Vertiv GXT-MT+ 6 KVA ES, GXT-MT+ 10 KVA ES User Manual

LIEBERT® GXT MT + 6 kVA  10 kVA TOWER
Compact Tower UPS for High Performance Power Protection
Liebert® GXT MT+ features true on-line double conversion technology, delivering best-in-class power protection for critical applications
Liebert GXT MT+ features an attractive design style, together with an LCD display and synoptic scheme in the front panel for easy use. Load protection is ensured with DSP control technology, wide input voltage operation and high output power factor (0.8). Its small size, the shutdown software included and the maintenance bypass make the Liebert GXT MT+ the perfect and safest choice to protect your critical load.
Flexibility:
yy Multiple communication options
(USB, RS232)
yy Network and volt-free contact cards
(optional)
yy LCD display and intuitive synoptic in
the front panel for easy UPS status.
Higher Availability:
yy Wide input voltage range
yy Input circuit breaker
yy Maintenance bypass
yy Automatic frequency detection.
Optimized Total Cost of Ownership:
yy Minimized installation time and costs
yy Small and compact footprint and size.
Ideally Suited for:
yy VoIP equipment
yy Small oice networks
yy Computer rooms
yy Process automation equipment
yy Network storage devices.
Lieber t GXT MT+ 6 kVA - 10 kVA Tower
LIEBERT® GXT MT + 6 kVA  10 kVA Tower
Liebert® GXT MT + 6 kVA - 10 kVA Tower Specifications
MODEL NUMBER GXTMT+ 6 KVA ES GXTMT+ 10 KVA ES
Power Rating 6000 VA / 4800 W 10000 VA / 8000 W
DIMENSIONS, W x D x H - mm
Unit 190 x 369 x 6 88 190 x 442 x 688
Shipping 290 x 495 x 910 320 x 580 x 910
WEIGHT  KG
Unit 60 75
Shipping 65 81
INPUT AC PARAMETERS
Voltage Range Without Bat tery Operation
Frequency Range (synchronization) 46 - 54 or 56 - 6 4 Hz; Autosen sing
Input Socket Hardwired (L-N-G)
Output Sockets Hardwired (L-N-G)
Voltage 208 / 220 / 23 0 / 240 V AC
Waveform Sinewave
BATTERY PARAMETE RS
Typ e Valve-regulated, non-spillable, lead acid
Internal Batteries Yes
Quantity x Voltage x Rating 16 x 12 V x 9 Ahr 20 x 12 V x 9 Ahr
Recharge Time 9 hours recovers to 90% capacity ( Typical)
External Battery Cabinets Not permitted
ENVIRONMENTAL
Operating Temperature 0 ºC to 40 ºC
Relative Humidity <95% non condensing
Operating Altitude <1000 m without derating
Audible Noi se <55 dBA @ 1 meter <58 dBA @ 1 meter
STANDARDS AND CERTIFICATIONS
Safety EN62040-1:2008
EMC EN62040-2:2006 class C3
Compliance CE
(1)
From 110 V to 176 V AC derati ng applie s.
Note: Ext ernal bat tery cabinets a re not permitted. I nternal ba tterie s only.
(1)
From 110 to 300 V AC
Intelligent slot
RS232 (DB9) communication port
Cooling fans
Maintenance bypass
Emergency Power O (EPO)
USB communication port
Input breaker
Input /Output
Tech Support Always On! Our Commitment to your daily Business, provided by multi language Tech Support.
Toll-free 0080011554499
Lieber t GXT MT+ 6 kVA - 10 kVA Tower
Toll +39 02 98250222 eoc@VertivCo.com
VertivCo.com | Emerson Network Power Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2016 Vertiv C o. All rights reserve d. Vertiv™, the Vertiv logo a nd Liebert® GXT MT + 6 kVA - 10 kVA Tower are trade marks or registered t rademarks of Vertiv Co. A ll other names and log os referred to are trade na mes, trademarks or re gistered trademar ks of their respective ow ners. While every p recaution has bee n taken to ensure accura cy and completenes s herein, Vertiv Co. as sumes no responsi bility, and disclaims a ll liability, for damag es resulting from use o f this information or for an y errors or om issions. Speci fications are subje ct to change without n otice.
MKA4L0UKGXTG2 Rev.1-08/2014