The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages result from
use of this information or for any errors or omissions.
Refer to local regulations and building codes relating to the application,
installation, and operation of this product. The consulting engineer, installer,
and/or end user is responsible for compliance with all applicable laws and
regulations relation to the application, installation, and operation of this
product.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use, or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
4.3 Transferring from Normal (Inverter) to Bypass Mode50
4.4 Transferring from Bypass to Normal (Inverter) Mode51
4.5 Transferring to Maintenance Bypass Mode52
4.6 Transferring from Maintenance Bypass to Normal Mode52
4.7 Remote Emergency Power Off (REPO)53
5 Maintenance55
5.1 Cleaning the UPS55
5.2 Routine Maintenance55
6 Specifications57
6.1 Standard Battery Backup Time with a Single UPS59
Appendices61
Appendix A: UPS Prompts and Alarms61
ii
Vertiv™ Liebert® ITA2 Installer/User Guide
Important Safety Information
IMPORTANT! This manual contains important safety instructions that must be followed during the installation and
maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory information,
available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install, connect to supply, or
operate this UPS.
Importan t Safety Information
1
Vertiv™ Liebert® ITA2 Installer/User Guide
This page intentionally left blank
2
Importan t Safety Information
Vertiv™ Liebert® ITA2 Installer/User Guide
1 Product Description
The Vertiv™ Liebert® ITA2 uninterruptible power system (UPS) is an intelligent, online UPS with sine wave output. The UPS
offers reliable, high-quality AC power to small-scale computer centers, networks, communication systems, automatic control
systems, and similar sensitive electronic equipment.
1.1 Front-panel Components
The front panel of the UPS provides ventilation holes and an operation/display panel with LED indicators and function keys.
Figure 1.1 Liebert® ITA2 UPS
ItemDescription
1Ventilation holes
2Menu keys, see 1.1 above .
3LCDpanel. See Operation and Display Panel on page37 .
4Run/Alarm indicator LEDs, see LED Indicators on page38 .
5Power button, see 1.1 above .
1 Pr oduct Descri ption
3
Vertiv™ Liebert® ITA2 Installer/User Guide
1.2 Rear Panel Components
Figure 1.2 UPS Rear Panel with Terminal Block Battery Connectors
ItemDescription
1Vertiv™ Liebert® IntelliSlot™ port
2Dry contac t port
3REPO port
4RS-232 port
5Multi-functionport
6Parallel/LBS ports
7Ventilation holes
8AC output terminals
9AC input terminals
10Ventilation holes
11Battery input terminals
12USB port
4
1 Pr oduct Descri ption
Figure 1.3 UPS Rear Panel with Plug-n-Play Battery Connectors
ItemDescription
1Liebert®IntelliSlot™ port
2Dry contac t port
Vertiv™ Liebert® ITA2 Installer/User Guide
3REPO port
4RS-232 port
5Multi-functionport
6Parallel/LBS ports
7Ventilation holes
8AC output terminals
9AC input terminals
10Ventilation holes
11Battery-connector ports
12USB port
1.3 UPS States and Operating Modes
NOTE: See Table 3.2 on page38 , for description of the run indicator and alarm indicator LED's mentioned in this
section.
1 Pr oduct Descri ption
5
Vertiv™ Liebert® ITA2 Installer/User Guide
1.3.1 Normal Mode
Normal operation supplies clean, conditioned, sine wave power to connected equipment from normal utility input. The
battery charger charges the batteries. On the front panel display, the run indicator (green)is On, the alarm indicator is Off
and the buzzer is silent.
Figure 1.4 Normal Mode Operation
6
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide
1.3.2 Battery Mode
Battery Mode supplies battery power to the load if utility power fails or if the utility voltage goes outside of the permissible
range. On the front panel display, the run indicator (green) is On, the alarm indicator (yellow)is On, and the buzzer beeps
once each second. The LCD "Current" screen displays "On Battery."
Figure 1.5 Battery Mode Operation
ItemDescription
1Bypass input
2Maintenance bypass breaker (MBB )
3Bypass input breaker (BIB)
4Static switch
5Rectifier input
6Rectifier input breaker (RIB)
7Rectifier
8Battery charger
9Battery
10Inverter
11Automatic inverter switch
12Maintenance isolation breaker (MIB)
13UPSoutput
1 Pr oduct Descri ption
7
Vertiv™ Liebert® ITA2 Installer/User Guide
1.3.3 Bypass Mode
Bypass Mode supplies power to the load from the bypass source if an overload or fault occurs during normal operation. On
the front panel display, the run indicator (green) is On, the alarm indicator (yellow)is On, and the buzzer beeps once each
second. The LCD "Current" screen displays "On Bypass."
Figure 1.6 Bypass Mode Operation
ItemDescription
1Bypass input
2Maintenance byass breaker (MBB )
3Bypass input breaker (BIB)
4Static switch
5Rectifier input
6Rectifier input breaker (RIB)
7Rectifier
8Battery charger
9Battery
10Inverter
11Automatic inverter switch
12Maintenance isolation breaker (MIB)
13UPSoutput
8
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide
1.3.4 Auto Restart Mode
When enabled, which is the default setting, Auto Restart Mode automatically restarts the UPS after a shutdown that resulted
from depleted batteries after an extended power outage. A built-in 10-second delay after utility power is restored allows
other equipment to start first and stabilize before the UPS restarts.
1.3.5 Fault State
When the UPS is in Normal Mode and the inverter fails or UPS overtemperature occurs, operation transfers to Bypass Mode.
When the UPS is in Battery Mode (with no bypass utility), and the inverter fails or overtemperature occurs, the UPS shuts
down and stops output power. During a fault state, the front panel display alarm indicator (red)is On, the buzzer beeps
continuously, and fault information displays on the LCD.
1.3.6 Maintenance Bypass Mode
Used when the UPS requires maintenance or repair, Maintenance Bypass Mode operation powers the connected equipment
with utility power while electrically isolating the internal UPS components.
The optional Liebert® ITA2 Maintenance Bypass Cabinet (MBC) is required for this mode. If your system includes a Liebert
ITA2 MBC, refer to the Liebert ITA2 MBC Installer/User Guide, available on the product page at www.Vertiv.com.
NOTICE
Risk of power interruption. Can damage the connected equipment.
If utility power fails or if its quality is out of range while the UPS is in Maintenance Bypass Mode, the UPS may
shut down without notice and shut off output power to the load.
NOTE: The UPS has no user-serviceable parts. If the UPS malfunctions and requires service, visit
http://www.Vertiv.com/en-us/support/ or contact your local Vertiv™ representative.
1.3.7 Start up on Bypass Mode
Default : Disabled. When the inverter is in the soft start stage, the bypass mode will not be automatically triggered.
Change the startup on bypass via Paramset or the LCD settings page to enable.
When the DC bus soft start is completed, the bypass mode will be automatically triggered. If the inverter can enter the soft
start stage and the soft start is completed, the ups will automatically switch from bypass mode to normal mode.
When the DC bus soft start is completed, the bypass mode will be automatically triggered. If the inverter can not
automatically enter the soft start phase, the ups will always operate in the bypass mode.
1 Pr oduct Descri ption
9
Vertiv™ Liebert® ITA2 Installer/User Guide
This page intentionally left blank
10
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide
2 Installation
Installation must be performed by properly trained and qualified personnel. Do not start the UPS until after the installation is
finished and the system is commissioned by an authorized engineer.
WARNING! Risk of electrical shock. Can cause property damage, injury, and death. The unit has several
circuits that are energized with high DC and AC voltages. Check for voltage with both AC and DC voltmeters
before making contact and before working within the UPS. Only properly trained and qualified personnel
wearing appropriate, OSHA-approved personal protective equipment (PPE) should prepare for installation,
install and maintain the equipment. When performing maintenance with any part of the equipment under
power, service personnel and test equipment must stand on rubber mats.
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out
and tagged appropriately to prevent activation during the installation. After the power cables are connected,
the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
WARNING! Risk of heavy unit falling. Improper handling can cause equipment damage, injury, and death.
Exercise extreme care when handling unit cabinets and rack-mounted units to avoid equipment damage or
injury to personnel. The UPS weighs approximately 50.7lb. (23kg).
NOTE: The UPS can be connected to 3-phase, 5-wire (A, B, C, N, PE) TN, TT and IT AC power distribution system
(IEC60364-3).
2.1 Pre-Installation Preparation
Before beginning the installation, consider the environmental requirements, service clearances and external protective
devices for installing the equipment.
2.1.1 Environment of Installation Area
Install the UPS in a clean, well-ventilated environment with the ambient temperature within the specifications listed in 6 on
page57 .
The environment must:
•Have convenient wiring.
•Have adequate access for operators.
•Be clean and well-ventilated.
•Be free from water, heat source and flammable and explosive substances.
•Be free from dust, volatile gases and corrosive materials.
•Comply with local fire codes.
2 In stallation
11
Vertiv™ Liebert® ITA2 Installer/User Guide
2.1.2 Installation Clearances
Internal fans provide forced-air cooling for the UPS. Cooling air enters through the front panel and hot air is exhausted
through the back. Maintain at least 8 in.(200mm) in the front and rear of the UPS, see Figure 2.1 below .
Figure 2.1 Required Clearances
ItemDescription
1UPS (top view).
2Wall or other solid surface.
2.1.3 Installation Tools
IMPORTANT! All tools used to install and maintain the ITA2 UPS and equipment must be insulated.
The following tools are required to properly install your UPS:
•Torque Wrench
•Slotted screwdriver
•Multimeter
•#3 Phillips-head screwdriver
•T10 Torx screwdriver
12
2 In stallation
Vertiv™ Liebert® ITA2 Installer/User Guide
2.1.4 Storage
If you do not install the UPSimmediately, you must store it indoors and protect it from excessive moisture, heat and other
harsh conditions. Store the batteries in a dry, well-ventilated environment with a temperature range of 68°F ~ 77°F (20°C ~
25°C).
NOTICE
Risk of failure to properly charge batteries. Can damage the batteries and void the warranty.
Batteries will lose charge during storage. Batteries must be recharged as recommended by the battery
manufacturer every 3 to 6 months, depending on the storage temperature:
•At 68-77°F (20-25°C): charge after 6 months in storage
•At 78-86°F (26-30°C): charge after 3 months in storage
•At 87°F or higher (31°C or higher): charge after 1 month in storage.
2.1.5 External Protective Devices
Circuit breakers and other external protective devices must be installed on the UPS input. The following sections provide
general guidance for installation by properly trained and qualified personnel.
Rectifier and Bypass Input Protection
Overcurrent Protection—Install an appropriate overcurrent protective device should on the utility input power distribution.
Consider the current capacity of power cables and the system-overload requirements in selection of the input protection
and wiring, see Table 2.1 on page18 , and Table 2.2 on page19 .
Dual-Input System Protection—In a dual-input system, install separate protective devices for the utility and bypass at the
utility input power distribution.
Utility/Bypass Back-Feed Protection—The UPS includes back-feed protection in the event of a fault.
Earth Leakage Current—The residual current detector (RCD) for the UPS upstream input power distribution should be:
•Sensitive to the DC unidirectional pulse (Level A) in the power distribution network
•Insensitive to the transient current pulse
•General sensitivity type, settable: 0.3A ~ 1A
The residual current circuit breaker (RCCB) must be sensitive to the DC unidirectional pulse (Level A) in the power
distribution network, but insensitive to the transient current pulse, see Figure 2.2 below .
Figure 2.2 RCCB symbols
2 In stallation
When using the earth RCD in a split-bypass system, the RCD should be installed at the upstream input power distribution
end to prevent false alarms.The earth leakage current fed by the RFI filter in the UPS ranges from 3.5mAto100mA.
Vertiv™ recommends that you verify the sensitivity of each differential device of the upstream input power distribution and
downstream power distribution (to load).
13
Vertiv™ Liebert® ITA2 Installer/User Guide
Battery
The UPS includes an overcurrent protection device for the battery.
UPS Output
The UPS includes output overcurrent protection in all modes of operation. If the customer-provided output distribution
panel is not within sight of the UPS, the distribution panel must include a main breaker.
2.2 Equipment Handling and Unpacking
WARNING! Risk of heavy unit falling. Improper handling can cause equipment damage, injury, and death.
Exercise extreme care when handling unit cabinets and rack-mounted units to avoid equipment damage or
injury to personnel. The UPS weighs approximately 50.7lb. (23kg).
During unpacking:
•Inspect the UPS for damage. If you find any problem, file a damage claim with the carrier immediately and
send a copy to Vertiv at:
Attn: Traffic Department
Vertiv Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43085 USA
•Check the accessories and model numbers against the delivery list. If you find any problem, notify your local
Vertiv representative immediately.
2.3 Tower Installation
NOTE: The UPS may be installed with a maintenance bypass cabinet (MBC) or battery cabinets. If so, install the MBC
and battery cabinets before installing the UPS.
14
2 In stallation
1.Take the support bases out of the accessories box.
2. If battery cabinets will be connected, take out the spacers that shipped with the battery cabinet.
3. If an MBC will be connected, take out the spacers shipped with the accessories.
4. Connect the spacers and the support bases as shown in Figure 2.3 below . Each tower assembly requires
twosupport base/spacer assemblies, one in the front and one in the rear.
5. Place the UPS, battery cabinets and the MBC on the twosupport base assemblies.
Figure 2.3 Support Bases
Vertiv™ Liebert® ITA2 Installer/User Guide
ItemDescription
1Support bases
2Spacers with connectors
Figure 2.4 Tower-Mounted Liebert® ITA2 UPS System with Battery Cabinets and MBC
2 In stallation
15
Vertiv™ Liebert® ITA2 Installer/User Guide
2.4 Rack Installation
NOTICE
Risk of improper transport. Can cause damage to the UPS, MBC or battery cabinets.
Never attempt to lift or move the UPS, MBC or battery cabinets with the rack brackets. The brackets and
screws are not meant to lift the units.
NOTICE
Risk of improper installation. Can make rack top-heavy and cause a tipping hazard.
The battery cabinets are heavier than the UPS. Vertiv™ recommends installing the battery cabinets as near the
bottom of the rack as possible to maintain a low center of gravity. Install the UPS above the battery cabinets.
Install each unit on its own set of rack-mount guide rails. The rail kit will support the weight of a single UPS,
MBC or battery cabinet.
NOTE: The UPS may be installed with a maintenance bypass cabinet (MBC) or battery cabinets. If so, install the MBC
and battery cabinets before installing the UPS.
To mount the unit in the rack:
NOTE: Install the battery cabinets from bottom to top to minimize tipping hazard.
1.Referring to Figure 2.5 on the facing page , use four of the M4×10 screws on each bracket, and attach a
bracket to each front corner.
2. Referring to Figure 2.5 on the facing page , mount the right and left guide rails for the UPS and each battery
cabinet:
•Adjust the length of each guide rail to the dimensions of the rack.
•Align the install holes on the ends of the rail to the square holes in the rack, and use four of the provided
screws, two on each end to attach the rail to the rack.
3. Place the unit on the guide rails and push it completely into the rack along the guide rails.
4. Use M5×16 screws to secure the unit brackets to the rack, see Figure 2.5 on the facing page .
16
2 In stallation
Figure 2.5 Guide Rail and Rack Bracket Installation
Vertiv™ Liebert® ITA2 Installer/User Guide
2 In stallation
ItemDescription
1Bracket screw, four per bracket
2Bracket, two
3Rail screw, four per rail
4Guide rail, one per side
5Rac k-mount screw, four per bracket
17
Vertiv™ Liebert® ITA2 Installer/User Guide
Figure 2.6 Rack-Mounted Liebert® ITA2 UPS System with Battery Cabinets and MBC
2.5 Connecting Power Cables
WARNING! Risk of electrical shock. Can cause property damage, injury and death. The unit has several
circuits that are energized with high DC and AC voltages. Check for voltage with both AC and DC voltmeters
before making contact and before working within the UPS. Only properly trained and qualified personnel
wearing appropriate, OSHA-approved personal protective equipment (PPE) should prepare for installation,
install and maintain the equipment. When performing maintenance with any part of the equipment under
power, service personnel and test equipment must stand on rubber mats.
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out
and tagged appropriately to prevent activation during the installation. After the power cables are connected,
the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
When connecting input and output cables, follow national and local wiring regulations, take the environment into account
and refer to NFPA70, Table310-16. The recommended minimum cables and overcurrent protection are listed in Table 2.1
below , and Table 2.2 on the facing page . The values are based upon an 86°F(30°C)ambient temperature.
The UPS has two modes of output power distribution, self-distribution and via the optional maintenance bypass cabinet.
These steps describe self-distribution mode connections. The connections for maintenance bypass power distribution are
included with the installation instructions for the ITA2 MBC.
Table 2.1 Currents and Wire Size—UPS Rectifier Input
Unit Rating
8kVA24308AWG8AWG10AWG30lb-in.
10kVA37506AWG6AWG10AWG30lb-in.
18
Maximum Current,
Amps
Recommended OPD,
Amp Trip
75°C THW
Copper Wire (ph ase)
Numb er of Cables per
Phase: 1
75°C THW
Copper Wire
(neutral)
Numb er of
Cables: 1
75°C THW
Copper Wire
(Ground)
Numb er of
Cables: 1
Recommended
Torque
2 In stallation
Table 2.2 AC Currents and Wire Size—UPS Bypass Input* and Output
Tyco Electronics: 1 577648-1Ty co Electronics: 132331-1—
2.5.1 Connecting a Single-Input Configuration
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning
installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out
and tagged appropriately to prevent activation during the installation. After the power cables are connected,
the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
Recommended
Torque
1.Prepare for connection by removing the conduit box cover, opening knockout holes and routing cables through
the conduit.
2. Leave the shorting busbars in place on the UPS input terminal block.
3. Refer to the single-input terminal block illustrated in Figure 2.7 on page21 , and connect the cables from the
upstream feeder panel:
•Phase A to L1
•Phase B to L2
•Phase C to L3
•Neutral to N
•Ground to PE (next to pA)
NOTE: The UPS has two output terminal block sections, “always on” and “programmable/controllable.” The always on
connections are listed first, and the programmable connections are inside parentheses.
4. For output connections, refer to Figure 2.7 on page21 , and connect the cables from the UPS to the
downstream feeder panel on the panelboard main breaker:
•A (pA) to PhaseA
•B (pB) to PhaseB
•C (pC) to PhaseC
•Neutral N (N) to neutral bus
•Ground from PE (stud next to C) to the ground bus
2 In stallation
19
Loading...
+ 51 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.