56,724 61,728 5 9.2 23.7
272 272-544 59,756 65,257 68,146 4 8.7 15.1
Flow Rate Range
min-max
gpm
Heat Rejection per ITD* (Btu/h/°F) Pressure Drop* (ft of water)
Flow Rate per Circuit (gpm/circuit) Flow Rate per Circuit (gpm/circuit)
1 1.5 2 1 1.5 2
Table 2.3 Drycooler Performance Data per Circuit—Metric
Heat Rejection per ITD* (kW/°C) Pressure Drop* (kPa)
Model No.
Hz
No. of Internal Circuits
Flow Rate Range min-max lps
Flow Rate per Circuit (lps/circuit) Flow Rate per Circuit (lps/circuit)
0.06 0.09 0.13 0.06 0.09 0.13
68 6-13 23.9 29.8 32.1 24.5 48.0 81.5
120 60
150 60
150 50
* Data is based on 4 0% ethylene glycol solutionat 4 6.1°C (115°F) average solution temperature expressed inkW.
136 13-26 30.8 31.9 32.0 14.9 27.5 70.7
272 26-38 30.7 30.6 30.5 11.9 26.0 45.1
68 6-13 24.9 33.1 37.5 24 .5 48.0 81.5
136 13-26 36.0 39.1 39.8 14.9 27.5 70.7
272 26-38 37.9 38.4 39.0 11.9 26.0 4 5.1
68 6-13 24.4 31.1 34.2 24.5 48.0 81.5
136 13-26 32.8 34.6 34.7 14.9 27.5 70.7
272 26-38 33.3 33.4 33.3 11.9 26.0 45.1

2.2 Typical Application

The most popular use for the Liebert® 10 Fan Drycooler™ is at sites with large cooling loads, such as data center/telecom sites where multiple indoor air conditioners are used. See 2.2 abovefor a general outline of suggested quantity of indoor units for each Liebert 10 Fan Drycooler or contact your Vertiv™ representative for custom matchup. See Typical application on page3.
Vertiv | Liebert® 10-fan Drycooler User Manual | 7
Table 2.4 Maximum Liebert evaporator units per Every 10 Fan Drycooler
Liebert Deluxe Model 60 Hz (50 Hz)
110 G
(111 G)
116 G
(121 G)
192 G
240 G
363 G
1. Ratings based on using40% ethylene glycol @ listed outdoor ambient rating temperature, 120°F (48.9°C) entering glycol. Selections are validfor standard or TEAO motors. Consult your localLiebert representative for Quiet-Line selections.
Liebert Deluxe Unit Capacity
8 tons
(28.1 kW)
10 tons
(35.2 kW)
15 tons
(52.7 kW)
20 tons
(70.3 kW)
30 tons
(105 kW)
Maximum Deluxe Units/10 Fan Drycooler
12 95°F (35°C) 384 (24.2) D*N*150**272
9 100°F ( 37.8°C) 288 (18.2)
6 105°F (40.6°C) 192 (12.1)
10 95°F (35°C) 380 (24.0) D*N*150** 272
7 100°F (37.8°C) 266 (16.8)
5 105°F (40.6°C) 190 (12.0)
7 95°F (35°C) 378 (23.8) D*N*150**272
5 100°F (37.8°C) 270 (17.0)
4 105°F (40.6°C) 216 (13.6)
6 95°F (35°C) 402 (25.4) D*N*150* *272
4 100°F (37.8°C) 268 ( 16.9)
3 105°F (40.6°C) 201 (12.7)
4 95°F (35°C) 31 2 (19.7) D*N*150**272
3 100°F (37.8°C) 234 (14.8)
2 105°F (40.6°C) 156 (9.8)
Outdoor Ambient Rating
Total Syst em
gpm (lps)
Drycooler Model #
D*N*150* *136
D*N*150* *136
D*N*150* *136
D*N*150* *136
D*N*150* *136
1

2.3 Engineering Data, Calculations and Selection Procedure

An alternate, detailed procedure is available to calculate values and select the correct the 10 Fan Drycooler(s) for the application. This can be used to assist in selecting drycoolers for applications for ambient conditions that are not standard. Use the following steps.
1. Determine the following items to begin this procedure:
Design outdoor ambient air temperature, Toa(F or C)
Fluid Flow Rate, VT(gpm or lps)
% ethylene glycol concentration
Fluid temperatures at drycooler: Entering, Tefand leaving Tlf(F or C), or
Total Required Heat Rejection, QRT(Btu/h or kW) and one of the fluid temperatures above
2. Find the following values using these equations and known values above:
Initial Temperature Difference (ITD) of entering fluid to outdoor design air, ITD = Tef- T
Total Required Heat Rejection, QRT= VT* cv* (Tef- Tlf), where cvis found in the following table, or
Leaving fluid temperature, Tlf= Tef- QRT/ (VT* cv) where cvis found in the following table.
3. Find the Average Fluid Temperature, T
oa
= (Tef+ Tlf) / 2
f,avg
Vertiv | Liebert® 10-fan Drycooler User Manual | 8
4. Find Required Heat Rejection per ITD, QR
= QRT/ (ITD * f), where f is the capacity
ITD
correction factor found in Capacity Correction Factor on the next page.
5. Using Product Performance Data & Selection on page5 with columns titled Flow Rate Range and Heat Rejection per ITD, choose the Drycooler Model matching application fluid flow rate and meeting/exceeding the required Heat Rejection per ITD, QR
from Step4. above.
ITD
6. Find the Flow Rate per Circuit, VC= VT/ circuits for the drycooler selected in Product
Performance Data & Selection on page5. This should be in the range of 1.0 to 2.0 gpm/circuit
(0.06 to 0.13 lps/circuit) for proper long-term performance.
7. In Product Performance Data & Selection on page5, for the selected Model Number, find the Actual Heat Rejection per ITD using the gpm/circuit from Step6. above. You may interpolate between columns as required. The Actual Heat Rejection should be equal to or greater than per ITD, QR
(higher altitude application sites should use correction factors to reduce Actual
ITD
Heat Rejection results). If it is less, repeat process from Step5. above using a larger model. If 10 Fan Drycooler solution is oversized, lower capacity drycoolers are available and may be considered as an alternative solution.
8. Calculate the Total Actual Heat Rejection, QA, for the drycooler, using the Actual Heat Rejection per ITD (Step7. above) and actual ITD and correcting for % glycol and AFT (see
Capacity Correction Factor on the next page).
QA = QA
ITD
* ITD * f
9. After selecting a model, look up the unit’s Pressure Drop in Product Performance Data &
Selection on page5. Multiply this pressure drop by the correction factor found in Pressure drop correction factor on page11. If the resulting pressure drop is higher than your system
design, go back to Step5. above and select a model with more circuits or consider multiple units. Contact your sales representative for additional design assistance.
10. Electrical data for model selected is found in Electrical Specifications on page11.
Table 2.5 Specific Heats for Aqueous Ethylene Glycol Solutions (Cv)
% Ethylene Glycol 0% 10% 20% 30% 40% 50%
Btu/h/gpm°F 500 490 480 470 450 433
kW/lps°C 4.18 4.09 4.01 3.93 3.76 3.62
Table 2.6 Altitude Correction
Alt it ude - Feet (M)
Correction Factor 1 .000 0.979 0.960 0.900 0.841 0.762 0.703
0 (0)
1000 (305)
2000 (610)
5000 (1525)
8000 (2440)
12000 (3660)
15000 (4575)
Vertiv | Liebert® 10-fan Drycooler User Manual | 9
Figure 2.1 Capacity Correction Factor
Vertiv | Liebert® 10-fan Drycooler User Manual | 10
Figure 2.2 Pressure drop correction factor
Table 2.7 Electrical Specifications
Voltag
Drycool er Model
D0N*150
DTN*1 50 TEAO 70 72 90 70 72 90 35 36 45 n/a n/a n/a n/a 32 35
DGN*120 QuietLine 48 50 60 48 50 60 24 25 30 28 30 35 24 25 30
e­Phase
Motor Type
STANDA RD
60 Hz 50 Hz
208-3 230-3 460-3 575-3 380/415-3
FLAMCAOPDFLAMCAOPDFLAMCAOPDFLAMCAOPDFLAMCAOP
D
70 72 90 70 72 90 35 36 45 28 30 35 35 36 40

2.4 Selection Example

For the following example, English (I-P) units will be used. Metric units are also provided in the tables and figures.
Find a drycooler to cool 340 gpm of 20% ethylene glycol/water solution from 125°F to 115°F. Application is near sea level and has an outdoor design air temperature of 95°F.
Vertiv | Liebert® 10-fan Drycooler User Manual | 11
1. Assume the following values:
Toa= 95°F
VT= 340 gpm
20% ethylene glycol
Tef= 125°F
Tlf= 115°F
2. Initial temperature difference, ITD = Tef- Toa= 125 - 95 = 30°F
Since Tefis known, calculate Total Required Heat Rejection, QRT= VT* cv* (Tef- Tlf)
Using Specific Heats for Aqueous Ethylene Glycol Solutions (Cv) on page9, cv= 480 for 20% ethylene glycol.
QRT= 340 gpm * 480 Btu/h / gpm°F * (125°F - 115°F) = 1,632,000 Btu/h
3. Average Fluid Temperature, T
4. Required Heat Rejection per ITD, QR
= (Tef+ Tlf) / 2 = 125°F + 115°F) / 2 = 120°F
f,avg
= QRT/ (ITD * f), where f is found from Figure 2.1 on
ITD
page10.
Using Figure 2.1 on page10, f = 1.04 for 120°F and 20% EG concentration.
QR
= 1,632,000 Btu/h / (30°F * 1.04) = 52,300 Btu/h / °F
ITD
5. Locate Model Number(s) in Product Performance Data & Selection on page52 on page5, matching flow rate of 340 gpm and meeting or exceeding 52,300 Btu/h / °F. Either Model 120 with 272 circuits or the Model 150 with 272 circuits matches the flow rate requirements and meets or exceeds the Required Heat Rejection per ITD. For this example, Model 150 will be chosen to complete the procedure.
6. Flow rate per circuit, VC= VT/ circuits = 340 gpm / 272 circuits = 1.25 gpm/circuit. This is within the 1.0 to 2.0 gpm/circuit range.
7. Using Product Performance Data & Selection on page5, the actual Heat Rejection per ITD, QA
for Model 150 with 272 circuits @ 1.25 gpm/circuit is 69,526 Btu/h / °F, which exceeds our
ITD
Required Heat Rejection per ITD of 52,300 Btu/h / °F. No correction for altitude is required.
8. Total Actual Heat Rejection for the drycooler, QA = QA
* ITD * f, where f is found in Capacity
ITD
Correction Factor on page10.
QA = 69,526 Btu/h / °F * 30°F * 1.04 = 2,169,211 Btu/h
9. Pressure drop for 1.25 gpm/circuit is 6.25 ft., water using Product Performance Data & Selection on page5 for 40% ethylene glycol and T find correction factor for the pressure drop for 20% ethylene glycol and T
= 115°F. Use Figure 2.2 on the previous page to
f,avg
= 120° F.
f,avg
Therefore, the pressure drop will be 6.259 * 0.93 = 5.8 ft., water.
10. Using Electrical Specifications on the previous page and Drycooler Model D0N*150 with a 460 VAC, 3-phase, 60 Hz motor, the electrical requirements will be FLA = 31 amps, WSA = 32 amps and OPD = 35 amps.
Vertiv | Liebert® 10-fan Drycooler User Manual | 12

3 INSTALLATION

NOTE: Follow all unit dimensional drawings carefully. Determine whether any building alterations are required to run piping and wiring. Also refer to the submittal engineering dimensional drawings.

3.1 Location Considerations

The drycooler should be located for maximum security and maintenance accessibility. Avoid ground level sites with public access or areas which contribute to heavy snow or ice accumulations. To assure an adequate air supply, it is recommended that drycoolers be located in a clean air area, away from loose dirt and foreign matter that may clog the coil. In addition, drycoolers must not be located in the vicinity of steam, hot air, or fume exhausts.
The unit may be mounted either at ground level or on a roof, given proper structural support and following a review of local codes. Pit installations are not recommended. Air re-circulation will severely affect unit and/or system performance. For these same reasons, units should not be installed closer than 72" (1829 mm) from a wall. This clearance should be increased to 96" (2438mm) in corner wall situations. In multiple unit installations, units should not be installed closer than 72" (1829 mm) end to end or 96" (2438 mm) side to side. For further details, see the following figure.
Vertiv | Liebert® 10-fan Drycooler User Manual | 13
Figure 3.1 Clearance considerations
Vertiv | Liebert® 10-fan Drycooler User Manual | 14

3.2 Site Preparation

Drycoolers should be installed in a level position to assure proper venting and drainage. This space should have all services (electrical, drain, water) in close proximity. Also, the space should be level and free of loose gravel, sand, flooring or roofing. For roof installation, mount drycoolers on steel supports in accordance with local codes. To minimize sound and vibration transmission, mount steel supports across load-bearing walls. For ground installations, a concrete pad is sufficient to carry the load. The base should be at least 2 inches (51 mm) higher than the surrounding grade and 2 inches (51 mm) larger than the dimensions of the unit base. The drycooler base has mounting holes for securing the drycooler once installed. See the following figure.
Figure 3.2 Unit Dimensions
Vertiv | Liebert® 10-fan Drycooler User Manual | 15
Table 3.1 Drycooler Physical Data
Model #Model #
D*N*150* *068 10
D*N*150* *136 10
D*N*150* *272 10
DGN*120**068 10
DGN*120**1 36 10
DGN*120**272 10
No. of Fans
CFM (CMH)
60Hz.
99030 (168250)
99030 (168250)
99030 (168250)
74160 (126000)
74160 (126000)
74160 (126000)
CFM (CMH)
50Hz.
82450 (140080)
82450 (140080)
82450 (140080)
N/A 92.8 (351) 5100 (2313)
N/A 92.8 (351) 5100 (2313)
N/A 92.8 (351) 5100 (2313)
Coil Internal
Vol. Gal (L)
92.8 (351) 5100 (2313)
92.8 (351) 5100 (2313)
92.8 (351) 5100 (2313)
Net Weight
Lb (kg)

3.3 Equipment Inspection Upon Delivery

When the Liebert® 10 Fan Drycooler™ arrives, inspect it for any visible or concealed damage. Do not accept a damaged unit from the shipper!
NOTE: Any damage caused in transit must be reported immediately to the carrier and a damage claim filed with a copy sent to your sales representative. Failure to do so may result in an inability to recover costs for damage.
Before removing the drycooler from the truck/container, review the previous section, Site Preparation on the previous page.
NOTICE
Risk of exposure to freezing temperatures. Can cause equipment damage.
If the drycooler is not installed immediately upon receipt, special storage precautions should be taken. It is recommended that the unit be stored in a dry, heated place. Do not store the unit at temperatures below 36°F (2.2°C). If the storage temperature is below 36°F (2.2°C), water vapor can condense in the coil, freeze and cause permanent damage. Failure to store unit properly will void the warranty.

3.4 Lifting and Handling the Drycooler

WARNING! Risk of unit very heavy unit tipping over. Can cause equipment damage, personal injury and death.
Do not unload the drycooler with a forklift. The drycooler’s high center of gravity makes it a tipping hazard. Further, tilted forks may damage the drycooler. Use chains and hooks when removing the unit from the truck and when moving it between areas of equal height.
Riggers are required to lift the unit into place. Refer to Rigging Instructions belowFigure 3.3 below for lift locations. Any time the unit is lifted, use slings or chains (with spreader bars) attached to the three lifting eyes on either side of the unit base. Do not allow any part of the lifting apparatus to bear against the coil fins. All lifting apparatus must also clear the fan guards on the top of the unit.
Vertiv | Liebert® 10-fan Drycooler User Manual | 16

3.4.1 Unit Weight

Dry weight of the unit is 5100 lb. (2313kg).
WARNING! Risk of unit very heavy unit tipping over. Can cause equipment damage, personal injury and death.
To avoid a tilt hazard, adjustment may be necessary to locate the center of gravity before lifting the unit.
Figure 3.3 Rigging Instructions

3.5 Piping Connections

See Figure 3.4 on page19 for a typical piping diagram. See Figure 3.5 on page20 piping locations.
Notice
Risk of overpressurization. Can cause equipment damage.
To avoid the possibility of burst pipes, it is necessary to install a relief valve in the system. This valve may be obtained from your supplier as an option or may be sourced from another vendor. Galvanized pipe must not be used in glycol systems. To help prevent piping failures, supply and return lines must be supported such that their weight does not bear on the piping of the unit or pumps.
NOTE: Units are shipped pressurized with a 30 psig dry air holding charge.
Vertiv | Liebert® 10-fan Drycooler User Manual | 17
It is recommended that manual service shutoff valves be installed at the supply and return connections to each unit. This enables routine service and/or emergency isolation of the unit. In addition, multiple pump packages require a check valve at the discharge of each pump to prevent backflow through the standby pump(s).
Vertiv™ recommends installing filters/strainers in the supply line. These filters or strainers should be a type that can be easily replaced or cleaned, with 16-20 mesh screen. These filters extend the service life of the drycooler and the system’s pumps.
Vertiv™ recommends installing hose bibs at the lowest point of the system to facilitate filling.
Consideration of the minimum glycol temperature to be supplied from the drycooler will determine if the glycol supply and return lines must be insulated toprevent condensation on the glycol lines in low ambient conditions.
All fluid piping must comply with local codes. Care in sizing pipes will help reduce pumping power and operating costs.

3.5.1 Expansion Tanks, Fluid Relief Valves and Other Devices

An expansion tank must be provided for expansion and contraction of the fluid due to temperature change in this closed system. Vents are required at system high points to vent trapped air when filling the system. A relief valve is also a necessary piping component.
Depending on the complexity of the system, various other devices may be specified. Pressure gauges, flow switches, automatic air separator, tempering valves, standby pumps and sensors for electrical controls are just a few of these devices.
NOTICE
Risk of burst pipes and leaking water from freezing temperatures. Can cause equipment and building damage.
Immediately following the use of water for leak testing or system cleaning, charge the tested system with the proper percentage of glycol and water for the coldest design ambient expected. Complete system drain-down cannot be ensured, and damage to the system could result from freezing of residual water.
Vertiv | Liebert® 10-fan Drycooler User Manual | 18
Figure 3.4 Typical piping diagram
Vertiv | Liebert® 10-fan Drycooler User Manual | 19
Figure 3.5 Piping dimensions
Vertiv | Liebert® 10-fan Drycooler User Manual | 20
Table 3.2 Piping, drycoolers
Model #. No. Fans
D*N*150* *068 10 68 2 2 2.625" (66.7mm) 2.625" (66.7mm)
D*N*150* *136 10 136 2 2 4.125'' (104.8mm) 4.125'' (104 .8mm)
D*N*150* *272 10 272 2 2 4.125'' (104 .8mm) 4.125'' (104.8mm)
DGN*120**068 10 68 2 2 2.625" (66.7mm) 2.625" ( 66.7mm)
DGN*120**1 36 10 136 2 2 4.125'' (1 04.8mm) 4.125'' (104.8mm)
DGN*120**272 10 272 2 2 4.125'' (1 04.8mm) 4.125'' (104 .8mm)
No. of Internal Circuits
No. of Inlets
No. of Outlets
Connection Sizes (ODS)
(A) Inlet (B) Outlet
Table 3.3 Piping specifications
Model
D0N*150** 68
DGN*120** 272
*Cut off closed end of connection tube; connectcouplings and elbows as required.
No. of Internal Circuits
No. of Inlets (A)
2 2
No. of Outlets (B)
Connection Sizes, Inlet and Outlet OD (in.)*
2.625
4.125
Coil Internal Volume, Gal. (l)
92.8 (351)DTN*1 50** 1 36
Table 3.4 Volume in Standard Type L Copper Piping
Diameter (in.) Volume
Outside Inside gal/ft l/m
1-3/8 1.265 0.065
1-5/8 1.505 0.092 1.15
2-1/8 1.985 0.161 2.00
2-5/8 2.465 0.248 3.08
3-1/ 8 2.945 0.354 4.40
3-5/8 3.425 0.479 5.95
4-1/8 3.905 0.622 7.73
Vertiv | Liebert® 10-fan Drycooler User Manual| 21

3.6 Filling Instructions

3.6.1 Preparing the System for Filling

It is important to remove any dirt, oil or metal filings that may contaminate the cooling system piping in order to prevent contamination of the fresh glycol solution and fouling of the drycooler piping. The system should be flushed thoroughly using a mild cleaning solution or high-quality water and then completely drained before charging with glycol. Cleaning new systems is just as important as cleaning old ones. New systems can be coated with oil or a protective film; dirt and scale are also common. Any residual contaminants could adversely affect the heat transfer stability and performance of your system. In many cases, in both old and new systems, special cleaners are needed to remove scale, rust and hydrocarbon foulants from pipes, manifolds and passages. Clean heat transfer surfaces are important in maintaining the integrity of the heating/cooling system. For more information on cleaners and degreasers, contact your sales representative. Follow the manufacturer’s instructions when using these products.
Calculate the internal volume of the system as closely as possible. The Liebert® 10 Fan Drycooler™ volume, not including the load or field-supplied piping, is 92.8 gallons (351 l). Use Volume in Standard Type L
Copper Piping on the previous page for field-installed piping volumes.

3.6.2 Glycol Solutions

NOTE: Glycol solutions should be considered for the protection of the coil. When glycol solutions are not used, damage can occur either from freezing or from corrosion from water.
When considering the use of any glycol products in a particular application, you should review the latest Material Safety Data Sheets and ensure that the use you intend can be accomplished safely. For Material Safety Data Sheets and other product safety information, contact the supplier nearest you. Before handling any other products mentioned in the text, you should obtain available product safety information and take necessary steps to ensure safety of use.
NOTICE
Risk of improper handling of glycol. Can cause environmental damage.
When mishandled, glycol products pose a threat to the environment. Before using any glycol products, review the latest Material Safety Data Sheets and ensure that you can use the product safely. Glycol manufacturers request that the customer read, understand and comply with the information on the product packaging and in the current Material Safety Data Sheets. Make this information available to anyone responsible for operation, maintenance and repair of the drycooler and related equipment.
NOTICE
Risk of using improper glycol. Can cause equipment damage.
Automotive antifreeze is unacceptable and must NOT be used.
No chemical should be used as or in a food, drug, medical device, or cosmetic, or in a product or process in which it may contact a food, drug, medical device, or cosmetic until the user has determined the suitability and legality of the use. Since government regulations and use conditions are subject to change, it is the user's responsibility to determine that this information is appropriate and suitable under current, applicable laws and regulations.
Vertiv | Liebert® 10-fan Drycooler User Manual| 22
Typical inhibited formula ethylene glycol and propylene glycol manufacturers and suppliers are Union Carbide (Ucartherm) and Dow Chemical (Dowtherm SR-1, Dowfrost). These glycols are supplied with corrosion inhibitors and do not contain a silicone anti-leak formula. Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of construction than water itself. Aqueous solutions of these glycols, however, assume the corrosivity of the water from which they are prepared and may become increasingly corrosive with use when not properly inhibited.
There are two basic types of additives:
Corrosion inhibitors and
Environmental stabilizers
The corrosion inhibitors function by forming a surface barrier that protects the metals from attack. Environmental stabilizers, while not corrosion inhibitors in the strictest sense of the word, decrease corrosion by stabilizing or favorably altering the overall environment. An alkaline buffer, such as borax, is a simple example of an environmental stabilizer, since its prime purpose is to maintain an alkaline condition (pH above 7).
The percentage of glycol to water must be determined by using the lowest design outdoor temperature in which the system is operating. The following table indicates the solution freeze point at several c concentration levels of ethylene glycol. Propylene glycol concentrations should be 1% higher than ethylene glycol table values to find the freeze point. For example, 41% propylene glycol freezes at -10°F.
Table 3.5 Ethylene glycol concentrations
% Glycol by Volume 0* 10 20 30 40 50
Freezing Point °F (°C) 32 ( 0) 25 (-3.9) 1 6 (-8.9) 5 (-15.0) -10 (- 23.3) -32 ( -35.5)
Apparent Specific Gravity @ 50°F ( 10°C)
* A minimal amount of glycol should be considered for inhibitive coil protection.
1 1,014 1.028 1,04 2 1,057 1.071
Notice
Risk of poor water quality. Can cause equipment damage.
The quality of water used for dilution must be considered because water may contain corrosive elements that reduce the effectiveness of the inhibited formulation. Surface water that is classified as soft (low in chloride and sulfate ion content—less than 100 ppm each) should be used.

3.6.3 Filling the System

Vertiv™ recommends installing hose bibs at the lowest point of the system.
When filling a glycol system, keep air to a minimum. Air in glycol turns to foam and is difficult and time­consuming to remove. (Anti-foam additives are available and may be considered.)
Open all operating systems to the loop. With the top vent(s) open, fill the system from the bottom of the loop. This will allow the glycol to push the air out of the top of the system, minimizing trapped air. Fill to approximately 80% of calculated capacity. Fill slowly from this point, checking fluid levels until full.
NOTE: For glycol solution preparation and periodic testing, follow manufacturer’s recommendations. Do not mix products of different manufacturers.
Vertiv | Liebert® 10-fan Drycooler User Manual| 23

3.7 Electrical Connections

Each unit is shipped from the factory with all internal unit wiring completed. Refer to the electrical schematic when making connections. All wiring must be done in accordance with the National Electric Code and all local and state codes.
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within the unit.
The fans may start unexpectedly. The line side of the factory disconnect remains energized when the disconnect is Off. Use a voltmeter to confirm that the electric power is turned Off before making any electrical connections.

3.7.1 Line Voltage

Drycooler rated voltage should be verified with available power supply upon receipt of unit but before installation. Refer to the unit electrical schematic and serial tag for specific electrical requirements. All wiring must be done in accordance with the National Electric Code as well as all local and state codes.
CAUTION: Risk of using improper wire. Can cause equipment damage or a safety hazard from overheated wire and/or connections.
Size the system electrical service for the total of all drycoolers and ancillary components FLA/WSA/OPD. Unit-specific wiring diagrams are provided on each unit. Use copper wiring only. Make sure that all connections are tight.
Line voltage electrical service is required for all drycoolers at the location of the drycooler. The power supply does not necessarily have to be the same voltage supply as required by the indoor unit for which the drycooler operates. This power source may be 208, 230, 460 or 575V 60Hz; or 380/415V 50Hz. A unit disconnect is standard. However, a site disconnect may be required per local code to isolate the unit for maintenance. Route the supply power to the site disconnect switch and then to the unit. Route the conduit through the hole provided in the cabinet. Connect earth ground to lug provided near terminal board. For units with multi-voltage transformer, the transformer connections should match (change if necessary) the local power supply. See the following figure.
Vertiv | Liebert® 10-fan Drycooler User Manual| 24
Figure 3.6 Electrical Field Connections

3.7.2 Low Voltage Control Wiring

A control interlock between the drycooler and the heat load(s) will require 24V Class 2 copper wiring for remote On/Off sequencing of the drycooler with the load. Refer to the electrical schematic for wiring to Terminals 70 & 71. See the following figure for typical low-volt system wiring.
If the current sensing relay option is provided, 24V Class 2 wiring will be necessary to make the connections to monitor motor operation.
NOTE: Make sure all electrical connections are tight.
Vertiv | Liebert® 10-fan Drycooler User Manual| 25
Figure 3.7 Typical Low Volt Wiring Diagram

3.8 Checklist for Completing Installation

NOTE: After installation, proceed with the following list to verify that the installation is complete. Complete and return the Warranty Inspection Check Sheet which is shipped with the unit and return to the address indicated on the check sheet.
1. Proper clearances for service access have been maintained around the equipment.
2. Equipment is level and mounting fasteners are tight.
3. Piping completed to coolant loop.
4. All piping connections are tight as well as secured and isolated for vibration reduction.
5. All piping connections inspected for leaks during initial operation.
6. Line voltage to power wiring matches equipment nameplate.
7. Power wiring connections completed to disconnect switch, including earth ground.
8. Power line circuit breakers or fuses have proper ratings for equipment installed.
9. Control wiring connections completed to heat loads/evaporator(s), including wiring to optional controls.
10. All wiring connections are tight.
11. Foreign materials have been removed from in and around all equipment installed (shipping materials, construction materials, tools, etc.).
Vertiv | Liebert® 10-fan Drycooler User Manual| 26
12. Fans rotate freely and in correct direction without unusual noise and discharge the air upwards.
13. Glycol has been added to the drycooler to prevent freeze damage.
Vertiv | Liebert® 10-fan Drycooler User Manual| 27
This page intentionally left blank.
Vertiv | Liebert® 10-fan Drycooler User Manual| 28

4 OPERATION

WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within the unit.
The fans may start unexpectedly. Disconnect the power supply before working on the unit. Line side of factory disconnect remains energized when the disconnect is Off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.

4.1 Initial Startup Procedure

Refer to Checklist for Completing Installation on page26 and verify that all installation items have been completed prior to proceeding.
Turn the unit ON. Check the fans for proper rotation (air discharging up). Check the pumps for proper rotation.
Notice
Risk of overheated pumps. Can cause equipment damage.
Do not run pumps without fluid in the system. Pump seals require fluid to keep them cool; running them for any amount of time will damage the seals, which may cause a failure.

4.1.1 Control Setpoints

The fluid temperature controls should be set according to the following table for standard cooling only or free-cooling GLYCOOL applications. See the following figure.
Table 4.1 Control Settings
Heat Rejection Method
Standard
Free-Cooling (GL YCOOL)
Fluid Temperature Control
1TAS 68°F ( 20°C) -
1STG - 5°F (2.8°C) 73°F (22.8°C) 85°F ( 29.4°C)
2STG - 10°F (5.6°C) 78°F (25.6°C) 90°F (32.2°C)
1TAS 42°F (5.6°C) -
1STG - 2°F (1.1°C) 44° F (6.7°C) 52°F (11.1°C)
2STG - 4°F (2.2°C) 46°F (7.8°C) 54° F (12.2°C)
Setpoint Offset Differential Open Close
68°F (20°C) 80°F (26.7°C)
12°F (6.7°C)
42°F ( 5.6°C) 50°F (10°C)
8°F ( 4.4°C)
Vertiv | Liebert® 10-fan Drycooler User Manual| 29
Figure 4.1 Fluid Temperature Controls

4.1.2 Current-Sensing Relays

If supplied, be sure that the current-sensing relays (CSR) are wired as per the wiring schematic using 24V Class 2 copper wiring. When the thermostat closes, a 24-volt signal will be sent to the relevant terminals of the CSR. When this occurs, a time delay starts, allowing the amperage to be sensed on the load side of the contactors.
First, set selection under amperage on selector switch, then start all fans. Set the trip delay for 50%. Disconnect one of the load side wires from a fan being monitored by the control. Turn the potentiometer until the LED is lit. Reconnect the fan wire. Check and repeat for the other circuits. Be sure to set the fluid temperature controls as per the specifications, as illustrated within the unit electrical schematic (supplied with the unit), or refer to Control Setpoints on the previous page. See the following figure or current sensing relay layout.
Vertiv | Liebert® 10-fan Drycooler User Manual| 30
Figure 4.2 Current Sensing Relays

4.1.3 Cold Weather Operation

Glycol solution should be used for operation of units located where outdoor ambients will include temperatures at or below freezing. Refer to the installation sections referring to Piping Connections on page17 and Glycol Solutions on page22 for further details.
Vertiv | Liebert® 10-fan Drycooler User Manual| 31
This page intentionally left blank.
Vertiv | Liebert® 10-fan Drycooler User Manual| 32

5 SYSTEM MAINTENANCE

WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power supplies before working within the unit.
The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions

5.1 General Procedures

NOTE: When ordering replacement parts for equipment, it is necessary to specify the unit’s model number, serial number and voltage. Record those numbers in the spaces below.
Model Number ___________________
Serial Number ___________________
Voltage __________________________
Periodic attention is necessary for continued satisfactory operation of your unit. A daily inspection of the system should be made to verify that the unit is performing satisfactorily. It is suggested that a daily log be maintained recording inlet and outlet coolant temperature, ambient temperature and the coolant pressure gauge readings. The coolant sight glass should be checked and the fans checked for unusual sounds which may indicate wear or future trouble.
Monthly inspections should include removal and cleaning of strainer, and cleaning and inspection of coil. The coil can be cleaned with water, compressed air or steam as required. During monthly inspections, it is also wise to check the coolant to assure sufficient glycol in the mixture to prevent freeze-up. Each fan motor amp draw should be checked. If performance or operation problems are also detected, refer to
Troubleshooting on page37 for required action. Use copies of the Maintenance Inspection Checklist on
page35.
Restricted air flow through the drycooler coil will reduce the operating efficiency of the unit and can result in high fluid temperatures and loss of cooling. Clean the drycooler coil of all debris that will inhibit air flow. This can be done with compressed air or a commercial coil cleaner. Check for bent or damaged coil fins and repair as necessary. In winter, do not permit snow to accumulate around the sides or underneath the drycooler.
Check all fluid lines and capillaries for vibration isolation. Support as necessary. Visually inspect all fluid lines for signs of fluid leaks.
Inspect the motor/fan assemblies to insure bearings are free and the motor is secure within the mount.
The glycol level in drycooler systems must be periodically checked. At the high point of the system, check for:
Positive pressure
Air to be vented
An unclogged expansion tank
Proper concentration of inhibitors and antifreeze
Vertiv | Liebert® 10-fan Drycooler User Manual| 33
The first three checks may give an indication of leaks in the system.

5.2 Special Procedures

5.2.1 Drycooler Cleaning

Keeping the outdoor drycooler coils clean is an important factor in maintaining peak efficiency, reliability and long life of the equipment. It is much easier to keep up on frequent cleanings rather than wait until heavy build up has occurred which may create head pressure problems with the evaporator units.
When to Clean
Normal conditions typically dictate cleaning twice a year, spring and fall. On-site or area conditions such as cottonwood trees, construction, etc., can increase cleaning frequency. On your standard bimonthly or quarterly preventive maintenance schedule, a visual inspection of the coil is recommended to monitor conditions.
What to Use
The best overall drycooler coil cleaner to use is plain water. If the coil has been maintained and cleaned at regular intervals, water is sufficient to remove dirt and debris from the fins. Heavy buildup on the exterior of the fins can be removed with a brush. Water pressure from a garden hose and sprayer usually works well. If a pressure washer is used, make sure the equipment is set to a lower pressure setting and that the nozzle is set to the fan spray, not stream. Otherwise, damage to the fins could result. If a cleaner is required, Vertiv™ recommends using a non-acidic type cleaner. Acid-type cleaners can be aggressive to the coil fins as well as surrounding areas. Many sites do not allow the use of acidic cleaners for environmental reasons.
How to Clean
The best way to clean coils is from the inside out. This requires removing the coil guards or grilles (if provided), the fan guards and blades to access the coil surface. The sprayer can then be worked across the coil pushing the dirt and debris out. Although this does extend the time involved, the results are well worth it. This method should be used at least once a year. Spraying the coil from the outside repeatedly can push a majority of the dirt to the inner section of the fins and continue to restrict air flow. Keep in mind you may not have the luxury of shutting the unit(s) down for an extended time. A scheduled shutdown with the operator may be in order. If using a cleaner along with the spraying process, follow recommended manufacturer instructions and be sure to rinse the coil thoroughly. Any residue left on the coil can act as a magnet to dirt.
Vertiv | Liebert® 10-fan Drycooler User Manual| 34

5.2.2 Maintenance Inspection Checklist

Date:____________________________________ Prepared By:____________________________________
Model #:_________________________________ Serial Number:__________________________________
NOTE: Regular inspections are necessary to assure proper cleanliness of the cooling fins. Should inspection reveal dirt or corrosion, appropriate cleaning should be performed.
Monthly Semiannually
Drycooler Drycooler
_____1. Coil surfaces free of debris _____1. Complete all monthly items
_____2. Fans/grilles free of debris _____2. Piping in good condition
_____3. Fan motors securely mounted _____3. Piping secure
_____4. Motor bearings in good condition _____4. Wash coil as needed
_____5. No water/glycol leaks Pump Package
Pump Package _____ 1. Complete all monthly items
_____1. Pump rotation _____2. Test changeover operation
_____2. Pump securely mounted _____3. Pump #1 amp draw __________
_____3. No water/glycol leaks Pump #1 amp draw __________
_____4. No abnormal noises Pump #1 amp draw __________
_____4. Glycol level and general condition
_____5. Glycol freeze point ____°F and pH ____
_____6. Check all electrical connect
_____7. Check contactors for pitting
Drycooler Electric Panel
_____1. Check all electrical connections
_____2. Check all electrical connections
_____3. Operational sequence/setpoints
Fan Motors
_____1. Motor #1 amp draw __________ amps
_____2. Motor #2 amp draw __________ amps
_____3. Motor #3 amp draw __________ amps
_____4. Motor #4 amp draw __________ amps
_____5. Motor #5 amp draw __________ amps
_____6. Motor #6 amp draw __________ amps
_____7. Motor #7 amp draw __________ amps
_____8. Motor #8 amp draw __________ amps
_____9. Motor #9 amp draw __________ amps
____10. Motor #10 amp draw __________ amps
Vertiv | Liebert® 10-fan Drycooler User Manual| 35
NOTES:
Signature: ______________________________________________________________________________
Make photocopies of this form for your records.
Vertiv | Liebert® 10-fan Drycooler User Manual| 36

6 TROUBLESHOOTING

Symptom Possible Cause C heck Or Remedy
No main power Check L1, L 2 and L 3 for r ated voltage
Disconnect switch open Close disconnect switch
Blown fuse or circuit breaker tripped
Unit will not operate
Unit runs, butmotor protector keeps tripping
Outlet temperature from unittoo high
Liquidsquirts from surge tank fill cap when pump is turned off
Pump suddenly stops pumping Clogged strainer or impeller Clean outdebris
Pumping suddenly slows Clogged impeller, diffuser or line Cleanoutdebris and use s trainer
Excessive leakage around the pumps haft while operating
Pump performance poor
Pump has noisy operation
Pump discharge press ure too high
Control fuse or circuitbreaker tripped
Improperly wired Check wiring diagram
No outputvoltage from transformer
Motor protector defective Replace protector
Motor protector too small Check amp. draw
Fan or pumpmotor has shorted winding
Low or unbalanced voltage Determine r eason and correct
Low or no coolant flow
Ambientair temperature higher thandesign
Heat load higher thandesign
Throttling valve improperly Res et valve to proper differential pres sure
Air in system Ventall highpoints, repeat as necessar y. Check liquidlevel in surge tank.
Worn seal or packing Replace seal or packing
Worn impeller or seal Replace withnew impeller or s eal
Suctionlifttoo high Relocate pumpcloser to supply
Motor not up to speed; low voltage
Worn bearings Replace pump
Worn motor bearings Replace pump
Low discharge head Throttle discharge -- improve conditions
Debris lodgedin impeller Remove cover and clean out
Cavitating pumps Adjust s ystem pres sures
Throttling valve improperly set Reset valve to proper differential pressure
Valve closed in circuit Open all valves downstream of unit
Strainer cloggedor dirty Remove strainer plug and clean
Check fuses or circuitbreaker
Check for 24 VAC. If no voltage, check for s hort. Replace fuse or res et circuit breaker.
Check for 24 VAC. If no voltage, check primary voltage
Repair motor
See Pump will not operate or no coolant flow on the next page entry in this table
Correct possible hot air discharge to fans from another source
Check for misapplication, need larger cooler. Correct possible additionalheat loadbeing added to cooling circuit.
Larger lead wires may be required. Check for proper line voltage,±10%
Vertiv | Liebert® 10-fan Drycooler User Manual| 37
Symptom Possible Cause C heck Or Remedy
No power to pump motor See Unit will notoperate on the previous page in this table
Low coolant level Check coolantlevel
Tubes plugged in cooling coil Flush coil withreputable cleaner
Pump will notoperate or no coolantflow
Valve closed downstream of cooling unit
Strainer cloggedor dirty Remove strainer plug and clean
Pump cavitating ( err atic gauge operation)
Open all valves
Possibility of air in lines. Bleed all components. Check surge tank to pump inlet connection. Check for pipingrestrictions.
Vertiv | Liebert® 10-fan Drycooler User Manual| 38
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2017 Vertiv Co. Allrights reserved. Vertiv and the Vertivlogo are trademarks or registered trademarks of VertivCo. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims allliability, for damages resulting from use of this information or for any errors or omissions. Spec ifications are subject to change without notice.
SL-10061_REV3_10-17/590-1691-501A
Loading...