Operation and Maintenance Manual — 225-600kVA, Three-Phase, SingleModule & Multi-Module
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission of
Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Vertiv| Liebert® NX™ Operation and Maintenance Manual | iv
IMPORTANT SAFETY INSTRUCTIONS
!
!
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your
Liebert NX UPS. Read this manual thoroughly, paying special attention to the sections that apply
to your installation, before working with the UPS. Retain this manual for use by installing
personnel.
WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
This UPS has several circuits that are energized with high DC as well as AC voltages. Check
for voltage with both AC and DC voltmeters before working within the UPS. Check for
voltage with both AC and DC voltmeters before making contact.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should be involved in installing the UPS or preparing the UPS for
installation. When performing maintenance with any part of the equipment under power,
service personnel and test equipment should be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance.
Special safety precautions are required for procedures involving handling, operation and
maintenance of the UPS system. Observe all safety precautions in the installation manual,
SL-25535, and in this manual before as well as during performance of all maintenance
procedures. Observe all DC safety precautions before working on or near the DC system.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or
death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury
to personnel. The UPS module weight is up to 4450lb. (2019kg).
Locate center of gravity symbols and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from
vertical at all times.
Slots at the base of the module cabinets are intended for forklift use. Base slots will support
the unit only if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging
from unit, or prepare unit for installation
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 1
!
WARNING
!
Risk of electric shock and fire. Can cause equipment damage, personal injury or death.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the UPS system should be kept free of puddles of water, excess
moisture and debris.
Only test equipment designed for troubleshooting should be used. This is particularly true
for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before
making contact or using tools. Even when the power is turned Off, dangerously high
potential electric charges may exist at the capacitor banks and at the DC connections.
All wiring must be installed by a properly trained and qualified electrician. All power and
control wiring must comply with all applicable national, state and local codes.
One person should never work alone, even if all power is disconnected from the equipment.
A second person should be standing by to assist and to summon help in case of an
accident.
Battery Cabinet Precautions
The following warning applies to all battery cabinets supplied with UPS systems. Additional
warnings and cautions applicable to battery cabinets may be found in Important Safety Instructions on page 1 and 5.4 - Battery Maintenance.
WARNING
Risk of electric shock, fire and smoke. Can cause equipment damage, injury and death.
Internal battery strapping must be verified by manufacturer prior to moving a battery
cabinet after initial installation.
• Do not tilt.
Call 1-800-543-2378 before moving battery cabinets after initial installation.
For systems using DC sources other than batteries, refer to the manufacturer’s
recommendations for handling and care.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or
IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life
support equipment are subject to additional terms and conditions.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC
rules. These limits provide reasonable protection against harmful interference in a commercial
environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used
in accordance with this instruction manual, may cause harmful interference to radio communications.
Operation of this unit in a residential area may cause harmful interference that the user must correct at
his own expense.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 2
1.0 INTRODUCTION
1.1GENERAL DESCRIPTION
The Liebert NX UPS is a maximum-efficiency UPS that provides continuous, high-quality AC
power to business-critical equipment, such as telecommunications and data processing
equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in
voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges
and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse-width modulation,
transformer-free technology and fully digital controls to enhance its reliability and efficiency and
increase the ease of use.
As shown in Figure 1, the AC utility source is input to the rectifier which converts the AC utility
into DC power at the DC bus operating voltage. This feeds the inverter and the DC/DC
booster/charger. The inverter converts that DC power from the rectifier—or DC power from the
DC source (via the booster/charger)—into AC power for the load.
The DC source will power the load through the inverter in the event of a power failure. When the
system is being powered by the utility, the booster/charger converts a portion of the DC power
from the rectifier to a voltage suitable for charging the batteries or other DC source. When the
load is being powered by the DC source, the booster/charger converts the DC source output to
the voltage needed to drive the inverter.
The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to an external maintenance bypass.
NOTE
Vertiv recommends that the Liebert NX 225-600kVA always be installed with a maintenance
bypass system that fully isolates the UPS from the load and the AC power source. This allows
service personnel to safely repair the UPS if needed while maintaining power to the critical load.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 3
Figure 1Typical single module UPS system one-line diagram
BFB
CB1
(Note 5)
UPS Module
2 Wire +GND
(See Note 2)
3 Wire
+ GND
To DC Supply
Module Rectifier
AC Input
Module Bypass
AC Input
UPS
Output
3 Wire + GND
Critical
Load
Booster/
Charger
3 Wire + GND
AC
DC
1. UPS rectifier bypass input and output cables must be run in separate
conduits.
2. All power cables from DC supply should be sized for a total maximum of
2V drop at maximum discharge current.
3. Control wiring and power wiring must be run in separate conduits.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 4
1.2MODES OF OPERATION
1.2.1Normal Mode
Operating in normal mode, the Liebert NX's rectifier derives power from a utility AC source and
supplies regulated DC power to the inverter, which regenerates precise AC power to supply the
connected equipment. The rectifier also uses the utility source power to charge the DC sources.
1.2.2Eco Mode
When the Liebert NX 225-600 kVA is in Eco Mode, the load will be supported by the bypass
source as long as the power quality of the bypass source remains within specified limits. This
reduces energy consumption and boosts efficiency to greater than 98%. If the power quality of
the bypass source deviates from acceptable levels, the inverter will take the load and the UPS will
operate in normal mode. It will remain in normal mode until the power quality of the bypass source
has remained within limits for a suitable time, at which point the Liebert NX will return to Eco
Mode.
Eco Mode may be inhibited either automatically, such as when the Liebert NX is being fed by a
generator source, or manually, by sending a signal to one of the programmable input contacts.
Examples of control circuits to provide this functionality and a more detailed explanation of Eco
Mode operation can be found in 2.6 - Eco Mode Active.
1.2.3Bypass Mode
When the Liebert NX is in bypass mode, the load is directly supported by utility power and is
without DC source backup protection.
The Liebert NX’s inverter and bypass static switch will shift the load from the inverter to bypass
mode without an interruption in AC power if the inverter is synchronous with the bypass and any
of the following occurs:
•Inverter fails
• Inverter overload capacity is exceeded
• Inverter is manually turned Off by the user
• UPS is operating on battery and battery voltage reaches end of discharge level
NOTE
If the inverter is not in sync with the bypass, the static switch will transfer the load from the
inverter to the bypass WITH interruption in AC power to the critical load. The default interruption
time is 16ms; the minimum is 4ms. Vertiv
™
can adjust the length of the interruption.
1.2.4Battery Mode
When utility AC power fails, the Liebert NX protects the critical load by instantaneously
channeling DC source power to the inverter, which continues supporting the critical load without
interruption.
When utility power returns and is within acceptable limits, the Liebert NX automatically shifts
back to Normal mode, with the rectifier powering the critical load.
1.2.5Maintenance Bypass
The installation of a Maintenance Bypass Cabinet or Assembly is recommended to allow you to
totally isolate the UPS from all power sources. Use of the Maintenance Bypass is described in
2.0 - Operation.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 5
1.3OPTIONS
A number of options are available from Vertiv for your UPS system. Some options are not
available for all ratings. Described below are the most frequently provided options. Other options
are available. Contact your Vertiv sales representative for more information.
• LIFE Services™—A remote service delivery capability which enables the UPS to alert a special Vertiv
Support Center to provide more efficient and proactive identification, resolution, and prevention of
potential UPS issues.
• Network and BMS Connectivity and Monitoring—Communication cards support SNMP, Modbus or both
(Dual Protocol)
• Battery and Racks—The batteries provide power in the event of a power outage. The Liebert NX UPS can
use a variety of battery types, provided the battery plant is designed for the UPS DC voltage range and the
load requirements of your application.
• Battery Cabinets—Valve-regulated, lead-acid (VRLA) sealed batteries are available in matching cabinets
for convenient installation and maintenance in otherwise unprotected space. Depending on the UPS
module rating, two or more cabinets may be connected in parallel to provide the additional run time.
• Module Battery Disconnect—The UPS system utilizes a separate Module Battery Disconnect for remotely
located batteries. A sensing circuit in the UPS module, set at the battery low voltage limit, trips the Module
Battery Disconnect to safeguard the battery from excessive discharge. The Module Battery Disconnect
has an undervoltage release mechanism designed to ensure that during any shutdown or failure mode all
battery potential is removed from the UPS system.
• Battery DC Ground Fault Detection—Monitors battery ground fault current and generates a warning on
the UPS touchscreen LCD and other customer-specific annunciation options.
• Maintenance Bypass—This switchboard provides make-before-break maintenance bypass. It includes:
Maintenance Bypass Breaker (MBB) and Maintenance Isolation Breaker (MIB).
• Load Bus Synchronization—The Load Bus Sync (LBS) option keeps independent UPS systems (and
therefore their critical load buses) in sync, even when the modules are operating on DC source or
asynchronous AC sources. This means that critical loads connected to both load buses can switch
seamlessly between the two.
• MultiBus Synch Module (MBSM)—Permits synchronizing operation of up to 11 UPS modules.
• Input Circuit Breaker—The UPS may be equipped with an internal input circuit breaker (CB1).
• Remote Status Panel—This option provides key status indicators. If ordered with your UPS, the power
supply for this option is factory installed. To add this option to a unit which has already been shipped
contact Liebert Service.
• EPO (Emergency Power Off)—Your UPS may be equipped with an EPO button on its front panel near the
operator touch screen. Contacts for a remote EPO to be installed on site are also provided standard on all
units.
• Temperature-Compensated Charging—When the battery temperature exceeds a preset limit (typically
77°F [25°C]), this optional circuit proportionally reduces float charging voltage to prevent overcharging the
battery.
• Battery Load Testing—When activated, this option forces the battery string to assume the load for a short
period of time.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 6
2.0 OPERATION
Input Circuit
Breaker, CB1
Back-Feed Circuit
Breaker, BFB
Static Switch
Subassembly
External
Communication
Panel (Comms
Options)
Rectifier
Subassemblies
Inverter
Subassemblies
DC-DC
Converter
Subassemblies
Control LCD
The Liebert NX UPS is equipped with a microprocessor-based display touchscreen designed for
convenient and reliable operation. The display is driven by menu-prompted software.
The Liebert NX interface display enables the operator to perform such tasks as:
The touchscreen display has a blue background and multicolored text. The display turns On
automatically, but dims and the back-light goes out after 15 minutes of inactivity. Touching the
screen will reactivate the back-light for 15 minutes. If any screen other than the mimic screen is
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 9
• Check operational status
• Monitor the power flow through the UPS system and all meter readings
• Execute operational procedures
• Check status reports and event files
• Adjustment programmable parameters
accessed, that screen will be displayed for 5 minutes without any interaction. If there is no activity
4
1
3
5
9
2
6
8
7
1. Bypass Input: Voltage and frequency readings
2. Animated One Line Mimic
3. System Status
4. About Button
5. Output: Voltage, current and frequency readings
6. Battery: Voltage and current readings
7. Control Buttons
8. Menu Buttons
9. Line power Input: Voltage, current and frequency
readings
Green
Gray
Green
Green
Green
COLOR CODE FOR ICONS
AND POWER PATH LINES
Green = OK and In the Active Power Path
Gray = Not Active
Yellow = Advisory
Red = Faulted or Disabled
Green
Critical
Load
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module Bypass
AC Input
UPS
Output
AC
DC
Booster/
Charger
for 5 minutes, the display will revert to the basic mimic screen.
Figure 5Main display screen, typical
Figure 6Normal Mode
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 10
Figure 7Utility fail
BFB
UPS Module
From DC Supply
Module Rectifier
AC Input
Module Bypass
AC Input
UPS
Output
Critical
Load
Booster/
Charger
BFB
UPS Module
To DC Supply
Module Rectifier
AC Input
Module By pass
AC Input
UPS
Output
Critical
Load
Booster/
Charger
Figure 8Load on bypass
2.3TOUCHSCREEN NAVIGATION
Several menu items can be accessed from the main display screen (see Figure 17). These menu
items are detailed in subsequent sections.
2.3.1Main Display Screen
This is the default screen. It displays the following information:
• Bypass Input Voltage
• Bypass Input Frequency
•Input Voltage
•Input Current
• Input Frequency
•Output Voltage
•Output Current
• Output Frequency
• DC Source Voltage
• DC Source Current
System Status
Only one of the following three status indicators is actively highlighted at any given time:
System Normal Indicator—When the green check mark status icon (?) is highlighted, the system
is operating normally and no warning or alarm has occurred. During line power failures (with all
other conditions being nominal), this icon is not highlighted.
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 11
Warning Indicator—The yellow triangle icon is activated and highlighted by abnormal
In this case, the UPS is operating in double-conversion mode without power backup. All power paths (except the internal
bypass and maintenance bypasses lines) are green (active). The bypass static switch and the bypass lines are gray,
Green
Gray
Green
Green
Green
Red
conditions that could affect the normal operation of the UPS. These conditions do not originate
with the UPS, but may be caused either by the surrounding environment or by the electrical
installation (line power side and load side). A description of the active warning(s) can be viewed
by touching the yellow triangle or using the Status button at the bottom of the page.
Fault Indicator—When the red circle with white cross is highlighted, immediate attention should
be given to the severity of the alarm, and service should be called promptly. A description of the
active alarm(s) can be viewed by touching the Status button at the bottom of the page.
No matter which indicator is active, all available diagnostic information on the unit can be
displayed by touching this area.
Control Buttons: Start Inverter and Stop Inverter—The touchscreen display features two
buttons for starting and shutting down the inverter. The start/stop control incorporates a safety
feature for preventing accidental operation. When the start or stop function for the inverter is
selected, a pop-up window appears asking for confirmation of the action.
Reset Fault—Reset faults (becomes red when there is a system fault).
Alarm Silence—Silence the buzzer in the case of an alarm.
NOTE
If screen is inactive for 30 seconds, the LCD will revert to the system status screen.
2.3.2 Status
This menu item displays a Status summary of warnings, faults and other events, as well as status
screens for each functional block, such as Rectifier, Inverter and Load.
Figure 9Main display screen, MBD open
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 12
Figure 10 Load status
Green
Green
Green
Green
Gray
Green
Green
Gray
Green
Green
Green
Green
Figure 11Rectifier status
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 13
Figure 12 Bypass status
Green
Gray
Green
Green
Green
Green
Green
Gray
GreenGreen
Green
Green
Figure 13 Inverter status
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 14
Figure 14 Charger/Booster status
Green
Gray
GreenGreen
Green
Green
Green
Gray
GreenGreen
Green
Red
Figure 15 Battery status
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 15
2.3.3 Events Log Menu
This menu item displays recent Events that occurred while the UPS was in operation.
Figure 16 Status summary
2.3.4 Measures Menu
This menu item displays the full set of measurements for each functional block (rectifier, bypass,
booster/charger, batteries, inverter and load).
Table 1Measurements for functional blocks
RectifierBypassInverterCharger/BoosterBatteryLoad
Voltage - L-LVoltage - L-LTemperatures
Current - PhaseFrequency—
Frequency——
kVA per Phase——Battery VoltageBackup TimekW per Phase
Temperatures——Battery CurrentCapacitykVA per Phase
Rectifier
Output Voltage
Input Supervision
Counter
(# of Mains failures)
———— —Load%
———— —
——Temperatures—Frequency
————
Booster
Output Voltage
Booster Output
Voltage Setting
Charger Current
Limit
Battery Voltage% per phase
Battery CurrentVoltage L-L
TemperaturesCurrent per Phase
Overload Time
Remaining
Tota l Loa d Power
(kW)
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 16
Table 1Measurements for functional blocks
RectifierBypassInverterCharger/BoosterBatteryLoad
———— —
———— —
Figure 17 Rectifier measures
Tota l Loa d Power
(kVA)
Ambient
Temperature
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 17
Figure 18 Bypass measures
Figure 19 Inverter measures
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 18
Figure 20 Charger/Booster measures
Figure 21 Battery measures
Vertiv™ |Liebert® NX™ Operation and Maintenance Manual | 19
Loading...
+ 57 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.