Vermont Casting SR42A, SR36A, SC36A, SC42A User Manual

SR/SC Series "A"
Woodburning Fireplace
Homeowner's Installation and Operating Manual
For Models:
SR36A SR42A
For use in U.S./Canada Underwriter's Laboratories Report No. MH6018
SC36A SC42A
DO NOT DISCARD THIS MANUAL: Retain for future use.
7412948 12/06 Rev. 17
SR/SC Series "A" Woodburning Fireplace
Safety Information
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING FIREPLACE.
IMPORTANT:
Read all instructions and warnings carefully before starting installation. Failure to
follow these instructions may result in a possible fire hazard and will void the warranty.
Description
The SR/SC Series "A" fireplaces are solid fuel, wood­burning premium fireplaces. The SR36A/42A are radiant clean-face models and the SC36A/42A are circulating models with removable grilles (louvres). Both models are fully insulated fireplaces.
Precautions
CFM Corporation fireplaces and component parts have been highly tested and will operate safely when installed in accordance with instructions provided in this manual. Carefully read and understand all instructions before beginning installation.
If you notice any damage to fireplace or component parts, immediately report damage to your Majestic Fire­places dealer.
Only use CFM Corporation components or the warranty will be voided and a fire hazard may be created.
CFM Corporation warranty will be voided by and CFM Corporation disclaims any responsibility for the following actions:
Do not install a solid fuel burning insert or other products not specified for use with this fireplace.
Proposition 65 Warning: Fuels used in gas, wood-
burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
WARNING: Check with your electronics manufac­turer before installing a television or other electronic device above this fireplace.
Drafts
The fireplace should not be located in areas that create drafts (ie: frequently opened doors and central heating air inlets/outlets) that hamper the normal flow of air into the fire.
Gas Logs
If you plan to install a gas log, the gas line should be installed before framing the fireplace. The gas line must be installed by a certified gas line installer.
Installation of any damaged fireplace or chim-
ney component;
Modification of fireplace, chimney assembly or
any component parts thereof; (except for chase flashings as detailed in Chimney Top installation instructions).
Standard for Factory Built Fireplaces
SR36A / SR42A SC36A / SC42A
Listed
UL127 / ULC-S610
Installation other than as instructed by CFM
Corporation; or
Installation and/or use of any component part
not manufactured or approved by CFM Corpo­ration in combination or assembly with a Majes­tic Fireplaces fireplace system, notwithstand­ing any independent testing laboratory or other third party approval of such component parts or accessory.
Any such action may possibly cause a fire hazard.
Consult local building codes to ensure that you are in compliance before installing the fireplace.
Fireplaces must be vented to the out-of-doors.
Do not obstruct or modify air inlets/outlets in any manner.
Do not install combustible materials on any of the black fireplace surround.
Burn only solid wood fuel or gas logs.
Units: SC36A FB40C0 SR36A FB40R0 SC42A GB40C0 SR42A GB40R0
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . 2
Specifications and Framing Parts Identification
. . . . . . . . . . . . . . . . . 5
Chimney Requirements . . . . . . . . . . . . . 6
Planning Information . . . . . . . . . . . . . . . . 7
Installation . . . . . . . . . . . . . . . . . . . . . . . 8
Replacement Parts . . . . . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . 20
. . . . . . . . . . 3
2
7412948
SR/SC Series "A" Woodburning Fireplace
5/8" (16mm)
1/2" (13mm)
1/2"
36"
(914mm)
38
"
(971mm)
40" (1016mm)
5/8"
(16mm)
22"
(578mm)
1"
(45mm)
35" (902mm)
24"
(610mm)
7"
(197mm)
7"
(191mm)
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 41"
Rough Opening Height
Rough Opening Depth
Gas Line Access
48" (1232mm)
48" (1232mm)
68" (1740mm)
8"
(210mm)
22"
(559mm)
22
"
(572mm)
22" (559mm)
43
"
(1111mm)
14"
(372mm)
15"
(391mm)
11"
(279mm)
39"
(1006mm)
3"
(76mm)
8"
(203mm)
7"
(191mm)
Outside Air
Gas Line Access
(1041mm)
Electrical Access
8" Dia. (203mm)
34" (876mm)
36"
(914mm)
14
"
(372mm)
15"
(391mm)
11"
(279mm)
40"
(1016mm)
39
"
(1006mm)
3"
(76mm)
5/8"
(16mm)
5/8" (16mm)
48" (1232mm)
48" (1232mm)
5/8”(13mm)
1/2"
68" (1740mm)
8"
(210mm)
22"
(559mm)
22
"
(572mm)
22" (559mm)
22"
(578mm)
24"
(610mm)
43"
(1111mm)
8"
(203mm)
7"
(197mm)
7"
(191mm)
7"
(191mm)
Outside Air
Gas Line Access
Gas Line Access
Electrical Access
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 41"
Rough Opening Height
Rough Opening Depth
(1041mm)
8" Dia. (203mm)
34" (876mm)
SR36A Series Woodburning Fireplace
Fig. 1 SR36A Series specifications and framing.
SC36A Series Woodburning Fireplace — Circulating Model
Fig. 2 SC36A Series specifications and framing.
7412948
FP589
FP590
3
SR/SC Series "A" Woodburning Fireplace
5/8" (16mm)
1/2" (13mm)
1/2"
42"
(1067mm)
38
"
(971mm)
46" (1168mm)
5/8"
(16mm)
22"
(578mm)
1"
(45mm)
38" (965mm)
24"
(610mm)
7"
(197mm)
7"
(191mm)
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 47"
Rough Opening Height
Rough Opening Depth
Gas Line Access
50" (270mm)
50" (1270mm)
70" (1791mm)
8"
(210mm)
22"
(559mm)
22
"
(572mm)
26"
(667mm)
43
"
(1111mm)
14"
(372mm)
15"
(391mm)
11"
(279mm)
39"
(1006mm)
3"
(76mm)
8"
(203mm)
7"
(191mm)
Outside Air
Gas Line Access
(1194mm)
Electrical Access
8" Dia. (203mm)
36" (914mm)
42"
(1067mm)
46"
(1168mm)
39"
(1006mm)
5/8"
(16mm)
5/8" (16mm)
1/2" (13mm)
1/2"
22"
(578mm)
24"
(610mm)
7"
(197mm)
7"
(191mm)
Gas Line Access
Recessed Nailing Flange
11" Dia. (279mm)
Rough Opening Width 47"
Rough Opening Height
Rough Opening Depth
50" (1270mm)
50" (1270mm)
70" (1791mm)
8"
(210mm)
22"
(559mm)
22"
(572mm)
26
"
(667mm)
43"
(1111mm)
14"
(372mm)
15
"
(397mm)
11"
(279mm)
3"
(76mm)
8"
(203mm)
7"
(191mm)
Outside Air
Gas Line Access
Electrical Access
(1194mm)
8" Dia. (203mm)
36" (914mm)
SR42A Series Woodburning Fireplace
Fig. 3 SR42A Series specifications and framing.
SC42A Series Woodburning Fireplace — Circulating Model
Fig. 4 SC42A Series specifications and framing.
4
FP591
FP592
7412948
A
B
C
FP1531
Front Width Back Width Depth
A B C
SR/SC36A 31
¹⁄₈" 19⁷⁄₈" 15¹⁄₂"
(791 mm) (505 mm) (394 mm)
SR/SC42A 36
³⁄₄" 22⁷⁄₈" 15¹⁄₂"
(934 mm) (581 mm) 394 mm)
Fig. 4a Hearth dimensions.
Chase Installation
Insulation methods shown are optional for cold climate, not a requirement for unit operation.
SR/SC Series "A" Woodburning Fireplace
Termination Cap
Storm Collar
Pan Flashing
Batt Insulation (cut out around fiestop)
Firestop
Ceiling Level
Nailing Flange
Gas Line Access (both sides)
Electrical Access
Outside Air Cover Plate
Fig. 5 Fireplace and chase parts identification.
Draftstop
Standoff
Surround
Damper Control
Gas Line Knockout (both sides)
Screen
Grate
Firebox
Metal Safety Strips (1, 2 or 3 pieces)
FP554
7412948
5
SR/SC Series "A" Woodburning Fireplace
OFFSET
RISE
D
RISE
B
G
H
B
OFFSET
C
E
6 FT.
G
H
A
HEARTH FLOOR
CHIMNEY SECTION
CHIMNEY FLUE EXIT
ELBOW
30°
OFFSET
ELBOW
30°
OFFSET
ELBOW
30°
RETURN
ELBOW
30°
RETURN
ELBOW
SKCS8 SUPPORT
Example 1 Example 2 Example 3
Chimney Requirements - Offset Installations
IWF282
30˚ Elbow Offsets
Notes: G + H cannot exceed 20 feet.
Air Space Clearances: SK8 (2-wall) = 1¹⁄₂" and "S" Series (3-wall) = 2"
Illustration Key
The following safety rules apply to offset installations (letters correspond with il­lustration above):
A. Height of the chimney is measured from the hearth to the chimney exit.
Maximum: 90'0" 90'0" Minimum: Without Elbows 12' 6" 12' 6" With 2 Elbows* 14' 6" 14' 6" With 4 Elbows* 21' 0" 21' 0"
B. Do not use more than 4 elbows per chimney.
Attach the straps of the return (top) elbow to a structural framing member.
The offset (first) elbow of any pair does not have straps.
* In Canada, two (2) SK845 are allowed.
Fig. 6 Chimney system requirements.
6
SR/SC36A SR/SC42A
1'
3' 4'
1¹⁄₂'
0 0 0 0 0 3" 11"
1 0 0 0 0 8¹⁄₄" 20" 0 1 0 0 0 11 2 0 0 0 0 13 1 1 0 0 0 16¹⁄₂" 34¹⁄₄" 0 0 1 0 0 20 2 1 0 0 0 21 0 0 0 1 0 26¹⁄₄" 51¹⁄₄" 0 1 1 0 0 28¹⁄₂" 55¹⁄₄" 1 0 0 1 0 31 0 1 0 1 0 34 0 0 2 0 0 37¹⁄₂" 70³⁄₄" 1 1 0 1 1 41 0 0 1 1 1 45" 83
IWF269
C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.
D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)
E. A chimney support (Model SKCS8) is required every 6 feet of angled run of chimney. Chimney supports are required for every 30 feet and 60 feet (SK8 pipe) or 20 feet and 40 feet (3-wall pipe) of ver­tical chimney height above the hearth.
Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling.
NOTE: This offset distance may not be your full offset distance. See Examples 2 and 3.
0 1 2 0 1 47 0 0 0 2 1 51" 94" 0 1 1 1 1 53 0 0 3 0 1 56 0 1 0 2 1 59¹⁄₄" 108¹⁄₂" 0 0 2 1 1 62¹⁄₄" 113¹⁄₂" 0 1 3 0 1 64 0 0 1 2 1 68 0 1 2 1 1 70¹⁄₂" 128" 0 0 0 3 1 74 0 1 1 2 2 78" 140 0 0 3 1 2 81" 146" 0 1 0 3 2 84" 151¹⁄₄" 0 0 2 2 2 87" 156 0 1 3 1 2 89 0 0 1 3 2 93" 166³⁄₄" 0 1 2 2 2 95 0 0 0 4 2 99 0 1 1 3 2 101¹⁄₄" 181³⁄₄" 0 0 3 2 2 104¹⁄₄" 186¹⁄₄" 0 1 0 4 2 107 0 0 2 3 2 110 0 1 3 2 3 114" 203¹⁄₄" 0 0 1 4 3 117 0 1 2 3 3 120" 213 0 0 0 5 3 123
Offset
Chimney
Support
Rise
¹⁄₄" 25¹⁄₄" ¹⁄₂" 29¹⁄₄"
¹⁄₄" 40³⁄₄" ³⁄₄" 43¹⁄₂"
¹⁄₂" 60¹⁄₄ ¹⁄₂" 65¹⁄₂"
¹⁄₂" 77³⁄₄"
³⁄₄"
¹⁄₄" 87¹⁄₂"
¹⁄₄" 98" ¹⁄₄" 103¹⁄₄"
¹⁄₂" 117¹⁄₂" ¹⁄₄" 124"
¹⁄₄" 134¹⁄₂"
³⁄₄"
¹⁄₂"
¹⁄₄" 160¹⁄₄"
¹⁄₄" 170³⁄₄" ¹⁄₄" 177³⁄₄"
¹⁄₄" 191¹⁄₂" ¹⁄₄" 196³⁄₄"
³⁄₄" 209³⁄₄"
¹⁄₂"
³⁄₄" 220"
7412948
SR/SC Series "A" Woodburning Fireplace
L
1
L
1
L
T
MODEL SK
2 WALL CHIMNEY
TOTAL
LENGTH
(L
T
)
INSTALLED
LENGTH
(L
1
)
SK81 SK818 SK83 SK84
11
"
17
"
35
"
47
"
10
"
16
" 34" 46
"
2' Min.
2' Min.
3'
Min.
0 To 10'
3'
Min.
0 To 10'
Reference Point
Planning Information
Preplanning an installation is very important to ensure safety and to save time and money. An installer must
predetermine where a fireplace will be set and how the chimney system will be run.
Mounting the Fireplace
A fireplace may only be mounted on the following sur­faces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath each of the four (4) corners of the fireplace.
The fireplace
must be spaced 1/2" (13mm) from a com-
bustible back wall and 1/2" (13mm) from a combustible side wall or support. (Page 14, Fig. 20)
Planning the Chimney Run
The Ten Foot Rule
Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 8)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak of the roof is 10' (3m) or less, the top of the chimney must be at least 2' (610mm) above the peak of the roof, but never less than 3' (914mm) in height above the highest point where it passes through the roof.
2. If a horizontal distance from the chimney to the peak of the roof is more than 10' (3m), a chimney height reference point is established on the surface of the roof a distance of 10' (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (610mm) above the reference point, but never less than 3' (614mm) in height above the high­est point where it passes through the roof.
WF288
Fig. 7 Installed lengths of chimney sections.
Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 6) Never install a chimney below minimum heights.
In planning a chimney system, it is important to know:
1. The height of a chimney is measured from the hearth to the exit point on the termination.
2. A chimney cannot be offset more than 30° from a vertical plane.
3. A chimney may run straight up or it may be neces­sary to offset it to avoid obstructions.
4. The maximum length of an angled run (total chimney system) is 20' (6m).
5. No more than 2 offsets (4 total 30° elbows in U.S./or 2 total 45° elbows in Canada) per fireplace may be used.
6. A guy wire stabilizer is required for chimneys extend ing more than 6' (1.8m) above a roof line.
7412948
AC246
Fig. 8 Ten Foot Rule illustration.
-
7
SR/SC Series "A" Woodburning Fireplace
Chimney Supports
The chimney system is supported by the fireplace for vertical chimney heights less than 30' (9m) above the hearth. Chimney supports are required if the vertical height exceeds 30' (9m) with SK8 chimneys or 20' (6m) with 3-wall chimneys. Locate chimney supports at ceiling holes or other structural framing at 30' (9m) (SK8) or 20' (6m) (3-wall) heights. Spacing between chimney supports must not exceed 30' (9m) (SK8) or 20' (6m) (3-wall). Use Chimney Support Model SKCS8.
(NOTE: The SKCS8 can not be mounted directly to the fireplace.) Support provided by elbow straps fulfills
the support requirement only if they are spaced as pre­viously described. (A chimney support is 2¹⁄₂" (64mm) long when installed.)
Angled chimney runs require a support every 6' (1.8m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 9)
Chase Installation
A chase is a vertical box like structure which encloses the fireplace and/or chimney. Chases are typically built on the outside of the house with fireplace opening cut into the outer wall of a room. (Page 5, Fig. 5)
If you need help in determining fireplace location or how the chimney system should be run, contact your Majestic Fireplaces dealer for assistance.
Installation
Insulating Fireplace Enclosure for Cold
Climates
If you live in a cold climate, it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible.
Insulate base of fireplace with a noncombustible in sulation rated for a minimum of 300°F. Insulating is very important for outside wall installations over a concrete slab. If fireplace is installed on a platform, insulation should be placed on top of the platform before fireplace is set. (Fig. 10)
When a fireplace is installed in a chase or on an outside wall, enclosure should be treated like any outside wall in a home. Insulation should be in­stalled on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material. Insu­lation may then be installed above sheeting material to assure the space around the fireplace is totally protected. (Fig. 5)
When installing the chimney, DO NOT caulk be­tween outer pipe and firestop. It is vital that some air be allowed to flow through this very thin gap.
CAUTION: WHEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE, BE SURE ALL RE­QUIRED AIR SPACES ARE MAINTAINED. (Page
14, Fig. 20)
-
Chimney Sup­port Strap
SKCS8
Fig. 9 Chimney support installation
8
FP284
7412948
SR/SC Series "A" Woodburning Fireplace
Framing
Framing can be constructed before or after the fireplace is set in place, however, most installers build the frame before setting the fireplace.
Frame fireplace with 2 x 4 lumber or heavier materials. Refer to framing dimensions in Figures 1, 2, 3 or 4 for basic fireplace specifications.
NOTE: Framing should be positioned to accommodate wall covering and fireplace facing material.
Installing Electrical Wire
(for Circulator Models)
If a circulating fireplace is to be installed, run the 120 VAC, 60 Hz wiring to the left side of installation. Wiring must be completed before the fireplace is secured and finish material applied.
Remove the cover plate and electrical knockout on the lower left side of the fireplace and set aside. Follow the instructions on Page 10 for proper wiring and installation of the EB1.
If the fan kit is not being installed with the fireplace, it is highly recommended that 120 VAC supply be made available since someone may elect to install a blower at a later date.
Option For Circulating Models Only —
EB1 (Receptacle) Hook-Up
• Wiring should be installed by a certified electrician.
• Turn off circuit breaker before wiring models.
Once fireplace is secured, complete wiring the fan kit. Remove knockout in the center of the back of the EB1 and install listed cable clamps. Feed electri­cal wire through listed cable clamp leaving approxi­mately six (6) inches of wire exposed through the EB1. Secure listed cable clamp to the wire.
Attach white wire from power source to one (1) wire of receptacle and secure with nut. Attach black wire from power source to the other wire of recep­tacle and secure with nut. Be sure nuts are secured tightly.
Secure EB1 assembly to inside of electrical box coverplate using two screws. Attach cover to face of the EB1 while being careful to position excess wire completely within the EB1, then attach coverplate to
fireplace.
Install Fan Kit Assembly
Refer to optional Model FK12 fan kit assembly in­stallation instructions for field installation.
Hard Flat Surface
Insulation
Platform
Fig. 10 Insulating between platform and fireplace.
FP555
Chimney Setup
Since you have already preplanned the chimney run, you should know exactly how the installation is to be ac­complished — how much pipe is required, the number of elbows, if any, and type of termination to be used.
CAUTION: REPORT TO YOUR DEALERS ANY PARTS DAMAGED IN SHIPMENT, SPECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SEC­TIONS AND ELBOWS.
NOTE: Fireplaces may use CFM Corporation model SK8, or Model S (three wall) chimney systems. The SR/SC Series "A" Fireplace will accept the SK8 chim­ney system as is; but a TWABR adapter collar is required when using the Model S (triple wall) chimney system. The installation procedure described in this manual applies only to the SK8 system. Either chimney system may be used, but may not be mixed.
7412948
9
SR/SC Series "A" Woodburning Fireplace
9"
(235mm)
AB
AB
A "SK" Series framing = 14" X 14" (368 x 368mm) B "S" Series framing = 17" X 17" (445 x 445mm)
Straight-Up Chimney Installation
To mark the centerline of the flue, put the fireplace in final position and measure out from the wall: 9¹⁄₄" (235mm). Mark a spot on the ceiling directly above the fireplace. Draw a line parallel to the back wall through this mark. (Fig. 11)
Using a plumb bob positioned directly over center point of fireplace flue collar, mark the ceiling to establish the
chimney center point. (Fig. 11)
Offset Installation
In order to clear an obstruction, it may be necessary to offset chimney from vertical. This is accomplished by using CFM Corporation elbows. Use the 30° Offset Elbow table on Page 6 to determine proper offset and parts required.
Chimney Centerline
Actual Centerpoint
Each offset requires two (2) elbows. The second elbow is equipped with support straps. It is very important to install the second elbow in each offset as close to the ceiling or support as possible so that the elbow straps can be secured to framing members to help support the weight of the chimney.
Determine offset distance of your chimney arrangement from centerline of fireplace to centerline of chimney where it is to pass through ceiling.
Locate center point of the chimney on ceiling as though a straight up chimney arrangement is to be used. Mea­sure your offset dimension from straight up chimney center point on ceiling.
Ceiling Chimney Hole/ Possible Obstructions
The size of the hole in ceiling will vary with the angle at which the chimney passes through ceiling.
Drive a nail up through ceiling at marked chimney cen­ter point. Go to floor above and see where hole will be cut. Check to see where existing ceiling joists and other possible obstructions are located...i.e. wiring, plumbing etc... If necessary, reposition chimney and/or fireplace
to avoid obstructions.
Plumb Line
Plumb Bob
Imaginary Cen-
Fig. 11 Locate centerline of chimney with plumb line.
terpoint
FP556
Cutting the Hole
Cover fireplace collar opening and cut proper sized chimney hole in chimney. The SK8 pipe allows you to run pipe through a typical 16” on center joist without
cutting joists.
Framing the Ceiling Hole
Frame the ceiling chimney hole as shown in Figure
12. It is good practice to use framing lumber that is the same size as the ceiling joists; this is a requirement at attic level.
Existing Ceiling Joist
Chimney Hole
Ceiling
New Framing Members
10
FP551
Fig. 12 Typical frame for ceiling chimney hole.
7412948
SR/SC Series "A" Woodburning Fireplace
1"
The following table gives firestop spacer model num­bers:
Angle of Chimney at Ceiling
Size of Chimney Vertical 30°
8" Flue SKFS2A SKFS6A "SK" Series 14¹⁄₂" x 14¹⁄₂" 14¹⁄₂" x 25¹⁄₂" (368mm x 368mm) (368mm x 648mm) 8" Flue FS2A FS6A "S" Series 3-Wall 17¹⁄₂" x 17¹⁄₂" 17⁷⁄₈" x 29⁵⁄₈" (445mm x 445mm) (454mm x 753mm)
Fig. 13 Ceiling chimney hole sizes necessary for installing firestop spacer.
The inside dimension of the frame must be the same as the hole size selected from Figure 13 in order to provide required the 1¹⁄₂" (38mm) of air space between the outside diameter of the chimney and the edges of
the framed ceiling hole.
Positioning, Safety Strips,
Securing the Fireplace
Slide fireplace into position.
Lift the fireplace front slightly and slide the metal safety strips under front bottom edge about 1¹⁄₂" (38mm), al­lowing the remainder to extend in front of firebox. Over­lap strips at least 1/2" (13mm) to provide a positive joint. (Flat safety strips are packed with fireplace.) (Fig. 14)
Metal Safety Strips (1, 2 or 3 pieces)
NOTE: Safety strips are not required over noncom­bustible floors where all supports at the base of the fireplace are noncombustible.
Four (4) nailing flanges are incorporated on each cor­ner of the surround. Bend the nailing flanges out, level the box, then secure it firmly in place by nailing the flanges to the framing members as shown in Figure
15.
Nail Top Standoffs
Nail Side­Nailing Flanges
FP549
Fig. 15 Fasten fireplace in position.
Installing Outside Air Kit
An outside air kit is installed in all SR/SC Series Fire­places. If desired, or if local codes mandate the use of an air kit, then an AK-MST is required to complete the installation (from air kit to the outdoors). If the outside air kit is to be used, the AK-MST MUST be installed BE- FORE the fireplace is enclosed. Refer to the AK-MST
instructions for field installation.
"Z" Safety Strip (not sup­plied)
Hearth Ext.
1/2" Min. Overlap
FP557
Fig. 14 Safety strip installation.
Fire­place
Plat­form
Safety strips are used to ensure that any combustible materials in front of the fireplace are protected even though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z” shaped metal safety strip must be fabricated and used to protect combustible surfaces in front of the fireplace. This “Z” shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1¹⁄₂" (38mm) wide and equal in length to the metals strips provided with the fireplace.
7412948
Installing the Chimney System
Start by attaching the first chimney section to the collar on top of the fireplace.
Install the pipe as pictured in Figure 16. When you get a good lock, you will hear the pipe clearly snap together. Once sections are snap-locked in place, it is extremely difficult to get them apart. Make sure the
pipe is firmly snapped and locked together as each pipe section is mounted.
When installing elbows, only outer pipe will snap­lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing member. (Fig. 17)
11
SR/SC Series "A" Woodburning Fireplace
UP
Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must
install a firestop spacer.
Installing the Firestop Spacer
in the Ceiling Hole
A firestop spacer is used to keep pipe spaced properly and required for safety.
Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spac ers provide minimum required air space to chimney pipe for ceiling thickness up to 8" (203mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.
-
Pipe Section
Pipe Rim
Hem
Lance
Pipe Rim
FP558
Fig. 16 Install pipe, listening for the snap-lock to fasten.
Proper Firestop Spacer Installation
Figure 18 shows different installation procedures for both an area that is an attic and an area that is not an attic.
If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.
Firestop spacers are not available for nor are they re­quired on vertical walls.
DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.
Canadian Requirements
for Insulation Shield
In Canada, an attic insu­lation shield is required to prevent attic insulation from contacting the chim­ney section. Framing dimensions for the chim­ney hole should measure 14¹⁄₂" x 14¹⁄₂" (368 x 368mm). An attic shield MUST be installed on top of attic joists (above the
floor level). (Fig. 19)
Attic Installation
Fig. 18 Installing firestop spacer.
Elbow Strap
Angled Strap
FP270/271
Fig. 17 Attach straps to a structural framing member.
Support Structure
Elbow Strap (must be tight)
Ceiling Hole Framing
Angle Firestop
Chimney Support Strap (must be tight)
Ceiling Installation
Nails (4)
Firestop Spacer
Firestop
Joist
Spacer
Nails (4)
Joist
FP593
12
7412948
Install the attic insulation shield with the flanges on its base extending down into the framing hole. Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails. Attic shields are not
required at the roof.
Continue Installing Pipe to Complete Run
Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snapped locked in place before proceeding to next pipe section.
Chimney Supports
SR/SC Series "A" Woodburning Fireplace
Attic Insulation Shield
Nails (4 required)
Attic Joist
If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to adjacent structural framing, as shown on, Page 8, Fig.
9. Bend straps as necessary and make sure they are
secure so they will support the weight of the chimney. A chimney support is 2¹⁄₂" (64mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.
NOTE: Chimney supports are generally used in long runs in a chase installation.
Additional Ceilings
If you encounter additional ceilings, repeat same steps required for first ceiling installation. Refer to firestop
illustration on Page 12, Figure 18.
Penetrating the Roof
Run pipe to roofline. Since the chimney system must be vented to the out-of-doors, you must use an approved termination.
If a chase is used, refer to the installation manual pro­vided with the termination cap.
Locate Chimney Centerpoint On Roof
Use same procedure detailed in locating centerpoint of the flue system.
Drive a nail up through roof at the center point. This will determine center point on outside of the roof.
Base
Ceiling
Fig. 19 Attic shield installlation (Canadian requirement).
Flanges
FP263
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER MATERIALS.
Mark an outline of the roof hole around the center of the point nail. NOTE: Hole dimensions given in the chim­ney top installation instructions are horizontal dimen­sions; therefore, the hole size must be marked on the roof accordingly.
Cover the opening of the installed chimney so debris cannot get into the system.
Cut and frame the hole. It is good practice to use fram­ing lumber that is the same size as the rafters. Install the frame securely because the chimney top and flash­ing anchored to the frame must be able to withstand heavy winds.
Install Remainder of Chimney Sections
Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.
Check the chimney top installation instructions for details on how high above the roof top the chimney sec-
tions (all pipes) should extend.
Cut and Frame Roof Hole
Size of roof hole varies with the type of chimney termination installed. Refer to installation instructions provided with the chimney termination to find correct size of roof hole.
There must be a 1¹⁄₂ (38mm) air space between out­ermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materials such as: ceiling members, joists, flooring, combustible insulation and roof structures.)
7412948
13
SR/SC Series "A" Woodburning Fireplace
Front View
Side View
Standoff
Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas).
Air Space Clearances
Only noncombustible material may be applied as facing to the black fireplace surround.
Wall Shield
Hearth Extension
0" Clearance to Floor
Firestop
1/2" Air Space to Back
1/2" Air Space to Sides
1"
1/2" air space to sides
Installing Top Housing
or Termination
Follow the installation instructions provided with the chimney termination you have selected.
Installing Chimney In a Chase
Refer to Page 5, Figure 5 for an illustration of a typical chase installation.
CAUTION: Treatment of firestop spacers and construc­tion of chase may vary with type of building. These instructions are not a substitute for local building codes. You must check your local building codes to determine specific requirements for your city or state. NOTE: Other building materials may be required in addition to Firestop Spacers.
Finishing
CAUTION: All joints between the finished wall and
the fireplace surround (top/sides) must be sealed with noncombustible material to prevent cold air leakage into the room. Only noncombustible material may be applied to the facing of the fireplace surround. (Black painted area) (Fig. 20)
Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12" (305mm) from the top of the fireplace opening for radiant models and 12" (305mm) from top of grille opening for circulating models. Do not install a mantel face plate less than 6" (159mm) from top of fireplace opening for radiant models and 6" (159mm) from top of grille opening for circulating models. (Fig. 22) If a combustible material is used be-
low a flat mantel shelf, consult your local building codes for minimum clearance from top of fireplace opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or deco­rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 21 and 22)
NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installation).
Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combus­tible material it must be within the safe zone indicated in Figure 23.
Finish Wall
FP559
Fig. 20 Minimum clearances to combustibles.
14
7412948
SR/SC Series "A" Woodburning Fireplace
1" Ref.
Combustible materials are permitted within a shaded area shown in Figure 23 titled Minimum Wall Clearances.
*
**
12"
(305mm)
Max.
1/2"
12"
(305mm)
Max.
12"
(305mm)
Min.
1"
(38mm)
*
12"
(305mm)
Min.
1"
(38mm)
6"
(159mm)
Min.
12"
(305mm)
Max.
12"
(305mm)
Min.
1"
(38mm)
6"
(159mm)
Min.
Mantel Clearance - Radiant
Model - No Noncombustible
Facing Material
Combustible Mantel and Trim
* Minimum width from top of sur­round to bottom of screen rail
Fig. 21 Mantel clearances.
Combustible Man­tel and Trim
Finished Wall
Header
Standoff
Noncombustible Material
Radiant Sur­round Face
Fireplace Open­ing
Mantel Clearance - Radiant Model
- with Noncombustible Facing Material
Noncombustible Fac-
ing Material Radiant Surround Face
Fireplace Open­ing
Top View
Fireplace Front
Must be sealed with Noncombustible Material
Combustible Man­tel and Trim
Finished Wall
Header
Standoff
Noncombustible Material
2 x 4 Stud
Finished Wall
Mantel Clearance -
Circulating Model
Finished Wall
Header
Standoff
Noncombustible Material
Circulating Front
Fireplace Opening
FP531a
*12" from top of fireplace opening for radi­ant models
12" from top of grille opening for circulating models **6" from top of fireplace opening for radi­ant models (Noncombustible material must separate the black face surround of the fire­place and any combustible mantel material) 6" from top of grille opening for circulating models
Fig. 22 Combustible mantle clearances.
Face Plate
MA81
7412948
15
SR/SC Series "A" Woodburning Fireplace
Minimum Wall Clearances
WITH Noncombustible Surround Facing
WITHOUT Noncombustible Surround Facing
Minimum Hearth Extension Dimensions
(for On-Site Construction)
G
H
G
J
Seal cracks between the fireplace and hearth extension with noncombustible material
Safety strips must overlap 1/2" minimum
May install noncombustible decorative covering OR .018" min. sheet metal
FIREPLACE HEARTH
COMBUSTIBLE FLOOR
MINIMUM INSULATION VALUE "R"
4" MIN.
FIREBOX OPENING
A - Min. clearance to combustible perpendicular wall
B - Min. clearance to combustible perpendicular wall when using noncombustible wall shield*
SIDE WALL
SIDE WALL
F**
C**
E
E
D
4" BRICK (Example material)
Combustible material permitted within shaded area.
*
Noncombustible wall shield requires 1" CFM Corporation EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40".
**
Dimension/degree of angle will vary depending on thickness
of noncombustible surround facing.
4"
Shaded area starts 1/2" away from edge of unit.
Side Wall Protection
Adjacent combustible side walls that are within the minimum dimensions shown in Figure 23 of fireplace opening must be protected with CFM Corporation Wall Shield Model SP40 or a specifically built wall shield described below.
The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85
minimum.
Examples of wall shield insulation:
1. Manville - CERAFORM 126, K=.27, 1/2 inches thick
2. CFM Corporation - EH2416, K = .458, 1 inch thick required.
Hearth Installation
A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for mini­mum dimensions and mounting detail.
NOTE: Hearth Extension must not cover the air inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 24 for examples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.
The top of insulation must be covered with a noncom­bustible decorative covering or a piece of .018” mini­mum sheet metal, to protect hearth extension material. (Fig. 23)
Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 23 and 25)
Fig. 23 Combustible side wall protection and hearth extension dimensions.
A B C D E F G H J
SR/SC36A 16" 12" 48° 41° 18" 14" 7³⁄₄" 16" 48" 406mm 305mm 457mm 356mm 197mm 406mm 1219mm SR/SC42A 20" 12" 42° 35° 18" 14" 11¹⁄₂" 20" 61¹⁄₂" 508mm 305mm 457mm 356mm 292mm 508mm 1562mm
16
FP594
7412948
SR/SC Series "A" Woodburning Fireplace
COMMON MATERIALS AND FACTORS
MATERIAL K*
R
MINIMUM
THICKNESS
EH2416
Common Brick
0.458
5.0
1.09 0.50 in.**
0.10 5.46 in.**
(CFM Corporation)
R Value is for Z\x inch. * Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material
Side View
Wall Covering
FP533ADD
Fig. 24 Hearth extension material factors.
WARNING: HEARTH EXTENSION MUST BE IN­STALLED IN ACCORDANCE WITH FIGURE 23 AND MUST NOT COVER THE BOTTOM FRONT OPENING OF THE CIRCULATING MODEL.
Alternate noncombustible materials may be used providing the (total) thermal resistance (Rt value) of the alternate material employed is greater than or equal to R = 1.09. Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R.
T = given thickness R = thermal resistance for a given thickness (T) K = thermal conductivity
Noncombustible material with a lower R value may be used, provided thickness of material is sufficiently greater to maintain an equivalent (total) thermal resis-
tance (Rt).
Example of Determining Hearth Extension Equivalents
Noncombus­tible Decorative Facing
Seal all cracks between fireplace sur­round and wall materi­als with noncombus­tible material
Noncombustible Decorative Cov­ering
Hearth Extension Insulation
FP550
Fig. 25 Sealing gaps.
2 x 4 Header (Do not notch at standoffs)
Seal crack between fireplace and hearth extension with noncom­bustible material
Safety Strips Must be overlapped 1/2" minimum
To determine the thickness required for any new mate­rial:
NEW K of new material (per inch) thickness required = thickness K of listed material (per inch) material
Example for Common Brick
T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required thickness).
7412948
X of listed
17
SR/SC Series "A" Woodburning Fireplace
1"
Min.
1/2"
Installing Line for Gas Logs
CFM Corporation fireplaces are designed to accept a 1/2" (13mm) gas line for installation of an approved gas appliance. (CFM Corporation manufactures a wide va­riety of gas logs for use in CFM Corporation fireplaces.)
Be sure to have the appliance installed in accordance with building codes.
Gas connection may enter from either left or right side of the fireplace.
Locate appropriate gas line in the outer casing of fire­place and remove insulation from gas line tube. (Fig.
26)
From inside the fireplace, locate the knockout on the firebrick -- be sure you are on the appropriate or "gas line" side of the fireplace. Using a flat bladed screw­driver or small chisel and hammer, carefully tap around the knockout until it loosens and falls out.
Install 1/2" (13mm) certified gas pipe through opening. After gas pipe installation is complete, use insulation that was removed from gas line tube to repack space around the pipe. Material should be inserted from outside of the fireplace and packed tightly to totally seal between the pipe and tube.
NOTE: Gas pipe should not come in contact with any wood structures until it has reached a point at least one (1) inch away from fireplace side.
NOTE: When installing an ANSI Z21.11.2 ventless ap-
pliance the finishing material used for the mantel must be rated at 250°F or greater.
BTU input of a gas appliance installed in fireplace should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a decorative gas appliance only when (1.) incorporating an automatic shutoff device and (2.) complying with the Standard for Decorative Gas Appliances for Installa­tion in Vented Fireplaces (ANSI Z21.60) or CSA draft requirements for Gas-Fired Log Lighters for Woodburn­ing Fireplaces (Draft No. 4, August 1993).
Decorative gas appliance should be installed in accor­dance with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 (latest edition).
Hole in Outer Casing
Gas Line Tube
Ceramic Knockout
Hole in Casing
Fig. 26 Gas line access.
CAUTION: WHEN USING DECORATIVE GAS APPLIANCE, FLUE DAMPER MUST BE SET IN FULLY OPEN POSITION. IF YOU HAVE GLASS DOORS ON THE FIREPLACE, THEY MUST ALSO BE FULLY OPENED.
WARNING: DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIRE­PLACE WITH THE CHIMNEY REMOVED.
WARNING: WHEN INSTALLING AN UNVENTED AS LOG SET, THE CFM Corpo­ration MODEL AH3244BK OR AH3244PB 4" ADJUSTABLE HOOD MUST BE USED.
Fireplace Top View
Supply Line
Repack Insula­tion
Ceramic Knockout (Both sides)
FP560
18
If installing an unvented gas log set, refer to statement below:
Only unvented gas logsets which have been found to com­ply with the Standard for Unvented Room Heaters, ANSI Z21.11.2, are to be installed in this fireplace.
7412948
SR/SC Series "A" Woodburning Fireplace
1
2
3
4
5
6
a
b
c
7
8
9
10
11
12
d
14
13
e
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
SR36A/42A, SC36A/42A SERIES
For units FB40RO, GB40RO, FB40CO, GB40CO
Ref. Description SR/SC36A SR/SC42A
1. Damper Weld Assembly RP199 RP199
2. Damper Bracket 3030176 3030176
3. Screen Rod Assembly 3030126 3032112
4. Screen Assembly (two per fireplace) 20005487 20005631
5. Screen Pulls 5584139 5584139 6a. Firebrick - Hearth 20005621 20005421 6b. Firebrick - Rear 20005627 20005462 6c. Firebrick - Right Side 20005626 20005461 6d. Firebrick - Left Side 20005625 20005460 6e. Firebrick - Ashlip 20005619 20005418
7. Top Brick Retainers (three per fireplace) 3030172 3030172
8. Cable Clips (two per fireplace) 7512135 7512135
9. Outer Collar Assembly (SK8 Chimney) 3030143 3030143
10. Nailing Flange - Bag of 4 w/screws 2253160 2253160
11. Top Grille Assembly (SC Only) 3041143 3035131
12. Grille Assembly (SC Only) 0056034 3035130
13. Basket Grate 3041130 3041130
14. O.S.A. Assy. 20003076 20003076
7412948
19
SR/SC Series "A" Woodburning Fireplace
Accessories
The following accessories for this appliance are available from your local Majestic Fireplaces distributor. Should you need additional information beyond what your distributor can furnish, contact: CFM Corporation, 2695 Meadowvale Blvd., Mississauga, Ontario, Canada L5N 8A3, Attn: Technical Services.
CAUTION: This fireplace and chimney assembly is a highly engineered system, and, as such, must be oper ated only with CFM Corporation approved components. If you use an unapproved component to make any modifications, you may create a possible fire hazard and will void the CFM Corporation warranty. In addition, such action may void the coverage provided by the owner’s insurance.
Model NumberDescriptionAccessory
-
Glass Door — Standard Bi-Fold door set Brushed Brass finish 36GDKBBSR (SR/SC36A)
42GDKBBSR (SR/SC42A) Black finish 36GDKBKSR (SR/SC36A)
42GDKBKSR (SR/SC42A) Polished Brass finish 36GDKDPSR (SR/SC36A)
42GDKDPSR (SR/SC42A) Pewter finish 36GDKSSR (SR/SC36A)
42GDKSSR (SR/SC42A) Fan Kit Provides forced air flow FK12 Variable Speed Control Provides speed adjustment of fans SCVS Outside Air Termination Completes connection from air kit to out-of-doors AK-MST Chimney Adapter Converts fireplace to 3-wall system TWABR Hearth Extension Insulation Provides hearth extension floor protection EH2416 Grate SR/SC36A/42A Holds firewood in firebox RSBG36 Hearth Patch Compound Patch cracks in hearth HPC-1
20
Contact your Majestic Fireplaces distributor or dealer for finishing Marble and Mantels, available in a wide selection of styles.
7412948
SR/SC Series "A" Woodburning Fireplace
Chimney Components
U.S.
Model NumberDescriptionComponent
Round Top Termination Top used to terminate chimney at roof. RLTSK8
(Flashing not included.) Round Top Termination - Top used to terminate chimney at chase. RLTSK8L
Extended (Flashing not included.) Flashing Metal finishing required around Contemporary 8-6-12 with 8" flue:
Termination to prevent rain leakage. 0-6/12 pitch 8-12-12 with 8" flue: 6/12-12/12 pitch
Square Termination Top housing of simulated brick pattern S20B (R, T, W) Housing available in red, tan or white. Appropriate Must also include: adapter required. Flashing included. PLTSK8 or SLTSK8
Adapter Kit Unites Square Termination with chimney CF8CA pipe (required).
Housing Extensions Extends Square Termination on steep 202036 pitched roofs.
Square Chase Termination Housing used to terminate chimney through CT100 a chase top. Appropriate adapter required. (Flashing not included.)
Adapter Kit Unites Square Chase Termination with chimney CTSK pipe (required).
Chase Top Housing Low profile pyramid-style chimney cap used to PLTSK8 terminate chimney through a chase. Includes adapter. (Flashing not included.)
Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 through a chase. Terra Cotta Masonry. Includes adapter. (Flashing not included.)
SK8 Chimney Sections Pipe used to build 8" (SK8) flue systems. SK81 (1' Long) SK818 (1¹⁄₂' Long) SK83 (3' Long) SK84 (4' Long)
SK8 Chimney Elbows Elbow used to create an offset in an 8" SK830-2 chimney system. Only 30˚ elbows available. Packaged 2 per carton (offset and return).
Firestop Required at each floor level of chimney SKFS2A — installation. (Plus attic on multi-story installation.) (8" straight flue) SKFS6A — (8" 30˚ inclined flue)
Chimney Support Used to support chimney for each of: 30' vertical SKCS8 height and 6' of angled chimney run.
7412948
21
SR/SC Series "A" Woodburning Fireplace
(Chimney Components con't.)
Canada
Model NumberDescriptionComponent
Chimney Collar Enclosure Installs on the "over the chimney collar" of the CCE-SK
fireplace; provides outside air to assist in cooling the chimney system.
Attic Insulation Shield Used to prevent insulation from coming in AIS-SK contact with the chimney system.
SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN (1¹⁄₂' Long) roof. SK84CAN (4' Long)
45˚ Chimney Elbows Provides 45˚ offset and return. For Canadian SK845/2 installations only. For use with SK8 chimney only. (Maximum use of 2, or 1 pair.)
22
7412948
SR/SC Series "A" Woodburning Fireplace
LIMITED WARRANTY & 30 YEAR PROTECTION PLAN
For MAJESTIC FIREPLACES® PRE-ENGINEERED Fireplace Systems
CFM Corporation warrants its MAJESTIC FIREPLACES®
Pre-Engineered Fireplace (“Fireplace”) and the CFM Cor­poration supplied firegrate, glass doors, outside air system, fan motor, and liners to be free from defects in material or workmanship, as follows:
A. Fireplace and Chimney Components: (exclusive of CFM Corporation-supplied firegrate, glass doors, outside air system, fan motor, and liners all of which are covered by separate warranties under paragraphs B through D below): At its option for a period of thirty (30) years from the date the Fireplace is installed, CFM Corporation will; (1) For a period of five (5) years from the date the Fire place is installed, CFM Corporation, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 10th year after the date the Fireplace is installed, if replacement parts are available, CFM Corporation will provide a replacement for any defective part without charge for the part itself. The consumer must pay for everything else other than the part. (3) Thereafter, through the 30th year after the date the Fireplace is installed, if replacement parts are available,CFM Corporation will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory.
B. Firegrate, Glass Doors, Outside Air System:
For a period of 90 days from the date the Fireplace is in stalled CFM Corporation, at its option, will provide a replace­ment for any defective part, without charge for the part itself, FOB CFM Corporation factory, (The consumer must pay for everything else other than the part,).
C. Fan Motor:
(1) For a period of one (1) year from the date the Fireplace is installed, CFM Corporation, at its option, will repair or re­place any defective part without charge. (2) Thereafter, through the 30th year after the date the Fire place is installed CFM Corporation, at its option, if replace­ment parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory.
D. Liners (Refractory or Metal):
(1) For a period of two (2) years from the date the Fire place is installed, CFM Corporation, at its option, will repair or replace any defective part without charge. (2) Thereafter, through the 30th year after the date the Fireplace is installed CFM Corporation, if replacement parts are available, will provide a replacement for any defective part at a cost to the consumer of CFM Corporation then current list price, FOB CFM Corporation factory. This warranty is subject to the following conditions and limita­tions: (1) This warranty is extended only to a Fireplace installed in the continental United States, the state of Alaska and Cana da; only if and so long as the Fireplace is installed according to the installation instructions furnished with the Fireplace,
-
-
-
-
and operated at all times under normal conditions, use and service according to the operative instructions furnished with the Fireplace, and only if and so long as the Fireplace is not removed from its original installation. (2) This warranty is non-transferrable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company. (3) The sole and exclusive remedies for breach of any war ranties hereunder shall be for the repair, replacement or provi sion of a replacement part at CFM Corporation then current list price, FOB CFM Corporation factory, for any defective part as specified in paragraphs A through D. (4)CFM Corporation shall not be liable for damage from any smoking of a MAJESTIC FIREPLACES Pre-Engineered Fire­place System related to environmental geographic conditions (such as, for example, nearby structures or roof peaks, trees, hills, or mountains), inadequate ventilation, or negative air pressure in the place where the Fireplace system is installed, related to any mechanical system (such as, for example, furnaces, fans, air conditioners, clothes dryers, etc.) (5) Except as otherwise expressly specified in paragraphs A through D, NONE OF THESE WARRANTIES COVER, AND CFM CORPORATION SHALL NOT BE RESPONSIBLE FOR, ANY CONSTRUCTION, INSTALLATION, LABOR, TRANS­PORTATION OR OTHER COSTS OR EXPENSES ARISING FROM A DEFECTIVE PART, ITS REPAIR OR REPLACE MENT OR OTHERWISE, NOR SHALL CFM CORPORATION IN ANY EVENT BE RESPONSIBLE FOR ANY INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES EXCEPT TO THE EXTENT REQUIRED BY LAW. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this exclusion or limitation may not apply to you. NO IMPLIED WARRANTIES, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, SHALL REMAIN IN EFFECT
-
AFTER THE EXPIRATION OF THE WARRANTIES SET FORTH IN PARAGRAPHS A THROUGH D. Some states do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. In order to obtain performance of any of the above warranty obligations write to CFM Corporation at this address: CFM Corporation 2695 Meadowvale Blvd. Mississauga, Ontario, Canada L5N 8A3 Attention: Director of Warranty Services Since local building requirements may vary greatly through­out the country, users of CFM Corporation products should determine in advance whether there are any building code restrictions on the use of a specific product. RATION MAKES NO REPRESENTATION OR WARRANTY REGARDING, AND SHALL NOT BE RESPONSIBLE FOR, ANY BUILDING CODE COMPLIANCE. The foregoing warranties give you specific legal rights and you may also have other rights which vary from state to state.
CFM CORPO-
-
-
-
7412948
23
CFM Corporation
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3
800-668-5323 • www.cfmcorp.com
Loading...