Vermont Casting SDV30 User Manual

INSTALLER / CONSUMER
CERT IF IED
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
SAFETY INFORMATION
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE.
WARNING! IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY Installation and service must be performed by a qualified installer, service agency or the gas suppler.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier from
your neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
DO NOT STORE OR USE GASO­LINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
Stardance Direct Vent/Natural Vent Gas Heater
Model SDV30: 3900-3916, 3940­3956
This appliance may be installed in an after market permanently located manufactured (mobile) home where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases unless a certified kit is used.
Homeowner’s Installation
and Operating Manual
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
20007065 1/07 Rev. 13
Stardance Direct Vent/Natural Vent Gas Heater
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a Vermont Castings stove.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible fire hazard and will void the warranty.
Installation & Operating Instructions .............................................................................................3
Stove Dimensions ................................................................................................................4
Installation Requirements .....................................................................................................
Locating the Stove ...............................................................................................................5
Clearance Requirements .....................................................................................................5
Parallel & Corner Installation ................................................................................................
Wall and Ceiling Clearances ................................................................................................6
Hearth Requirements ...........................................................................................................
Gas Specifications................................................................................................................7
Gas Inlet and Manifold Pressures ........................................................................................7
Horizontal & Termination - Direct Vent ONLY .......................................................................
Vertical Termination - Direct Vent ONLY ...............................................................................8
Vent Termination Clearances ...............................................................................................
General Venting Information - Termination Location ..........................................................10
Termination Clearances .....................................................................................................11
Venting Requirements - Natural Vent ONLY ......................................................................11
Venting Requirements and Options - Direct Vent ONLY ....................................................
Assembly Procedures
Install the Optional Fan ......................................................................................................13
Venting System Assembly - Direct Vent .............................................................................14
Install Vent Adapter Pipe ....................................................................................................
Side Wall Termination Assembly ........................................................................................15
Vent Termination Below Grade ...........................................................................................
Vertical (Through the Roof) Vent Assembly .......................................................................17
Venting System Assembly - Natural Vent ...........................................................................18
Install the Vent Pipe ...........................................................................................................
Install the Log Set ..............................................................................................................19
Connect Gas Supply Line ..................................................................................................
Burner Information..............................................................................................................20
Air Shutter Adjustment & Instructions .................................................................................20
Complete the Assembly .....................................................................................................
Install ON/OFF Switch ........................................................................................................21
Thermostat Connection (Optional) .....................................................................................
Install the Front Plate .........................................................................................................22
Operation
Your First Fire .....................................................................................................................
Pilot and Burner Information ..............................................................................................23
Flame & Temperature Adjustment / Flame Characteristics ................................................
Lighting and Operating Instructions ...................................................................................24
Troubleshooting - Honeywell #8420 Gas Control System ..................................................25
Instructions for RF Comfort Control Valve ..........................................................................
Fuel Conversion Instructions ..............................................................................................30
Maintenance
Annual System Inspection ..................................................................................................33
Logset and Burner/Cleaning and Inspection ......................................................................33
Care of Cast Iron ................................................................................................................
Cleaning the Glass .............................................................................................................33
Glass Replacement ............................................................................................................
Gasket Replacement ..........................................................................................................34
Inspect the Vent System Annually ......................................................................................34
Check the Gas Flame Regularly ........................................................................................
Stove Disassembly .............................................................................................................34
Wiring Diagram ...................................................................................................................
Replacement Parts .........................................................................................................................36
Optional Accessories ....................................................................................................................39
Warranty
2
Energuide ........................................................................................................................................44
..........................................................................................................................................42
5
6
6
7
8
12
14
17
19
19
21
22
23
23
26
33
33
34
35
20007065
Stardance Direct Vent/Natural Vent Gas Heater
General Information
The Stardance Direct Vent/Natural Vent Room Heater, Model Nos. 3900-3916, 3940-3956 is a vented gas appliance listed to the ANSI standard Z21.88b-2002 and CSA-2.33b-2002 for Vented Room Heaters, and CSA 2.17-M91, Gas-Fired Appli ances For Use at High Altitudes.
The installation of the Stardance Direct Vent/Natural Vent Room Heater must conform with local codes, or in the absence of lo­cal codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition and CSA B-149.1 Installation Code. (EXCEP TION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP gas at maximum input.) Refer to Page 32 (RF only).
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation, or company that either in person or through a representative is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the con­nection, installation, repair, or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
The Stardance Direct Vent/Natural Vent Room Heater should be inspected before use and at least annually by a qualified service agency. It is imperative that control com­partments, burners, and circulating air passageways of the appliance be kept clean.
The Stardance Direct Vent/Natural Vent Room Heater and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Stardance Direct Vent/Natural Vent Room Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
‘Direct Vent’ describes a sealed combustion system in which incoming outside air for combustion and outgoing exhaust enter and exit through two separate concentric passages within the same sealed vent system. The system does not use room air to support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof. Conventional venting systems (Natural Vent) take air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere.
This appliance is approved for bedroom installations in the U.S. and Canada.
This appliance may be installed in an aftermarket* manufac­tured (mobile) home, where not prohibited by state or local codes.
-
-
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
The Stardance Direct Vent/Natural Vent Room Heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located out of traffic and away from furniture and draperies.
WARNING: This appliance is hot while in operation. Keep children, clothing, and furniture away. Contact may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be care­fully supervised when they are in the same room as the appliance.
Clothing or other flammable materials should not be placed on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the appli­ance.
The appliance area must be kept clear and free from com­bustible materials, gasoline, and other flammable vapors and liquids.
The flow of combustion and ventilation air must not be obstructed. The installation must include adequate acces­sibility and clearance for servicing and proper operation.
WARNING: Do not operate the Room Heater with the glass panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualified service person.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is de­signed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing. Proposition 65 Warning:
oil fired appliances, and the products of combustion of such fu els, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
* Aftermarket:
from the manufacturer.
Completion of sale, nor for purpose of resale,
Fuels used in gas, woodburning or
-
20007065
3
Stardance Direct Vent/Natural Vent Gas Heater
9"
(229 mm)
C
L
Valve Inlet
26"
(680 mm)
25"
(635 mm)
14"
(355 mm)
3"
(76 mm)
C
L
Valve Inlet
Stardance Direct Vent / Natural Vent Dimensions
Attention
The Stardance stove is shipped from the factory as a Direct Vent Gas Heater. This heater may be converted into a Natural Vent unit in the field. If a Natural Vent heater is desired, the Vermont Castings Z31D00 FSDHAG Draft Hood must be directly installed to the top of the unit according to the installation instructions. The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item.
When the Stardance stove is converted to Natural Vent, it uses 4” vent pipe. For aes­thetic purposes the CFM direct vent system may be used up to the ceiling.
4
20007065
Installation Requirements
A
B
E
C
D
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP­TION: Do not derate this appliance for altitude. Main­tain the manifold pressure at 3.5 inches w.c. for Natural Gas, and 10 inches w.c. for Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualified ser vice person who is familiar with the building codes and installation techniques appropriate for your area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to refer a qualified service person.
WARNING: Due to high temperatures, the HEATER should be located out of traffic and away from fur­niture and draperies.
The surface of the Heater Is hot when it is in use. Young children should be watched carefully when they are in the same room when the Heater is in use, and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances that follow.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements. NOTE: We do not recommend the use of wallpaper
next to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the wallpaper adhesive.
Stardance Direct Vent/Natural Vent Gas Heater
-
ST207
Fig. 2 Possible stove locations.
Clearance Requirements
Minimum Clearances to Combustible
Materials
Measure side clearances as shown in Figures 3 and 4 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the steel rear skirt.
The Stardance heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel instal­lation.
Warning:
• Always maintain required clearances (air spaces) to nearby combustibles to prevent fire hazard. Do not fill air spaces with insula­tion. All venting components must maintain a 1” (25 mm) clearance to combustible materials. Maintain a 6” (150 mm) clearance when using a single wall pipe.
• The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent appliance must use its own separate vent system. Common vents are pro­hibited.
• Refer to the manufacturer’s instructions in­cluded with the venting system for complete installation procedures.
20007065
5
Stardance Direct Vent/Natural Vent Gas Heater
C
L
C
L
B
D
C
A
A
A
B
B
A
A
C
D
B
Parallel Installation: Minimum Clearance
and Flue Centerline, Direct Vent and
Natural Vent
ST128b
Stove Clearances: A: 4” (102 mm) B: 4” (102 mm) Pipe Centerlines: C: 15¹⁄₂” (395 mm) D: 9” (229 mm)
Fig. 3 Parallel installation, minimum back and side clear­ances, and flue centerlines.
Wall Centerline from Floor
Direct Vent Only
ST131b
Effective Minimum Wall Thimble 56” (1480 mm) (CFM Pipe) Centerline 52” (1378 mm) (Simpson Duravent Pipe)
Fig. 5 Minimum wall thimble centerline.
Wall and Ceiling Clearances
Corner Installation:
Minimum Clearance and Flue Centerline,
Direct Vent and Natural Vent
ST101b
A: Rear Wall 4” (102 mm) B: Min. Clearance 45¹⁄₄” (1154 mm)* C: Min. Alcove Height 72” (1830 mm)
Stove Clearance: A: 4” (102 mm) Pipe Centerline: B: 14¹⁄₂” (370 mm)
Fig. 4 Corner installation, minimum corner clearance and flue centerline.
ST129b
D: Max. Alcove Depth 48” (1220 mm) Sidewall Clearance 4” (102 mm)
Fig. 5 Dimensions and clearances to ceiling or alcove.
Hearth Requirements
The Stardance Heater must be installed on rigid floor ing. When the heater is installed directly on any com­bustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
-
6
20007065
Stardance Direct Vent/Natural Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST134a FDV28 Horizontal vent run 12/3/99 djt areas modified 1/11/00 djt
Max. Min.
Input Input Model Fuel Gas Control BTU/h BTU/h
SDV30RN Nat Millivolt 28,000 20,000 SDV30RP Prop Millivolt 28,000 19,000 SDV30RFN Nat Comfort Control 28,000 20,000 SDV30RFP Prop Comfort Control 28,000 19,500
Weight: Fully assembled; 202 lbs.
Natural LP (Propane) Inlet Minimum 5.5” w.c. 11.0” w.c. Inlet Maximum 14.0” w.c. 14.0” w.c. Manifold Pressure 3.5” w.c. 10” w.c.
The installation of your Vermont Castings stove must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/ NFPA 54 - latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude up to 4,500 feet (1,370m). Maintain the mani­fold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP Gas.
Input ratings are shown in BTU per hour and are cer­tified without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local au­thorities having jurisdiction for installations at eleva­tions above 4,500 feet (1,370m).
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause in­jury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
20007065
Gas Specifications
Gas Inlet and Manifold Pressures
Stardance Direct Vent / Natural Vent
Certified to:
ANSI Z21.88-2005 / CSA 2.33-2005
Vented Gas Fireplace Heaters
High Elevations
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610mm) off the top of the unit, before the first elbow. The hori­zontal run may extend up to 20’ (6m) and include a vertical rise of up to 40’ (12m). (Fig. 7) Horizontal termination must also meet the criteria shown in Figures 9 through 11.
• Approved vent systems must terminate above and including the heavy line in Figure 7.
• Two 45˚ elbows may be substituted for each single 90˚ elbow.
• With a rise between 2’ - 5’, one 90˚ or two 45˚ el bows may be used.
May use up to
three 90° Elbows
One 90°
Elbow
Fig. 7 Horizontal vent termination window.
Unacceptable
Venting Configureation
-
ST134a
7
Stardance Direct Vent/Natural Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Vertical Run (in feet)
(Measure from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST132a FDV28 Vertical vent run 12/3/99 djt area modified 1/11/00 djt
Vertical Termination - Direct Vent ONLY
A vertical vent system must terminate no less than 8’ (2.44m) and no more than 40’ (12m) above the appli­ance flue collar. A 2Z\v” restrictor plate (supplied) must be used where specified in all vertically terminated vent systems. (Fig. 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with stove directly at stove outlet. A vertically terminated vent system must also conform to the following criteria:
• No more than three 90˚ elbows may be used.
• Two 45˚ elbows may be substituted for one 90˚ el bow. No more than six elbows may be used.
• Vent must rise a minimum of 2 feet before offset is used.
• Termination height must conform to roof clearance as specified in Figure 9.
All Vertical Termina­tions in this area Require use of the 2¹⁄₄” Restrictor Plate*
Fig. 8 Vertical vent termination window. *The restrictor Plate is used on Direct Vent Installations Only.
8
Vertical Terminations
must be within this
area
Unacceptable Venting
Configuration
No Restrictor Plate
-
ST132a
Vent Termination Clearances
When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Fig­ure 10.
Important: All vent clearances must be maintained. Check your vent termination clearances against Figures 9 through 11.
The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.
The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into contact with combustion exhaust gases.
• Other nearby openings {within 12” (305mm)} through which exhaust gas could reenter the building.
• All vegetation within 3’ ((76mm) that may interfere with the draft.
Other factors that influence where the installation will be sited include the location of outside walls, where additional heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.
IMPORTANT Direct Vent Only
• The horizontal termination must not be recessed into the exterior wall or siding.
• Horizontal vent runs must be level toward the vent termination.
• Clearances around the vent termination must be maintained.
• For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have restricted access for connecting the Hori­zontal Vent Cap straps to the vent pipe. See the maker’s instructions for recommended installation procedures.
20007065
Stardance Direct Vent/Natural Vent Gas Heater
Vent Termination Clearances
Your stove is approved to be vented either through the side wall, or vertical through the roof.
• CFM Corporation does not require any opening for inspection of vent pipe.
• Only CFM Corporation and Simpson DuraVent vent ing components specifically approved and labelled for this stove may be used.
• Minimum clearances between vent pipes and com bustible materials is one (1”) inch (25 mm), except where stated otherwise.
• Venting terminals shall not be recessed into a wall or siding.
• Horizontal venting must be installed on a level plane without an inclining or declining slope.
-
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24” from the front of the termination hood.
Do not locate termination hood where excessive snow
-
or ice build up may occur. Be sure to check vent termi­nation area after snow falls, and clear to prevent ac­cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ­ing the minimum clearances as shown on this page.
20007065
9
Stardance Direct Vent/Natural Vent Gas Heater
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I


Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
2
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2’ (610mm) from the center line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm) F = Clearance to outside corner see next page see next page G = Clearance to inside corner (see next page) see next page see next page H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm) J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10 feet (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡ balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes † A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings ‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent units are certified as part of the appliance, with clearances tested and approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
Fig. 9 Vent termination clearances.
10
20007065
Venting Runs
Horizontal Run (in feet)
Vertical Run (in feet)
(Measured from top of the unit before any elbow)
A: Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.
B: Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows. (Ratio = 2/3, Hor./Vert.)
= Acceptable venting configuration
= Unacceptable venting configuration















A
B
NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
F =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
G
Balcony ­with no side wall
M =
Combustible & Noncombustible 12" (305 mm)
M
Balcony ­with perpendicular side wall
M = 24" (610 mm) P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible & Noncombustible
V
V
V
E = Min. 6” (152 mm) for
non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls
O = 8’ (2.4 m) Min.
O
P
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 10 Termination clearances.
Stardance Direct Vent/Natural Vent Gas Heater
No.
of Caps D 1 3’ (.9 mm) 2 x D 2 6’ (1.8 m) 1 x D 3 9’ (2.7 m) 2/3 x D 4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
Min.
Max.
Actual
Actual
Actual
Actual
Actual
584-15
Venting Requirements - Natural Vent Only
Fig. 11 Vent termination window - Natural Vent ONLY.
20007065
NOTE: When using the FSDHAG, the restrictor plate supplied with the stove is not used.
11
Stardance Direct Vent/Natural Vent Gas Heater
Venting Requirements and Options -
Direct Vent ONLY
Approved Vent System Components
The Stardance Heater must be vented to the outdoors through an adjacent exterior wall or through the roof. The venting system must be comprised of the appropri­ate listed venting components specified on this page. These parts are available from DuraVent Corporation or your Vermont Castings Dealer.
See Figure 4 for dimensions relevant to the standard minimum-vent kits.
Simpson DuraVent Components Minimum Horizontal Vent Kit 2792
Starter Pipe Assembly (incl. inner & outer sections) 2768* 90° Elbow, Blk. 990B* 45° Elbow, Gal. 945 6” Straight, Blk. 908B* 9” Straight, Blk. 907B 11” - 14B\,” Adjustable Straight Section 911B 12” Straight 906 24” Straight 904B* 36” Straight 903B 48” Straight 902 Horizontal Vent Cap 984* Wall Plate 940* Vinyl Siding Shield 950 Snorkel Termination - 14” 982 Snorkel Termination - 36” 981 Wall Strap 988 Cathedral Ceiling Support Box 941 Storm Collar 953 Firestop Spacer 963 Flashing 0/12 - 6/12 943 Flashing 6/12 - 12/12 943S Steel Chimney Kit A 931 Kit B 932 Kit C 933 Masonry Chimney Kit 934 Vertical Termination Cap (High Wind) 991 Vertical Termination Cap (Low Profile) 980
*Included in Minimum Horizontal Vent Kit #2792
All DuraVent Straight vent pipe sections have a net length 1¹⁄₂” (37mm) less than the nominal dimension; i.e., a 6” (152mm) Straight pipe section has an effective length of 4¹⁄₂” (115mm).
CFM Vent Components
The following kits are available to meet the needs of most installations. All pipe has a 7” outer diameter and includes a 4” diameter inner section. A (CG) designa­tion indicates the part is finished in Charcoal Gray paint. Consult your dealer about other vent parts that may be appropriate to complete the installation.
Min. Through the Wall Vent Kit 7TFSSK
(1) 90-Degree Elbow (CG) (1) 24” Straight pipe (CG) (1) 24” - 42” Adjustable Straight Pipe (1) Side Wall Termination (1) Firestop (1) Zero-clearance sleeve (1) Hardware package (1) Finishing plate (CG) (1) Finishing collar (CG) (4) Charcoal Gray flue pipe rings
Starter Kit for Below Grade Installation 7TDVSKS
(1) Snorkel Termination (7TDVSNORK)
Vertical Termination Kit, 1/12-6/12 Pitch 7TDVSKVA
(1) Combination Horizontal Offset / Roof Support (1) Vertical Termination (1) Storm Collar (1) 1/12-6/12 Flashing (1) Finishing Plate (CG) (1) Finishing Collar (CG) (1) Polished Brass Flue Pipe Ring (1) Hardware Package
Vertical Termination Kit, 7/12-12/12 Pitch 7TDVSKVB
(1) 7/12 - 12/12 Flashing and all of the other Vertical Termination parts.
Vertical Termination, Flat Roof 7DVSKVF
(1) Flat Flashing and all of the other Vertical Termination parts.
Twist Lock 12” Straight Pipe (CG) 7TFSDVP12
(1) 12” Non-adjustable Pipe
Twist Lock 12”-18” Straight Pipe (CG) 7TFSDVP1218
(1) 12” - 18” Adjustable Pipe
Twist Lock 24” Straight Pipe (CG) 7TFSDVP24
(1) 24” Non-adjustable Pipe
Twist Lock 48” Straight Pipe (CG) 7TFSDVP48
(1) 48” Nonadjustable Pipe
Twist Lock 45-Degree Elbow (CG) 7TFSDVT45
for vertical offsets (1) 45-degree Elbow
Draft Hood Adapter FSDHAG NV Stove Kit 7FSSK
(1) 7” Diameter Polished Brass Trim Ring (1) 48” Nonadjustable Pipe (CG) (1) 24” Nonadjustable Pipe (CG) (1) Finishing Plate (1) Finishing Collar (CG) (1) 90 Degree Elbow (CG)
Stove Kit 7FSDHASK
Includes all parts in the 7FSSK plus the Draft Hood Adapter FSDHAG
Combination Offset/Roof Support 7DVCS Attic Insulation Shield 7DVAIS 7” Charcoal Gray Pipe Rings, (4) 7FSDRG 7” Polished Brass Pipe Rings (4) 7FSDRP Wall Thimble 942G
NOTE: Direct vent pipe may be used on the Natural
Vent system from the top of the draft hood adapter to the ceiling.
12
20007065
Stardance Direct Vent/Natural Vent Gas Heater
Install the Optional Fan
If you are installing the optional convection Fan Kit #2767 (FK26), continue here. If you are not installing a Fan Kit, go to Page 14, Venting System Assembly.
1. The fan kit includes a Blower Assembly and a Rheo­stat Assembly, connected by a cable. (Fig. 12) The Blower Assembly mounts to the bottom rear of the stove, and the Rheostat mounts to the valve bracket to the left of the valve. The assembly includes a ‘snapstat’ which automatically turns the fan On (or Off) above (or below) approximately 109˚. The Rheo­stat also provides a range of fan speed settings from Off (which overrides the snapstat function) to High. Unpack and inspect the Blower assembly. Confirm the fan spins freely.
WARNING
This appliance is equipped with a three-prong (grounded) plug for your protection against shock hazard and should be plugged directly into a prop­erly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Not Used on RF Models
Not Used on Stardance
Snapstat Bracket
Snapstat/ Extension Assembly
4. The rheostat control switch attaches to the left side of the valve bracket at the front of the stove. (Fig. 15)
Remove retaining nut from shaft of rheostat. (if
preinstalled)
Insert the rheostat through the hole in the back
of the left side of the valve bracket, aligning the locator pin with the smaller hole in that bracket.
Thread the retaining nut onto the shaft of the
rheostat, tightening with a wrench. Do not over­tighten.
Attach the control knob to the rheostat shaft.
Use the wire tie to secure the fan and rheostat
wire harnesses together.
Rear Skirt
Sheet Metal Screws
Rear Skirt Insert
Fig. 13 Remove rear skirt insert.
ST313
Rheostat Assembly
Not Used on RF Models
Blower Assembly
ST473
Fig. 12 Fan kit components.
Connect to PC Board on RF Models Only
2. Remove the rear skirt insert panel at the bottom of the Rear Skirt (Fig. 13) and fasten the blower assem­bly to the firebox back with the two Phillips pan-head bolts originally installed in the firebox back. (‘1’, Fig.
14)
NOTE: Steps 3 and 4 do not apply when the RF
valve is used. After attaching blower assembly to the firebox, run the spliced female leads to the front of the stove and attach to back of RF valve. (Page 28, Fig. 51)
3. Attach the snapstat assembly to the snapstat bracket with two sheet-metal screws. (‘2’, Fig. 15) Attach the snapstat bracket to the stove with a hex-head bolt passing through the bracket and into the stove base. (‘3’, Fig. 14)
Star Washer
Sheet Metal Screws
Phillips Pan Head Bolts
Star Washer
NOTE: Shown without shell for clarification
Fig. 14 Attach the fan assembly and the snapstat.
Fig. 15 Attach the fan rheostat.
1
Rheostat Retaining Collar
Rheostat Knob
2
3
Snapstat
1/4” - 20 Hex Bolt
Snapstat Bracket
ST314
ST347a
20007065
13
Stardance Direct Vent/Natural Vent Gas Heater
CEMENT
CEMENT
Venting System Assemlby - Direct Vent
General Information
The Stardance is approved for installation only with the vent components listed on Page 12. Follow the vent component instructions exactly.
For U.S. installations: The venting system must con­form with local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
For Canadian installations: The venting system must conform to the current CSA B149.1 installation code.
Install the Vent Adapter Pipe
(CFM Corporation Vent Components)
1. Install the Restrictor Plate. Consult the ‘Vent Run
Specifications’ on Page 8 to determine whether the restrictor plate is needed. If so, put the restrictor plate in place within the inner flue collar as shown in Figure 16.
First Section of Vent Pipe
#8 x 1/2” Sheet Metal Screws
3” Inner Starter PIpe
ST211
Fig. 17 Connect the inner starter with the next section of in­ner vent pipe.
ST210
Fig. 16 Install the restrictor plate only if required for the vent­ing configuraiotn. Refer to Page 8.
2. Attach Inner Starter Pipe, (found in with the log­set), to the next section of inner pipe.
• Run a bead of sealant about 1/2” from the upper end of the Inner starter pipe and join the two sec­tions together.
• Drill three pilot holes into the Inner Starter and secure the assembly with three sheet metal screws. (Fig. 17)
3. Dry fit the Inner Pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall.
• Side Wall Terminations: Dry fit the outer elbow
with the vertical outer vent and confirm the centerline alignment with the wall thimble opening.
4. Attach the Inner Vent Assembly to the stove.
• Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1/4-20 x 3/8” Phillips screws provided in the parts bag. (Fig. 18)
ST212
Fig. 18 Attach inner assembly to flue collar.
5. Install the Outer Adapter Pipe. Apply a 1/4” bead of cement around the inside wall of the pipe, about 1” from the end. Insert the pipe over the stove flue collar, keeping the vertical seam oriented to the back of the stove. Also, be sure to align holes on the pipe with the holes on the flue collar of the firebox. Fasten the pipe to the holes in the flue collar with the #12 x 1/2” sheet metal screws provided. (Fig. 19)
ST213
Fig. 19 Fasten outer pipe with #12 x 1/2” sheet metal screw.
14
20007065
Loading...
+ 30 hidden pages