Vermont Casting 3225, RDVOD, 3226, 3227, 3228 User Manual

...
INSTALLER / CONSUMER
CERT IFIED
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
SAFETY INFORMATION
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING APPLIANCE.
WARNING! IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY
Installation and service must be performed by a qualified installer, service agency or the gas suppler.
WHAT TO DO IF
YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electric switch; do
not use any phone in your building.
Immediately call your gas supplier
from your neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier,
call the fire department.
Radiance Direct Vent/Natural Vent Gas Heater
Model RDVOD: 3225 thru 3232, 3350 thru 3354, 3360 thru 3369, 3390 thru 3399
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
This appliance may be installed in an after market permanently located manufactured (mobile) home where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases unless a certified kit is used.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Homeowner’s Installation
and Operating Manual
20004188 4/06 Rev. 14
Radiance Direct Vent /Natural Vent Gas Heater
Installation & Operating Instructions
The Radiance Direct Vent/Natural Vent Room Heater, Model Nos. 3350 thru 3354, 3360 thru 3369 and 3390 thru 3399, is a vented gas appliance listed to the ANSI standard Z21.88b-2002 and CSA-2.33b-2002 for Vented Room Heaters, and CSA 2.17­M91, Gas-Fired Appliances For Use at High Altitudes.
The installation of the Radiance Direct Vent/Natural Vent Room Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition and CSA B-149.1 Installation Code. (EX CEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5 inches w.c. for Natural Gas and 10 inches w.c. for LP gas at maximum input.) Refer to Page 30 (RF only).
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
Installation and replacement of gas piping, gas utiliza­tion equipment or accessories, and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation, or company that either in person or through a representative is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the con­nection, installation, repair, or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
The Radiance Direct Vent/Natural Vent Room Heater should be inspected before use and at least annually by a qualified service agency. It is imperative that control com partments, burners, and circulating air passageways of the appliance be kept clean.
The Radiance Direct Vent/Natural Vent Room Heater and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Radiance Direct Vent/Natural Vent Room Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
An accessible tap is located above the pilot/On-Off knob for checking the inlet pressure.
‘Direct Vent’ describes a sealed combustion system in which incoming outside air for combustion and outgoing exhaust enter and exit through two separate concentric passages within the same sealed vent system. The system does not use room air to support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof. Conventional venting systems (Natural Vent) take air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere.
This appliance is approved for bedroom installations in the U.S. and Canada. Check local codes for natural vent require ments.
This appliance may be installed in an aftermarket* manu­factured (mobile) home, where not prohibited by state or local codes.
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
The Radiance Direct Vent/Natural Vent Room Heater, when
-
installed, must be electrically grounded in accordance with lo cal codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located
out of traffic and away from furniture and draperies.
WARNING: This appliance is hot while in operation. Keep children, clothing, and furniture away. Contact may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be care fully supervised when they are in the same room as the appliance.
Clothing or other flammable materials should not be placed on or near the appliance.
Any safety screen, glass or guard removed for servic­ing an appliance must be replaced prior to operating the appliance.
The appliance area must be kept clear and free from combustible materials, gasoline, and other flammable va
-
pors and liquids.
The flow of combustion and ventilation air must not be obstructed. The installation must include adequate acces sibility and clearance for servicing and proper operation.
WARNING: Do not operate the Room Heater with the glass panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualified service person.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is designed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
* Aftermarket: Completion of sale, nor for purpose of resale, from the manufacturer.
-
Proposition 65 Warning: Fuels used in gas, woodburning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of Cali­fornia to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 25249.6
-
-
-
-
20004188
3
Radiance Direct Vent/Natural Vent Gas Heater
29"
(7.6cm)
31"
(7.9cm)
7" Outer Dia. (1.8cm)

4"
(1.2cm)
14"
(3.7cm)
    
28"
(711mm)
5"
(127mm)
9"
(241mm)
18"
(464mm)
Supply
Inlet
Radiance Direct Vent/Natural Vent Stove Dimensions
See Page 6 for Flue Collar Centerline Dimensions.
4188
Fig. 1 Radiance dimensions.
Attention
The Radiance stove is shipped from the factory as a Direct Vent Gas Heater. This heater may be converted into a Natural Vent unit in the field. If a Natural Vent Heater is desired, the Vermont Castings Z31D00 FSD­HAG Draft Hood must be directly installed to the top of the unit according to the installation instructions. The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item.
When the Radiance stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic purposes the CFM direct vent system may be used up to the ceiling.
44
20004188
Installation Requirements
A
B
E
C
D
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP­TION: Do not derate this appliance for altitude. Main­tain the manifold pressure at 3.5” w.c. for Natural Gas, and 10” w.c. for Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local
codes.
Radiance Direct Vent /Natural Vent Gas Heater
Direct Vent System Only
The installation should be done by a qualified ser vice person who is familiar with the building codes and installation techniques appropriate for your area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to refer a qualified service person.
WARNING: Due to high temperatures, the HEATER should be located out of traffic and away from furni­ture and draperies.
The surface of the Heater Is hot when it is in use. Young children should be watched carefully when they are in the same room when the Heater is in use, and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances that follow.
Locating The Stove
In choosing a location for the stove, consider:
The location of outside walls;
Where additional heat is needed:
Where family members gather most often;
The vent system requirements.
NOTE: We do not recommend the use of wallpaper next to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the wallpaper adhesive.
-
A. Flat on corner wall B. Room Divider C. Island
Fig. 2 Possible stove locations.
D. Cross Corner E. Flat on wall
ST207a
Clearance Requirements
Minimum Clearances to Combustible Materials
Measure side clearances as shown in Figures 3, 4 and 5 from the outer edge of the cast iron stove top. Mea­sure rear clearances from the outermost surface of the steel rear skirt.
The Radiance heater is approved for installation into an alcove constructed of combustible materials to the dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel instal­lation.
WARNING:
• Always maintain required clearances (air spaces) to nearby combustibles
to prevent fire hazard. Do not fill air spaces with insulation. All venting components must maintain a 1” (25mm) clearance to com­bustible materials. Maintain a 6” (150mm) clear­ance when using single wall pipe.
• The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.
• Refer to the manufacturer’s instructions includ ed with the venting system for complete instal­lation procedures.
-
20004188
5
Radiance Direct Vent/Natural Vent Gas Heater
42" (1070mm)
Min. Alcove Width
48"
(1220mm)
Max. Alcove
Depth
6"
(150mm)
6"
(150mm)
4" (102mm)
18"
(457mm)
18"
(457mm)
6"
(150mm)
6"
(150mm)
A
A
C
D
B
Parallel Installation: Minimum Clearance
and Flue Centerline, Direct Vent and Natu
-
ral Vent
ST130
Fig. 3 Parallel installation, minimum back and side clear­ances, and flue centerlines.
Corner Installation: Minimum Clearance and
Flue Centerline, Direct Vent & Natural Vent
Wall Centerline from Floor
Direct Vent Only
A Effective Minimum Centerline 57” (1448 mm)
(CFM Corporation Pipe)
55” (1399 mm) (Simpson DuraVent Pipe)
Fig. 5 Minimum wall centerline.
Wall and Ceiling Clearances
ST131b
ST129
Fig. 4 Corner installation, minimum corner clearances and flue centerline.
66
Direct Vent Only
A: Rear Wall 4” (102 mm) B: Min. Clearance 44” (1118 mm)* C: Min. Alcove Height 72” (1830 mm)* D: Max. Alcove Depth 48” (1220 mm) Sidewall Clearance 6” (150 mm)
* needed for installing DuraVent Minimum Vent Kit #2792 or CFM Corporation Minimum Vent Kit #7TFSMSK.
ST101b
Fig. 6 Dimensions and clearances to ceiling or alcove.
Hearth Requirements
The Radiance Heaters must be installed on rigid floor­ing. When the heater is installed directly on any com­bustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
20004188
Radiance Direct Vent /Natural Vent Gas Heater












                   
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)




















ST134a FDV28 Horizontal vent run 12/3/99 djt areas modified 1/11/00 djt
Gas Specifications
Max. Min. Input Input Model Fuel Gas Control BTU/h BTU/h
RDVODRN Nat Millivolt 35,000 25,000
RDVODRP Prop Millivolt 35,000 27,500 RDVODRFN Nat Comfort Control 35,000 25,000 RDVODRFP Prop Comfort Control 35,000 27,500
Weight: Fully assembled; 350 lbs.
Gas Inlet and Manifold Pressures
Natural LP (Propane)
Inlet Minimum 5.5” w.c. 11.0” w.c.
Inlet Maximum 14.0” w.c. 14.0” w.c.
Manifold Pressure 3.5” w.c. 10” w.c.
Radiance Direct Vent/Natural Vent
Certified to:
ANSI Z21.88b-2002 / CSA 2.33b-2002
Vented Gas Fireplace Heaters
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610mm) off the top of the unit, before the first elbow. The hori­zontal run may extend up to 20’ (6m) and include a vertical rise of up to 40’ (12m). (Fig. 7) Horizontal termi­nation must also meet the criteria shown in Figures 10 through 12.
• Approved vent systems must terminate above and including the heavy line in Figure 7.
• Two 45˚ elbows may be substituted for each single 90˚ elbow.
• With a rise between 2’ - 5’, one 90˚ or two 45˚ elbows may be used.
The installation of your Vermont Castings stove must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 - latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude up to 4,500 feet (1,370m). Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP Gas.
High Elevations
Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).
WARNING: Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
20004188
May use up to
three 90° Elbows
One 90°
Elbow
Unacceptable
Venting Configuration
Fig. 7 Horizontal vent termination window.
ST134a
7
Radiance Direct Vent/Natural Vent Gas Heater













                  
Vertical Run (in feet)
(Measure from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)




















ST132a FDV28 Vertical vent run 12/3/99 djt area modified 1/11/00 djt
Vertical Termination - Direct Vent ONLY
A vertical vent system must terminate no less than 8’ (2.44m) and no more than 40’ (12m) above the appli­ance flue collar. A 2¹⁄₄" restrictor plate (supplied) must be used, where specified, in all vertically terminated vent systems. (Refer to Figure 8) NOTE: The restrictor
plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with stove directly at stove outlet. A vertically terminated
vent system must also conform to the following criteria:
No more than three 90° elbows may be used.
Two 45° elbows may be substituted for one 90˚
elbow. No more than six 45° elbows may be used.
Vent must rise a minimum of 2 feet before offset is
used.
Termination height must conform to roof clearance
as specified in Figure 9.
All Vertical Termi­nations in this area Require use of the 2¹⁄₄” Restrictor Plate*
Fig. 8 Vertical vent termination window.
*The Restictor Plate is used on Direct Vent installations only.
88
Vertical terminations
must be within this area
Unacceptable
Venting Configuration
No Restrictor Plate
No offset may be used
within this area
Vent Termination Clearances
When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 9.
Important: All vent clearances must be maintained. Check your vent termination clearances against Figures 9 through 11.
The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.
The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
Obstructions or impediments to venting.
Nearby combustible materials that could come into
contact with combustion exhaust gases.
Other nearby openings {within 12” (305 mm)}
through which exhaust gas could reenter the build­ing.
All vegetation within 3’ (76 mm) that may interfere
with the draft.
Other factors that influence where the installation will be sited include the location of outside walls, where additional heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.
IMPORTANT Direct Vent Only
• The horizontal termination must not be recessed into the exterior wall or siding.
• Horizontal vent runs must be level toward the vent termination.
• Clearances around the vent termination must be maintained.
For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have restricted access for connecting the Hori­zontal Vent Cap straps to the vent pipe. See the maker’s instructions for recommended installa­tion procedures.
ST132a
20004188
Radiance Direct Vent /Natural Vent Gas Heater
Vent Termination Clearances
Your stove is approved to be vented either through the side wall, or vertical through the roof.
CFM Corporation does not require any opening
for inspection of vent pipe.
Only CFM Corporation and Simpson DuraVent
venting components specifically approved and labelled for this stove may be used.
Minimum clearances between vent pipes and
combustible materials is one (1”) inch (25 mm), except where stated otherwise.
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24” from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termi­nation area after snow falls, and clear to prevent ac­cidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ­ing the minimum clearances as shown on this page.
20004188
9
Radiance Direct Vent/Natural Vent Gas Heater
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I








V
B
INSIDE
CORNER DETAIL
V
A
G
V
N
N
V
V
G
G
A
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2’ (610mm) from the center line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm) F = Clearance to outside corner see next page see next page G = Clearance to inside corner (see next page) see next page see next page H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm) J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and < (23cm) for appliances > 10,000 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10’ (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡ balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes † A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings ‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Stoves are certified as part of the appliance, with clearances tested and approved by the list­ ing agency.
1010
Fig. 9 Vent termination clearances.
20004188
2
Radiance Direct Vent /Natural Vent Gas Heater
Venting Runs
Horizontal Run (in feet)
Vertical Run (in feet)
(Measured from top of the unit before any elbow)
A: Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.
B: Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows. (Ratio = 2/3, Hor./Vert.)
= Acceptable venting configuration
= Unacceptable venting configuration















A
B
NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
A =
Combustible 6"(152mm)
Noncombustible 2"(50mm)
B =
Combustible 6"(152mm)
Noncombustible 2"(50mm)
A
Balcony ­with no side wall
G = Combustible & Noncombustible
12"(305mm)
G
Balcony ­with perpendicular side wall
H = 24"(610mm)
J = 20"(508mm)
H
J
B
Recessed Location
C = Maximum depth of 48"
(1219mm) for recessed location.
D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)
E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)
C
D
C
E
V
V
Combustible & Noncombustible
V
V
V
Fig. 10 Termination clearances.
Fig. 11 Vent termination window - Natural Vent ONLY.
20004188
Venting Requirements - Natural Vent Only
NOTE: When using the FSDHAG, the restrictor plate supplied with the stove is not used.
584-15
11
Radiance Direct Vent/Natural Vent Gas Heater
Venting Requirements and Options -
Direct Vent ONLY
Approved Vent System Components
The Stardance Heater must be vented to the outdoors through an adjacent exterior wall or through the roof. The venting system must be comprised of the appropriate listed venting components specified on this page. These parts are available from DuraVent Corporation or your Vermont Castings Dealer.
See Figure 4 for dimensions relevant to the standard minimum-vent kits.
Simpson DuraVent Components
Minimum Horizontal Vent Kit 2792
Starter Pipe Assembly (incl. inner & outer sections) 2768* 90° Elbow, Blk. 990B* 45° Elbow, Gal. 945 6” Straight, Blk. 908B* 9” Straight, Blk. 907B 11” - 14⁵⁄₈” Adjustable Straight Section 911B 12” Straight 906 24” Straight 904B* 36” Straight 903B 48” Straight 902 Horizontal Vent Cap 984* Wall Plate 940* Vinyl Siding Shield 950 Snorkel Termination - 14” 982 Snorkel Termination - 36” 981 Wall Strap 988 Cathedral Ceiling Support Box 941 Storm Collar 953 Firestop Spacer 963 Flashing 0/12 - 6/12 943 Flashing 6/12 - 12/12 943S Steel Chimney Kit A 931 Kit B 932 Kit C 933 Masonry Chimney Kit 934 Vertical Termination Cap (High Wind) 991 Vertical Termination Cap (Low Profile) 980 *Included in Minimum Horizontal Vent Kit #2792 All DuraVent Straight vent pipe sections have a net length 1¹⁄₂” (37mm) less than the nominal dimension; i.e., a 6” (152mm) Straight pipe section has an effective length of 4¹⁄₂” (115mm).
CFM Vent Components
The following kits are available to meet the needs of most installations. All pipe has a 7” outer diameter and includes a 4” diameter inner section. A (CG) designa­tion indicates the part is finished in Charcoal Gray paint. Consult your dealer about other vent parts that may be appropriate to complete the installation.
Min. Through the Wall Vent Kit 7TFSSK
(1) 90-Degree Elbow (CG) (1) 24” Straight pipe (CG) (1) 24” - 42” Adjustable Straight Pipe (1) Side Wall Termination (1) Firestop (1) Zero-clearance sleeve (1) Hardware package (1) Finishing plate (CG) (1) Finishing collar (CG) (4) Charcoal Gray flue pipe rings
Starter Kit for Below-Grade Termination 7TDVSKS
(1) Snorkel Termination (7TDVSNORK)
Vertical Termination Kit, 1/12-6/12 Pitch 7TDVSKVA
(1) Combination Horizontal Offset / Roof Support (1) Vertical Termination (1) Storm Collar (1) 1/12-6/12 Flashing (1) Finishing Plate (CG) (1) Finishing Collar (CG) (1) Polished Brass Flue Pipe Ring (1) Hardware Package
Vertical Termination Kit, 7/12-12/12 Pitch 7TDVSKVB
(1) 7/12 - 12/12 Flashing and all of the other Vertical Termination parts.
Vertical Termination, Flat Roof 7DVSKVF
(1) Flat Flashing and all of the other Vertical Termination parts.
Twist Lock 12” Straight Pipe (CG) 7TFSDVP12
(1) 12” Non-adjustable Pipe
Twist Lock 12” - 18” Adjustable Pipe 7TFSDVP1218
(1) 12” - 18” Adjustable Pipe
Twist Lock 24” Straight Pipe (CG) 7TFSDVP24
(1) 24” Non-adjustable Pipe
Twist Lock 48” Straight Pipe (CG) 7TFSDVP48
(1) 48” Nonadjustable Pipe
Twist Lock 45-Degree Elbow (CG) 7TFSDVT45
for vertical offsets (1) 45-degree Elbow
Draft Hood Adapter FSDHAG NV Stove Kit 7FSSK
(1) 7” Diameter Polished Brass Trim Ring (1) 48” Nonadjustable Pipe (CG) (1) 24” Nonadjustable Pipe (CG) (1) Finishing Plate (1) Finishing Collar (CG) (1) 90 Degree Elbow (CG)
Stove Kit 7FSDHASK
Includes all parts in the 7FSSK plus the Draft Hood Adapter FSDHAG
Combination Offset/Roof Support 7DVCS Attic Insulation Shield 7DVAIS 7” Charcoal Gray Pipe Rings, (4) 7FSDRG 7” Polished Brass Pipe Rings (4) 7FSDRP Wall Thimble 942G
NOTE: Direct vent pipe may be used on the Natural
Vent system from the top of the draft hood adapter to the ceiling.
1212
20004188
Radiance Direct Vent /Natural Vent Gas Heater
Assembly Procedures
Failure to position the parts in accor­dance with these diagrams or failure to
use only parts specifically approved for use with this heater may result in property dam­age or personal injury.
This heater and components are heavy. Have help available for assembly.
WARNING
Tools Required
• Phillips screwdriver (stub) • power drill
• utility knife • reciprocating saw
• metal drill bit: size 28 (.140”/3.5mm)
Parts Bag Contents:
Control door handle/screw
(3) Vent Screws
(2) Switch bracket screws
Ceramic handle w/insert lifter (handle for operable
door)
On-Off switch, housing, and wiring harness
(3) Phillips round-head bolts, 1/4”- 20 x 1/2”
(2) Bag of Lava Rocks
(1) Tube of Vent Gasket Cement
(1) Vent Restrictor Plate, 2¹⁄₄" inside diameter
Owner Registration Card
(4) CS, Hex Hd 3/8-16 x 1 Gr 2-Z
(4) Washer, Fl 3/8-Z
Unpack and Assemble Legs
The Radiance is shipped upright. Cut the shipping straps and set stove upright.
1. Slide stove to the rear of the pallet just far enough to access rear leg holes. Make sure the stove does not tip over backwards. (Fig. 12)
2. Attach the rear legs using 3/8” hex head bolts and flat washer supplied. Tighten with a 9/16” wrench or socket.
3. Carefully tip the stove onto its rear legs. Adjust the pallet to allow access to one of the front leg holes. Be sure to leave the pallet under the stove to prevent the stove from falling fully forward. (Fig.
13) CAUTION: To prevent valve tubing from being crushed or damaged, make sure to rest valve on wooden pallet.
ST720
Fig. 12 Slide stove back just far enough to access rear leg holes.
Washer
Hex Head Bolt
Fig. 13 Carefully tip stove onto back legs. Leave pallet under stove to keep stove from falling fully forward.
4. Have your assistant attach one leg using the hard­ware described.
5. Move the pallet to allow access to the other front leg hole. Attach remaining leg.
6. Remove pallet and allow stove to gently rest on all four legs.
7. Adjust leg levelers to compensate for irregularities in the hearth.
NOTE: Verify the two relief doors (located on top of the firebox) are properly seated on the gasket. The doors should sit flush on the gasket, and should lift easily from the seal around the opening.
20004188
13
Loading...
+ 26 hidden pages