Vertiv ITA2 User Manual

Liebert® ITA2
Installer/User Guide
8 - 10kVA, 60Hz, 208/220V, Three-Phase UPS
Vertiv™ Liebert® ITA2 Installer/User Guide
Refer to local regulations and building codes relating to the application, installation, and operation of this product. The consulting engineer, installer, and/or end user is responsible for compliance with all applicable laws and regulations relation to the application, installation, and operation of this product.
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
Vertiv™ | Liebert® ITA2 In staller/U ser Guide
Vertiv™ Liebert® ITA2 Installer/User Guide
TABLE OF CONTENTS
Important Safety Information 1
1 Product Description 3
1.1 Front-panel Components 3
1.2 Rear Panel Components 4
1.3 UPS States and Operating Modes 5
1.3.1 Normal Mode 6
1.3.2 Battery Mode 7
1.3.3 Bypass Mode 8
1.3.4 Auto Restart Mode 9
1.3.5 Fault State 9
1.3.6 Maintenance Bypass Mode 9
1.3.7 Start up on Bypass Mode 9
2 Installation 11
2.1 Pre-Installation Preparation 11
2.1.1 Environment of Installation Area 11
2.1.2 Installation Clearances 12
2.1.3 Installation Tools 12
2.1.4 Storage 13
2.1.5 External Protective Devices 13
2.2 Equipment Handling and Unpacking 14
2.3 Tower Installation 14
2.4 Rack Installation 16
2.5 Connecting Power Cables 18
2.5.1 Connecting a Single-Input Configuration 19
2.5.2 Connecting a Dual-input Configuration 22
2.6 Connecting a Single Battery Cabinet System 23
2.6.1 Connecting the Cables 23
2.7 Connecting Additional Battery Cabinet Systems 29
2.8 Communication Connections 32
2.8.1 Liebert IntelliSlot Ports 32
2.8.2 REPO Connection 33
2.8.3 Dry Contact Connections 34
2.8.4 Connecting USB Communication Cables 35
2.9 Connecting Serial Port Communication Cables 35
2.9.1 Connecting Multi-Function Port (RJ-45) 36
3 Operation and Display Panel 37
3.1 LED Indicators 38
3.2 Audible Alarm (Buzzer) 38
3.3 LCD Menu and Screens 39
i
Vertiv™ Liebert® ITA2 Installer/User Guide
3.3.1 Startup and UPS Mimic Screens 39
3.3.2 Main Menu 40
3.4 Editing Display and Operation Settings 43
3.4.1 Changing the Password 46
3.4.2 Selecting the Display Language 46
3.4.3 Setting the Date and Time 46
4 Operating the UPS 49
4.1 Silencingthe Audible Alarm 49
4.2 UPS Startup 49
4.3 Transferring from Normal (Inverter) to Bypass Mode 50
4.4 Transferring from Bypass to Normal (Inverter) Mode 51
4.5 Transferring to Maintenance Bypass Mode 52
4.6 Transferring from Maintenance Bypass to Normal Mode 52
4.7 Remote Emergency Power Off (REPO) 53
5 Maintenance 55
5.1 Cleaning the UPS 55
5.2 Routine Maintenance 55
6 Specifications 57
6.1 Standard Battery Backup Time with a Single UPS 59
Appendices 61
Appendix A: UPS Prompts and Alarms 61
ii
Vertiv™ Liebert® ITA2 Installer/User Guide

Important Safety Information

IMPORTANT! This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory information, available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install, connect to supply, or operate this UPS.
Importan t Safety Information
1
Vertiv™ Liebert® ITA2 Installer/User Guide
This page intentionally left blank
2
Importan t Safety Information
Vertiv™ Liebert® ITA2 Installer/User Guide

1 Product Description

The Vertiv™ Liebert® ITA2 uninterruptible power system (UPS) is an intelligent, online UPS with sine wave output. The UPS offers reliable, high-quality AC power to small-scale computer centers, networks, communication systems, automatic control systems, and similar sensitive electronic equipment.

1.1 Front-panel Components

The front panel of the UPS provides ventilation holes and an operation/display panel with LED indicators and function keys.
Figure 1.1 Liebert® ITA2 UPS
Item Description
1 Ventilation holes
2 Menu keys, see 1.1 above .
3 LCDpanel. See Operation and Display Panel on page37 .
4 Run/Alarm indicator LEDs, see LED Indicators on page38 .
5 Power button, see 1.1 above .
1 Pr oduct Descri ption
3
Vertiv™ Liebert® ITA2 Installer/User Guide

1.2 Rear Panel Components

Figure 1.2 UPS Rear Panel with Terminal Block Battery Connectors
Item Description
1 Vertiv™ Liebert® IntelliSlot™ port
2 Dry contac t port
3 REPO port
4 RS-232 port
5 Multi-functionport
6 Parallel/LBS ports
7 Ventilation holes
8 AC output terminals
9 AC input terminals
10 Ventilation holes
11 Battery input terminals
12 USB port
4
1 Pr oduct Descri ption
Figure 1.3 UPS Rear Panel with Plug-n-Play Battery Connectors
Item Description
1 Liebert®IntelliSlot™ port
2 Dry contac t port
Vertiv™ Liebert® ITA2 Installer/User Guide
3 REPO port
4 RS-232 port
5 Multi-functionport
6 Parallel/LBS ports
7 Ventilation holes
8 AC output terminals
9 AC input terminals
10 Ventilation holes
11 Battery-connector ports
12 USB port

1.3 UPS States and Operating Modes

NOTE: See Table 3.2 on page38 , for description of the run indicator and alarm indicator LED's mentioned in this section.
1 Pr oduct Descri ption
5
Vertiv™ Liebert® ITA2 Installer/User Guide

1.3.1 Normal Mode

Normal operation supplies clean, conditioned, sine wave power to connected equipment from normal utility input. The battery charger charges the batteries. On the front panel display, the run indicator (green)is On, the alarm indicator is Off and the buzzer is silent.
Figure 1.4 Normal Mode Operation
6
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide

1.3.2 Battery Mode

Battery Mode supplies battery power to the load if utility power fails or if the utility voltage goes outside of the permissible range. On the front panel display, the run indicator (green) is On, the alarm indicator (yellow)is On, and the buzzer beeps once each second. The LCD "Current" screen displays "On Battery."
Figure 1.5 Battery Mode Operation
Item Description
1 Bypass input
2 Maintenance bypass breaker (MBB )
3 Bypass input breaker (BIB)
4 Static switch
5 Rectifier input
6 Rectifier input breaker (RIB)
7 Rectifier
8 Battery charger
9 Battery
10 Inverter
11 Automatic inverter switch
12 Maintenance isolation breaker (MIB)
13 UPSoutput
1 Pr oduct Descri ption
7
Vertiv™ Liebert® ITA2 Installer/User Guide

1.3.3 Bypass Mode

Bypass Mode supplies power to the load from the bypass source if an overload or fault occurs during normal operation. On the front panel display, the run indicator (green) is On, the alarm indicator (yellow)is On, and the buzzer beeps once each second. The LCD "Current" screen displays "On Bypass."
Figure 1.6 Bypass Mode Operation
Item Description
1 Bypass input
2 Maintenance byass breaker (MBB )
3 Bypass input breaker (BIB)
4 Static switch
5 Rectifier input
6 Rectifier input breaker (RIB)
7 Rectifier
8 Battery charger
9 Battery
10 Inverter
11 Automatic inverter switch
12 Maintenance isolation breaker (MIB)
13 UPSoutput
8
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide

1.3.4 Auto Restart Mode

When enabled, which is the default setting, Auto Restart Mode automatically restarts the UPS after a shutdown that resulted from depleted batteries after an extended power outage. A built-in 10-second delay after utility power is restored allows other equipment to start first and stabilize before the UPS restarts.

1.3.5 Fault State

When the UPS is in Normal Mode and the inverter fails or UPS overtemperature occurs, operation transfers to Bypass Mode. When the UPS is in Battery Mode (with no bypass utility), and the inverter fails or overtemperature occurs, the UPS shuts down and stops output power. During a fault state, the front panel display alarm indicator (red)is On, the buzzer beeps continuously, and fault information displays on the LCD.

1.3.6 Maintenance Bypass Mode

Used when the UPS requires maintenance or repair, Maintenance Bypass Mode operation powers the connected equipment with utility power while electrically isolating the internal UPS components.
The optional Liebert® ITA2 Maintenance Bypass Cabinet (MBC) is required for this mode. If your system includes a Liebert ITA2 MBC, refer to the Liebert ITA2 MBC Installer/User Guide, available on the product page at www.Vertiv.com.
NOTICE
Risk of power interruption. Can damage the connected equipment.
If utility power fails or if its quality is out of range while the UPS is in Maintenance Bypass Mode, the UPS may shut down without notice and shut off output power to the load.
NOTE: The UPS has no user-serviceable parts. If the UPS malfunctions and requires service, visit http://www.Vertiv.com/en-us/support/ or contact your local Vertiv™ representative.

1.3.7 Start up on Bypass Mode

Default : Disabled. When the inverter is in the soft start stage, the bypass mode will not be automatically triggered.
Change the startup on bypass via Paramset or the LCD settings page to enable.
When the DC bus soft start is completed, the bypass mode will be automatically triggered. If the inverter can enter the soft start stage and the soft start is completed, the ups will automatically switch from bypass mode to normal mode.
When the DC bus soft start is completed, the bypass mode will be automatically triggered. If the inverter can not automatically enter the soft start phase, the ups will always operate in the bypass mode.
1 Pr oduct Descri ption
9
Vertiv™ Liebert® ITA2 Installer/User Guide
This page intentionally left blank
10
1 Pr oduct Descri ption
Vertiv™ Liebert® ITA2 Installer/User Guide

2 Installation

Installation must be performed by properly trained and qualified personnel. Do not start the UPS until after the installation is finished and the system is commissioned by an authorized engineer.
WARNING! Risk of electrical shock. Can cause property damage, injury, and death. The unit has several circuits that are energized with high DC and AC voltages. Check for voltage with both AC and DC voltmeters before making contact and before working within the UPS. Only properly trained and qualified personnel wearing appropriate, OSHA-approved personal protective equipment (PPE) should prepare for installation, install and maintain the equipment. When performing maintenance with any part of the equipment under power, service personnel and test equipment must stand on rubber mats.
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out and tagged appropriately to prevent activation during the installation. After the power cables are connected, the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
WARNING! Risk of heavy unit falling. Improper handling can cause equipment damage, injury, and death. Exercise extreme care when handling unit cabinets and rack-mounted units to avoid equipment damage or injury to personnel. The UPS weighs approximately 50.7lb. (23kg).
NOTE: The UPS can be connected to 3-phase, 5-wire (A, B, C, N, PE) TN, TT and IT AC power distribution system (IEC60364-3).

2.1 Pre-Installation Preparation

Before beginning the installation, consider the environmental requirements, service clearances and external protective devices for installing the equipment.

2.1.1 Environment of Installation Area

Install the UPS in a clean, well-ventilated environment with the ambient temperature within the specifications listed in 6 on page57 .
The environment must:
Have convenient wiring.
Have adequate access for operators.
Be clean and well-ventilated.
Be free from water, heat source and flammable and explosive substances.
Be free from dust, volatile gases and corrosive materials.
Comply with local fire codes.
2 In stallation
11
Vertiv™ Liebert® ITA2 Installer/User Guide

2.1.2 Installation Clearances

Internal fans provide forced-air cooling for the UPS. Cooling air enters through the front panel and hot air is exhausted through the back. Maintain at least 8 in.(200mm) in the front and rear of the UPS, see Figure 2.1 below .
Figure 2.1 Required Clearances
Item Description
1 UPS (top view).
2 Wall or other solid surface.

2.1.3 Installation Tools

IMPORTANT! All tools used to install and maintain the ITA2 UPS and equipment must be insulated.
The following tools are required to properly install your UPS:
Torque Wrench
Slotted screwdriver
Multimeter
#3 Phillips-head screwdriver
T10 Torx screwdriver
12
2 In stallation
Vertiv™ Liebert® ITA2 Installer/User Guide

2.1.4 Storage

If you do not install the UPSimmediately, you must store it indoors and protect it from excessive moisture, heat and other harsh conditions. Store the batteries in a dry, well-ventilated environment with a temperature range of 68°F ~ 77°F (20°C ~ 25°C).
NOTICE
Risk of failure to properly charge batteries. Can damage the batteries and void the warranty.
Batteries will lose charge during storage. Batteries must be recharged as recommended by the battery manufacturer every 3 to 6 months, depending on the storage temperature:
At 68-77°F (20-25°C): charge after 6 months in storage
At 78-86°F (26-30°C): charge after 3 months in storage
At 87°F or higher (31°C or higher): charge after 1 month in storage.

2.1.5 External Protective Devices

Circuit breakers and other external protective devices must be installed on the UPS input. The following sections provide general guidance for installation by properly trained and qualified personnel.
Rectifier and Bypass Input Protection
Overcurrent Protection—Install an appropriate overcurrent protective device should on the utility input power distribution. Consider the current capacity of power cables and the system-overload requirements in selection of the input protection and wiring, see Table 2.1 on page18 , and Table 2.2 on page19 .
Dual-Input System Protection—In a dual-input system, install separate protective devices for the utility and bypass at the utility input power distribution.
Utility/Bypass Back-Feed Protection—The UPS includes back-feed protection in the event of a fault.
Earth Leakage Current—The residual current detector (RCD) for the UPS upstream input power distribution should be:
Sensitive to the DC unidirectional pulse (Level A) in the power distribution network
Insensitive to the transient current pulse
General sensitivity type, settable: 0.3A ~ 1A
The residual current circuit breaker (RCCB) must be sensitive to the DC unidirectional pulse (Level A) in the power distribution network, but insensitive to the transient current pulse, see Figure 2.2 below .
Figure 2.2 RCCB symbols
2 In stallation
When using the earth RCD in a split-bypass system, the RCD should be installed at the upstream input power distribution end to prevent false alarms.The earth leakage current fed by the RFI filter in the UPS ranges from 3.5mAto100mA. Vertiv™ recommends that you verify the sensitivity of each differential device of the upstream input power distribution and downstream power distribution (to load).
13
Vertiv™ Liebert® ITA2 Installer/User Guide
Battery
The UPS includes an overcurrent protection device for the battery.
UPS Output
The UPS includes output overcurrent protection in all modes of operation. If the customer-provided output distribution panel is not within sight of the UPS, the distribution panel must include a main breaker.

2.2 Equipment Handling and Unpacking

WARNING! Risk of heavy unit falling. Improper handling can cause equipment damage, injury, and death. Exercise extreme care when handling unit cabinets and rack-mounted units to avoid equipment damage or injury to personnel. The UPS weighs approximately 50.7lb. (23kg).
During unpacking:
Inspect the UPS for damage. If you find any problem, file a damage claim with the carrier immediately and send a copy to Vertiv at:
Attn: Traffic Department
Vertiv Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43085 USA
Check the accessories and model numbers against the delivery list. If you find any problem, notify your local Vertiv representative immediately.

2.3 Tower Installation

NOTE: The UPS may be installed with a maintenance bypass cabinet (MBC) or battery cabinets. If so, install the MBC and battery cabinets before installing the UPS.
14
2 In stallation
1. Take the support bases out of the accessories box.
2. If battery cabinets will be connected, take out the spacers that shipped with the battery cabinet.
3. If an MBC will be connected, take out the spacers shipped with the accessories.
4. Connect the spacers and the support bases as shown in Figure 2.3 below . Each tower assembly requires twosupport base/spacer assemblies, one in the front and one in the rear.
5. Place the UPS, battery cabinets and the MBC on the twosupport base assemblies.
Figure 2.3 Support Bases
Vertiv™ Liebert® ITA2 Installer/User Guide
Item Description
1 Support bases
2 Spacers with connectors
Figure 2.4 Tower-Mounted Liebert® ITA2 UPS System with Battery Cabinets and MBC
2 In stallation
15
Vertiv™ Liebert® ITA2 Installer/User Guide

2.4 Rack Installation

NOTICE
Risk of improper transport. Can cause damage to the UPS, MBC or battery cabinets.
Never attempt to lift or move the UPS, MBC or battery cabinets with the rack brackets. The brackets and screws are not meant to lift the units.
NOTICE
Risk of improper installation. Can make rack top-heavy and cause a tipping hazard.
The battery cabinets are heavier than the UPS. Vertiv™ recommends installing the battery cabinets as near the bottom of the rack as possible to maintain a low center of gravity. Install the UPS above the battery cabinets.
Install each unit on its own set of rack-mount guide rails. The rail kit will support the weight of a single UPS, MBC or battery cabinet.
NOTE: The UPS may be installed with a maintenance bypass cabinet (MBC) or battery cabinets. If so, install the MBC and battery cabinets before installing the UPS.
To mount the unit in the rack:
NOTE: Install the battery cabinets from bottom to top to minimize tipping hazard.
1. Referring to Figure 2.5 on the facing page , use four of the M4×10 screws on each bracket, and attach a bracket to each front corner.
2. Referring to Figure 2.5 on the facing page , mount the right and left guide rails for the UPS and each battery cabinet:
Adjust the length of each guide rail to the dimensions of the rack.
Align the install holes on the ends of the rail to the square holes in the rack, and use four of the provided screws, two on each end to attach the rail to the rack.
3. Place the unit on the guide rails and push it completely into the rack along the guide rails.
4. Use M5×16 screws to secure the unit brackets to the rack, see Figure 2.5 on the facing page .
16
2 In stallation
Figure 2.5 Guide Rail and Rack Bracket Installation
Vertiv™ Liebert® ITA2 Installer/User Guide
2 In stallation
Item Description
1 Bracket screw, four per bracket
2 Bracket, two
3 Rail screw, four per rail
4 Guide rail, one per side
5 Rac k-mount screw, four per bracket
17
Vertiv™ Liebert® ITA2 Installer/User Guide
Figure 2.6 Rack-Mounted Liebert® ITA2 UPS System with Battery Cabinets and MBC

2.5 Connecting Power Cables

WARNING! Risk of electrical shock. Can cause property damage, injury and death. The unit has several circuits that are energized with high DC and AC voltages. Check for voltage with both AC and DC voltmeters before making contact and before working within the UPS. Only properly trained and qualified personnel wearing appropriate, OSHA-approved personal protective equipment (PPE) should prepare for installation, install and maintain the equipment. When performing maintenance with any part of the equipment under power, service personnel and test equipment must stand on rubber mats.
WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out and tagged appropriately to prevent activation during the installation. After the power cables are connected, the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
When connecting input and output cables, follow national and local wiring regulations, take the environment into account and refer to NFPA70, Table310-16. The recommended minimum cables and overcurrent protection are listed in Table 2.1 below , and Table 2.2 on the facing page . The values are based upon an 86°F(30°C)ambient temperature.
The UPS has two modes of output power distribution, self-distribution and via the optional maintenance bypass cabinet. These steps describe self-distribution mode connections. The connections for maintenance bypass power distribution are included with the installation instructions for the ITA2 MBC.
Table 2.1 Currents and Wire Size—UPS Rectifier Input
Unit Rating
8kVA 24 30 8AWG 8AWG 10AWG 30lb-in.
10kVA 37 50 6AWG 6AWG 10AWG 30lb-in.
18
Maximum Current,
Amps
Recommended OPD,
Amp Trip
75°C THW
Copper Wire (ph ase)
Numb er of Cables per
Phase: 1
75°C THW
Copper Wire
(neutral)
Numb er of
Cables: 1
75°C THW
Copper Wire
(Ground)
Numb er of
Cables: 1
Recommended
Torque
2 In stallation
Table 2.2 AC Currents and Wire Size—UPS Bypass Input* and Output
Vertiv™ Liebert® ITA2 Installer/User Guide
Unit Rating
8kVA 23 30 10AWG 10AWG 10AWG 30lb-in.
10kVA 28 40 8AWG 8AWG 10AWG 30lb-in.
Maximum Current,
Amps
* Bypass input for dual-input configurationsonly.
Recommended OPD,
Amp Trip
75°C THW
Copper Wire (ph ase)
Numb er of Cables per
Phase: 1
75°C THW
Copper Wire
(neutral)
Numb er of
Cables: 1
75°C THW
Copper Wire
(Ground)
Numb er of
Cables: 1
Table 2.3 Ring Terminal Part Numbers
AWG (mm2)
10 (5.26) 8 (8.36) 6 (13.3)
McMaster-Carr: 7113K462 McMaster-Carr: 7113K444 McMaster-Carr: 711 3K366
Manufacturer Part#
Thomas & Betts: RC1 0-14 Thomas & Betts: RDV71 7 Thomas & Betts: RE6-14
Tyco Electronics: 1 577648-1 Ty co Electronics: 132331-1

2.5.1 Connecting a Single-Input Configuration

WARNING! Risk of electrical shock. Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent protection devices are open (Off), and that they are locked out and tagged appropriately to prevent activation during the installation. After the power cables are connected, the terminal block’s protective cover must be reinstalled to remove the electric shock hazard.
Recommended
Torque
1. Prepare for connection by removing the conduit box cover, opening knockout holes and routing cables through the conduit.
2. Leave the shorting busbars in place on the UPS input terminal block.
3. Refer to the single-input terminal block illustrated in Figure 2.7 on page21 , and connect the cables from the upstream feeder panel:
Phase A to L1
Phase B to L2
Phase C to L3
Neutral to N
Ground to PE (next to pA)
NOTE: The UPS has two output terminal block sections, “always on” and “programmable/controllable.” The always on connections are listed first, and the programmable connections are inside parentheses.
4. For output connections, refer to Figure 2.7 on page21 , and connect the cables from the UPS to the downstream feeder panel on the panelboard main breaker:
A (pA) to PhaseA
B (pB) to PhaseB
C (pC) to PhaseC
Neutral N (N) to neutral bus
Ground from PE (stud next to C) to the ground bus
2 In stallation
19
Loading...
+ 51 hidden pages