Vertiv GXT-MT+ 6 KVA ES, GXT-MT+ 10 KVA ES User Manual

LIEBERT® GXT MT + 1 kVA  3 kVA Gen. 2
Compact Tower UPS for High Performance Power Protection
Liebert® GXT MT+ Gen. 2 features true on-line double conversion technology, delivering best-in-class power protection for critical applications
The new Liebert GXT MT+ Gen. 2 has been designed according to comprehensive technical specifications, allowing it to provide a high level of availability for connected IT equipment.
Its Eco mode function is in charge of delivering high levels of eiciency, leading to optimized total cost of ownership (TCO) advantages.
Liebert GXT MT+ furthermore oers intelligent monitoring and network management functions for improved system shutdown and control.
Flexibility:
yy Multiple communication options
(USB, RS232)
yy Network and volt-free contact cards
(optional)
yy Schuko and IEC output sockets
yy Frequency converter operation
50/60 Hz.
Higher Availability:
yy Wide input voltage range
yy Input circuit breaker
yy Automatic frequency detection.
Optimized Total Cost of Ownership:
yy Eco mode for high eiciency
yy Minimized installation time
and costs.
Ideally Suited for:
yy VoIP equipment
yy Small oice networks
yy Computer rooms
yy Process automation equipment
yy Network storage devices.
Lieber t GXT MT+ 1 kVA - 3 kVA Gen. 2
LIEBERT® GXT MT + 1 kVA  3 kVA Gen. 2
Liebert® GXT MT + 1 kVA - 3 kVA Gen. 2 Specifications
MODEL NUMBER GXT MT+ 1 KVA G2 ES GXT MT+ 2 KVA G2 ES GXT MT+ 3 KVA G2 ES
Power Rating 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W
DIMENSIONS, W x D x H - mm
Unit 145 x 282 x 22 3 145 x 397 x 23 8 190 x 421 x 33 6
Shipping 230 x 360 x 325 230 x 472 x 325 320 x 560 x 460
WEIGHT  KG
Unit 9.7 17. 3 27. 5
Shipping 10.7 18.7 29.5
INPUT AC PARAMETERS
Voltage Range Without Bat tery Operation
Frequency Range (synchronization) 47 - 53 or 57 - 63 Hz; Autosensing
Input Socket 1 x IEC 320 - C14 1 x IEC 320 C20
Output Sockets
Voltage 220 / 230 / 24 0 V AC
Waveform Sinewave
BATTERY PARAMETE RS
Typ e Valve-regulated, non-spillable, lead acid
Internal Batteries Yes
Quantity x Voltage x Rating 2 x 12 V x 9 Ahr 4 x 12 V x 9 Ahr 6 x 12 V x 9 Ahr
Recharge Time 4 hours recovers to 90% capacity ( Typical)
External Battery Cabinets Not permitted
ENVIRONMENTAL
Operating Temperature 0 ºC to 40 ºC
Relative Humidity 20% to 90% non condensing
Operating Altitude <1000 m without derating
Audible Noi se <50 dBA @ 1 meter
STANDARDS AND CERTIFICATIONS
Safety EN62040-1:2008
EMC EN62040-2:2006 class C2
Compliance CE
(1)
From 110 V to 175 V AC, an d 280 V to 300 V AC, d erating ap plies .
Note: Ext ernal bat tery ca binets are n ot permi tted. Internal bat teries on ly.
(1)
3 x IEC320 C1 3 &
1 x Schuko
From 110 to 300 V AC
3 x IEC 320 C13 &
2 x Schuko & Terminals
Slot (for opti onal card)
USB Port & RS 232 Port (DB9)
USB Port &
Input breaker
RS232 Por t (DB9)
IEC320 C13 socket s
Schuko socket s
Input breaker
IEC320 C1 3
socket s
Schuko socket s
Output
terminals
Tech Support Always On! Our Commitment to your daily Business, provided by multi language Tech Support.
AC Input
Lieber t GXT MT+ G2 - 1 kVA Lieber t GXT MT+ G2 - 2 kVA Lieber t GXT MT+ G2 - 3 kVA
Toll-free 0080011554499 Toll +39 02 98250222 eoc@VertivCo.com
VertivCo.com | Emerson Network Power Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827
© 2016 Vertiv C o. All rights reserve d. Vertiv™, the Vertiv logo a nd Liebert® GXT MT + 1 kVA - 3 kVA Gen. 2 ar e trademarks or regis tered trademarks of Vert iv Co. All other names an d logos referred to are tr ade names, tradem arks or registered trademar ks of their respective ow ners. While every p recaution has bee n taken to ensure accura cy and completenes s herein, Vertiv Co. as sumes no responsi bility, and disclaims a ll liability, for damag es resulting from use o f this information or for an y errors or om issions. Speci fications are subje ct to change without n otice.
MKA4L0UKGXTG2 Rev.1-08/2014
Loading...